Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3
Table of Contents
Basic Power Supply 10 A
TopicPageTopicPage
Additional Resources3Hold-Up Time11
Terminology and Abbreviations4DC OK Relay Contact11
Product Overview5Efficiency and Power Loss12
Front Side and User Elements6Lifetime Expectancy and Mean Time Between
Failur e (MTB F)
Protection Features6Functional Diagram13
Safety Features7EMC14
Installation Notes7Application Notes15
Terminals and Wiring7Specifications15
Installation Notes7Environment19
Input8Dielectric Strength20
DC-Input9Standards Compliance and Certifications22
Input Inrush Current9Approximate Dimensions and Weight23
Output10
13
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Switched Mode Power Supply Technical Data, publication
1606-TD002
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
.
Rockwell Automation Publication 1606-RM056A-EN-P - December 20163
Page 4
Basic Power Supply 10 A
Terminology and
Abbreviations
TermDefinition
230V ACA figure with the unit (V AC) at the end is a momentary figure without any additional
tolerances included.
50 Hz vs. 60 HzAs long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz
mains frequency. AC 120V parameters are valid for 60 Hz mains frequency.
AC 230V A figure that is displayed with the AC or DC before the value represents a nominal
voltage with standard tolerances included. for example: DC 12V describes a 12V battery,
whether it is full (13.7V) or flat (10V)
Earth, GroundThis document uses the term “earth” which is the same as the U.S. term “ground”.
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol.
PELVProtection by extra-low voltage
SELVSafety by extra-low voltage
4Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 5
Basic Power Supply 10 A
Product Overview
1606-XLB Basic Power Supplies are
compact, industrial grade power supplies that
focus on the essential features needed in
industrial applications.
The mechanically robust housing is made of
a high-grade, reinforced molded material,
which permits the units to be used in
ambient temperatures up to 70 °C (158 °F).
This power supply features a wide input
voltage range, which makes it suitable for
global use.
The addition of a DC-OK signal makes the power supply ideal for many
industry applications such as: process, automation, and many other critical
applications where preventive function monitoring can help to avoid long
downtimes.
The 1606-XLB240E power supply offers these features:
• Wide input range, AC 100…240V
•Active PFC
• Cost optimized without compromising quality or reliability.
• Small width of only 49 mm (1.93 in.)
• Efficiency up to 95.2%
• Full power between -25…+55 °C (-13…+131 °F)
•DC-OK relay contact
•1-year warranty
Rockwell Automation Publication 1606-RM056A-EN-P - December 20165
Page 6
Basic Power Supply 10 A
Front Side and User Elements
Figure 1 - Front Side of DC-UPS
LetterDescription
AInput terminals - (screw terminals)
N, L - Line input
PE - Protective earth input
BOutput terminals - (screw terminals, two pins per pole)
+ Positive output
– Negative (return) output
COutput voltage potentiometer -
Guaranteed adjustment range: 24…28V
Fac tory set: 24.1V
DDC-OK status indicator (green) On, when the output voltage is >18V
EDC-OK Relay Contact (push-in terminals)
Protection Features
Attribute1606-XLB240E
Output protection Electronically protected against overload, no-load, and short circuits
Output overvoltage protection typ 30.5V DC
max 32 V DC
Degree of protection IP 20 EN/IEC 60529 Caution: For use in a
(1) If there is a protection event, audible noise can occur.
In case of an internal power supply
anomaly, a redundant circuit limits the
maximum output voltage. In such a case,
the output shuts down and stays down
until the input voltage is turned off and on
again for at least 1 minute or until the
green status indicator went off.
controlled environment according to
CSA 22.2 No 107.1-01.
Output shut-down with automatic restart
(1)
6Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 7
Safety Features
Basic Power Supply 10 A
Attribute1606-XLB240E
Input/output
separation
Class of protectionIPE (Protective Earth) connection required
Isolation resistance> 5 MOhminput to output, 500V DC
Tou ch curr en t
(leakage current)
SELVIEC/EN 60950-1
PELV
double or reinforced insulat ion
typ 0.30 mA/0.79 mA100V AC, 50 Hz, TN-,TT-mains/IT-mains
typ 0.42 mA/1.1 mA120V AC, 60 Hz, TN-,TT-mains/IT-mains
typ 0.67 mA/1.7 mA230V AC, 50 Hz, TN-,TT-mains/IT-mains
Figure 3 - Input Current vs. Output Load at 24VFigure 5 - Power Factor vs. Output Load
8Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 9
Basic Power Supply 10 A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A
DC-Input
Input Inrush Current
Do not operate the power supply with DC-input voltage.
A NTC inrush limiter limits the input inrush current after turn-on of the
input voltage.
AttributeAC 100VAC 120VAC 230VNotes
Inrush
current
Inrush energytyp11.5 A peak14 A peak26 A peak25 °C (77 °F) ambient, cold
(1) The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Figure 6 - Input Inrush Current, Typical Behavior,
230V AC Input, 24V 10 A Output, 25°C (77 °F) Ambient
max14.5 A peak17 A peak32 A peak40 °C (104 °F) ambient,
(1)
typ7 A peak8.5 A peak16 A peak40 °C (104 °F) ambient,
max0.2 A
2
s0.3 A
2
s1 A
2
s40 °C (158 °F) ambient,
cold start
cold start
start
cold start
Rockwell Automation Publication 1606-RM056A-EN-P - December 20169
Page 10
Basic Power Supply 10 A
Output Voltage
0
012.5
4
8
12
28V
16
20
24
15A7.52.5510
Adjustment
Range
Output Current
Continuous
current
Hiccup
PLUS
mode
Output
Current
0
13.5A
7s7s
7s
1s1s
3s
t
Short -circuit
Normal
operation
Normal
operation
First
pulse: 3s
Output
Attribute1606-XLB240ENotes
Output voltagenomDC 24V
Adjustment range24…28Vguaranteed
(1)
30V
Factory settingstyp24.1V±0.2%, at full load, cold unit
Line regulationmax5 mV90…264V AC
Load regulationmax100 mVstatic value, 0A .. 10A, see Figure 7
Ripple and noise voltagemax100 mVpp20 hz to 20 MHz, 50 Ohm
Output currentnom10 Aat 24V, below +55 °C (131 ° F) ambient temperature
6.25 Aat 28V, below +55 °C (131 ° F) ambient temperature
8.6 Aat 24V, at +70 °C (158 ° F) ambient temperature
5.4 Aat 28V, at +70 °C (158 ° F) ambient temperature
Output powernom240 Wambient temperature < 55 ° C (131 ° F)
150 Wambient temperature < 70 °C (158 ° F)
Overload behaviorcontinuous currentoutput voltage > 13V DC, see Figure 7
PLUS
Hiccup
Short circuit currentmin11 A
modeoutput voltage < 13V DC, see Fi gure 7
(2)
max15 Aload impedance 50mOhm, see Figure 7
typ4.8 A
(3)
Output capacitancetyp2 850 μFincluded inside the power supply
(1) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value that can be achieved. The typical value is
about 28.5V.
(2) Discharge current of output capacitors is not included.
(3) Discharge current of output capacitors is not included.
at clockwise end position of potentiometer
load impedance 50mOhm, see Figure 7
average (R.M.S.) current, load impedance 50 mOhm, see
Figure 7
Figure 7 - Output Voltage vs. Output Current, typFigure 8 - Short circuit (50 mOhm) on output, Hiccup
10Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 11
Hold-Up Time
0
10
20
30
40
80ms
90120230Vac
Input Voltage
50
60
Hold-up Time
70
a
b
c
d
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
21.8V
open
Output Voltage
closed
TypeAC 100VAC 120VAC 230VNotes
24V, 5 Atyp65 ms65 ms65 msSee Figure 9
min53 ms53 ms53 ms
24V, 10 Atyp32 ms32 ms32 ms
min26 ms26 ms26 ms
Figure 9 - Hold-up Time vs. Input VoltageFigure 10 - Shut-down Behavior, Definitions
Basic Power Supply 10 A
DC OK Relay Contact
This feature monitors the output voltage, which is produced by the power
supply itself. It is independent of a back-fed voltage from a unit that is
connected in parallel to the power supply output such as a redundant
application.
Attribute1606-XLB240E
Contact closesAs soon as the output voltage reaches 21.8V
Contact opensAs soon as the output voltage dips below 21.7V
Rockwell Automation Publication 1606-RM056A-EN-P - December 201611
on page 21
Page 12
Basic Power Supply 10 A
Efciency
2
92
94
95
90
96%
10A4786
Output Current
953
93
91
(
a
)
(
c
)
(a) 100Vac
(b) 120Vac
(c) 230Vac
(
b
)
Efciency
120180230 264Vac
90
91
92
93
Input Voltage
94
95
96%
100
Power Losses
120180230 264Vac
8
10
12
14
Input Voltage
16
18
20W
100
Efficiency and Power Loss
AttributeAC 100VAC 120VAC 230VNotes
Efficiencytyp93.2%94.0 %95.2 %at 24V, 10 A
Average
(1)
efficiency
Power lossestyp4.0 W4.0 W3.4 Wat 24V, 0A
(1) The average efficiency is an assumption for a typical ap plication where the power supply is loaded with 25% of the nominal load
for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time
and with 100% of the nominal load for the rest of the time.
Figure 12 - Efficiency vs. Output Current, typFigure 14 - Power Losses vs. Output Current at 24V, typ
typ92.7%93.1 %93.9 %25% at 2.5 A
25% at 5 A
25% at 7.5 A
25% at 10 A
typ9.0 W8.5 W7.5 Wat 24V, 5 A
typ17.5 W15.3 W12.1 Wat 24V, 10 A
Power Losses
24W
(a) 100Vac
21
(b) 120Vac
18
(c) 230Vac
12
9
6
3
0
0248910A
Output Current
6157
)
(
a
(
)
b
)
(
c
12Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Figure 13 - Efficiency vs. Input Voltage at 24V, 10 A, typFigure 15 - Power Losses vs. Input Voltage at 24V, 10 A
Page 13
Lifetime Expectancy and
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectier
Inrush Current Limiter
V
OUT
L
N
DC-ok
Contact
DC-ok
LED
DC-ok
Relay
Mean Time Between Failure
(MTBF)
Basic Power Supply 10 A
AttributeAC 100VAC 120VAC 230VNotes
Lifetime expectancy
(1)
89 000 h93 000 h103 000 hat 24V, 5 A and 40 °C (158 °F)
252 000 h262 000 h291 000 hat 24V, 5 A and 25 °C (77 °F)
47 000 h55 000 h74 000 hat 24V, 10 A and 40 °C (158 °F)
133 000 h156 000 h209 000 hat 24V, 10 A and 25 °C (77 °F)
MTBF
SN 29500,
(2)
IEC 61709
pendingat 24V, 10 A and 40 °C (104 °F)
at 24V, 10 A and 25 °C (77 °F)
MIL HDBK 217 Fat 24V, 10 A and 40 °C (104 °F) ; Ground
Benign GB40
at 24V, 10 A and 25 °C (77 °F) ; Ground
Benign GB25
at 24V, 10 A and 40 °C (104 °F) ; Ground
Fixed GF40
at 24V, 10 A and 25 °C (77 °F) ; Ground
Fixed GF25
(1) The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expec tancy is specified in operational hours and is calculated
according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum
life of up to 15 years (131 400 h). Any number exceeding this value is a calculated theoretical lifetime that can be used to compare
devices.
(2) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of for example, 1 000 000 h means
that statistically one unit fails every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the
failed unit has been running for 50 000 h or only for 100 h.
Functional Diagram
Figure 16 - Functional Diagram
Rockwell Automation Publication 1606-RM056A-EN-P - December 201613
Page 14
Basic Power Supply 10 A
EMC
EMC ImmunityAccording to Generic Standards EN 61000-6-1 and EN 61000-6-2Criterion
Electrostatic
discharge
Electromagnetic RF
EN 61000-4-2contact discharge
air discharge
8kV
8kV
Criterion A
Criterion A
EN 61000-4-380MHz-2.7GHz20V/mCriterion A
field
Fast transients
(Burst)
EN 61000-4-4input lines
output lines
DC-OK signal
4 kV
2 kV
2 kV
Criterion A
Criterion A
Criterion A
(coupling clamp)
Surge voltage on
input
Surge voltage on
output
Surge voltage on
EN 61000-4-5L ->N
L ->PE, N ->PE
EN 61000-4-5+ ->-
+/- ->PE
2 kV
4 kV
500V
1 kV
Criterion A
Criterion A
Criterion A
Criterion A
EN 61000-4-5DC-OK signal… PE1 kVCriterion A
DC-OK
Conduc ted
EN 61000-4-60.15…80 MHz10VCriterion A
disturbance
Mains voltage dipsEN 61000-4-110% of 120V AC
40% of 120V AC
40% of 120V AC
70% of 120V AC
0% of 200V AC
40% of 200V AC
70% of 200V AC
Vol tag e
EN 61000-4-110% of 220V AC (=0V)5000 msCriterion C
0V AC, 20 ms
48V AC, 200 ms
48V AC, 500 ms
84V AC, 20 ms
0V AC, 20 ms
80V AC, 200 ms
140V AC, 500 ms
Criterion A
Criterion C >7 A
Criterion A <7 A
Criterion A
Criterion A
Criterion C
Criterion A
interruptions
Voltage sagsSEMI F47 0706dips on the input voltage according to SEMI F47 standard
80% of 120V AC (96V AC)
70% of 120V AC (84V AC)
50% of 120V AC (60V AC)
50% of 120V AC (60V AC)
1000ms
500ms
200ms
200ms
Criterion A
Criterion A
Criterion C >8 A
Criterion A <8 A
Powerful transientsVDE 0160over entire load range750V, 0.3msCriterion A
(1) Criterion A: Power supply shows normal operation behavior withing the defined limits.
Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the
power supply occurs.
(1)
EMC EmissionAccording to Generic Standards: EN 61000-6-3, EN 610000-6-4
Conducted emission input lines EN 55011, EN 55022
FCC Part 15
CISPR 11, CISPR 22
Conducted emission output
(1)
lines
IEC/CISPR 16-1-2 , IEC/CISPR 16-2-1 limits for DC power port according
Radiated emissionEN 55011, EN 55022Class B
Harmonic input currentEN 61000-3-2Fulfilled for class A equipment
Voltage fluctuations, flickerEN 61000-3-3Fulfilled
This device complies with FCC Part 15 rules.Operation is subjected to following two conditions: (1) this device may not
cause harmful interference, and (2) this device must accept any interference received, including interference that may
cause undesired operation.
(1) For information only, not mandatory for EN 61000-6-3.
(2) Tested with constant current loads, non-pulsing.
14Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Class B
EN 61000-6-3 not fulfilled
(2)
Page 15
Basic Power Supply 10 A
10ms/DIV
Output
Voltage
Output
Current
24V
0A
20A
14.9V
20A Peak load (resistive) for 50ms
Output voltage dips from 24V to 14.9V.
Application Notes
Peak Current Capability
The unit can deliver peak currents (up to several milliseconds) which are
higher than the specified short-term currents.
This helps to start current demanding loads. Solenoids, contactors, and
pneumatic modules often have a steady state coil and a pick-up coil. The inrush
current demand of the pick-up coil is several times higher than the steady-state
current and usually exceeds the nominal output current. The same situation
applies when starting a capacitive load.
The peak current capability also delivers the safe operation of subsequent
circuit breakers of load circuits. The load branches are often individually
protected with circuit breakers or fuses. If there is a short or an overload in one
branch circuit, the fuse or circuit breaker need a certain amount of overcurrent
to open in a timely manner. This avoids voltage loss in adjacent circuits.
The extra current (peak current) is supplied by the power converter and the
built-in large sized output capacitors of the power supply. The capacitors get
discharged during such an event, which causes a voltage dip on the output. The
following two examples show typical voltage dips:
Figure 17 - Peak Load with 2x the Nominal Current for 50 ms, typFigure 18 - Peak Load with 5x the Nominal Current for 5 ms, typ
24V
Output
50A
0A
1ms/DIV
50A Peak load (resistive) for 5ms
Output voltage dips from 24V to 3.7V.
Peak Current CapabilityVoltage DipPeak Load
Peak current voltage dips typ24…14.9Vat 20 A for 50 ms, resistive load
typ24…7.1Vat 50 A for 2 ms, resistive load
typ24…3.7Vat 50 A for 5 ms, resistive load
Voltage
3.7V
Output
Current
Rockwell Automation Publication 1606-RM056A-EN-P - December 201615
Page 16
Basic Power Supply 10 A
Back Feeding Loads
Loads such as decelerating motors and inductors can feed voltage back to the
power supply. This feature is also called return voltage immunity or resistance
against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load
feeds back voltage to the power supply. It does not matter whether the power
supply is on or off.
The maximum allowed feed-back-voltage is 35V DC. The absorbing energy
can be calculated according to the built-in large sized output capacitor that is
specified in Output
on page 10.
External Input Protection
The unit is tested and approved for branch circuits up to 30 A (UL) and 32 A
(IEC). An external protection is only required if the supplying branch has an
ampacity greater than this. Check also local codes and local requirements. In
some countries local regulations can apply.
If an external fuse is necessary or utilized, minimum requirements need to be
considered to avoid nuisance tripping of the circuit breaker. A minimum value
of 10A B-characteristic or 6A C-characteristic breaker should be used.
Parallel Use to Increase Output Power
Do not use the power supply in parallel to increase the output power.
Parallel Use for Redundancy
Power supplies can be paralleled for redundancy to gain higher system
availability. Redundant systems require a certain amount of extra power to
support the load in case one power supply unit fails. The simplest way is to put
two power supplies in parallel. This is called a 1+1 redundancy. In case one
power supply unit fails, the other one is automatically able to support the load
current without any interruption.
Please note: This simple way to build a redundant system does not cover
failures such as an internal short circuit in the secondary side of the power
supply. In such a case, the defect unit becomes a load for the other power
supplies and the output voltage can not be maintained any more. This can only
be avoided by utilizing decoupling diodes that are included in the redundancy
module.
16Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 17
Basic Power Supply 10 A
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth
(see notes)
Recommendations for building redundant power systems:
– Use the DC-OK signal contact to monitor the individual power
supply units.
– Use separate input fuses for each power supply.
– Use separate mains systems for each power supply whenever it is
possible.
– It is desirable to set the output voltages of all units to the same value
(± 100 mV) or leave it at the factory setting.
Series Operation
Power supplies of the same type can be connected in series for higher output
voltages. It is possible to connect as many units in series as needed, providing
the sum of the output voltage does not exceed 150V DC. Voltages with a
potential above 60V DC are not SELV any more and can be dangerous. Such
voltages must be installed with a protection against touching.
Earthing of the output is required when the sum of the output voltage is above
60V DC.
Avoid return voltage (for example, from a decelerating motor or battery) which
is applied to the output terminals.
Keep an installation clearance of 15 mm (0.59 in.) (left/right) between two
power supplies and avoid installing the power supplies on top of each other.
Pay attention that leakage current, EMI, inrush current, harmonics increase
when using multiple power supplies.
Figure 19 - Series Operation
Rockwell Automation Publication 1606-RM056A-EN-P - December 201617
Page 18
Basic Power Supply 10 A
Inductive and Capacitive Loads
The unit is designed to supply any kind of loads, including capacitive and
inductive loads. If extreme large capacitors, such as EDLCs (electric double
layer capacitors or “UltraCaps”) with a capacitance larger than 2.0 F are
connected to the output, the unit might charge the capacitor in the
HiccupPLUS mode, see Output
on page 10.
Charging of Batteries
Do not use the power supply to charge batteries.
Operation on Two Phases
The power supply can also be used on two-phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying voltage is
+10%
below 240V
.
Figure 20 - Operation on Two Phases
Power Supply
L
Fuse
N
PE
AC
internal
fuse
DC
L3
L1
max.
+10%
240V
L2
Use in a Tightly Sealed Enclosure
When the power supply is installed in a tightly sealed enclosure, the
temperature inside the enclosure is higher than outside. In such situations, the
inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the
temperature rise inside the enclosure.
The power supply is placed in the middle of the box; no other heat producing
items are inside the box.
•Enclosure
– Rittal Type IP66 Box PK 9516 100
–Plastic
– 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.)
•Input
– 230V AC
18Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 19
Specifications
Basic Power Supply 10 A
AttributeCase ACase B
(1)
Load
Temperature inside the box
Temperature outside the box24.9 °C (76.8 °F)24.9 °C (76.8 °F)
Temperature rise23.7 K18.8 K
(1) Load is placed outside the box.
(2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.)
Attribute1606-XLB240ENotes
Output Voltage24V DC
Adjustment range24…28V DC
Output Current10 Aat 24V, amb <55°C (131°F)
Output power240 Wambient <55°C (131°F)
Output ripple< 100 mVpp20 Hz…20 MHz
AC Input voltage100…240V AC±10%
Mains frequency50…60Hz±6%
AC Input current2.17 A/1.18 Aat 120/230V AC
Power factor0.98/0.93at 120/230V AC
AC Inrush current14A/26A peakat 120/230V AC, 40°C (104 °F)
Efficiency94.0%/95.2%at 120/230V AC
Losses15.3W/12.1Wat 120/230V AC
Temperature range-25 …+70 °C (-13…+158 °F)operational
Derating6W/°C55…70 °C (131…158 °F)
Hold-up timetyp 32 ms/ 32 msat 120/230V AC
Dimensions49 x 124 x 124 mm (W x H x D
Weight540 g/1.2 lb
(2)
6.25 Aat 24V, amb <70°C (158 °F)
8.6 Aat 28V, amb <55°C (131°F)
5.4 Aat 28V, amb <70°C (158 °F)
150 Wambient <70°C (158 °F)
24V, 10 A24V, 8 A (=80%)
48.6 °C (199.4 °F)43.7 °C (110.1 °F)
Rockwell Automation Publication 1606-RM056A-EN-P - December 201619
Page 20
Basic Power Supply 10 A
0
-10 0+20+40
+70°C
2.5A
5.0A
7.5A
10A
+55
Allowable Output Current at 24V
6.3A
Ambient Temperature
-25
Allowed Output
Current at 24V
0
020004000
6000m
2A
4A
6A
8A
10A
12A
Altitude
A
.
.
.
T
a
m
b
<
5
5
°
C
B
.
.
.
T
a
m
b
<
4
5
°
C
C
.
.
.
T
a
m
b
<
3
5
°
C
A
B
C
Environment
Attribute1606-XLB240ENotes
Operation al temperature
(1)
-25… +70 °C (14...158 °F)reduce output power, see Figure 21.
Storage temperature-40… +85°C (-40…185 °F)for storage and transportation
Output derating6W/°C50°…70 °C (131…158 °F)
(2)
Humidity
Vibration sinusoidal
5...95% r.h.IEC 60068-2-30
(3)
2…17.8 Hz: ±1.6 mm (0.06 in.);
IEC 60068-2-6
17.8…500Hz: 2 g 2 hours/axis
(4)
Shock
30 g 6ms, 20 g 111ms
IEC 60068-2-27
3 bumps/direction, 18 bumps in total
Altitude0…2000 m (0…6 560 ft)without any restrictions
2000…6000 m (6 560… 20,000 ft)reduce output power or ambient temperature,
see Figure 22. IEC 62103, EN 50178,
overvoltage category II
Altitude derating15 W/1000 m or 5 °C/1000 m> 2000 m (6500 ft), see Figure 22 .
Overvoltage categoryIIIIEC 62103, EN 50178, altitudes up to 2000 m
IIaltitudes from 2000 m to 6000 m
Degree of pollution2IEC 62103, EN 50178, not conductive
LABS compatibilityThe unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
(1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.)
below the unit.
(2) Do not energize while condensation is present.
(3) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.)
(4) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.)
Figure 21 - Output Current vs. Ambient TemperatureFigure 22 - Output Current vs. Altitude
20Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 21
Basic Power Supply 10 A
Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground.
Type and factory tests are conducted by the manufacturer. Field tests can be
conducted in the field using the appropriate test equipment, which applies the
voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals
together and all output poles before conducting the test. When testing, set the
cutoff current settings to the value in the following table.
ABCD
Type test60 s2500V AC3000V AC1000V AC500V AC
Factory test5 s2500V AC2500V AC500V AC500V AC
Field test5 s2000V AC2000V AC500V AC500V AC
Cutoff current setting> 15 mA> 15 mA> 20 mA> 1 mA
Figure 23 - Dielectric Strength
InputDC-ok
L
N
Earth, PE
*)
B
B
C
DA
Output
+
-
To meet the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of the output
circuit shall be connected to the protective earth system. This helps to avoid
situations in which a load starts unexpectedly or cannot be switched off when
unnoticed earth faults occur.
Rockwell Automation Publication 1606-RM056A-EN-P - December 201621
Page 22
Basic Power Supply 10 A
Standards Compliance and
Certifications
EC Declaration of Conformity The CE Marking indicates conformance with the low voltage and EMC
UL 508Listed for use as Industrial Control Equipment ;U.S.A. (UL 508) and Canada
UL 60950-1Recognized for use as Information Technology Equipment,
RCM Declaration of Conformity C-tick is for products intended for sale and use within the Australian
EACEAC is for products intended for sale and use within the Russian market.
Directive. EN 60950-1, EN 61000-6
(C22.2 No. 14-15); File: E56639
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); File: E 168663.
market.
22Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 23
Approximate Dimensions
49
(1.93)
125
(4.92)
124
(4.88)
116.65
(4.59)
and Weight
AttributeValue
Width49 mm (1.93 in.)
Height124 mm (4.88 in.)
Depth
Weight540 g (1.21 lb)
DIN railUse 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm (0.30 or 0.59 in.).
Plastic Material of
Housing
Installation ClearancesKeep the following installation clearances: 40 mm (1.57 in.) on top, 20 mm (0.79 in.) on the bottom,
(1) The DIN rail height must be added to the unit depth to calculate the total required installation depth.
Basic Power Supply 10 A
(1)
124 mm (4.88 in.)
Flame ret ardant Polycarbo nate (PC) - UL9 4-V0 Vicat soft ening temperature specified with 149 °C (300 °F )
according to ASTM D1525
5 mm (0.20 in.) on the left and right sides are recommended when the device is loaded permanently with
more than 50 % of the rated power. Increase thi s clearance to 15 mm (0. 59 in.) in case the adjacent device
is a heat source (for example, another power supply).
Dimensions are in mm (in.).
Figure 24 - Front View
Figure 25 - Side View
Rockwell Automation Publication 1606-RM056A-EN-P - December 201623
Page 24
Basic Power Supply 10 A
Notes:
24Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 25
Page 26
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf
.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone NumbersLocate the phone number for your country.http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Automation, and Rockwell Softwa re are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respec tive companies.