Allen-Bradley 1734-AENTR Installation Manual

Installation Instructions
POINT I/O Dual Port EtherNet/IP Adapter
Catalog numbers 1734-AENTR
Table of Contents
Topic Page
Important User Information 2
Environment and Enclosure 3
North American Hazardous Location Approval 4
European Hazardous Location Approval 4
About The Adapter 6
Before You Begin 7
Determine Compatibility 7
Understand Messaging 7
Install the Adapter 8
Set the Network Address 9
Replace The Adapter 11
Wire The Adapter 13
Interpret Status Indicators 15
Specifications 17
Additional Resources 22
2 POINT I/O Dual Port EtherNet/IP Adapter

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-State Controls (Publication SGI-1.1
http://www.rockwellautomation.com/literature/
solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
) describes some important differences between
SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Publication 1734-IN040C-EN-P - December 2018

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication
1770-IN041
• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
, for more installation requirements.

Preventing Electrostatic Discharge

POINT I/O Dual Port EtherNet/IP Adapter 3
ATTENTION: This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1734-IN040C-EN-P - December 2018
4 POINT I/O Dual Port EtherNet/IP Adapter

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, H azardous Locations and nonhazardous locations only. Each produ ct is supplied with markings on the rat ing nameplate indicating the hazardous location tempe rature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in you r system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipm ent by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
Informations sur l’utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne co nviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dan gereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combin és dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à insp ection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non dangereu x avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereu x avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution d e composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

European Hazardous Location Approval

The following applies to products marked II 3 G:
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at
http://www.rockwellautomation.com/products/certification
• The type of protection is Ex nA IIC T4 Gc according to EN 60079-15.
• Comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO 04 ATEX 0330347X.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.
for details.
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 5
ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
ATTENTION: Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
ATTENTION: In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module.
ATTENTION: This equipment is certified for use only within the surrounding air temperature range of -20…+55 °C (-4…+131 °F). The equipment must not be used outside of this range.
ATTENTION: Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.
WARNING: Special Conditions for Safe Use:
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance with EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments. The enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when applied in Zone 2 environments.
• The instructions in the user manual shall be observed.
• This equipment must be used only with ATEX certified Rockwell Automation backplanes.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.
Publication 1734-IN040C-EN-P - December 2018
6 POINT I/O Dual Port EtherNet/IP Adapter
1
2
4
5
6
3
44849
WARNING: Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
WARNING: Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

About The Adapter

Read this publication for information about the POINT I/O™ Dual Port EtherNet/IP™ adapter, a communications adapter for POINT I/O modules.
This adapter is for the POINT I/O backplane that provides connectivity to an EtherNet/IP network with two RJ-45 connectors for 2 port pass-through to support daisy-chain or ring, and the existing star and tree network topologies.
1734-AENTR Adapter
Module
Status
Network
1734-AENTR
Activity
Network
POINT I O
Status
Point Bus
Status
System
Power
Field
Power
3
02
0
Link 1
Activity/
Status
2
5
4
7
6
Publication 1734-IN040C-EN-P - December 2018
Link 2
Activity/
Status
POINT I/O Dual Port EtherNet/IP Adapter 7
Description Description
1 Status indicators 4 DIN rail locking screw (orange)
2 Removable Terminal Block (RTB) handle 5 Ethernet network RJ-45 connectors
3 Removable Terminal Block (RTB) 6 Node address pen push thumbwheel

Before You Begin

To effectively use your adapter, note the following considerations.

Determine Compatibility

RSLogix 5000® version 17 or greater must be used for the 1734-AENTR Add-on Profile. The 1734-AENTR adapters will accept I/O connections with the electronic keying for the 1734-AENT. This allows the 1734-AENTR adapter to be used in a daisy-chain topology with the 1734-AENT profile used for the 1734-AENTR.
If using the adapter with a 1756-ENBT module, 1768-ENBT module or an L3xE processor, use the following required firmware versions for these bridge modules:
• 1756-ENBT firmware version 4.006 or greater
• 1768-ENBT firmware version 2.003 or greater
• L3xE processor firmware version 17 or greater
If you use the BootP utility to assign IP addresses to the adapter, use version 2.3.2 or greater.

Understand Messaging

Class 3 (Explicit Message) requests through the 1734-AENTR adapter to a specific POINT I/O module do not always receive a response from the I/O modules. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a time-out.

Establish I/O Connections

When you start a POINT I/O system and establish I/O connections, the outputs transition to the Idle state, applying Idle state data before going to Run mode. This occurs even when the controller making the connection is already in Run mode.
Publication 1734-IN040C-EN-P - December 2018
8 POINT I/O Dual Port EtherNet/IP Adapter

Configure Autobaud

The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.

Install the Adapter

Follow this procedure to install the adapter on the DIN rail.
1. Position the adapter vertically above the DIN rail. Make sure that the DIN rail lock is in horizontal position.
2. Press down firmly to install the adapter on a DIN rail, noting that the locking mechanism locks the adapter to the DIN rail.
3. Set the node address on the node address pen push thumbwheel. See Set the
Network Address for more information on setting the IP address.
4. Slide the safety end cap up to remove it, exposing the backplane and power interconnections.
ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1
, for more information.
ATTENTION: Allow 25.4 mm (1 in.) of space between adjacent equipment for adequate ventilation.
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 9
ATTENTION: Do not remove or replace an Adapter Module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

Set the Network Address

The adapter ships with the pen push thumbwheel switches set to 999 and DHCP enabled. You can set the network Internet Protocol (IP) address in the following ways:
• Use the pen push thumbwheel switches on the adapter.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from nonvolatile memory.
The adapter reads the thumbwheel switches first to determine if the switches are set to a valid number. You set the node address using the 3-position pen push thumbwheel switch using a pen tip. Press the + or - buttons with a pen tip to change the number.
Note : Press a pen tip into the center of the button cross, perpendicular to the button. You only need a small amount of force to press the button (approximately 2N).
Valid settings range from 001…254. When you use the thumbwheel to assign an address and set it to 001, the adapter gateway address is set to 0.0.0.0. and the subnet mask is
255.255.255.0. When you use the thumbwheel to assign an address and set it between
002...254, the adapter gateway address is set to 192.168.1.1.
The adapter does not have a host name assigned, or use any Domain Name System when using the thumbwheel settings.
Publication 1734-IN040C-EN-P - December 2018
10 POINT I/O Dual Port EtherNet/IP Adapter
02
0
1734-AENTR
Module Status
Network Activity
Network Status
Point Bus Status
System Power
Field Power
POINT I O
Link 1 Activity/ Status
44848
Network node address pen push thumbwheel – Press the center of either the + or - buttons to change the number
Network Address Thumbwheel
Refer to publication POINT I/O and ArmorPOINT® I/O Dual Port EtherNet/IP Adapter User Manual, 1734-UM017
If you set the switches to an invalid number (for example, 000 or a value greater than 254 excluding 888), the adapter checks to see if you enabled DHCP.
DHCP Enabled and Not Enabled
DHCP State Adapter Action
Enabled Asks for an address from a DHCP server. The DHCP server also assigns other
Not enabled Uses the IP address (along with other TCP configurable parameters) stored in
Transport Control Protocol (TCP) parameters.
nonvolatile memory.
WARNING: When you change switch settings while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
for more information.
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 11

Replace The Adapter

Use these procedures to install a replacement adapter to an existing system.
1. Disconnect the Ethernet connector(s) from the adapter.
2. Pull up on the Removable Terminal Block (RTB) handle to remove the terminal
block.
WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
3. Remove the adjacent module from its base.
4. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical
position. This releases the locking mechanism.
5. Lift straight up to remove.
6. Slide the safety end cap up to remove it, which exposes the backplane and power
connections.
7. Position the replacement adapter vertically above the DIN rail, making certain the DIN rail lock is in the horizontal position.
8. Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.
Publication 1734-IN040C-EN-P - December 2018
12 POINT I/O Dual Port EtherNet/IP Adapter
TIP
9. Press firmly to seat the adapter on the DIN rail, noting that the adapter locking mechanism will snap into place.
10. Set the node address on the Node Address pen push thumbwheel using a pen tip.
Press a pen tip into the center of the button cross, perpendicular to the button. You only need a small amount of force to press the button (approximately 2N).
11. Insert the end of the terminal block opposite the handle into the base unit, noting that this end has a curved section that engages with the wiring base.
12. Rotate the terminal block into the wiring base until it locks itself into place.
13. Replace the adjacent module in its base.
14. Reconnect the Ethernet cable(s) to the adapter.
15. Set the IP Address for this module.
16. Configure the adapter’s chassis size.
Publication 1734-IN040C-EN-P - December 2018

Wire The Adapter

02
0
1734-AENTR
Module Status
Network Activity
Network Status
Point Bus Status
System Power
Field Power
POINT I O
Link 1 Activity/ Status
Link 2 Activity/ Status
IP ADDRESS
Chas Gnd
C
V
NC
Ethernet RJ-45 connectors
NCVNC
Chas Gnd
V
0
4
2
6
Chas Gnd
1
5
3
7
V DC
C
C
NC = No Connection Chas GND = Chassis Ground C = Common V = Supply
44848
POINT I/O Dual Port EtherNet/IP Adapter 13
IMPORTANT
Do not connect 120/240V AC power to this supply. This DC supply will be connected to the internal power bus.
Publication 1734-IN040C-EN-P - December 2018
14 POINT I/O Dual Port EtherNet/IP Adapter
WARNING: When used in a Class I, Division 2, hazardous location, this
equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
WARNING: If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING: Do not wire more than two conductors on any single terminal.
WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment
must be powered from a Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV) compliant source.
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 15
43264
Network status POINTBus status
System power Field power
Module status Network activity
Link 1 activity/ status
Link 2 activity/ status

Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the status indicators.
Status Indicators
02
0
IP ADDRESS
Indicator Status for Modules
Indicator Status Description
Module status
Off No power applied to device Flashing green Device needs commissioning due to missing, incomplete, or
incorrect configuration. Solid green Device operating normally Flashing red Recoverable fault.
Complete firmware update, verify address switches. Solid red Unrecoverable fault, may require device replacement Flashing red/green Module self-test
Link 1 Activity/ Status
Link 2 Activity/ Status
1734-AENTR
POINT I O
Module Status
Network Activity
Network Status
Point Bus Status
System Power
Field Power
Publication 1734-IN040C-EN-P - December 2018
16 POINT I/O Dual Port EtherNet/IP Adapter
Indicator Status for Modules
Indicator Status Description
Network activity
Network status
POINTBus status
System power
Field power Off Not active. Adapter power is off.
Off No link established with Port 1 or Port 2. Flashing green Transmit or receive activity present on Port 1 and/or Port 2 @ 100
Solid green Link established with Port 1 and/or Port 2 @ 100 Mb.
Solid yellow Link established with Port 1 and/or Port 2 @ 10 Mb. Off Device is not on-line
Flashing green Device is on-line but has no CIP connections in the established state. Solid green Device on-line and has CIP connections in the established state. Flashing red One or more CIP connections in timed-out state. Check for I/O
Solid red Duplicate IP address detected.
Flashing red/green Module self-test Off Device is not online.
Flashing green Device is online but has no connections in the established state.
Solid green Adapter online with connections established. Flashing red Recoverable fault occurred:
Solid red Unrecoverable fault occurred - thse adapter is bus off. Flashing red/green LED powerup test is in progress. Off Not active. Adapter power is off or there is a DC-DC converter
Solid green System power is on. DC-DC converter output is active (5V).
Solid green Power is on. 24V input is present.
Mb.
Transmit or receive activity present on Port 1 and/or Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
Link established with Port 1 and Port 2.
One port @ 100 Mb and the other port @ 10 Mb.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
module failure and controller operation.
Note: This does not apply to POINTGuard I/O connection timeout.
Verify IP address setting and correct, as needed.
- Device has not completed Dup_MAC_ID test.
- Device not powered - check module status indicator.
Firmware (NVS) update in progress.
At cycle power, the number of expected modules does not equal the
number of modules present.
A module is missing.
Node fault (I/O connection timeout) occurred.
problem.
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 17
Indicator Status for Modules
Indicator Status Description
Link 1 or Link 2 activity / status
Off No link established. Solid green Link established @ 100 Mbps. Flashing green Transmit or receive activity present on indicated port @ 100 Mbps. Solid yellow Link established @ 10 Mbps. Flashing yellow Transmit or receive activity present on indicated port @ 10 Mbps.

Specifications

POINT I/O EtherNet/IP Adapter — 1734-AENTR
Attribute Value
Expansion I/O capacity, max •63 modules
POINTBus current requirements, max •50 mA (Catalog number 1734-IB4D)
Module location Starter module - left side of the 1734 system
(1)
Maximum 31 direct connections for standard I/O or maximum 20 direct connections if any safety I/O module resides in the backplane.
•Up to 5 rack-optimization (for digital modules only) and/or enhanced rack-optimization (for digital, analog, and specialty modules) connections
•31 direct connections
• 1734-AENTR, 1734-AENTRK backplane current output = 0.8 A.
•Actual number of modules can vary.
•Add up current requirements of modules you want to use to make sure they do not exceed the amperage limit of 0.8 A for the 1734-AENTR or 1734-AENTRK adapter.
•Backplane current can be extended beyond 0.8 A by 1734-EP24DC or 1734-EPAC backplane extension power supplies.
•Add multiple 1734-EP24DC or 1734-EPAC modules to reach the 63 module max.
•75 mA (Catalog numbers 1734-IB2, 1734-IB4, 1734-IB8, 1734-IV2, 1734-IV4, 1734-OB2, 1734-OB4, 1734-OB8, 1734-OB2E, 1734-OB2EP, 1734-OB4E, 1734-OB8E, 1734-OV2E, 1734-OV4E, 1734-232ASC, 1734-485ASC, 1734-ARM, 1734-IV8, 1734-OV8E, 1734-IE4C, 1734-IE8C, 1734-OE4C, 1734-IA4, 1734-IM4, 1734-OA4, 1734-IR2E, 1734-IE2C, 1734-OE2C, 1734-IE2V, 1734-OE2V, 1734-IA2, 1734-IM2, 1734-OA2)
•80 mA (Catalog numbers 1734-OW2, 1734-OW4)
•100 mA (Catalog numbers 1734-OX2, 1734-8CFG, 1734-8CFGDLX, 1734-4IOL)
•110 mA (Catalog number 1734-SSI)
•160 mA (Catalog numbers 1734-IJ2, 1734-IK2)
•175 mA (Catalog number 1734-IT2I)
•180 mA (Catalog numbers 1734-VHSC5, 1734-VHSC24)
•220 mA (Catalog numbers 1734-IR2, 1734-IR2E)
(1)
Publication 1734-IN040C-EN-P - December 2018
18 POINT I/O Dual Port EtherNet/IP Adapter
Power Supply
Attribute Value
Input voltage rating 24V DC @ 10A Input voltage, range 10...28.8V DC Field side power, max 24V DC @ 400 mA Inrush current, max 6 A for 10 ms Input overvoltage protection Reverse polarity protected POINTBus output current, max 5V DC @ 0.8A Interruption Output voltage stays within specifications when input drops out
for 10 ms @ 10V with max load
Ethernet Communication
Attribute Value
Ethernet communication rate 10/100 Mbits/s, half or full-duplex Ethernet ports 2, configured as Embedded Switch Ethernet network topologies supported Star, Tree, Daisy-chain/Linear, and Ring Ethernet connectors RJ-45, Category 5 Ethernet cable Category 5:
Ethernet wire connections, max See Wire Size
shielded or unshielded
on page 19
General Specifications
Attribute Value
Indicators 3 red/green status indicators on CPU:
Power consumption, max 10.4 W @ 28.8V DC Power dissipation, max 6.3 W @ 28.8V DC
– Module status – Network status (Ports 1 and 2 combined) – POINTBus status 1 green/yellow status indicator on CPU: – Network activity (Ports 1 and 2 combined) 2 green/yellow status indicators on base: – Link 1 activity/status – Link 2 activity/status
2 green power supply status indicators on DC-DC Converter: – System power (5V DC to POINTBus Out) – Field power (24V DC from Field In)
Publication 1734-IN040C-EN-P - December 2018
POINT I/O Dual Port EtherNet/IP Adapter 19
General Specifications
Attribute Value
Input overvoltage protection Reverse polarity protected Thermal dissipation, max 21.5 BTU/hr @ 28.8V DC Isolation voltage 50V (continuous), Reinforced Insulation Type, between
Field power supply 10...28.8V DC @ 10A Field power output 10...28.8V DC @ 9A Module input 10...28V DC @ 1000 mA POINTBus output, max 5V DC @ 0.8A Dimensions (HxWxD), approx. 76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.) Enclosure type rating None (open-style) Terminal base screw torque 0.8 Nm (7 lb-in) Weight, approx. 0.28 Kg (0.62 lb) Wiring category
(1) (2)
Wire Size Power connections:
North American temp code T4 ATEX Temp Code T4
(1)
Use this Conductor Category information for p lanning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 17 70-IN041
(2)
Use this Conductor Category information for p lanning conductor routing as described in the appropriate System Level Installation Manual.
circuits
all Type tested @ 500V AC for 60 s
1 – on power ports 1 – on communications ports
2
0.34... 2.1 mm @ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max or 90 °C (194 °F) for ControlLogix.
Ethernet wiring: RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1 or Category 5 cable according
to ISO/IEC 24702.
(22...14 AWG) solid or stranded copper wire rated
.
At the end of its life, this equipment should be collected separately from any unsorted municipal waste.
Publication 1734-IN040C-EN-P - December 2018
20 POINT I/O Dual Port EtherNet/IP Adapter
Environmental Specifications
Attribute Value
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold),
Temperature, surrounding air, max 55 °C (131 °F) Temperature, nonoperating IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Shock, operating IEC60068-2-27 (Test Ea, Unpackaged Shock):
Shock, nonoperating IEC60068-2-27 (Test Ea, Unpackaged Shock):
Emissions IEC 61000-6-4 ESD immunity IEC61000-4-2:
Radiated RF immunity IEC 61000-4-3:
EFT/B immunity IEC 61000-4-4:
Surge transient immunity IEC 61000-4-5:
Conducted RF immunity IEC61000-4-6:
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat) IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
5...95% non-condensing
5 g @ 10...500 Hz
30 g
50 g
6 kV contact discharges 8 kV air discharges
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
±4 kV @ 5 kHz on power ports ±3 kV @ 5 kHz on communications ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±2 kV line-earth (CM) on communications ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz
Publication 1734-IN040C-EN-P - December 2018
Certifications
POINT I/O Dual Port EtherNet/IP Adapter 21
Certification (when product is marked)
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
CE European Union 2014/30/EU EMC Directive, compliant with:
RCM Australian Radiocommunications Act, compliant with:
Ex
KC Korean Registration of Broadcasting and Communications Equipment,
EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications
(1)
See the Product Certification lin k at http://www.rockwellautomation.com/global/certification/ove rview.page for Declaration of Conformity, Certificates, and other certification details.
Value
(1)
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2011/65/Eu RoHS, compliant with:
EN 50581; Technical Documentation
AS/NZS CISPR11; Industrial Emissions
European Union 2014/34/EU ATEX Directive, compliant with:
EN 60079-0:2012 + A11:2013; General Requirements EN 60079-15:2010; Potentially Explosive Atmospheres, Protection “n” II 3 G Ex nA IIC T4 Gc DEMKO 04 ATEX 0330347X
compliant with: Article 58-2 of Radio Waves Act, Clause 3
Publication 1734-IN040C-EN-P - December 2018
22 POINT I/O Dual Port EtherNet/IP Adapter

Additional Resources

Refer to these related publications, as needed.
Resource Description
1734 POINT I/O and 1738 ArmorPOINT I/O Dual Port EtherNet/IP Adapter User Manual, publication
1734-UM017
Industrial Automation Wiring and Grounding Guidelines, publication
1770-IN041
.
.
If you would like a manual, you can:
• download a free electronic version from the internet:
http://www.rockwellautomation.com/literature/
• purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative.
A detailed description of module functionality, configuration, installation procedure and information on how to use the POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP adapters.
More information on proper wiring and grounding techniques.
Publication 1734-IN040C-EN-P - December 2018
Notes:
POINT I/O Dual Port EtherNet/IP Adapter 23
Publication 1734-IN040C-EN-P - December 2018
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At
http://www.rockwellautomation.com/support/
technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/
, you can find technical manuals, a knowledge base of FAQs,
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States or Canada 1.440.646.3434 Outside United States or
Canada
Use the Worldwide Locator at
http://www.rockwellautomation.com/support/americas/phone_en.html
contact your local Rockwell Automation representative.
, or
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for the return
(call the phone number above to obtain one) to your distributor to complete the return process.
procedure.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
http://www.rockwellautomation.com/literature/
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page
Allen-Bradley, ArmorPOINT, POINT I/O, Rockwell Automation, Rockwell Software, RSLog ix 5000, and Te chConnect are trademarks of Rockwell Automation, Inc. EtherNet/IP is a tradema rk of ODVA, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
.
, available at
.
Publication 1734-IN040C-EN-P - December 2018
Supersedes Publication 1734-IN040B-EN-P - December 2009 Copyright © 2018 Rockwell Automation, Inc. All rights reserved.
Loading...