Allen-Bradley 1734-IB8S Owners Manual

User Manual
Original Instructions
POINT Guard I/O Safety Modules
Catalog Numbers 1734-IB8S, 1734-OB8S, 1734-IE4S, 1734-OBV2S

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Table of Contents

Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Terminology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
POINT Guard I/O Overview Understand Suitability for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installing and Replacing Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Securing the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
POINT Guard I/O Modules in CIP Safety Systems. . . . . . . . . . . . . . 15
1734-IB8S Digital Input Module Features . . . . . . . . . . . . . . . . . . . 15
1734-OB8S Safety Digital Output Module Features. . . . . . . . . . 16
1734-OBV2S POINT Guard I/O Module Features . . . . . . . . . . 16
1734-IE4S Safety Analog Input Module Features. . . . . . . . . . . . . 17
Programming Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
CIP Safety Architectures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Safety Application Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Safety Inputs, Safety Outputs, and Safety Data
Chapter 2
Safe States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
POINT Guard Digital I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . 21
POINT Guard I/O Analog Input Module. . . . . . . . . . . . . . . . . . . 22
Safety Inputs (1734-IB8S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Using a Test Output with a Safety Input . . . . . . . . . . . . . . . . . . . . 22
Single-channel Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dual-channel Mode and Discrepancy Time. . . . . . . . . . . . . . . . . . 25
Dual-channel, Equivalent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Dual-channels, Complementary . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Safety Input Fault Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Input Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Safety Analog Inputs (1734-IE4S) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Input Range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Scaling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Digital Input Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Sensor Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Channel Offset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Process Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Using a Single-channel Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Dual-channel Equivalent Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Tachometer Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Safety Outputs (1734-OB8S and 1734-OBV2S) . . . . . . . . . . . . . . . . . 37
Safety Output with Test Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Dual-channel Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Single-channel Mode, 1734-OB8S Only. . . . . . . . . . . . . . . . . . . . . 39
Safety Output Fault Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 3
Table of Contents
Muting Lamp Operation (1734-IB8S) . . . . . . . . . . . . . . . . . . . . . . . . . . 40
I/O Status Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Digital I/O Status Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Analog I/O Status Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Chapter 3 Guidelines for Placing Power Supplies and Modules in a System
Choosing a Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Power Supply Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Example 1: Isolating Field Power Segments . . . . . . . . . . . . . . . . . . 45
Example 2: POINT Guard I/O Used with AC I/O Modules. . 46
Placing Series A Digital and Analog Modules . . . . . . . . . . . . . . . . . . . . 47
Placing Series B Digital Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Chapter 4
Install the Module Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Environment and Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
European Hazardous Location Approval . . . . . . . . . . . . . . . . . . . . 51
North American Hazardous Location Approval. . . . . . . . . . . . . . 52
Prevent Electrostatic Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Mount the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Install the Mounting Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Connect the Module to the Mounting Base. . . . . . . . . . . . . . . . . . 55
Connect the Removable Terminal Block . . . . . . . . . . . . . . . . . . . . 56
Remove a Mounting Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Wire Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Terminal Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Connection Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Wiring Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Emergency Stop Dual-channel Devices . . . . . . . . . . . . . . . . . . . . . . 63
Single-channel Safety Contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Dual-channel Safety Contactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Bipolar Safety Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Safety Analog Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
4 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Chapter 5
Table of Contents
Configure the Module in a GuardLogix Controller System
Set up the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Add and Configure the Ethernet Bridge. . . . . . . . . . . . . . . . . . . . . . . . . 76
Add and Configure the 1734 Ethernet Adapter. . . . . . . . . . . . . . . . . . 77
Add and Configure Safety Digital Input Modules . . . . . . . . . . . . . . . . 80
Add the Safety Digital Input Module. . . . . . . . . . . . . . . . . . . . . . . . 80
Configure the Safety Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 85
Configure the Test Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Add and Configure Safety Digital Output Modules . . . . . . . . . . . . . . 89
Add the Safety Digital Output Module. . . . . . . . . . . . . . . . . . . . . . 89
Configure the Safety Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . 93
Add and Configure Safety Analog Input Modules. . . . . . . . . . . . . . . . 94
Add the Safety Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . 94
Configure the Safety Analog Input Channel Operation. . . . . . . 97
Configure the Safety Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 98
Configure Safety Analog Input Alarms (Optional) . . . . . . . . . . . 99
Configure Tachometer Operation . . . . . . . . . . . . . . . . . . . . . . . . . 101
Values and States of Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Configure Safety Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Configuration Ownership . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Save and Download the Module Configuration. . . . . . . . . . . . . . . . . 107
Update POINT Guard I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Configure the Module for a SmartGuard Controller
Chapter 6
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Set the Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Auto-addressing with a 1734-PDN Adapter . . . . . . . . . . . . . . . . . . . . 112
Set Up Your DeviceNet Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Configure the POINT Guard I/O Modules . . . . . . . . . . . . . . . . . . . . 115
Configure Digital Safety Inputs and Test Outputs. . . . . . . . . . . 115
Configure Digital Safety Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Configure Safety Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Configure the SmartGuard Controller . . . . . . . . . . . . . . . . . . . . . . . . . 124
Set Up the Input and Output Connections . . . . . . . . . . . . . . . . . 124
Complete the Set Up of the SmartGuard Controller . . . . . . . . 128
Save and Download Module Configuration . . . . . . . . . . . . . . . . . . . . 129
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 5
Table of Contents
Chapter 7
Configuring Safety Connections between a GuardLogix Controller and POINT Guard I/O Modules on a DeviceNet Network
Replacing POINT Guard I/O Modules
Configure the Module in RSNetWorx for DeviceNet Software . . 131 Add the POINT Guard I/O Module to the Controller Project. . . 132
Complete the Safety Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Download the DeviceNet Network Configuration. . . . . . . . . . . . . . 138
Verify Your DeviceNet Safety Configuration . . . . . . . . . . . . . . . . . . . 139
Determine If Devices Can Be Verified. . . . . . . . . . . . . . . . . . . . . . 140
Select Devices to Verify . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Review the Safety Device Verification Reports . . . . . . . . . . . . . . 143
Lock Safety Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Chapter 8
The Safety Network Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Manually Setting the Safety Network Number. . . . . . . . . . . . . . . . . . 146
Resetting a Module to Out-of-box Condition . . . . . . . . . . . . . . . . . . 147
By Using the Logix Designer Application. . . . . . . . . . . . . . . . . . . 148
By Using RSNetWorx for DeviceNet Software. . . . . . . . . . . . . . 149
Replace a Module in a GuardLogix System on an
EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Replacement with ‘Configure Only When No Safety
Signature Exists’ Enabled. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Replacement with ‘Configure Always’ Enabled. . . . . . . . . . . . . . 155
Replace a Module When Using a SmartGuard or GuardLogix
Controller on a DeviceNet Network. . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Appendix A
Indicators Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Network Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Configuration Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
1734-IE4S Sensor Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
1734-IE4S Safety Analog Input Status . . . . . . . . . . . . . . . . . . . . . . . . . 164
1734-IB8S Safety Input Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
1734-OB8S Safety Output Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
1734-OBV2S Safety Output Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Appendix B
Get I/O Diagnostic Status from Modules in Logix Systems
Message Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Configure the Message Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Class, Instance, and Attribute Data for I/O Modules . . . . . . . . . . . . 169
6 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Table of Contents
Appendix C
Specifications Technical Specifications for Series A Modules . . . . . . . . . . . . . . . . . . 173
Safety Digital Input Module Specifications . . . . . . . . . . . . . . . . . 173
Safety Digital Output Module Specifications . . . . . . . . . . . . . . . 175
Safety Analog Input Module Specifications . . . . . . . . . . . . . . . . . 176
Technical Specifications for Series B Modules . . . . . . . . . . . . . . . . . . 185
Safety Digital Input Module Specifications . . . . . . . . . . . . . . . . . 185
Safety Digital Output Module Specifications . . . . . . . . . . . . . . . 188
Safety Digital Output Module Specifications 1734-OBV2S. . . . . . 190
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Appendix D
Safety Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Series A Safety Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Series B Safety Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Product Failure Rates (failures per hour) . . . . . . . . . . . . . . . . . . . . . . . 205
Appendix E
Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Appendix F
I/O Assemblies Input Assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Output Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Analog Input Assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Configuration Assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Using Data from Modules Configured Via the Generic Profile . . . 221
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 7
Table of Contents
Notes:
8 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018

Preface

Thoroughly read and understand this manual before installing and operating a system that uses POINT Guard I/O™ modules.
Always observe the following guidelines when using a module. In this manual, we use safety administrator to mean a person who is qualified, authorized, and responsible to secure safety in the design, installation, operation, maintenance, and disposal of the ‘machine’.
Keep this manual in a safe place where personnel can refer to it when necessary.
Use the module properly according to the installation environment, performance ratings, and functions of the machine.

Summary of Changes

Terminology

See Understand Suitability for Use on page 11
and Safety Precautions on
page 13.
Product specifications and accessories can change at any time. Consult with your Rockwell Automation representative to confirm specifications of purchased product. Dimensions and weights are nominal and are not for manufacturing purposes, even when tolerances are shown.
Consult your Rockwell Automation representative if you have any questions or comments. Also refer to the related documentation, which is listed on page 10
, as
necessary.
We updated the ATTENTION statement on pages 43 and the Series B Safety Digital Input Module Specifications beginning on page 185
Table 1 - Common Terms
Ter m Me ans
Connection Logical communication channel for communication between nodes. Connections are
maintained and controlled between masters and slaves.
EDS Electronic data sheet, a template that is used in RSNetWorx™ software to display the
configuration parameters, I/O data profile, and connection-type support for a given I/O module. RSNetWorx software uses these simple text files to identify products and commission them on a network.
ODVA Open DeviceNet Vendor Association, a nonprofit association of vendors that are established
for the promotion of CIP networks.
PFD Probability of failure on demand, the average probability of a system to fail to perform its
design function on demand.
PFH Probability of failure per hour, the probability of a system to have a dangerous failure occur
per hour.
Proof test Periodic test that detects failures in a safety-related system so that, if necessary, the system
can be restored to an as-new condition or as close as practical to this condition.
SNN Safety network number, which uniquely identifies a network across all networks in the
safety system. You are responsible for assigning a unique number for each safety network or safety subnet within a system.
Standard Devices or portions of devices that do not participate in the safety function.
.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 9
Preface

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
POINT I/O Selection Guide, publication 1734-SG001 Provides selection information for POINT I/O™ modules. Additional publication references
GuardLogix 5570 Controllers User Manual, publication 1756-UM022 Provides information on how to install, configure, program, and use GuardLogix® 5570
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093 Provides information on safety system requirements and describes the GuardLogix
GuardLogix Controllers User Manual, publication 1756-UM020 Provides information on how to install, configure, program, and use GuardLogix
GuardLogix Safety Application Instructions Safety Reference Manual, publication
SmartGuard 600 Controllers Safety Reference Manual, publication 1752-RM001 Describes SmartGuard™ 600-specific safety requirements and controller features.
Field Potential Distributor Installation Instructions, publication 1734-IN059 Provides installation information on 1734-FPD distributors.
POINT I/O 24V DC Expansion Power Supply Installation Instructions, publication 1734-IN058
POINT I/O 120/240V AC Expansion Power Supply Installation Instructions, publication 1734-IN017
POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN511 Provides installation information on 1734-TB and 1734-TBS assemblies.
POINT I/O One-piece Wiring Base Assembly Installation Instructions, publication 1734-IN028
ODVA Media Planning and Installation Guide, http://www.odva.org Describes the required media components and how to plan for and install these required
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.rockwellautomation.com/global/
certification/overview.page
1756-RM095
are listed as well.
controllers in Studio 5000 Logix Designer® projects.
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
controller system.
controllers in RSLogix 5000® projects.
Provides reference information that describes the GuardLogix Safety Application Instruction Set.
Provides installation information on 1734-EP24DC power supplies.
Provides installation information on 1734-EPAC power supplies.
Provides installation information on 1734-TOP, 1734-TOPS, 1734-TOP3, and 1734-TOP3S assemblies.
components.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/
technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
10 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
. To order paper copies of
Chapter 1

POINT Guard I/O Overview

Top ic Pag e
Understand Suitability for Use 11
Safety Precautions 13
POINT Guard I/O Modules in CIP Safety Systems 15
Safety Application Requirements 19
Use the POINT Guard I/O™ safety modules in the POINT I/O™ platform to distribute safety I/O on a safety-control network that meets the requirements up to and including SIL CL3, and PLe, Cat. 4 as defined in IEC 61508, IEC 61511, IEC 62061, and ISO 13849-1. Guard I/O modules can be used with GuardLogix® controllers, Compact GuardLogix controllers, and SmartGuard™ Controllers.

Understand Suitability for Use

You can configure the modules for use on DeviceNet™ networks by using the network configuration tool, RSNetWorx™ for DeviceNet software. For Ethernet networks, use the GuardLogix programming tool, the Logix Designer application.
Rockwell Automation is not responsible for conformity with any standards, codes, or regulations that apply to the combination of the products in your application or use of the product. See Standards on page 195 information.
Take all necessary steps to determine the suitability of the products for the systems, machine, and equipment with which it is used.
Know and observe all prohibitions of use applicable to these products.
Use this equipment within its specified ratings.
Never use these products for an application that involves serious risk to life or property without making sure that the system as a whole was designed to address the risks. Be sure that Rockwell Automation products are properly rated and installed for the intended use within the overall equipment or system.
for more
Only download firmware and access product release notes from the Rockwell Automation official download portal at http://www.rockwellautomation.com/
rockwellautomation/support/pcdc.page.
Do not download firmware from non-Rockwell Automation sites.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 11
Chapter 1 POINT Guard I/O Overview
TIP
Verify that the POINT Guard I/O firmware revision is correct before you commission the safety system. Firmware information for safety I/O modules is available at
http://www.rockwellautomation.com/products/certification/safety.
Field power must be applied to the 1734-IE4S module when updating firmware.
Verify that a safety administrator conducts a risk assessment on the machine and determines module suitability before installation.
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in the use of the system.
ATT EN TI ON : Use only appropriate components or devices that comply with relevant safety standards that correspond to the required safety category and safety integrity level.
Conformity to requirements of the safety category and safety integrity level must be determined for the entire system.
We recommend that you consult a certification body regarding assessment of conformity to the required safety integrity level or safety category.
You are responsible for confirming compliance with the applicable standards for the entire system.
Table 1 - Requirements for Controlling Devices
Device Requirement Allen-Bradley® Bulletin Safety Components
Emergency stop switches Use approved devices with direct opening mechanisms that comply with IEC/EN
Door interlocking switches, limit switches
Safety sensors Use approved devices that comply with the relevant product standards, regulations,
Relays with forcibly- guided contacts, contac tors
Other devices Evaluate whether devices used are appropriate to satisfy the requirements of safety
60947-5-1. Use approved devices with direct opening mechanisms that comply with IEC/EN
60947-5-1 and capable of switching microloads of 24V DC, 3 mA.
and rules in the country where used. Use approved devices with forcibly guided contacts that comply with EN 50205. For
feedback purposes, use devices with contacts capable of switching micro loads of 24V DC, 3 mA.
category levels.
Bulletin 800F, 800T
Bulletin 440K, 440G, 440H for interlock switch Bulletin 440P, 802T for limit switch
Any Guardmaster® product
Bulletin 700S, 100S
-
12 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
POINT Guard I/O Overview Chapter 1

Safety Precautions

Observe these precautions for proper use of POINT Guard I/O modules.
ATTENTION: As serious injury can occur due to loss of required safety function, follow these safety precautions.
Never use test outputs as safety outputs. Test outputs are not safety outputs.
Do not use Ethernet, DeviceNet, or ControlNet standard I/O data or explicit
message data as safety data.
Do not use light-emitting diode (LED) status indicators on the I/O modules for safety operations.
Do not connect loads beyond the rated value to the safety outputs.
Apply properly specified voltages to the module. Applying inappropriate
voltages can cause the module to fail to perform it’s specified function, which could lead to loss of safety functions or damage to the module.
Wire the POINT Guard I/O modules properly following the wiring requirements and guidelines in Wire Modules on page 57
Set unique network node addresses before connecting devices to the network.
Perform testing to confirm that device wiring, configuration, and operation is
correct before starting system operation.
Do not disassemble, repair, or modify the module. This can result in loss of safety functions.
.

Installing and Replacing Modules

ATTENTION:
Clear previous configuration data before connecting devices to the network or
connecting input or output power to the device.
Configure the replacement device properly and confirm that it operates correctly.
After installation of the module, a safety administrator must confirm the installation and conduct trial operation and maintenance.
When you clean a module, do not use the following:
Thinner
Benzene
Acetone
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 13
Chapter 1 POINT Guard I/O Overview

Securing the System

To secure access to the [device] by authorized users only, consider these options:
Password protect the source and execution of the control program
Remove the key from the controller
Deploy EtherNet/IP™ devices in accordance with recommended
architectures and concepts. See the Converged Plantwide Ethernet (CPwE) Design and Implementation Guide, publication ENET-TD001
Implement physical barriers, such as locked cabinets
To secure access to the system, consider these options:
Follow industry best practices to harden your personal computers and servers, including anti-virus/anti-malware and application whitelisting solutions. These recommendations are published in Knowledgebase article
KB546987
.
Develop and deploy backup and disaster recovery policies and procedures. Test backups on a regular schedule.
Minimize network exposure for all control system devices and systems, and verify that they are not accessible from the Internet.
Locate control system networks and devices behind firewalls and isolate them from the business network.
Subscribe to Rockwell Automation’s Security Advisory Index, Knowledgebase article KB54102
so you have access to information about
security matters that affect Rockwell Automation products.
14 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
POINT Guard I/O Overview Chapter 1

POINT Guard I/O Modules in CIP Safety Systems

POINT Guard I/O modules are used in the POINT I/O platform and implement CIP Safety™ protocol extensions over EtherNet/IP and DeviceNet networks to communicate safety messages. POINT Guard I/O modules connect to EtherNet/IP or DeviceNet networks via these network adapters.
Table 2 - Network Adapters
Network System Adapter
EtherNet/IP GuardLogix 1734-AENT (Firmware Revision 3 or later)
DeviceNet SmartGuard or GuardLogix 1734-PDN
(1) Not compatible with 1734-ADN, 1734-ADNX, 1734-APB, or 1734-ACNR adapters.
(1)
1734-AENTR
Distributed I/O communication for safety I/O data is performed through safety connections that support CIP Safety over an EtherNet/IP or DeviceNet network. Data processing is performed in the safety controller. A control monitors the status and fault diagnostics of POINT Guard I/O modules.
In addition to I/O state data, the modules include status data for monitoring I/O faults within each circuit.
A password can help protect the configuration information of the modules.

1734-IB8S Digital Input Module Features

Safety digital inputsSafety devices, such as Emergency Stop Push Button, gate switches, and
safety light curtains, can be connected.
– Dual-channel mode evaluates consistency between two input signals
(channels), which allows use of the module for safety Category 3 and 4 and in applications that are rated up to and including Performance Level e/SIL CL3 when both channels’ Point Mode configurations are set to Safety Pulse Test.
– Single-channel mode evaluates one input signal (channel), which allows
use of the module for safety Category 2 and in applications that are rated up to and including Performance Level d/SIL CL 2 when the channel's Point Mode configuration is set to Safety Pulse Test.
– You can configure a discrepancy time to control how long two channels
are allowed to be discrepant before a fault is declared.
– An external wiring short circuit check is possible when inputs are wired
in combination with test outputs. The module must be wired in combination with test outputs when this function is used.
– Independently adjustable on and off delays are available per channel.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 15
Chapter 1 POINT Guard I/O Overview
IMPORTANT
Test outputs (digital input modules only)Separate test outputs are provided for short circuit detection of a safety
input (or inputs).
Power (24V) can be supplied to devices, such as safety sensors.Test outputs can be configured as standard outputs. Specific test outputs can be used for broken-wire detection of a muting
lamp.

1734-OB8S Safety Digital Output Module Features

Solid-state outputs
Dual-channel mode provides redundant control by using two output
signals (channels), which allows use of the module for safety Category 3 and 4, and applications that are rated up to and including Performance Level e/SIL CL3 when both channels’ Point Mode configurations are set to Safety Pulse Test.
Single-channel mode provides control by using one output signal (channel), which allows use of the module for safety Category 2, and applications that are rated up to and including Performance Level d/SIL CL2 when the channel’s Point Mode configuration is set to Safety Pulse Te s t .
1734-OB8S Single-channel mode is only certified for functional safety applications with process safety times greater than or equal to 600 ms; or, applications with demand rates less than or equal to 1 demand per minute.
Safety outputs can be pulse-tested to detect field wiring short circuits to 24V DC.

1734-OBV2S POINT Guard I/O Module Features

4 bipolar outputs (2 pairs)
Dual-channel mode provides redundant control by using two output
signals (channels), which allows use of the module for safety Category 3 and 4, and applications that are rated up to and including Performance Level e/SIL CL3 when both channels’ Point Mode configurations are set to Safety Pulse Test.
Safety outputs can be pulse-tested to detect field wiring short circuits to 24V DC (for the sourcing output of the bipolar pair) and ground (for the sinking output of the bipolar pair).
16 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
POINT Guard I/O Overview Chapter 1

1734-IE4S Safety Analog Input Module Features

Connection of up to four voltage or current sensors.
Sensor power outputs are individually current-limited and monitored.
Measurement of process variables, such as temperature, pressure, or flow
rate.
Seven configurable input ranges (±10V, ±5V, 0…5V, 0…10V, 4…20 mA, 0…20 mA, Tachometer).
Tachometer mode converts 24V DC switching signals into pulses per second.
Single-channel or dual-channel for SIL 3-rated safety devices and applications.
Dual-channel mode evaluates the consistency between two input signals (channels), which allows use of the module in applications that are rated up to and including SIL CL3/PLe/Cat. 4.
You can configure a discrepancy time to control how long two channels are allowed to be discrepant before a fault is declared.

Programming Requirements

Use the minimum Software Versions listed here.
Cat. No. Studio 5000® Environment
1734-IB8S, 1734-OB8S
1734-OBV2S 21 18 21
1734-IE4S 21 18
(1) This version or later. (2) If you are using digital POINT Guard I/O modules with the analog POINT Guard I/O module, you must update the Add-on Profiles
to version 2.02.004 or later for the modules to be compatible with version 18 or later of RSLogix 5000 software and the Studio 5000 Environment. To find Add-on Profiles, go to http://www.rockwellautomation.com/support
(3) Dual-channel Analog (DCA) safety application instruction is available in RSLogix 5000 software, version 20 or later and Studio
5000 Environment, version 21 and later.
(1)
Versi on
21 17
RSLogix 5000® Software
(1)
Vers ion (EtherNet/IP Network)
(2)
(3)
RSNetWorx for DeviceNet Software Version (DeviceNet Network)
9
10
.
(1)
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 17
Chapter 1 POINT Guard I/O Overview
Safety Communication
GuardLogix Control ler
Compac tBlock™ Guard I/O™
POINT Guard I/O and POINT I/O
Standard Communication
Stratix™ Switch
GuardLogix Control ler
CompactBlock Guard I/O
POINT Guard I/O and POINT I/O
Safety Communication
Standard Communication
SmartGuard Control ler

CIP Safety Architectures

Use POINT Guard I/O modules in EtherNet/IP or DeviceNet safety architectures. Safety controllers control the safety outputs. Safety or standard PLC controllers can control the standard outputs.
Figure 1 - POINT Guard I/O Modules in EtherNet/IP Safety Architecture
Figure 2 - POINT Guard I/O Modules in DeviceNet Safety Architectures
18 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
POINT Guard I/O Overview Chapter 1

Safety Application Requirements

POINT Guard I/O modules are certified for use in safety applications up to and including Performance Level e (PLe/Cat. 4) and Safety Integrity Level 3 (SIL CL3) in which the de-energized state is the safe state. Safety application requirements include evaluating probability of failure rates (PFD and PFH), system reaction time settings, and functional verification tests that fulfill SIL 3 criteria.
Creating, recording, and verifying the safety signature is also a required part of the safety application development process. The safety controller creates the safety signatures. The safety signature consists of an identification number, date, and time that uniquely identifies the safety portion of a project. This number includes all safety logic, data, and safety I/O configuration.
For safety system requirements, including information on the safety network number (SNN), verifying the safety signature, functional verification test intervals, system reaction time, and PFD/PFH calculations, refer to the following publications.
For safety requirements in: See:
GuardLogix controller systems GuardLogix 5570 Controller Systems Safety Reference
Manual, publication 1756-RM099
SmartGuard 600 controller systems SmartGuard 600 Controllers Safety Reference Manual,
publication 1752-RM001
You must read, understand, and fulfill the requirements that are detailed in these publications before operating a safety system that uses POINT Guard I/O modules.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 19
Chapter 1 POINT Guard I/O Overview
Notes:
20 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Chapter 2
Output OFF
Input
Inputs to Network OFFNetworks
Safety Status
44076

Safety Inputs, Safety Outputs, and Safety Data

Top ic Pag e
Safe States 21
Safety Inputs (1734-IB8S) 22
Safety Analog Inputs (1734-IE4S) 29
Safety Outputs (1734-OB8S and 1734-OBV2S) 37
Muting Lamp Operation (1734-IB8S) 40
I/O Status Data 41

Safe States

POINT Guard Digital I/O Modules

ATTENTION:
The safe state of the outputs is defined as the off state.
The safe state of the module and its data is defined as the off state.
Use the POINT Guard I/O™ module only in applications where the off state is the
safe state.
The following are the safe states of the digital POINT Guard I/O modules:
Safety outputs: OFF
Safety input data to network: OFF (single channel and
dual-channel equivalent)
Safety input data to network: OFF/ON for input channels n/n+1 (dual-channel complementary)
Figure 3 - Safety Status
The module is designed for use in applications where the safe state is the off state.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 21
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
TIP
Where: T0 = Test Output 0 T1M = Test Output 1 with Muting T2 = Test Output 2 T3M = Test Output 3 with Muting I0…I7 = Safety Inputs
Safety Input Ter m in a l
External Contac t

POINT Guard I/O Analog Input Module

The following are the safe states of the POINT Guard I/O analog input module:
Safety input data to network in single-channel configuration: 0 (OFF)
Safety input data to network in dual-channel equivalent configuration:If a diagnostic fault occurs, the signal for the faulted channel is set to 0
(OFF).
– If a dual-channel discrepancy fault occurs, the dual-channel inputs
continue to report actual input signals.

Safety Inputs (1734-IB8S)

Safety inputs are used to monitor safety input devices.

Using a Test Output with a Safety Input

A test output can be used in combination with a safety input for short circuit, cross-channel, and open-circuit fault detection. Configure the test output as a pulse test source and associate it to a specific safety input.
The test output can also be configured as a power supply to source 24V DC to an external device, for example, a light curtain.
Figure 4 - Example Use of a POINT Guard I/O Input Module
I0 I1 I4 I5
0
I2 I3 I6 I7
2
COM COM COM COM
4
TO T1M T2 T3M
6
1
3
5
7
0
2
4
6
1
3
5
7
22 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
X
OUT
Y
On
Off
External Contact
Short-circuit between Input Signal Lines and Power Supply (positive side)
External Contact
Short-circuit between Input Signal Lines
44079
Figure 5 - Test Pulse in a Cycle
For the 1734-IB8S module, the pulse width (X) is typically 525 μs; the pulse period (Y) is typically 144 ms.
When the external input contact is closed, a test pulse is output from the test output terminal to diagnose the field wiring and input circuitry. By using this function, short-circuits between inputs and 24V power, and between input signal lines and open circuits can be detected.
Figure 6 - Short-circuit between Input Signal Lines
24V
IN+
COM
T0
24V 0V
IN0
T1
IN1
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 23
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
24V
0V
Tes t O utp ut 0
Input Terminal 0
External Device
Fault D etec ted
ON
OFF
ON
OFF
ON
OFF
ON
OFF
24V
0V
ON
OFF
Safety Input 0 Status
Fault Detection
ON
OFF
ON
OFF
ON
OFF
Safety Input 0 Status
Safety Input 0 Data
Safety Input 0 Data
Input Terminal 0
Normal Operation
External Device
Tes t O utp ut 0
Safety I/O Network Data Sent to the Control ler
Safety I/O Network Data Sent to the Control ler

Single-channel Mode

If an error is detected, safety input data and safety input status turn off.
Figure 7 - Normal Operation and Fault Detection (Not to Scale)
24 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
IMPORTANT

Dual-channel Mode and Discrepancy Time

To support dual-channel safety devices, the consistency between signals on two channels can be evaluated. Either equivalent or complementary can be selected.
If the length of a discrepancy between the channels exceeds the configured discrepancy time (10…65,530 ms in increments of 10 ms), the safety input data and the individual-safety input status turn off for both channels. In Dual-channel Complimentary mode, the safety input data goes to off/on for input channels n/n+1 respectively as described in Ta b l e 3
The dual-channel function is used with two consecutive inputs that are paired together, starting at an even input number, such as inputs 0 and 1, 2 and 3.
If you are using the safety application instructions with a GuardLogix® controller, set the inputs of the module inputs to Single (default). Do not use the dual-channel mode of the module, as this functionality is provided by the safety application instructions.
.
This table shows the relation between input terminal states and controller input data and status.
Table 3 - Terminal Input Status and Controller I/O Data
Dual-channel Mode Input Terminal Controller Input Data and Status Dual-channel
IN0 IN1 Safety
Input 0 Data
Dual-channels, Equivalent OFF OFF OFF OFF ON ON OFF Normal
OFF ON OFF OFF OFF OFF OFF Fault ON OFF OFF OFF OFF OFF OFF Fault ON ON ON ON ON ON ON Normal
Dual-channels, Complementary OFF OFF OFF ON OFF OFF OFF Fault
OFF ON OFF ON ON ON OFF Normal ON OFF ON OFF ON ON ON Normal ON ON OFF ON OFF OFF OFF Fault
Safety Input 1 Data
Safety Input 0 Status
Safety Input 1 Status
Resultant Data
Dual-channel Resultant
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 25
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
ON
OFF
IN0
Safety Input 0 Data
IN1
Faul t Dete cted
Discrepancy Time
Safety I/O Network Data Sent to the Control ler
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
IN0
Safety Input 0, 1 Status
IN1
Fault Detection
ON
OFF
ON
OFF
ON
OFF
Discrepancy Time
Safety Input 0, 1 Status
Safety Input 1 Data
Safety Input 1 Data
Safety Input 0 Data
Normal Operation
Safety I/O Network Data Sent to the Contro ller

Dual-channel, Equivalent

In Equivalent mode, both inputs of a pair must be in the same (equivalent) state. When a transition occurs in one channel of the pair before the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state before the discrepancy time elapsing, the inputs are considered equivalent. If the second transition does not occur before the discrepancy time elapses, the channels will fault. In the fault state, the input and status for both channels are set low (OFF). When configured as an equivalent dual pair, the data bits for both channels are sent to the controller as equivalent, both high or both low.
Figure 8 - Equivalent, Normal Operation and Fault Detection (Not to Scale)
26 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
ON
OFF
IN0
Safety Input 0 Data
IN1
Faul t Dete cted
Discrepancy Time
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
IN0
Safety Input 0, 1 Status
IN1
Fault Det ection
ON
OFF
ON
OFF
ON
OFF
Discrepancy Time
Safety Input 0, 1 Status
Safety Input 1 Data
Safety Input 1 Data
Safety Input 0 Data
Normal Operation
Safety I/O Network Data Sent to the Control ler
Safety I/O Network Data Sent to the Control ler

Dual-channels, Complementary

In Complementary mode, the inputs of a pair must be in the opposite (complementary) state. When a transition occurs in one channel of the pair before the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state before the discrepancy time elapsing, the inputs are considered complementary.
If the second transition does not occur before the discrepancy time elapses, the channels will fault. The fault state of complementary inputs is the even-numbered input that is turned off and the odd-numbered input turned ON. Note that if faulted, both channel status bits are set low. When configured as a complementary dual-channel pair, the data bits for both channels are sent to the controller in complementary, or opposite states.
Figure 9 - Complementary, Normal Operation and Fault Detection (Not to Scale)
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 27
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
44094
On-delay
ON OFF
ON OFF
Input Signal
Safety Input Network Data
44095
Safety Input Network Data
Off-delay
Input Signal
ON OFF
ON OFF

Safety Input Fault Recovery

If an error is detected, the safety input data remains in the OFF state. Follow this procedure to activate the safety input data again.
1. Remove the cause of the error.
2. Place the safety input (or safety inputs) into the safe state.
3. Allow the input-error latch time to elapse.
After these steps are completed, the I/O indicator (red) turns off. The input data is now active.

Input Delays

On-delay—An input signal is treated as Logic 0 during the on-delay time (0…126 ms, in increments of 6 ms) after the rising edge of the input contact. The input turns on only if the input contact remains on after the on-delay time has elapsed. This setting helps prevent rapid changes of the input data due to contact bounce.
Figure 10 - On-delay
Off-delay—An input signal is treated as Logic 1 during the off-delay time (0…126 ms, in increments of 6 ms) after the falling edge of the input contact. The input turns off only if the input contact remains off after the off delay time has elapsed. This setting helps prevent rapid changes of the input data due to contact bounce.
Figure 11 - Off-delay
28 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
IMPORTANT
EXAMPLE

Safety Analog Inputs (1734-IE4S)

Safety analog-input channels can be configured for current, voltage, or tachometer inputs, and for input type: single-channel or dual-channel equivalent.
If you are using the module with a GuardLogix controller, set the inputs of the module to Single (default). Do not use the dual-channel equivalent mode of the modules with the GuardLogix dual channel safety application instructions, as dual-channel functionality is provided by the GuardLogix instructions.

Input Range

You configure the module for the following voltage or current input ranges, or for tachometer inputs.
±10V
±5V
0…5V
0…10V
4…20 mA
0…20 mA
Tachometer (1…1000 Hz)
When ±10V and ±5V ranges are selected, you must make sure that a broken-wire condition is not a safety hazard. A broken wire causes the analog value to transition to 0, which is within the valid input range. Therefore, status bits do not indicate the broken-wire condition.

Scaling

The module converts input signals to the engineering units specified when you configure the module. You set the High Engineering value and the Low Engineering value to which the module scales the input signal before sending the data to the application program of the controller.
The module is configured as follows:
Input Range = 0…10V
Low Engineering value = 0
High Engineering value = 10,000
If the incoming signal is 1V, the data is 1000. If the incoming signal is 5.5V, the data is 5500.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 29
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
Configurable Digital Filter Settings
N = 1 Hz, 5 Hz, 10 Hz, or 50 Hz
Anti-alias Filter
10 Hz
1 pole 1 pole 1 pole 1 pole 1 pole
NNNN

Digital Input Filter

A single-pole, anti-aliasing filter of 10 Hz is followed by a four-pole digital filter. Choose from the following available corner frequencies.
1 Hz
5 Hz
10 Hz
50 Hz
The default input filter setting is 1 Hz.
Figure 12 - Filter Operation
The filter setting affects the step response of the module. See the technical specifications for the 1734-IE4S module, that start on page 176
.
For the analog input modes, the input filter settings set the low-pass filter to filter out noise that can be present on the signal. In Tachometer mode, the input filter removes noise that can be present on the calculated frequency, effectively changing how rapidly the tachometer frequency changes to provide a value with less jitter.

Sensor Power Supply

You can configure the module to supply power to the connected sensors, or you can supply power to the sensors from an external power supply. To comply with UL restrictions, field power and connected devices must be powered by one, Class 2-complaint power supply.
We recommend that you configure the module to supply power to the sensors. This configurations lets the module detect if a sensor loses power, if the sensor is drawing too much power, or if there is a short in the power wiring to the sensor.
At powerup or after a reconfiguration, each sensor power supply is tested by being turned on for 500 ms.
30 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
TIP
IMPORTANT
TIP
When a channel is configured for module sensor power, a sensor power diagnostic is executed on that channel at powerup. The diagnostic is used to make sure that the sensors are not drawing over- or under-current and that channel-to-channel shorts are not present.
When a sensor power over-current condition occurs, it can take as much as 15 seconds longer than the configured latch time for channel status to recover after the over-current condition is cleared.
If you use an external power supply, you must monitor the system for the following:
The supply voltage must be within the operating range of the sensor.
The current draw of the sensors must not be over- or under-current, which
could indicate a problem with the components of the sensor.
Channel-to-channel shorts must be detected, if they occur.

Channel Offset

You can configure an offset when differences in the sensors nominal input signals would otherwise exceed the desired discrepancy deadband. Use the Channel Offset if you are using two sensors of different types to measure the same variable. Sensors from two different vendors potentially give slightly differing data values for a given temperature or pressure. Use the Channel Offset to bring the data values back together. You can also use the Channel Offset with two identical sensors that are physically offset from each other.
The channel offset is applied before the channel discrepancy is evaluated.
The Channel Offset is applied only during the evaluation of discrepancy between two channels that are configured for Dual Channel and is not applied to any of the Process Alarms. Therefore, if you are using two sensors to measure the same process variable, and these sensors read different values, you potentially need to set the Process Alarms to different values based on the sensor readings.

Process Alarms

Process alarms alert you when an analog input value has exceeded the configured high or low limits for each channel. Process alarms are set at four configurable trigger points.
High High alarm
High alarm
Low alarm
Low Low alarm
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 31
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
IMPORTANT
High High alarm turns OFF. High alarm remains ON.
High High alarm turns ON. High alarm remains ON.
High alarm turns ON.
High alarm turns OFF.
Normal input range
Low alarm turns ON.
Low alarm turns OFF.
Low Low alarm turns OFF. Low alarm remains ON.
Low Low alarm turns ON. Low alarm remains ON.
Alarm deadbands
High High Alarm
High Alarm
Low Low Alarm
Low Alarm
You can configure a tolerance range, called a deadband, to work with process alarms. This deadband lets the process alarm status bit remain set, despite the alarm condition disappearing, as long as the data remains within the deadband of the process alarm.
If you are using the safety application instructions with a GuardLogix controller, do not use the process alarm of the module. Instead, perform analog range checking in your application logic.
Figure 13 - Alarms

Using a Single-channel Sensor

You must address the following requirements to meet SIL 3 with a single-channel sensor.
The module’s ±10V and ±5V analog input modes must not be used for SIL 3 with a single-channel sensor because 0V falls within the valid input range. Therefore, a stuck at ground fault cannot be detected.
In a single-channel sensor system, you must use other methods to make
32 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
If you are using a 3-wire sensor, you must verify its behavior to make sure
sure a channel-to-channel short cannot occur because these faults cannot be detected.
that if it loses its ground connection, the signal is 0 (safe state) at the module input when the fault occurs.
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
High High Alarm
High Alarm
Low Low A larm
Low Alarm
Channel A
Channel B
Discrepancy Time = 250 ms
Fault P rese nt
Input Status
Deadband
Difference between Channel A and Channel B

Dual-channel Equivalent Mode

If you are using the module with a GuardLogix controller, set the inputs of the module to Single (default). Do not use the dual-channel mode of the module as this functionality is provided by the GuardLogix safety application instructions.
The 1734-IE4S module supports Dual-channel Equivalent mode. In Dual-channel Equivalent mode, the values of both inputs of a pair must be within a configured tolerance range (discrepancy deadband). If the difference between the channel values exceeds the deadband for longer than the configured discrepancy time, a discrepancy fault is declared. When a dual-channel discrepancy fault occurs, the input status values for both channels are set low (off ) and the actual input values are reported. The fault is cleared when the difference between the values of the channel fall back within the discrepancy deadband tolerance range for the discrepancy time.
Figure 14
illustrates module operation in dual-channel equivalent mode. At A, the difference between the channel values exceeds the discrepancy deadband tolerance range and the discrepancy timer starts. When the timer expires at B, a dual-channel discrepancy fault occurs and the inputs status bits are set low. At C, the values fall back within the discrepancy deadband and the discrepancy timer starts again. When the timer expires at D, and the values are still within the discrepancy deadband, the fault is cleared. At E, the difference between the channels exceeds the discrepancy deadband and the discrepancy timer starts. A discrepancy fault occurs again at F, when the timer expires and the difference between the channel values remains greater than the discrepancy deadband.
Figure 14 - Timing Diagram
250 ms
1
250 ms
250 ms
0
1
0
A B C
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 33
D
E F
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
IMPORTANT
Low pulses are offset.
Sensor 1
Sensor 2
Low pulses occur simultaneously, causing a fault.
Sensor 1
Sensor 2

Tachometer Mode

In Tachometer mode, the module measures digital pulses between 0 and 24V DC and converts them into a frequency or pulses per second. Therefore, you can use 24V DC proximity sensors or 5V DC encoders, for example. The Tachometer function does not sense direction, so using a differential encoder does not yield direction data. Tachometer mode could be used, for example, to measure rotational speed of an axis that is connected to a gear.
Tachometer mode can operate as SIL 2 single-channel. SIL 3 is achievable by using two sensors, the dual-low detection parameter, and user program logic. Safety reaction time is dependent on the signal frequency.
When using two sensors in a dual-channel configuration, position the sensors to make sure that the low pulses occur at different times. If you have configured the module for dual low detection and both sensors are low simultaneously, a fault is declared.
Figure 15 - Sensor Pulses in Dual-channel Configuration
Signal Measurement
The edge-to-edge time of the pulse determines the frequency of the signal in pulses per second. The frequency range is 1 Hz…1 kHz.
In Tachometer mode, you define how the signal is measured, either on the falling (non-inverted) or rising (inverted) edge. For NPN-style sensors (sensor sinks), use falling edge. For PNP-style sensors (sensor sources), use rising edge.
34 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Depending on your application, you need to install an appropriately sized pull-up resistor for falling-edge signal measurements or a pull-down resistor for rising-edge signal measurements.
Figure 16 - Pulse Trains
Ideal Pulse Train Falling and rising edges are well-defined.
Rising edges are not well-defined.
Falling e dges are no t well-defined.
Falling Edge Rising Edge
Pull-down resistor helps define falling edges.
Pull-up resistor helps define rising edges.
Falling edge measurement
Rising edge measurement
Off and On Signal Levels
Safety Inputs, Safety Outputs and Safety Data Chapter 2
You configure the Off and On levels, in 1V increments, for the signal. When selecting these levels, assume a tolerance of at least ±0.5V. For example, if you set the On Level to 10V, you can expect the module to recognize a signal between
9.5 and 10.5V as On. While the accuracy of the module when measuring the analog signal is good, Tachometer mode emphasizes a wider voltage range and speed to be able to measure pulse widths accurately.
Also consider the variance of the voltage output from your sensor when making the On and Off Level settings. If possible, we recommend selecting On Levels that are 2V below and Off Levels that are 2V above the actual thresholds of the expected output voltage level of your device.
Determining Frequency in Pulses per Second
The edge-to-edge time of either the falling or rising edge of the pulse determines the frequency in pulses per second.
One pulse, by itself, does not generate a non-zero frequency. To report a frequency of 1 Hz, two falling or rising edge pulses must be detected within 1 second. The module reports 0 Hz until 1 Hz is detected. For example, if a falling or rising edge is not detected for 1.02 seconds after the previous edge, the module reports 0 Hz.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 35
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
A B C
1 kHz
1 Hz
Frequenc y = 0
Actual values are
repor ted.
Monitor frequency via an
alternate method.
Overfrequency
condition can be
cleared.
Frequency = 1 Hz
Overfrequency bit is set to 0. Frequency = 1000 Hz
Overfrequency Bit Operation
When the frequency exceeds 1 kHz, the module reports a data value of 1 kHz, sets the Overfrequency status bit to 0, and latches it. While the Overfrequency bit is set to 0, you must use an alternate method to monitor the frequency of the system because the value reported by the module is latched at 1 kHz. Once you have verified that the frequency is lower than 1 kHz, you can reset the Overfrequency condition by setting the Reset Tach bit, which lets the module begin measuring the frequency of field pulses again.
If you set the Reset Tach bit while the frequency is still above 1 kHz, the Tachometer Overfrequency bit transitions to 1 (within range) momentarily. However, as soon as the module begins to measure pulses, it detects another overfrequency condition and immediately set the Tachometer Overfrequency bit to 0 again. The Reset Tach bit is edge-sensitive.
ATT EN TI ON : Before resetting the Overfrequency condition, you must use another method to verify that the actual frequency is lower than 1 kHz.
See Output Assemblies on page 213 Overfrequency bit.
Figure 17 - Overfrequency Operation
In Figure 17, the module reports a frequency of 0 Hz until the frequency of the system reaches 1 Hz at A, when the module begins reporting the actual value. At B, the frequency exceeds 1 kHz, the Overfrequency bit is set to 0, and the module continues to report a data value of 1 kHz. Between B and C, you must monitor the frequency by an alternate method because the value reported by the module is not always accurate. After C, the Overfrequency condition can be cleared, provided you have used an alternate method to verify that the actual frequency is below 1 kHz.
for more information on resetting the
36 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
44096
X
Y
OUT
On
Off

Safety Outputs (1734-OB8S and 1734-OBV2S)

Read this section for information about safety outputs.

Safety Output with Test Pulse

When the safety output is on, the safety output can be configured to pulse test the safety output channel. By using this function, you can continuously test the ability of the safety output to remove power from the output terminals of the module. If an error is detected, the safety output data and individual safety output status turn off.
Figure 18 - Test Pulse in a Cycle
For the 1734-OB8S and 1734-OBV2S modules, the pulse width (X) is typically 475 μs; the pulse period (Y) is typically 575 ms.
To help prevent the test pulse from causing the connected device to malfunction, pay careful attention to the input response time of the output device.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 37
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
ON
OFF
OUT0
Safety Output 0, 1 Status
OUT0
OUT1
OUT1
Safety Output 0, 1 Status
Fault Detection
Error Detected
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Normal Operation
Safety I/O Network Data Sent to the Controller
Safety I/O Network Data Sent to the Controller

Dual-channel Mode

When the data of both channels is in the on state, and neither channel has a fault, the outputs are turned on. The status is normal. If a fault is detected on one channel, the safety output data and individual safety output status turn off for both channels.
Figure 19 - Dual-channel Setting (Not to Scale)
38 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
ON
OFF
OUT0
Safety Output 0 Status
OUT0
Safety Output 0 Status
Fault Detection
Error Detected
ON
OFF
ON
OFF
ON
OFF
Normal Operation
Safety I/O Network Data Sent to the Controller
Safety I/O Network Data Sent to the Controller

Single-channel Mode, 1734-OB8S Only

When the data of the channel is in the on state, and does not have a fault, the output is turned on. The status is normal. If a fault is detected on the channel, the safety output data and individual safety output status turn off.
Figure 20 - Single-channel Setting (not to scale)

Safety Output Fault Recovery

If a fault is detected, the safety outputs are switched off and remain in the off state. Follow this procedure to activate the safety output data again.
1. Remove the cause of the error.
2. Command the safety output (or safety outputs) into the safe state.
3. Allow the output-error latch time to elapse.
After these steps are completed, the I/O indicator (red) turns off. The output data can now be controlled.
Stuck high faults require a module power reset to clear the error.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 39
Chapter 2 Safety Inputs, Safety Outputs and Safety Data
TIP
1
2
3
4

Muting Lamp Operation (1734-IB8S)

Beginning with Firmware Revision 1.002, the operation of the muting status bits for the test outputs T1 and T3 has changed. Test outputs T1 and T3 are controlled by your PLC processor program to illuminate a muting lamp. Muting lamp status is monitored with a test that runs periodically during every test interval to detect a burned-out lamp. The test runs repeatedly when the test output is commanded on. Figure 21 explains how muting lamp operation, status, and fault detection are monitored.
The lamp test interval is 3 seconds. Two consecutive failed lamp tests are required to declare a burned-out lamp condition. The lamp test does not always run immediately after the test output is energized. It starts at the next 3-second interval. To allow time for two consecutive test intervals, program a minimum Test Output On Time of 6 seconds.
Figure 21 - Muting Lamp Timing Diagram
Ta b l e 4 shows the expected behavior of the muting status for test outputs T1 and
T3. Keep these points in mind as well:
When power is applied to the 1734-IB8S module, and T1 or T3 remains commanded off, the muting status defaults to on.
40 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Safety Inputs, Safety Outputs and Safety Data Chapter 2
IMPORTANT
This bit operation is designed to help prevent erroneous muting instruction faults from the GuardLogix controller. This bit status is not always the true indication of a burned-out lamp.
Before checking the state of the corresponding muting status, be sure that the test output is commanded on. Once the test output is commanded on, a maximum time of 6 seconds is required for the module to detect a burned-out lamp.
If a muting lamp circuit is open when power is applied to the module, the condition is detected when the test output is commanded on.
When a lamp burns out and is replaced, the fault (muting status bit) returns to the normal condition, independent of the state of the test output.
Table 4 - Muting Status Bit Operation

I/O Status Data

Tes t Outp ut Commanded State
ON Bad (open circuit) 0 Repair lamp.
ON Good 1 Normal condition. Lamp is operating properly.
OFF Bad (open circuit) 0 If lamp remains OFF after T1/T3 output cycled, repair lamp.
OFF Good 1 Normal condition.
Lamp Condition Muting
Status Bit
Description
In addition to I/O data, the module provides status data for monitoring the I/O circuits. The status includes diagnostic data that the controllers can read with 1 = ON/Normal and 0 = OFF/Fault/Alarm.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 41
Chapter 2 Safety Inputs, Safety Outputs and Safety Data

Digital I/O Status Data

The following data is monitored:
Individual Point Input Status
Combined Input Status
Individual Point Output Status
Combined Output Status
Individual Test Output Status
Individual Output Monitor (actual ON/OFF state of the outputs)
Individual Point status indicates whether each safety input, safety output, or test output is normal (normal: ON, faulted: OFF). For fatal errors, communication connections can be broken, so the status data cannot be read. Status bits are OFF in the controller data table when the connection is lost.
Combined status is provided by an AND of the status of all safety inputs or all safety outputs. When all inputs or outputs are normal, the respective combined status is ON. When one or more of them has an error, the respective combined status is OFF. This status is known as the combined safety input status or combined safety output status.

Analog I/O Status Data

Individual input status indicates whether each analog input point is normal (ON) or faulted (OFF). In addition, the following diagnostic data is monitored:
User 24V Supply Overrange or Underrange
Sensor Power Overcurrent or Undercurrent
Channel Signal Overrange or Underrange
Broken Wire Detected (4…20 mA current mode)
Single-channel Discrepancy Error (channel fault)
In SIL 2 or SIL 3 operation, a single-channel discrepancy error occurs when both measurements (internal to the module) of the same input signal are not within tolerance. If a single-channel discrepancy occurs, indicating a problem with the module, input status is set to zero and a zero input value is reported for that channel.
SIL 3 Dual-channel Discrepancy Error (channel fault)
AlarmsHigh High and Low Low Alarm Overrange or UnderrangeHigh and Low Alarms Overrange or UnderrangeDual-channel Tachometer Dual Low Inputs DetectedTachometer Frequency Overrange or Underrange
The alarm status is reported in the Alarm Status attribute for each channel.
42 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Chapter 3
TIP

Guidelines for Placing Power Supplies and Modules in a System

Top ic Pag e
Choosing a Power Supply 43
Power Supply Examples 45
Placing Series A Digital and Analog Modules 47

Choosing a Power Supply

The POINTBus™ backplane includes a 5V communication bus and field power bus that get their power from a communication adapter or expansion power supplies. All POINT I/O™ modules are powered from the POINTBus backplane by either the adapter or expansion power supply. POINT I/O adapters have built-in power supplies. Use the information and examples in this chapter to determine if you need an expansion power supply in your system.
ATT EN TI ON : To comply with the CE Low Voltage Directive (LVD), this equipment, and all connected I/O, must be powered from a safety extra low voltage (SELV) or protected extra low voltage (PELV) compliant source.
For UL-compliant applications, the 1734-IB8S, 1734-OB8S, and 1734-OBV2S modules, and all connected I/O, must be powered from a SELV- or PELV-compliant power source that is rated 150VA maximum.
For UL-compliant applications, the 1734-IE4S module, the module’s field power and connected I/O devices must be powered from a Class 2-compliant, limited voltage/limited current power source.
The following Rockwell Automation® 1606 power supplies are SELV- and PELV-compliant, and they meet the isolation and output hold-off time requirements of the SmartGuard™ 600 controller:
1606-XLP30E
1606-XLP50E
1606-XLP50EZ
1606-XLP72E
1606-XLP95E
1606-XLDNET4
1606-XLSDNET4
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 43
Chapter 3 Guidelines for Placing Power Supplies and Modules in a System
IMPORTANT
Follow the safety precautions that are listed in Chapter 1 and the wiring guidelines that are described in Chapter 4 the system.
To choose which types of power supplies meet your requirements, you must consider the power consumption requirements for the 5V and 24V bus when designing a POINTBus backplane.
Choose from these power supplies for the POINTBus backplane and field power:
Use the 1734-EP24DC expansion power supply to provide an additional 10 A of 24V DC field power and provide an additional 1.3 A of 5V current to the I/O modules to the right of the power supply.
Use the 1734-FPD field power distributor to provide an additional 10 A of 24V DC field power, and to pass through all POINT I/O backplane signals including the 5V bus supplied to the left, without providing additional POINTBus backplane power. This action lets you isolate field power segments.
Use the 1734-EPAC expansion power supply (for standard I/O modules) to provide an additional 10 A of 120/240V AC field power and provide an additional 1.3 A of 5V current to the I/O modules to the right of the power supply.
before connecting a power supply to
If you use the 1734-EPAC expansion power supply to the left of the POINT Guard I/O™ modules, you must use a 1734-FPD field power distributor or 1734-EP24DC expansion power supply. These distributors are used to isolate POINT Guard I/O field power from the AC field supply.
5V POINTBus power is required to establish and maintain communication (connection) between the module and the controller.
See the POINT I/O Selection Guide, publication 17 information on compatible power supplies.
34-SG001, for more
44 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Guidelines for Placing Power Supplies and Modules in a System Chapter 3
IMPORTANT

Power Supply Examples

Use these valid power-supply example configurations to help you understand various combinations of power supplies that can fit your system:
Example 1: Isolating Field Power Segments on page 45
Example 2: POINT Guard I/O Used with AC I/O Modules on page 46
These examples are for illustrative purposes only, to help you understand various power sourcing concepts.
You must define the requirements for segmenting field and bus power in your application.
POINT Guard I/O does not require separate field-bus power usage, that is, separate power supplies for the 1734-IB8S, 1734-OB8S, 1734-OBV2S, or 1734-IE4S modules. This step is optional.
POINT Guard I/O does not require separate POINTBus (communication) power-supply usage, which separates it from any other POINT I/O modules, except when additional POINTBus power is required.
Do not apply AC voltage to POINT Guard I/O modules.

Example 1: Isolating Field Power Segments

This power supply example uses a 1734-EP24DC expansion power supply and 1734-FPD field power distributor to illustrate mixing standard POINT I/O and safety POINT Guard I/O modules. The example illustrates the mixing standard while creating separate groups for input and output modules, along with digital and analog modules.
EtherNet/IP Adapter
Standard I/O
Standard I/O
1734-AENT
5V and 24V Supply for
Standard I/O
Modules
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
5V Supply for All Safety
Modules and 24V Supply
1734-EP24DC
for Safety Inputs
Group 2 Group 3 Group 4 Group 5Group 1
5V5V 5V
1734-IE4S
1734-IE4S
1734-IB8S
24V24V 24V 24V
24V Supply for
Safety Outputs
1734-OB8S
24V
1734-FPD
1734-IB8S
1734-OBV2S
24V Supply for
Analog Inputs
1734-FPD
Safety
1734-EP24DC
5V and 24V Supply for
Additional I/O
Modules (option)
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-IB8S
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 45
Chapter 3 Guidelines for Placing Power Supplies and Modules in a System
Standard I/O
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-EPAC
1734-EP24DC
1734-AENT
EtherNet/IP Adapter
Standard I/O
Standard I/O
Standard I/O
Standard I/O
1734-IB8S
1734-IB8S
1734-OBV2S
1734-OB8S
1734-IE4S
5V 5V
Group 2Group 1
120V AC
5V and 120V AC
Supply
5V and 24V Supply for
Safety Inputs and Outputs
5V and 24V Supply
for Standard I/O
Modules
24V
24V
5V
Group 3

Example 2: POINT Guard I/O Used with AC I/O Modules

This power supply example uses 1734-EP24DC and 1734-EPAC expansion power supplies to illustrate mixing standard POINT I/O and safety POINT Guard I/O modules, while creating a separate power group for AC I/O modules.
46 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Guidelines for Placing Power Supplies and Modules in a System Chapter 3

Placing Series A Digital and Analog Modules

Always install modules in accordance with their specified operating temperature ratings, as listed in Appendix C
, and provide a minimum of 5.08 cm (2 in.)
clearance above the modules.
Limit ambient temperature operation to 40 °C (104°F) if Series A POINT Guard I/O modules are used without 1734-CTM spacer modules.
Figure 22 - Placing Series A Digital Modules for up to 40 °C (104 °F) Operation
5.08 cm (2 in.)
1734-AENT
1734-IB8S/A
1734-OB8S/A
1734-IE4S/A
1734-IB8S/A
1734-IE4S/A
1734-IE4S/A
In any system where you have any Series A POINT Guard I/O modules, use a 1734-CTM spacer between every POINT Guard I/O module with ambient operation between 40 °C (104 °F) and 55 °C (131 °F).
Insert a 1734-CTM module next to each standard I/O module (gray) if the thermal dissipation specification of that module is more than 1 W.
Figure 23 - Placing Series A Digital and Analog Modules for Operation from 40 °C (104 °F)…55 °C (131 °F) max.
5.08 cm (2 in.)
1734-AENT
1734-IB8S/A
1734-OB8S/A
1734-IE4S/A
1734-IB8S/A
1734-IE4S/A
1734-IE4S/A
1734-CTM
When using Series A POINT Guard I/O modules in your system limit the power supply to 24V DC maximum, to limit the Series A POINT Guard I/O thermal dissipation of the module.
See System Temperature Derating When a 1734-IE4S Module Is Used on
page 194 for more information.
ATTENTION: Vertical orientation requires careful attention to design details and panel layout so that all modules in the stack must operate within their rated operating temperature range.
For Vertical installations, be sure that 1734-CTM spacer modules are installed next to any Series A POINT Guard IO modules operating above 40 °C (104 °F) ambient.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 47
Chapter 3 Guidelines for Placing Power Supplies and Modules in a System
1734-AENT
1734-OB8S/B
1734-IB8S/B
1734-OB8S/B
1734-IB8S/B
1734-OB8S/B
1734-IB8S/B
5.08 cm (2 in.)

Placing Series B Digital Modules

Always install modules in accordance with their specified operating temperature ratings, as listed in Appendix C
, and provide a minimum of 5.08 cm (2 in.)
clearance above the modules.
When used in a system that contains only Series B Guard I/O modules, series B Guard I/O modules are used without 1734-CTM spacer modules in environments with ambient operation up to 55 °C (131 °F).
See Technical Specifications for Series B Modules on page 185
for Series B POINT Guard I/O module derating requirements for every module with ambient operation between 40
Figure 24 - Placing Series B Digital Modules for up to 55 °C (131 °F) Operation
°C (104 °F) and 55 °C (131 °F).
ATT EN TI ON : Vertical orientation requires careful attention to design details and panel layout so that all modules in the stack operate within their rated operating temperature range.
48 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018

Install the Module

Slide-in Writable Label
Insertable I/O Module
31867-M
Module Locking Mechanism
Mounting Base
Top ic Pag e
Precautions 50
Install the Mounting Base 53
Connect the Module to the Mounting Base 55
Connect the Removable Terminal Block 56
Remove a Mounting Base 57
Wire Modules 57
Connection Details 61
Wiring E xample s 63
Chapter 4
Figure 25 - POINT Guard I/O™ Modules
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 49
Chapter 4 Install the Module

Precautions

Follow these precautions for use.
ATT EN TI ON : This equipment is certified for use only within the surrounding air temperature range of -20…+55 °C (-4…+131 °F). The equipment must not be used outside of this range.
ATT EN TI ON : Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
ATT EN TI ON : if you use multiple power sources when using the 1734-IE4S module, do not exceed the specified isolation voltage.

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
Industrial Automation Wiring and Grounding Guidelines, publication
NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
1770-4.1, for more installation requirements.
50 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4

European Hazardous Location Approval

The following applies to products marked II3G:
Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 2014/34/ EU. See the EC Declaration of Conformity at: http://www.rockwellautomation.com/products/certification for details.
The type of protection is "Ex nA IIC T4 Gc" according to EN 60079-15.
Comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010,
reference certificate number DEMKO09ATEX0919970X.
Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
May have catalog numbers followed by a "K" to indicate a conformal coating option.
WARNING: Special Conditions for Safe Use
This equipment must be used within its specified ratings as defined by
Rockwell Automation.
This equipment shall be mounted in an ATEX Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with EN 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.
Provision must be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when applied in Zone 2 environments.
The instructions in the user manual shall be observed.
This equipment must be used only with ATEX-certified Rockwell Automation
terminal bases.
Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 51
Chapter 4 Install the Module

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
Do not disconnect equipment unless power
has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l’utilisation de cet équipement en environnements dangereux.
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
Couper le courant ou s'assurer que l'environnement
est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Prevent Electrostatic Discharge

ATT EN TI ON : This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.
52 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
IMPORTANT
IMPORTANT

Mount the Module

Follow these guidelines when installing a module:
Use the module in an environment that is within the general specifications.
Use the module in an enclosure rated at IP54 (IEC60529) or higher.
Use DIN rail that is 35 mm (1.38 in.) wide to mount the terminal base in the
control panel.
Place other heat sources an appropriate distance away from the module to maintain ambient temperatures around the module below specified maximums.
You can mount your module horizontally or vertically.
To mount the module, you must install the mounting base, connect the module to the mounting base, and then connect the removable terminal block.

Install the Mounting Base

The mounting base assembly (catalog number 1734-TB or 1734-TBS) consists of a mounting base and a removable terminal block. Alternatively, you can use the POINT I/O™ one-piece mounting base (catalog number 1734-TOP, 1734­TOPS, 1734-TOP3, or 1734-TOP3S).
You need two mounting base assemblies for each POINT Guard I/O module. Do not use 1734-TB3 or 1734-TB3S mounting base assemblies.
WARNING: For ATEX applications, do not exceed 31.2V DC maximum.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 53
Chapter 4 Install the Module
IMPORTANT
TIP
Slide the mounting base to let the interlocking side pieces engage the adjacent module or adapter.
31868-M
Follow these steps to install the mounting base.
You need two mounting base assemblies for each POINT Guard I/O module. Do not use 1734-TB3 or 1734-TB3S mounting base assemblies.
1. Position the mounting base as shown in the illustration below step 2
.
2. Slide the mounting base down, allowing the interlocking side pieces to engage the adjacent module, power supply, or adapter.
3. Press firmly to seat the mounting base on the DIN rail until the mounting base snaps into place.
In high vibration environments, install slide locks helps prevent the movement of the mounting base along the DIN rail.
See the terminal base installation instructions for detailed information on installation and removal. Always follow instructions and torque specifications in terminal base installation instructions. See Additional Resources on page 10 terminal base installation publications.
54 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
for
Install the Module Chapter 4
Mounting Base Assembly
Keyswitch
Lockin g Mechanism

Connect the Module to the Mounting Base

Install the module before or after installing the mounting base.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Repeated electric arcs causes excessive wear to contacts on both the module and its mating connector. Worn contacts can create electrical resistance that can affect module operation.
1. With a screwdriver, rotate the keyswitches on the mounting base clockwise until the number required for the type of module aligns with the notch in the base.
Monitor which mounting base gets installed on the left and right of each module.
Cat. No. Key 1 (Left) Key 2 (Right)
1734-IB8S 8 1
1734-OB8S 8 2
1734-OBV2S 8 2
1734-IE4S 8 3
2. Verify the DIN rail (orange) lock screw is in the horizontal position, note that you cannot insert the module if the mounting-base locking mechanism is unlocked.
3. Insert the module straight down into the two side-by-side mounting bases, press to secure, and lock the module into place.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 55
Chapter 4 Install the Module

Connect the Removable Terminal Block

If a removable terminal block (RTB) is supplied with your mounting base assembly, you must remove it by pulling up on the RTB handle. This action lets you remove and replace the base as necessary without removing any of the wiring.
WARNING: When you connect or disconnect the removable terminal block
(RTB) with field-side power applied, an electric arc can occur. This arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
To reinsert the RTB, follow these directions.
1. Insert the RTB end opposite the handle into the base unit, note that this end has a curved section that engages with the mounting base.
2. Rotate the terminal block into the mounting base until it locks itself in place.
3. If an I/O module is installed, snap the RTB handle into place on the module.
56 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4

Remove a Mounting Base

To remove a mounting base, you must remove any installed module and the module that is installed in the base to the right. If the mounting base has a removable terminal base (RTB), unlatch the RTB handle on the I/O module and pull on the handle to remove the RTB.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This arc could cause an explosion in hazardous location installations. Be sure to remove power or that the area is nonhazardous before proceeding.
1. To remove it from the base, pull up on the I/O module.
2. Remove the module to the right of the base you are removing, note that
the interlocking portion of the base sits under the adjacent module.
3. Use a screwdriver to rotate the orange DIN rail lock screw on the mounting base to a vertical position, which releases the locking mechanism.

Wire Modules

4. Lift the mounting base off the DIN rail.
Follow these guidelines when wiring the modules.
Do not route communication, input, or output wiring with conduit that contains high voltage. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Wire correctly after confirming the signal names of all terminals.
Use shielded cable for analog and tachometer inputs.
When using the sensor power supply on the 1734-IE4S module, do not
connect an external power supply to the sensor.
If you use the 1734-IE4S sensor power supply of the module to power your input devices, you are responsible for verifying that your application operates properly with the diagnostic features of this output.
Tighten screws for communication and I/O connectors correctly.
When using analog inputs, wire only to voltage or only to current inputs,
not both. If you mix input types, it can induce noise on the input measurements.
.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 57
Chapter 4 Install the Module
ATT EN TI ON : Wire the POINT Guard I/O modules properly so that 24V DC line
does not touch the safety outputs accidentally or unintentionally. Do not connect loads beyond the rated value to safety outputs. Wire conductors correctly and verify operation of the module before placing the
system into operation. Incorrect wiring can lead to loss of safety function. Do not apply DC voltages that exceed the rated voltages to the module. Do not connect a power source to the sensor power supply in the 1734-IE4S
module or you could blow an internal fuse. When an internal fuse is blown, the module is inoperative.
Disconnect the module from the power supply before wiring. If wiring is performed while power is supplied, devices that are connected to the module can operate unexpectedly.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This arc could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
This equipment must be used within its specified ratings that Rockwell Automation has defined.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication
1770-4.1, for more information.
58 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
Where: T0 = Test Output 0 T1M = Test Output 1 with Muting T2 = Test Output 2 T3M = Test Output 3 with Muting I0…I7 = Inputs 0…7 COM = Supply Common
1734-TOP and 1734-TB Bases Shown
1734-TOP and 1734-TB Bases Shown
Where: O0…O7 = Safety Outputs 0…7 COM = Supply Common
COM
COM
COM
COM
O0
O1
O4
O5
O2
O3
O6
O7
1
3
0
2
4
5
6
7
1
3
5
7
0
2
4
6
COM
COM
COM
COM
1734-TOP and 1734-TB Bases Shown
Where: Channels O0 and O1 = safety output bipolar pair Channels O2 and O3 = safety output bipolar pair Channels O0 and O2 = sourcing outputs Channels O1 and O3 = sinking outputs COM = Sensor Power supply common V = Sensor Power supply

Terminal Layout

Figure 26, Figure 27, Figure 28, and Figure 29 on page 60 show the field wiring
connections for the POINT Guard I/O modules.
Figure 26 - 1734-IB8S Field Connections
I0
I2
COM
T0
I1
0
I3
2
COM
4
T1M
6
I4
1
I6
3
COM
5
T2
7
I5
0
I7
2
COM
4
T3M
6
Figure 27 - 1734-OB8S Field Connections
1
3
5
7
Figure 28 - 1734-OBV2S Field Connections
O0
O0
COM
V
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 59
O1
O1
COM
V
O2
O3
O2 O3
COM
COM
VV
Chapter 4 Install the Module
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
COM COM COM COM
S0 S1 S2 S3
S0 S1 S2 S3
1734-TOP3 Base Shown
Where: V0…V3 = Voltage inputs 0…3 I0…I3 = Current inputs 0…3 COM = Supply Common S0…S3 = Sensor power terminals
Figure 29 - 1734-IE4S Field Connections
60 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
I0 I1 T0 T1
24V DC
I0 I1 T0 T1
I0 I1 T0 T1

Connection Details

See the tables that show input device connection methods and their safety categories.
Connected Device Test Pulse from
Tes t Ou tput
Push Button No Connect the push button between 24V
Yes Connect the push button between I0
Connection Schematic Diagram Safety
DC and I0.
and T0. T0 must be configured as test pulse.
Category
1
2
Emergency stop button Door monitoring switch
No Connect the devices between T0 and I0
and I1, note that T0 is configured for 24V power supply.
Connect the devices between 24V DC and I0 and I1.
Yes Connect the device between I0 and T0,
and I1 and T1.
3
I0 I1 T0 T1
I0 I1 T0 T1
24V DC
4
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 61
Chapter 4 Install the Module
OSSD2
OSSD1
I0 I1 T0 T1In -
24V
DC
Com
OSSD2
OSSD1
Connected Device Test Pulse from
Connection Schematic Diagram Safety
Tes t Ou tput
Light Curtain Yes Connect the OSSD1 and OSSD2 to I0 and
I1, respectively. Connect the 24V power supply commons.
Category
3 or 4 based on light curtain being used
62 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
1734-TB, 1734-TOP, 1734­TOP3 Bases Sh own
Only with the 1734-TOP3 base.

Wiring Examples

Read this section for examples of wiring by application. See catalog number details for the appropriate module.

Emergency Stop Dual-channel Devices

This example shows wiring and controller configuration when using a digital POINT Guard I/O module with an emergency stop button and gate monitoring switch that have dual-channel contacts. When used in combination with the programs in a safety controller, this wiring is safety Category 4 (emergency stop button) and safety Category 3 (gate monitoring switch).
Figure 30 - 1734-IB8S POINT Guard I/O Module Wiring (dual-channel contacts)
IO
I2
COM
TO
I1
I3
COM
T1M
I4
I6
COM
T2
I5
I7
COM
T3M
COM
TO
Controller Configuration
Safety Input 0 Safety Input 0 Channel Mode Test Pulse from Test Output
Safety Input 1 Safety Input 1 Channel Mode Test Pulse from Test Output
Safety Input 2 Safety Input 2 Channel Mode S afety Input
Safety Input 3 Safety Input 3 Channel Mode S afety Input
Test Output 0 Test Output 0 Mode Pulse Test Output Test Output 1 Test Output 1 Mode Pulse Test Output Test Output 2 Test Output 2 Mode Power Supply Output Test Output 3 Test Output 3 Mode Power Supply Output
Parameter Name Configuration Setting
Sa fe ty I npu t 0 Tes t So urc e Test O ut put 0 Dual-channel Safety Input 0/1 Mode Dual-channel Equivalent Dual-channel Safety Input 0/1 Discrepancy Time 100 ms (application dependent)
Sa fe ty I npu t 1 Tes t So urc e Test O ut put 1
Sa fe ty I npu t 2 Tes t So urc e Test O ut put 2 Dual-channel Safety Input 2/3 Mode Dual-channel Equivalent
Sa fe ty I npu t 3 Tes t So urc e Test O ut put 3
COM
T1M
COM
T2
COM
T3M
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 63
Chapter 4 Install the Module
COM COM COMCOM
COM COM CO MCOM
00 01 04 05
02 03 06 07
K1K1
M
Where: O0…O7 = Safety Outputs COM = Com mon

Single-channel Safety Contactor

This example shows wiring and controller configuration when using a 1734-OB8S digital POINT Guard I/O module with one safety contactor.
When used in combination with the programs of the safety controller, this circuit configuration is safety Category 2.
Figure 31 - 1734-OB8S POINT Guard I/O Module Wiring (single safety contact)
Controller Configuration
Safety Output 0 Safety Output 0 Point Mode Safety Pulse Test
Parameter Name Configuration Setting
Point Operation Type Single Channel
64 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
Where: O0…O7 = Safety Outputs COM = Co mmon

Dual-channel Safety Contactors

This example shows wiring and controller configuration when using a 1734-OB8S digital POINT Guard I/O module with redundant safety contactors.
When used in combination with the programs of the safety controller, this circuit configuration is safety Category 4. Additional wiring, such as monitoring feedback, can be required to achieve safety Category 4.
Figure 32 - 1734-OB8S POINT Guard I/O Module Wiring (redundant safety contacts)
00 01 04 05
K1K1
K2K2
02 03 06 07
M
Controller Configuration
Safety Output 0 Safety Output 0 Point Mode Safety Pulse Test
Safety Output 1 Safety Output 1 Point Mode Safety Pulse Test
Parameter Name Configuration Setting
Point Operation Type Dual-channel
COM COM COMCOM
COM COM CO MCOM
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 65
Chapter 4 Install the Module
1734-IB8S
1734-OBV2S
COM
COM
COMCOM
V
O0 O1 O2 O3
K1
M
COM COM
I0 I1
I2 I3
V V V V T1M
K1
O0 O1 O2 O3
K1
1734-IB8S
1734-OBV2S

Bipolar Safety Outputs

These examples show how to wire a 1734-OBV2S output module with an input module to meet PLe and PLd safety requirements.
Figure 33 - 1734-OBV2S Dual Safety Output Wiring - PLe
M
Controller
K1K1
K2K2
O0 O1 O2 O3
O0 O1 O2 O3
COM
COM
V
V V V T0 T1M
COM COM
Parameter Name Configuration Setting
I0 I1
I2 I3
COM COM
Configuration
Safety output 0 Safety output 0 point mode Safety pulse test Safety output 1 Safety output 1 point mode Safety pulse test Safety input 1 Safety input 1 point operation type Single
Safety input 1 point mode Safety pulse test Safety input 1 test source 1
Test output 1 Test output 1 point mode Pulse test
Figure 34 - 1734-OBV2S Dual Safety Output Wiring - PLd
K1
K2
Controller
Parameter Name Configuration Setting
Configuration
Safety output 0 Safety output 0 point mode Safety pulse test Safety output 1 Safety output 1 point mode Safety pulse test Safety input 1 Safety input 1 point operation type Single
Safety input 1 point mode Safety pulse test
Test output 1 Test output 1 point mode Pulse test
Safety input 1 test source 1
66 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
IMPORTANT
IMPORTANT

Safety Analog Input Wiring

The following sections contain important guidelines for wiring safety analog inputs and wiring examples for the 1734-IE4S module.
Guidelines for Wiring Safety Analog Inputs
Follow these guidelines when wiring your safety analog inputs.
For eight terminal connections, either the 1734-TOP or 1734-TB terminal base can be used. For all 12 terminal connections, only the 1734-TOP3 base can be used. When using a 1734-TOP3 base, both of the COM terminals and both of the Sensor Power terminals for each channel are internally connected. The FE terminal connection that is shown on the diagrams represents a grounding lug on the panel or terminal connection to the DIN rail.
If the sensor has a digital output for use with Tachometer mode, it must be either a push-pull type output or have appropriate pull-up or pull-down resistors for NPN or PNP sensors. The analog input module does not provide the low impedance of these pull-up or pull-down resistors.
See Figure 47
and Figure 48 on page 74 for examples.
You must verify the behavior of your 3-wire sensor to make sure that if it loses its ground connection, the signal is 0 (safe state) at the module input when the fault occurs.
To obtain SIL 3, Cat. 3 or Cat.4, you must make sure that the analog input signals cannot short together or that the two sensors are installed to provide signals that are offset from one another. When the module is configured as the source for sensor power, a short-circuit is detected at powerup (Cat. 2). However, when an external power supply is used, another means must detect this fault.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 67
Chapter 4 Install the Module
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
FE
S1 S2 S3
SIL2 or SIL 3
2-wire Sensor
1734-TB Terminal Bases
Signal (I)
+24V
Cable Shield
For analog voltage-output sensors, the signal levels for operation for the application must be outside the signal level when the signal is not present, for example, when the wire is broken.
See Figure 47
and Figure 48 on page 74 for tachometer wiring detail.
SIL 2 3-wire Sensor
1734-TB Terminal Bases
Signal (V)
+24V
Cable Shield
Signal Return
Safety Analog Input Wiring Examples
Figure 35 - 2-wire Current (4…20 mA) Sensor (SIL2 or SIL 3)
Figure 36 - 3-wire Voltage or Tachometer Sensor (SIL 2)
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
S1 S2 S3
FE
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
68 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Figure 37 - 3-wire Current Sensor (SIL 2)
For 0…20 mA analog current-output sensors, the signal levels for operation for the application must be outside the signal level when the signal is not present, for example, when the wire is broken.
SIL 2 3-wire Sensor
1734-TB Terminal Bases
Signal (I)
+24V
Cable Shield
Signal Return
FE
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
COM COM COM COM
S0 S1 S2 S3
S0 S1 S2 S3
Signal Return and Common are at the same potential. See Figure 47
and Figure 48 on page 74 for tachometer wiring detail.
SIL 2 4-wire Sensor
1734-TOP3 Terminal Bases
Signal (V)
+24V
Cable Sh ield
Signal Return
Common
Install the Module Chapter 4
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
Figure 38 - 4-wire Voltage or Tachometer Sensor (SIL 2)
S0
S1 S2 S3
FE
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 69
Chapter 4 Install the Module
FE
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
COM COM COM COM
S0 S1 S2 S3
S0 S1 S2 S3
Signal Return and Common are at the same potential.
SIL 2
4-wire Sensor
1734-TOP3 Terminal Bases
Signal (I)
+24V
Cable Sh ield
Signal Return
Common
Field sensors are monitoring the same signal in a redundant configuration. You must configure a safety deadband between the two signals to achieve SIL 3.
SIL 2
2-wire
Sensor
1734-TB Terminal Bases
Signal (I)
+24V
Cable Shield
Cable Shield
+24V
SIL 2
2-wire
Sensor
Signal (I)
Figure 39 - 4-wire Current Sensor (SIL 2)
Figure 40 - 2-wire Current (4…20 mA) Sensor (SIL 3)
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
S1 S2 S3
FE
FE
70 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Figure 41 - 3-wire Voltage or Tachometer Sensor (SIL 3)
This wiring configuration can also be used for SIL 2 redundant Tachometer mode. For analog voltage-output sensors, the signal levels for operation for the application must be outside the signal level when the signal is not present, for example, when the wire is broken. Field sensors are monitoring the same signal in a redundant configuration.
You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2
3-wire
Sensor
1734-TB Terminal Bas es
Signal (V)
+24V
Cable Shield
Cable Shield
+24V
SIL 2
3-wire
Sensor
Signal (V)
Signal Return
Signal Return
See Figure 47
and Figure 48 on page 74 for tachometer wiring detail.
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
FE
S1 S2 S3
FE
For 0…20 mA analog current-output sensors, the signal levels for operation for the application must be outside the signal level when the signal is not present, for example, when the wire is broken.
Field sensors are monitoring the same signal in a redundant configuration. You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2 3-wire Sensor
1734-TB Terminal Bases
Signal (I)
+24V
Cable Shield
Cable Sh ield
+24V
SIL 2 3-wire Sensor
Signal (I)
Signal Return
Signal Return
Install the Module Chapter 4
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
Figure 42 - 3-wire Current Sensor (SIL 3)
S0
S1 S2 S3
FE
FE
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 71
Chapter 4 Install the Module
This wiring configuration may also be used for SIL 2 redundant Tachometer mode. Signal Return and Common are at the same potential. Field sensors are monitoring the same signal in a redundant configuration.
You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2 4-wire Sensor
1734-TOP3 Terminal Bases
Signal (V)
+24V
Cable Shield
Signal Return
Common
SIL 2 4-wire Sensor
Signal (V)
+24V
Signal Return
Common
Cable Sh ield
See Figure 47 and Figure 48 on page 74 for tachometer wiring detail.
FE FE
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
COM COM COM COM
S0 S1 S2 S3
S0 S1 S2 S3
Signal Return and Common are at the same potential. Field sensors are monitoring the same signal in a redundant configuration. You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2 4-wire
Sensor
1734-TOP3 Terminal Bases
Signal (I)
+24V
Cable Shield
Signal Return
Common
SIL 2
4-wire Sensor
Signal (I)
+24V
Signal Return
Common
Cable Shield
Figure 43 - 4-wire Voltage or Tachometer Sensor (SIL 3)
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0 S1 S2 S3
COM COM COM COM
S0 S1 S2 S3
FE FE
Figure 44 - 4-wire Current Sensor (SIL 3)
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
72 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Install the Module Chapter 4
IMPORTANT
V0
DC
V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
FE
S1 S2 S3
+
-
Signal Return and Common are at the same potential.
1734-TB Terminal Bases
Signal (V)
+24V
Cable Sh ield
Signal Return
4-wire
Sensor
See Figure 47
and Figure 48 on page 74 for tachometer wiring detail.
V0
DC
V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0
FE
S1 S2 S3
+
-
Signal Return and Common are at the same potential.
1734-TB Terminal Bas es
Signal (V)
+24V
Cable Shield
Signal Return
4-wire Sensor
In the following two examples, the negative terminal of the sensor power supply and that of the 1734 terminal base COMMON must be at the same potential. Use of an external power supply limits diagnostics and increases susceptibility to noise.
You are responsible for making sure that the sensor is receiving appropriate power. Safety sensors that are not properly powered do not always deliver accurate signals to the analog input module.
Follow the Guidelines for Wiring Safety Analog Inputs on page 67
.
Figure 45 - 4-wire Voltage or Tachometer Sensor (SIL 2) with External Power Supply
Figure 46 - 4-wire Current Sensor (SIL 2) with External Power Supply
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 73
Chapter 4 Install the Module
Sinking Sensor
(NPN-type)
1734-TOP3 Terminal Bases
Metal Oxide or Carbon Composition
1k 2W
25
20
15
10
5
0
Edge-to-edge Time
Measured Here
1734-IE4S with Trigger = Falling Edge
Transistor Pull-down
Resistor Pull-up
Electronics
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
COM COM COM COM
S0 S1 S2 S3
S0 S1 S2 S3
1734-TOP3 Terminal Bases
Sourcing Sensor
(PNP-type)
Metal Oxide or Carbon Composition
1k 2W
25
20
15
10
5
0
Edge-to- edge Time
Measured Here
1734-IE4S with Trigger = Rising Edge
Resistor Pull­down
Transistor Pull-up
Electronics
Figure 47 - Safety Analog Input Wiring for Sinking Tachometer Sensor
V0 V1 V2 V3
I0 I1 I2 I3
COM COM COM COM
S0 S1 S2 S3
COM COM COM COM
S0 S1 S2 S3
Figure 48 - Safety Analog Input Wiring for Sourcing Tachometer Sensor
74 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Follow the Guidelines for Wiring Safety Analog Inputs on page 67.
Chapter 5
IMPORTANT
TIP

Configure the Module in a GuardLogix Controller System

Top ic Pag e
Set up the Module 75
Add and Configure the Ethernet Bridge 76
Add and Configure the 1734 Ethernet Adapter 76
Add and Configure Safety Digital Input Modules 80
Add and Configure Safety Digital Output Modules 89
Add and Configure Safety Analog Input Modules 94
Values and States of Tags 103
Configure Safety Connections 105
Configuration Ownership 106
Save and Download the Module Configuration 107

Set up the Module

When using a GuardLogix® controller on an EtherNet/IP™ network, configure the POINT Guard I/O™ modules by using the Logix Designer application.
Yo u must configure each point that is used as a safety input or output. By default, all safety input and output points are disabled.
If you need an Add-on Profile, visit the My Support website at
http://support.rockwellautomation.com/ControlFLASH/LogixProfiler.asp.
At the bottom of each dialog box, click Help for information about how to complete entries in that dialog box. At the bottom of warning dialog boxes, click Help for information about that specific error.
When first setting up your POINT Guard I/O modules on an EtherNet/IP network, perform the following steps.
1.
Add and Configure the Ethernet Bridge.
2.
Add and Configure the 1734 Ethernet Adapter.
3.
Add and Configure Safety Digital Input Modules.
Add and Configure Safety Digital Output Modules.
4.
5. Add and Configure Safety Analog Input Modules
.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 75
Chapter 5 Configure the Module in a GuardLogix Controller System

Add and Configure the Ethernet Bridge

Follow this procedure to add and configure the Ethernet bridge. In this example, we use a 1756 GuardLogix controller.
1. From the I/O Configuration tree, right-click 1756 Backplane, 1756-Axx, and choose New Module.
2. In the Select Modules dialog box, check Communication and Allen-Bradley®.
3. Choose an Ethernet module from the list and click Create.
In this example, we chose the 1756-EN2T bridge. These module revisions support CIP Safety™.
Cat. No. Compatible Major Revision
1756-EN2F 1 or later
1756-EN2T 1 or later
1756-ENBT 3 or later
1756-EN2TR 3 or later
1756-EN3TR 3 or later
1768-ENBT 3 or later
4. Specify the properties for the new module.
a. In the Name field of the New Module dialog box, type the name of the
Ethernet bridge. b. In the Description field, type an optional description. c. In the IP address field, type the IP address. d. In the Slot field, choose the slot number.
76 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
5. To edit the Module Definition, click Change. a. In the Revision fields, choose the major and minor revisions. b. From the Electronic Keying pull-down menu, choose the appropriate
keying method.
Choose Description
Compatible Module Allows a module to determine whether it can emulate the module
Disable Keying None of the parameters in the physical module and module that is
Exact Match All parameters must match or the inserted module rejects a
that is defined in the configuration that is sent from the controller.
configured in the software must match.
Do not choose Disable Keying.
connection to the controller.
6. Click OK.
The I/O Configuration tree displays the Ethernet connection.

Add and Configure the 1734 Ethernet Adapter

1. Right-click the Ethernet connection and choose New Module.
2. On the Select Module dialog box, check Communication and
Allen-Bradley.
3. Choose an Ethernet adapter from the list and click Create.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 77
Chapter 5 Configure the Module in a GuardLogix Controller System
IMPORTANT
4. Specify the general properties of the Ethernet adapter.
a. In the Name field of the New Module dialog box, type the name of the
1734 Ethernet adapter. b. In the Description field, type a description, if desired. c. In the IP address field, type the IP address.
5. To edit the Ethernet adapter Definition, click Change.
.
a. In the Revision fields, choose the major and minor revisions.
1734-AENT adapter firmware must be major revision 3 or later to support POINT Guard I/O modules.
b. From the Electronic Keying pull-down menu, choose the appropriate
keying method.
Choose Description
Exact Match Module and type series must exactly match or the module is rejected by the
Compatible Module Controller checks module type and revision for compatibility. Compatible
Disable Keying Controller checks module type, but accepts any version. Do not choose Disable
controller.
modules that match or are newer are accepted.
Keying.
78 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
TIP
IMPORTANT
c. From the Connection pull-down menu, choose the appropriate
connection for the 1734 Ethernet adapter.
Choose Description
Listen Only Read or verify standard digital I/O data only, but does not control the modules.
None The adapter makes a direct connection to each of the module’s listed under the
Rack Optimization
(When you have multiple controllers, one controller is used to control and the other controllers are used to monitor.)
1734-AENT adapter in the I/O Configuration tree.
Standard digital I/O data is collected into one rack image.
POINT specialty, analog, or safety (POINT Guard I/O) modules do not use rack optimization.
If there are no standard digital I/O modules in your POINT I/O™ system, choose None.
d. From the Chassis Size pull-down menu, choose the number of
POINT I/O modules that are attached to the 1734 Ethernet adapter plus 1 for the 1734 Ethernet adapter.
Do not count terminal bases. Enter only the number of physical modules that are installed, plus 1 for the adapter. This number must match exactly. You cannot enter a higher number anticipating future expansion.
Each POINT Guard module that you configure can consume up to 2 connections of the 20 connection limit within the 1734-AENT or 1734-AENTR modules. Be sure that you are aware of and design your POINT system with these limits in mind.
6. Click OK to return to the Module Properties dialog box.
7. Click OK again to apply your changes.
The I/O Configuration tree displays the 1734 Ethernet adapter.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 79
Chapter 5 Configure the Module in a GuardLogix Controller System

Add and Configure Safety Digital Input Modules

To include a safety digital input module in the project, you add the module under the I/O chassis in the I/O Configuration tree. Then configure the general properties of the module, configure the digital inputs, and configure test outputs as described in the following sections.

Add the Safety Digital Input Module

To add the POINT Guard I/O safety digital input module, follow these steps.
1. Right-click the POINT I/O Chassis and choose New Module.
2. From the Select Module dialog box, check Digital and Allen-Bradley.
3. Select an input module and click Create.
80 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
4. Specify the general properties of the module.
a. In the Name field of the New Module dialog box, type a unique name
for the input module.
b. From the Module Number pull-down menu, choose a unique module
number that corresponds to the position of the module in the chassis. c. In the Description field, type a description, if desired. d. In the Safety Network Number field, use the default setting.
For a detailed explanation of the safety network number (SNN), see the
GuardLogix Controller Systems Safety Reference Manuals that are
listed in the Additional Resources on page 10
. However, in most cases,
you use the default that is provided by the Logix Designer application.
The purpose of the safety network number (SNN) is to make sure that
every module in a system can be uniquely identified. We suggest that all
safety modules on a network have the same SNN, to make
documentation easier. During configuration, the Logix Designer
application defaults an SSN of a safety device to match the SNN of the
lowest safety node on each network.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 81
Chapter 5 Configure the Module in a GuardLogix Controller System
5. To edit the Module Definition, click Change.
a. In the Series field, choose the input series letter of the module. b. In the Revision fields, choose the input revision number of the module. c. From the Electronic Keying pull-down menu, choose the appropriate
keying method for the input module.
Choose Description
Exact Match All parameters must match or the inserted module rejects a connection to the
Compatible Module
controller.
Allows an I/O module to determine whether it can emulate the module that is defined in the configuration that is sent from the controller.
d. From the Configured By pull-down menu, choose the appropriate
method by which this module is configured.
Choose Description
This Cont roller This s election d irects the co ntroller to configure the module.
External Means This selection directs the controller to establish a safety input connection only,
and the controller doesn’t configure the module or control the Test Outputs.
e. From the Input Data pull-down menu, choose Safety or None.
Choose Description
Safety These tags are created for the target module:
RunMode for module mode
ConnectionFaulted for communication status
Safety Data for safety inputs from the module
82 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
IMPORTANT
f. From the Output Data pull-down menu, choose from the following
options.
Choose Description
None Results in an input only connection to the module. Inputs and status are read, but no
(1)
Tes t
(1) To have this choice from the pull-down menu, you must choose ‘This Controller’ from the Configured By pull-down
menu.
outputs are written. You can still use the test outputs as pulse test outputs or a power supply. If you are not controlling the test outputs of the module via application logic, this is the recommended setting.
Creates these tags to enable application logic control of the test outputs on the module. This selection allows the test outputs to be used as standard outputs and muting outputs.
When test outputs are configured as standard outputs, they must not be used for safety purposes.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 83
Chapter 5 Configure the Module in a GuardLogix Controller System
g. From the Input Status pull-down menu, choose from the following
options.
Choose Description
None There are no status tags.
Pt. Status There is one status tag for each input point.
Combined Status -
Muting
Pt. Status - Muting There is a muting status tag for test output T1 and T3 with point status for each
Pt. Status-Muting-Test
Output
One BOOL tag represents an AND of the status bits for all input points. For example, if any input channel has a fault, this bit goes LO.
One BOOL tag represents the Input Power Status (error bit) from the input assembly.
A muting status tag for test output T1 and T3.
input point.
Status tags for each of the input points.
Muting status tag for test output T1 and T3.
Status tags for each of the test outputs.
(1)
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
h. From the Data Format pull-down menu, use the default ‘Integer’.
84 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
2 3 4
5
6
7
6. Click OK to return to the Module Properties dialog box.
7. Click OK again to apply your changes.
The I/O Configuration tree displays the module.

Configure the Safety Digital Inputs

To configure the safety digital inputs, follow this procedure.
1. From the Module Properties dialog box, click the Input Configuration tab.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 85
Chapter 5 Configure the Module in a GuardLogix Controller System
IMPORTANT
2. Assign the Point Operation Type.
Choose Description
Single Inputs are treated as single channels.
Dual-channel safety inputs can be configured as two individual single channels. This configuration does not affect pulse tests because it is handled on an individual channel basis.
IMPORTANT: Use single-channel mode when you intend to use the GuardLogix safety application instructions.
Equivalent Inputs are treated as a dual-channel pair. The channels must match within the
discrepancy time or an error is generated.
Complementary Inputs are treated as a dual-channel pair. They must be in opposite states within
the discrepancy time or an error is generated.
When you choose Equivalent or Complementary, you must also assign a Discrepancy Time.
A discrepancy time setting of 0 ms means that the channels in a dual configuration can be discrepant for an infinite amount of time without a fault being declared.
For a discrepancy time setting of 0 ms, the evaluated status of the inputs still goes to the safe state due to a ‘cycle inputs’ required condition. However, with a 0 ms discrepancy time setting, a fault is not declared.
A ‘cycle inputs’ required condition occurs when one input terminal goes from its normal Active->Inactive->Active state while the other input terminal remains in its normal Active state. Even though no fault is declared, the inputs must be cycled through the safe state before the evaluated status of the inputs can return to the Active state. When in a ‘cycle inputs’ required condition, the logical state does not necessarily match the voltage at the terminals.
Configuring discrepancy time on safety I/O modules masks input discrepancies that the controller safety instructions detect. The controller reads status to obtain this fault information.
86 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
3. Assign the Point Mode.
Choose Description
Not Used The input is disabled. If 24V is applied to the input terminal, it
Safety Pulse Test Pulse tests are performed on this input circuit. A test source on the
Safety A safety input is connected but there is no requirement for the POINT
Standard A standard device, such as a reset switch, is connected. This point
remains logic 0.
POINT Guard I/O module must be used as the 24V source for this circuit. The test source is configured by using the test source pull-down menu. The pulse test detects shorts to 24V and channel-to-channel shorts to other inputs.
Guard I/O module to perform a pulse test on this circuit. An example is a safety device that performs it s own pulse tests on the input wires, such as a light curtain.
cannot be used in dual-channel operation.
4. Assign a Test Source for each safety input on the module you want to pulse test.
Choose Description
None
Tes t O ut put 0
Tes t O ut put 1
Tes t O ut put 2
Tes t O ut put 3
(1)
(1)
If pulse tests are performed on an input point, then the test source that is sourcing the 24V for the input circuit must be selected.
If the incorrect test source is entered, the result is pulse test failures on that input circuit.
(1) Test Output 1 and 3 incorporate optional muting functionality.
5. Assign the Input Delay Time, Off -> On (0…126 ms, in increments of 6ms).
Filter time is for OFF to ON transition. Input must be high after input delay has elapsed before it is set logic 1. This delay time is configured per channel with each channel that is tuned to match the characteristics of the field device, for maximum performance.
6. Assign the Input Delay Time, Off -> On (0…126 ms, in increments of 6ms).
Filter time is ON to OFF transition. Input must be low after input delay has elapsed before it is set logic 0. This delay time is configured per channel with each channel that is tuned to match the characteristics of the field device, for maximum performance.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 87
Chapter 5 Configure the Module in a GuardLogix Controller System
7. From the Input Error Latch Time field, enter the time that the module
8. Click Apply.

Configure the Test Outputs

To complete the test output configuration, follow this procedure.
1. From the Module Properties dialog box, click the Test Output tab.
holds an error to make sure that the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms).
This setting provides more accurate diagnostics. The purpose for latching input errors is to make sure that intermittent faults that can exist only for a few milliseconds are latched long enough for the controller to read. The amount of time to latch the errors are based on the RPI, the safety task watchdog, and other application-specific variables.
2. Assign the Point Mode.
Choose Description
Not Used The test output is disabled (default for T2 and T3).
Standard The test output point is controlled programmatically by the GuardLogix
Pulse Test The test output is being used as a pulse test source (default for T0 and T1).
Power Supply A constant 24V is placed on the output terminal. It can be used to provide
Muting Lamp Output (terminals T1 and T3 only)
controller.
power to a field device.
An indicator lamp is connected to the output. When this lamp is energized, a burned-out bulb, broken wire, or short to GND error condition can be detected. Typically, the lamp is an indicator that is used in light cur tain applications.
There is also a Test Output Fault Action parameter that can only be read or written to via explicit messaging. If communication to the module times out, you can set the test outputs to Clear OFF (default) or Hold Last State. For more information, see Appendix B
.
3. Click Apply.
88 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5

Add and Configure Safety Digital Output Modules

To include a POINT Guard safety digital-output module in the project, you add the module to the POINT I/O chassis. Configure the general properties of the module, and configure the digital outputs as described in the following sections.

Add the Safety Digital Output Module

To add the POINT Guard I/O safety digital output module, follow these steps.
To add and configure POINT Guard I/O safety modules, follow these steps.
1. Right-click the POINT I/O chassis and choose New Module.
2. On the Select Module dialog box, select a safety output module and
click OK.
The 1734-OB8S module is shown in the examples.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 89
Chapter 5 Configure the Module in a GuardLogix Controller System
3. Specify the general properties of the module.
a. In the Name field of the New Module dialog box, type a unique name
for the output module.
b. From the Module Node pull-down menu, choose a unique module
node number that corresponds to the position of the module in the
chassis. c. In the Description field, type a description, if desired. d. In the Safety Network Number field, use the default setting.
For a detailed explanation of the safety network number (SNN), see the
GuardLogix Controller Systems Safety Reference Manuals that are
listed in the Additional Resources on page 10
. In most cases, you use
the default that is provided by the Logix Designer application.
4. Under Module Definition, click Change to edit the settings of the module.
a. In the Series field, choose the series letter of the output module. b. In the Revision fields, choose the revisions numbers of the output
module.
90 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
c. From the Electronic Keying pull-down menu, choose the appropriate
keying method from the following options.
Choose Description
Exact Match Al l parameters must match or the inserted module rejects a connection to
Compatible Module Lets an I/O module determine whether it can emulate the module that is
the controller.
defined in the configuration that is sent from the controller.
d. From the Configured By pull-down menu, choose the method by
which this module is configured.
Choose Description
This Controller This selection directs the controller to configure and control the safety
External Means This selection directs the controller to establish a safety input connection
outputs. The Output Data selection is set to Safety.
only, and the controller does not configure the module or be able to control the safety outputs. The Output Data selection is set to None.
e. From the Input Data pull-down menu, choose None.
None is the only valid selection, as this module is an output-only safety module.
f. From the Output Data pull-down menu, choose from the following :
Choose Description
Safety Automatically selected when Configured By = This controller. Results in an output
None Automatically selected when Configured By = External. When you select None, it results
connection. When you select Safety, an output tag is created for each output point and enables these outputs for use in the Safet y Task.
in an input only connection to the module. Status is read, but no outputs are written.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 91
Chapter 5 Configure the Module in a GuardLogix Controller System
g. From the Input Status pull-down menu, choose from the following.
Choose Description
None There are no status tags, only data for the outputs.
Pt. Status There is one status tag for each output point.
Pt. Status - Readback There is one status tag for each output point.
Combined Status ­Readback - Power
There is one data tag for the output readback.
There is one data tag for output readback on each output point.
O ne BOOL tag represents the Output Power Status (error bit) from the input
assembly.
One BOOL tag represents an AND of the status bits for all output points. (Combined Output Status). For example, if any output channel has a fault, this bit goes LO.
(1)
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
h. From the Data Format pull-down menu, use the default ‘Integer’.
5. Click OK to return to the Module Properties dialog box.
92 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
6. Click OK again to apply your changes.
The I/O Configuration tree displays the output module.

Configure the Safety Digital Outputs

To configure the safety digital outputs, follow this procedure.
1. From the Module Properties dialog box, click the Output Configuration tab.
2. Assign the Point Operation Type.
Choose Description
Single The output is treated as one channel.
Dual (default) The POINT Guard I/O module treats the outputs as a pair. It always sets them HI or LO as a
matched pair. Safety logic must set both of these outputs ON or OFF simultaneously or the module declares a channel fault.
3. Assign the Point Mode.
Choose Description
Not Used The output is disabled.
Safety The output point is enabled and does not perform a pulse test on the output.
Safety Pulse Tes t
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 93
The output point is enabled and performs a pulse test on the output. When the output is energized, the output pulses low briefly. The pulse test detects whether the output is functioning properly.
Chapter 5 Configure the Module in a GuardLogix Controller System
4. In the Output Error Latch Time field, enter the time that the module
5. Click Apply.
holds an error to make sure that the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms).
This action provides more accurate diagnostics. The purpose for latching output errors is to make sure that intermittent faults that can exist only for a few milliseconds are latched long enough for the controller to read. The amount of time to latch the errors is based on the RPI, the safety task watchdog, and other application-specific variables.

Add and Configure Safety Analog Input Modules

To include a POINT Guard safety analog input module in the project, you add the module to the POINT I/O chassis, configure the general properties of the module, and configure the analog inputs as described in the following sections.

Add the Safety Analog Input Module

Follow these steps to add the POINT Guard I/O safety analog input module.
1. Right-click the POINT I/O chassis and choose New Module.
2. From the Select Module dialog box, select an analog input module and
click Create.
94 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
3. Specify the general properties of the module.
a. In the Name field of the New Module dialog box, type a unique name
for the analog input module.
b. From the Module Number pull-down menu, choose a unique module
number that corresponds to the position of the module in the chassis. c. In the Description field, type a description, if desired. d. In the Safety Network Number field, use the default setting.
For a detailed explanation of the safety network number (SNN), see the
GuardLogix Controller Systems Safety Reference Manuals that are
listed in the Additional Resources on page 10. In most cases, you use
the default that is provided by the Logix Designer application.
The safety network number (SNN) is a unique number that identifies a
safety subnet. We suggest that all safety modules on a network have the
same SNN, to make documentation easier. During configuration, the
Logix Designer application defaults the SNN of a safety device to
match the SNN of the lowest safety node on the network.
4. To open the Module Definition dialog box, click Change.
a. In the Series field, choose the series letter of the analog input module. b. In the Revision fields, choose the revision number of the module.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 95
Chapter 5 Configure the Module in a GuardLogix Controller System
c. From the Electronic Keying pull-down menu, choose the appropriate
keying method for the input module.
Choose Description
Exact Match All parameters must match or the inserted module rejects a connection to the
Compatible Module
controller.
Allows an I/O module to determine whether it can emulate the module that is defined in the configuration that is sent from the controller.
d. From the Configured By pull-down menu, choose the appropriate
method by which this module is configured.
Choose Description
This Cont roller This s election d irects the co ntroller to configure the Inputs.
External Means This selection directs the controller to establish a safety input connection only,
and the controller does not configure the module.
e. From the Input Data pull-down menu, choose Safety. f. From the Output Data pull-down menu, choose from the following.
Choose Description
None An output tag is not generated.
Safety-Tachometer This option is available when the Configured By selection is This Controller. The
output tag contains data members for safety output data that is needed for Tachometer mode. If you are using Tachometer mode, you must choose this setting; otherwise, you are not able to configure other Tachometer parameters.
g. From the Process Data pull-down menu, choose from the following.
Choose Description
Status The input tag contains safety analog input data from the module.
Status - Alarms These tags are created for the target module:
Status - Alarms - Faults These tags are created for the target module:
Safety data for individual process alarms
Safety data for safety analog inputs from the module
Safety data for individual process alarms
Safety data for faults
Safety data for safety analog inputs from the module
h. From the Data Format pull-down menu, use the default ‘Integer’.
5. Click OK to return to the Module Properties dialog box.
6. Click OK again to apply your changes.
The I/O Configuration tree displays the 1734-IE4S module.
96 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
IMPORTANT
TIP

Configure the Safety Analog Input Channel Operation

To configure the safety analog input channels, follow this procedure.
1. From the Module Properties dialog box, click the Safety Input Configuration tab.
2. Assign the Operation Type.
Choose Description
Single Inputs are treated as single channels. Dual-channel safety inputs can be configured as two
Equivalent Inputs are treated as a dual-channel equivalent pair. The channels must match within the
individual, single channels. IMPORTANT: Use single-channel mode when you intend to use the GuardLogix safety
application instructions.
discrepancy time or an error is generated.
If you are using a Dual-channel Analog (DCA) safety instruction in your application program, you must configure the 1734-IE4S module for single-channel operation. Analog input pairs are then evaluated as pairs and compared to each other in the application logic.
3. If you chose Equivalent, you must also assign a Discrepancy Time, from 0…65,530 ms in 10 ms increments.
This measurement is the amount of time the two channels can differ from each other (larger than the deadband value) before a discrepancy error is declared. A discrepancy time setting of 0 ms means that the channels in a dual configuration can be discrepant for an infinite amount of time without a fault being declared. This setting would effectively eliminate the usefulness of dual channel mode.
4. Configure a deadband for the paired safety analog inputs.
The deadband can be any value from 0…32767 (engineering units) in increments of 1. When the paired input values exceed the deadband tolerance for longer than the Discrepancy Time, a discrepancy fault occurs.
Configure a deadband value for applications that use two sensors to measure the same variable; otherwise, spurious trips can occur.
5. If desired, configure a Channel Offset for the paired safety analog inputs.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 97
Chapter 5 Configure the Module in a GuardLogix Controller System
6. In the Input Error Latch Time field, enter the time that the module holds
7. Click Apply.

Configure the Safety Analog Inputs

The channel offset can be any value from -32768…32767 (engineering units) in increments of 1. Configure an offset when differences in the sensors nominal input signals would otherwise exceed the desired deadband. The channel offset is applied from the second to the first member of the channel pair, that is, from channel 1 to channel 0 or from channel 3 to channel 2.
an error to make sure that the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms).
This setting provides more accurate diagnostics. The purpose for latching input errors is to make sure that intermittent faults that can exist only for a few milliseconds are latched long enough for the controller to read. The amount of time to latch the errors must be based on the RPI, the safety task watchdog, and other application-specific variables.
To configure the analog input points, follow these steps.
1. From the Module Properties dialog box, click the Input Configuration tab.
2. Assign the Point Mode.
Choose Description
Not Used The input is disabled.
Safety Safety-related analog input value
Standard Standard analog input value, not being used for a safety function
If the channel operation is configured as dual-channel equivalent, when you click Apply, channel 1 is set to the same value as channel 0 and channel 3 is set to the same value as channel 2.
3. Configure the module for current, voltage, or tachometer inputs.
98 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Configure the Module in a GuardLogix Controller System Chapter 5
TIP
TIP
4. Configure an input filter.
A single-pole, anti-aliasing filter of 10 Hz is followed by a four-pole digital filter. Choose from the following available corner frequencies.
1 Hz (recommended for Tachometer mode)
5 Hz
10 Hz
50 Hz
For more information on the filter frequencies and step response, see the technical specifications for the 1734-IE4S module on page 176
or Digital
Input Filter on page 30.
5. Assign High and Low Engineering scaling values for the inputs, if desired.
The valid range for both the High and Low Engineering settings is
-30000…30000, in increments of 1. Scaling lets the module report in engineering units such as degrees, PSI, CFM, and percent, rather than in raw counts.
If the channel operation is configured as dual channel equivalent, when you click Apply, channel 1 is set to the same value as channel 0 and channel 3 is set to the same value as channel 2 if the channel operation is configured as dual channel equivalent.
6. To indicate how each sensor is powered, set the Sensor Power Supply value to External or Module.
Set this value to Module to supply power to the sensors connected to the POINT Guard Analog Input module. This value allows the module to detect a loss of sensor power.

Configure Safety Analog Input Alarms (Optional)

If you are using a Dual-channel Analog (DCA) safety instruction in your application program, we recommend that you do not configure these values on the module. Instead, to facilitate troubleshooting, use the application program to check for high and low alarm values via the Dual-Channel Analog Input instruction or other data comparison instructions.
Rockwell Automation Publication 1734-UM013P-EN-P - December 2018 99
Chapter 5 Configure the Module in a GuardLogix Controller System
To configure alarms for each of the safety analog input channels, follow these steps.
1. From the Module Properties dialog box, click the Alarm tab.
2. To configure each channel, click 0, 1, 2, or 3, as appropriate.
3. To enable the alarm, check the boxes:
Enable High High - Low Low Alarms
Enable High - Low Alarms
4. Type the alarm values from -32768…32767 in the appropriate fields,
following these guidelines:
The High High alarm value must be greater than or equal to the High alarm value.
The High alarm value must be greater that the Low alarm value.
The Low Low alarm value must be less than or equal to the Low alarm
value.
These values are based on the engineering units that are configured on
page 99
.
5. Configure a deadband value for the High High - Low Low alarms and High - Low alarms, if desired.
The valid range is 0…32767. The deadband lets the alarm status bit remain set, despite the alarm condition disappearing, as long as the input data remains within the deadband of the alarm. These values are based on the Engineering units that are configured on page 99
.
For more information on this feature, see Process Alarms on page 31
100 Rockwell Automation Publication 1734-UM013P-EN-P - December 2018
Loading...