Allen-Bradley 1606-XLB240E Owners Manual

Page 1
Reference Manual
Original Instructions

Basic Power Supply 10 A

Catalog Number 1606-XLB240E
Page 2

Important User Information

Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3

Table of Contents

Basic Power Supply 10 A
Topic Page Topic Page
Additional Resources 3 Hold-Up Time 11
Terminology and Abbreviations 4 DC OK Relay Contact 11
Product Overview 5 Efficiency and Power Loss 12
Front Side and User Elements 6 Lifetime Expectancy and Mean Time Between
Failur e (MTB F)
Protection Features 6 Functional Diagram 13
Safety Features 7 EMC 14
Installation Notes 7 Application Notes 15
Terminals and Wiring 7 Specifications 15
Installation Notes 7 Environment 19
Input 8 Dielectric Strength 20
DC-Input 9 Standards Compliance and Certifications 22
Input Inrush Current 9 Approximate Dimensions and Weight 23
Output 10
13

Additional Resources

These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Switched Mode Power Supply Technical Data, publication
1606-TD002
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://
www.rockwellautomation.com/global/certification/ overview.page
Provides specifications and approximate dimensions for full line of switched mode power supplies.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
.
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 3
Page 4
Basic Power Supply 10 A

Terminology and Abbreviations

Term Definition
230V AC A figure with the unit (V AC) at the end is a momentary figure without any additional
tolerances included.
50 Hz vs. 60 Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz
mains frequency. AC 120V parameters are valid for 60 Hz mains frequency.
AC 230V A figure that is displayed with the AC or DC before the value represents a nominal
voltage with standard tolerances included. for example: DC 12V describes a 12V battery, whether it is full (13.7V) or flat (10V)
Earth, Ground This document uses the term “earth” which is the same as the U.S. term “ground”.
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol.
PELV Protection by extra-low voltage
SELV Safety by extra-low voltage
4 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 5
Basic Power Supply 10 A

Product Overview

1606-XLB Basic Power Supplies are compact, industrial grade power supplies that focus on the essential features needed in industrial applications.
The mechanically robust housing is made of a high-grade, reinforced molded material, which permits the units to be used in ambient temperatures up to 70 °C (158 °F).
This power supply features a wide input voltage range, which makes it suitable for global use.
The addition of a DC-OK signal makes the power supply ideal for many industry applications such as: process, automation, and many other critical applications where preventive function monitoring can help to avoid long downtimes.
The 1606-XLB240E power supply offers these features:
• Wide input range, AC 100…240V
•Active PFC
• Cost optimized without compromising quality or reliability.
• Small width of only 49 mm (1.93 in.)
• Efficiency up to 95.2%
• Full power between -25…+55 °C (-13…+131 °F)
•DC-OK relay contact
•1-year warranty
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 5
Page 6
Basic Power Supply 10 A

Front Side and User Elements

Figure 1 - Front Side of DC-UPS
Letter Description
A Input terminals - (screw terminals)
N, L - Line input PE - Protective earth input
B Output terminals - (screw terminals, two pins per pole)
+ Positive output – Negative (return) output
C Output voltage potentiometer -
Guaranteed adjustment range: 24…28V Fac tory set: 24.1V
D DC-OK status indicator (green) On, when the output voltage is >18V
E DC-OK Relay Contact (push-in terminals)

Protection Features

Attribute 1606-XLB240E
Output protection Electronically protected against overload, no-load, and short circuits
Output overvoltage protection typ 30.5V DC
max 32 V DC
Degree of protection IP 20 EN/IEC 60529 Caution: For use in a
Over-temperature protection yes
Input transient protection MOV (Metal Oxide Varistor)
Internal input fuse Included not user replaceable
(1) If there is a protection event, audible noise can occur.
In case of an internal power supply anomaly, a redundant circuit limits the maximum output voltage. In such a case, the output shuts down and stays down until the input voltage is turned off and on again for at least 1 minute or until the green status indicator went off.
controlled environment according to CSA 22.2 No 107.1-01.
Output shut-down with automatic restart
(1)
6 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 7

Safety Features

Basic Power Supply 10 A
Attribute 1606-XLB240E
Input/output separation
Class of protection I PE (Protective Earth) connection required
Isolation resistance > 5 MOhm input to output, 500V DC
Tou ch curr en t (leakage current)
SELV IEC/EN 60950-1
PELV double or reinforced insulat ion
typ 0.30 mA/0.79 mA 100V AC, 50 Hz, TN-,TT-mains/IT-mains
typ 0.42 mA/1.1 mA 120V AC, 60 Hz, TN-,TT-mains/IT-mains
typ 0.67 mA/1.7 mA 230V AC, 50 Hz, TN-,TT-mains/IT-mains
< 0.37 mA/0.94 mA 110V AC, 50 Hz, TN-,TT-mains/IT-mains
< 0.54 mA/1.33 mA 132V AC, 60 Hz, TN-,TT-mains/IT-mains
< 0.88 mA/2.18 mA 264V AC, 50 Hz, TN-,TT-mains/IT-mains
IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

Installation Notes

Terminals and Wiring

• Use appropriate copper cables that are designed for minimum operating temperatures of:
– 75 °C (167 °F) for ambient up to 55 °C (131 °F) minimum. – 90 °C (194 °F) for ambient up to 70 °C (158 °F) minimum.
• Follow national installation codes and installation regulations.
• Verify that all strands of a stranded wire enter the terminal connection.
• Do not use the power supply without a PE connection.
• Securely tighten unused terminal compartments.
• Ferrules are allowed.
The terminals are IP20 fingersafe constructed and suitable for field- and factory wiring.
Attribute Input and Output DC-OK Signal
Terminal type Screw terminals Push-in terminals
Solid wire, max 6 mm
Stranded wire, max 4 mm
American Wire Gauge AWG 20-10 AWG 28-16
Wire diameter, max 2.8 mm (including ferrules) 1.6 mm (including ferrules)
Wire stripping length 7 mm (0.28 in.) 7mm (0.28 in.)
Screwdriver 3.5 mm slotted or cross-head No 2 Not required
Recommended tightening torque 1 N•m, 9 lb•in Not applicable
2
2
1.5 mm
1.5 mm
2
2
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 7
Page 8
Basic Power Supply 10 A
Turn-on
90V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output Voltage
Input Voltage
10A01234567
0
0.5
1.0
1.5
2.0
2.5
3A
Input Current, typ.
89
Output Current
a) 100Vac b) 120Vac c) 230Vac
c
a
b
10A234 6 8
0.70
0.75
579
0.80
0.85
0.90
0.95
1.00
Power Factor, typ.
1
Output Current
b
a
a) 100Vac b) 120Vac c) 230Vac
c

Input

Attribute 1606-XLB240E
AC input nom 100…240V AC Auto-select, suitable for TN-, TT- and IT mains networks
AC input range min 90…264V AC continuous operation
Allowed voltage L or N to earth max 300V AC continuous, IEC 62103
Input frequency nom 50…60 Hz ±6%
Turn-on voltage typ 81V AC at 24V 10 A, steady-state value, see Figure 2
Shut-down voltage typ 63V AC/71V AC at no load/nominal load, steady-state value, see Figure 2
External input protection See recommendations in External Input Protection on page 16.
Attribute AC 100V AC 120V AC 230V
Input current typ 2.60 A 2.17 A 1.18 A at 24V, 10 A, see Figure 3
Power factor
Crest factor
Start-up delay typ 400 ms 260 ms 200 ms see Figure 4
Rise time typ 60 ms at 24V, 10 A const. current load, 0 mF load capacitance, see Figure 4
Turn-on overshoot max 200 mV see Figure 4
(1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
(2) The crest factor is the mathematical ratio of the peak value to the T ms value of the input current waveform.
min 264…300V AC < 500 ms
(1)
(2)
typ 0.99 0.98 0.93 at 24V, 10 A, see Figure 5
typ 1.6 1.7 2.0 at 24V, 10 A
typ 230 ms at 24V, 10 A const. current load, 5 mF load capacitance, see Figure 4
Figure 2 - Input Voltage Range, typ Figure 4 - Turn-on Behavior, Definitions
Figure 3 - Input Current vs. Output Load at 24V Figure 5 - Power Factor vs. Output Load
8 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 9
Basic Power Supply 10 A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A
20ms/DIV
Input current 5A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
Ipeak = 16A

DC-Input

Input Inrush Current

Do not operate the power supply with DC-input voltage.
A NTC inrush limiter limits the input inrush current after turn-on of the input voltage.
Attribute AC 100V AC 120V AC 230V Notes
Inrush current
Inrush energy typ 11.5 A peak 14 A peak 26 A peak 25 °C (77 °F) ambient, cold
(1) The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Figure 6 - Input Inrush Current, Typical Behavior, 230V AC Input, 24V 10 A Output, 25°C (77 °F) Ambient
max 14.5 A peak 17 A peak 32 A peak 40 °C (104 °F) ambient,
(1)
typ 7 A peak 8.5 A peak 16 A peak 40 °C (104 °F) ambient,
max 0.2 A
2
s0.3 A
2
s1 A
2
s 40 °C (158 °F) ambient,
cold start
cold start
start
cold start
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 9
Page 10
Basic Power Supply 10 A
Output Voltage
0
0 12.5
4
8
12
28V
16
20
24
15A7.52.5 5 10
Adjustment
Range
Output Current
Continuous
current
Hiccup
PLUS
mode
Output Current
0
13.5A
7s 7s
7s
1s 1s
3s
t
Short -circuit
Normal
operation
Normal
operation
First pulse: 3s

Output

Attribute 1606-XLB240E Notes
Output voltage nom DC 24V
Adjustment range 24…28V guaranteed
(1)
30V
Factory settings typ 24.1V ±0.2%, at full load, cold unit
Line regulation max 5 mV 90…264V AC
Load regulation max 100 mV static value, 0A .. 10A, see Figure 7
Ripple and noise voltage max 100 mVpp 20 hz to 20 MHz, 50 Ohm
Output current nom 10 A at 24V, below +55 °C (131 ° F) ambient temperature
6.25 A at 28V, below +55 °C (131 ° F) ambient temperature
8.6 A at 24V, at +70 °C (158 ° F) ambient temperature
5.4 A at 28V, at +70 °C (158 ° F) ambient temperature
Output power nom 240 W ambient temperature < 55 ° C (131 ° F)
150 W ambient temperature < 70 °C (158 ° F)
Overload behavior continuous current output voltage > 13V DC, see Figure 7
PLUS
Hiccup
Short circuit current min 11 A
mode output voltage < 13V DC, see Fi gure 7
(2)
max 15 A load impedance 50mOhm, see Figure 7
typ 4.8 A
(3)
Output capacitance typ 2 850 μF included inside the power supply
(1) This is the maximum output voltage that can occur at the clockwise end position of the potentiometer due to tolerances. It is not a guaranteed value that can be achieved. The typical value is
about 28.5V.
(2) Discharge current of output capacitors is not included.
(3) Discharge current of output capacitors is not included.
at clockwise end position of potentiometer
load impedance 50mOhm, see Figure 7
average (R.M.S.) current, load impedance 50 mOhm, see
Figure 7
Figure 7 - Output Voltage vs. Output Current, typ Figure 8 - Short circuit (50 mOhm) on output, Hiccup
10 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 11

Hold-Up Time

0
10
20
30
40
80ms
90 120 230Vac
Input Voltage
50
60
Hold-up Time
70
a
b
c d
a) 24V 5A typ. b) 24V 5A min.
c) 24V 10A typ. d) 24V 10A min.
- 5%
Hold-up Time
Zero Transition
Output Voltage
Input Voltage
21.8V
open
Output Voltage
closed
Type AC 100V AC 120V AC 230V Notes
24V, 5 A typ 65 ms 65 ms 65 ms See Figure 9
min 53 ms 53 ms 53 ms
24V, 10 A typ 32 ms 32 ms 32 ms
min 26 ms 26 ms 26 ms
Figure 9 - Hold-up Time vs. Input Voltage Figure 10 - Shut-down Behavior, Definitions
Basic Power Supply 10 A

DC OK Relay Contact

This feature monitors the output voltage, which is produced by the power supply itself. It is independent of a back-fed voltage from a unit that is connected in parallel to the power supply output such as a redundant application.
Attribute 1606-XLB240E
Contact closes As soon as the output voltage reaches 21.8V
Contact opens As soon as the output voltage dips below 21.7V
Contact ratings max 60V DC, 0.3 A; 30V DC, 1 A; 30V AC, 0.5 A resistive load
min 1 mA at 5V DC min required load
Isolation voltage See Dielectric Strength
Figure 11 - DC-OK Relay Contact Behavior
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 11
on page 21
Page 12
Basic Power Supply 10 A
Efciency
2
92
94
95
90
96%
10A4786
Output Current
953
93
91
(
a
)
(
c
)
(a) 100Vac (b) 120Vac (c) 230Vac
(
b
)
Efciency
120 180 230 264Vac
90
91
92
93
Input Voltage
94
95
96%
100
Power Losses
120 180 230 264Vac
8
10
12
14
Input Voltage
16
18
20W
100

Efficiency and Power Loss

Attribute AC 100V AC 120V AC 230V Notes
Efficiency typ 93.2% 94.0 % 95.2 % at 24V, 10 A
Average
(1)
efficiency
Power losses typ 4.0 W 4.0 W 3.4 W at 24V, 0A
(1) The average efficiency is an assumption for a typical ap plication where the power supply is loaded with 25% of the nominal load
for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% of the nominal load for the rest of the time.
Figure 12 - Efficiency vs. Output Current, typ Figure 14 - Power Losses vs. Output Current at 24V, typ
typ 92.7% 93.1 % 93.9 % 25% at 2.5 A
25% at 5 A 25% at 7.5 A 25% at 10 A
typ 9.0 W 8.5 W 7.5 W at 24V, 5 A
typ 17.5 W 15.3 W 12.1 W at 24V, 10 A
Power Losses
24W
(a) 100Vac
21
(b) 120Vac
18
(c) 230Vac
12
9 6 3 0
024 8910A
Output Current
6157
)
(
a
(
)
b
)
(
c
12 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Figure 13 - Efficiency vs. Input Voltage at 24V, 10 A, typ Figure 15 - Power Losses vs. Input Voltage at 24V, 10 A
Page 13
Lifetime Expectancy and
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
Temper-
ature
Shut-
down
Input Fuse Input Filter Input Rectier Inrush Current Limiter
V
OUT
L
N
DC-ok Contact
DC-ok LED
DC-ok Relay
Mean Time Between Failure (MTBF)
Basic Power Supply 10 A
Attribute AC 100V AC 120V AC 230V Notes
Lifetime expectancy
(1)
89 000 h 93 000 h 103 000 h at 24V, 5 A and 40 °C (158 °F)
252 000 h 262 000 h 291 000 h at 24V, 5 A and 25 °C (77 °F)
47 000 h 55 000 h 74 000 h at 24V, 10 A and 40 °C (158 °F)
133 000 h 156 000 h 209 000 h at 24V, 10 A and 25 °C (77 °F)
MTBF
SN 29500,
(2)
IEC 61709
pending at 24V, 10 A and 40 °C (104 °F)
at 24V, 10 A and 25 °C (77 °F)
MIL HDBK 217 F at 24V, 10 A and 40 °C (104 °F) ; Ground
Benign GB40
at 24V, 10 A and 25 °C (77 °F) ; Ground Benign GB25
at 24V, 10 A and 40 °C (104 °F) ; Ground Fixed GF40
at 24V, 10 A and 25 °C (77 °F) ; Ground Fixed GF25
(1) The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expec tancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400 h). Any number exceeding this value is a calculated theoretical lifetime that can be used to compare devices.
(2) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of for example, 1 000 000 h means that statistically one unit fails every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50 000 h or only for 100 h.

Functional Diagram

Figure 16 - Functional Diagram
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 13
Page 14
Basic Power Supply 10 A
EMC
EMC Immunity According to Generic Standards EN 61000-6-1 and EN 61000-6-2 Criterion
Electrostatic discharge
Electromagnetic RF
EN 61000-4-2 contact discharge
air discharge
8kV 8kV
Criterion A Criterion A
EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
field
Fast transients (Burst)
EN 61000-4-4 input lines
output lines DC-OK signal
4 kV 2 kV 2 kV
Criterion A Criterion A Criterion A
(coupling clamp)
Surge voltage on input
Surge voltage on output
Surge voltage on
EN 61000-4-5 L ->N
L ->PE, N ->PE
EN 61000-4-5 + ->-
+/- ->PE
2 kV 4 kV
500V 1 kV
Criterion A Criterion A
Criterion A Criterion A
EN 61000-4-5 DC-OK signal… PE 1 kV Criterion A
DC-OK
Conduc ted
EN 61000-4-6 0.15…80 MHz 10V Criterion A
disturbance
Mains voltage dips EN 61000-4-11 0% of 120V AC
40% of 120V AC 40% of 120V AC 70% of 120V AC 0% of 200V AC 40% of 200V AC 70% of 200V AC
Vol tag e
EN 61000-4-11 0% of 220V AC (=0V) 5000 ms Criterion C
0V AC, 20 ms 48V AC, 200 ms 48V AC, 500 ms 84V AC, 20 ms 0V AC, 20 ms 80V AC, 200 ms 140V AC, 500 ms
Criterion A Criterion C >7 A Criterion A <7 A Criterion A Criterion A Criterion C Criterion A
interruptions
Voltage sags SEMI F47 0706 dips on the input voltage according to SEMI F47 standard
80% of 120V AC (96V AC) 70% of 120V AC (84V AC) 50% of 120V AC (60V AC) 50% of 120V AC (60V AC)
1000ms 500ms 200ms 200ms
Criterion A Criterion A Criterion C >8 A Criterion A <8 A
Powerful transients VDE 0160 over entire load range 750V, 0.3ms Criterion A
(1) Criterion A: Power supply shows normal operation behavior withing the defined limits.
Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the power supply occurs.
(1)
EMC Emission According to Generic Standards: EN 61000-6-3, EN 610000-6-4
Conducted emission input lines EN 55011, EN 55022
FCC Part 15 CISPR 11, CISPR 22
Conducted emission output
(1)
lines
IEC/CISPR 16-1-2 , IEC/CISPR 16-2-1 limits for DC power port according
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Fulfilled for class A equipment
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled
This device complies with FCC Part 15 rules.Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
(1) For information only, not mandatory for EN 61000-6-3.
(2) Tested with constant current loads, non-pulsing.
14 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Class B
EN 61000-6-3 not fulfilled
(2)
Page 15
Basic Power Supply 10 A
10ms/DIV
Output Voltage
Output Current
24V
0A
20A
14.9V
20A Peak load (resistive) for 50ms Output voltage dips from 24V to 14.9V.

Application Notes

Peak Current Capability

The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short-term currents.
This helps to start current demanding loads. Solenoids, contactors, and pneumatic modules often have a steady state coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state current and usually exceeds the nominal output current. The same situation applies when starting a capacitive load.
The peak current capability also delivers the safe operation of subsequent circuit breakers of load circuits. The load branches are often individually protected with circuit breakers or fuses. If there is a short or an overload in one branch circuit, the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner. This avoids voltage loss in adjacent circuits.
The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The following two examples show typical voltage dips:
Figure 17 - Peak Load with 2x the Nominal Current for 50 ms, typ Figure 18 - Peak Load with 5x the Nominal Current for 5 ms, typ
24V
Output
50A
0A
1ms/DIV
50A Peak load (resistive) for 5ms Output voltage dips from 24V to 3.7V.
Peak Current Capability Voltage Dip Peak Load
Peak current voltage dips typ 24…14.9V at 20 A for 50 ms, resistive load
typ 24…7.1V at 50 A for 2 ms, resistive load
typ 24…3.7V at 50 A for 5 ms, resistive load
Voltage
3.7V
Output Current
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 15
Page 16
Basic Power Supply 10 A

Back Feeding Loads

Loads such as decelerating motors and inductors can feed voltage back to the power supply. This feature is also called return voltage immunity or resistance against Back- E.M.F. (Electro Magnetic Force).
This power supply is resistant and does not show malfunctioning when a load feeds back voltage to the power supply. It does not matter whether the power supply is on or off.
The maximum allowed feed-back-voltage is 35V DC. The absorbing energy can be calculated according to the built-in large sized output capacitor that is specified in Output
on page 10.

External Input Protection

The unit is tested and approved for branch circuits up to 30 A (UL) and 32 A (IEC). An external protection is only required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In some countries local regulations can apply.
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of the circuit breaker. A minimum value of 10A B-characteristic or 6A C-characteristic breaker should be used.

Parallel Use to Increase Output Power

Do not use the power supply in parallel to increase the output power.

Parallel Use for Redundancy

Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one power supply unit fails. The simplest way is to put two power supplies in parallel. This is called a 1+1 redundancy. In case one power supply unit fails, the other one is automatically able to support the load current without any interruption.
Please note: This simple way to build a redundant system does not cover failures such as an internal short circuit in the secondary side of the power supply. In such a case, the defect unit becomes a load for the other power supplies and the output voltage can not be maintained any more. This can only be avoided by utilizing decoupling diodes that are included in the redundancy module.
16 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 17
Basic Power Supply 10 A
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth (see notes)
Recommendations for building redundant power systems:
– Use the DC-OK signal contact to monitor the individual power
supply units. – Use separate input fuses for each power supply. – Use separate mains systems for each power supply whenever it is
possible. – It is desirable to set the output voltages of all units to the same value
(± 100 mV) or leave it at the factory setting.

Series Operation

Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150V DC. Voltages with a potential above 60V DC are not SELV any more and can be dangerous. Such voltages must be installed with a protection against touching.
Earthing of the output is required when the sum of the output voltage is above 60V DC.
Avoid return voltage (for example, from a decelerating motor or battery) which is applied to the output terminals.
Keep an installation clearance of 15 mm (0.59 in.) (left/right) between two power supplies and avoid installing the power supplies on top of each other.
Pay attention that leakage current, EMI, inrush current, harmonics increase when using multiple power supplies.
Figure 19 - Series Operation
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 17
Page 18
Basic Power Supply 10 A

Inductive and Capacitive Loads

The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance larger than 2.0 F are connected to the output, the unit might charge the capacitor in the HiccupPLUS mode, see Output
on page 10.

Charging of Batteries

Do not use the power supply to charge batteries.

Operation on Two Phases

The power supply can also be used on two-phases of a three-phase-system. Such a phase-to-phase connection is allowed as long as the supplying voltage is
+10%
below 240V
.
Figure 20 - Operation on Two Phases
Power Supply
L
Fuse
N
PE
AC
internal
fuse
DC
L3
L1
max.
+10%
240V
L2

Use in a Tightly Sealed Enclosure

When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure is higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box; no other heat producing items are inside the box.
•Enclosure – Rittal Type IP66 Box PK 9516 100 –Plastic – 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in.)
•Input – 230V AC
18 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 19

Specifications

Basic Power Supply 10 A
Attribute Case A Case B
(1)
Load
Temperature inside the box
Temperature outside the box 24.9 °C (76.8 °F) 24.9 °C (76.8 °F)
Temperature rise 23.7 K 18.8 K
(1) Load is placed outside the box.
(2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.)
Attribute 1606-XLB240E Notes
Output Voltage 24V DC
Adjustment range 24…28V DC
Output Current 10 A at 24V, amb <55°C (131°F)
Output power 240 W ambient <55°C (131°F)
Output ripple < 100 mVpp 20 Hz…20 MHz
AC Input voltage 100…240V AC ±10%
Mains frequency 50…60Hz ±6%
AC Input current 2.17 A/1.18 A at 120/230V AC
Power factor 0.98/0.93 at 120/230V AC
AC Inrush current 14A/26A peak at 120/230V AC, 40°C (104 °F)
Efficiency 94.0%/95.2% at 120/230V AC
Losses 15.3W/12.1W at 120/230V AC
Temperature range -25 …+70 °C (-13…+158 °F) operational
Derating 6W/°C 55…70 °C (131…158 °F)
Hold-up time typ 32 ms/ 32 ms at 120/230V AC
Dimensions 49 x 124 x 124 mm ( W x H x D
Weight 540 g/1.2 lb
(2)
6.25 A at 24V, amb <70°C (158 °F)
8.6 A at 28V, amb <55°C (131°F)
5.4 A at 28V, amb <70°C (158 °F)
150 W ambient <70°C (158 °F)
24V, 10 A 24V, 8 A (=80%)
48.6 °C (199.4 °F) 43.7 °C (110.1 °F)
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 19
Page 20
Basic Power Supply 10 A
0
-10 0 +20 +40
+70°C
2.5A
5.0A
7.5A
10A
+55
Allowable Output Current at 24V
6.3A
Ambient Temperature
-25
Allowed Output Current at 24V
0
0 2000 4000
6000m
2A
4A
6A
8A
10A
12A
Altitude
A
.
.
.
T
a
m
b
<
5
5
°
C
B
.
.
.
T
a
m
b
<
4
5
°
C
C
.
.
.
T
a
m
b
<
3
5
°
C
A
B
C

Environment

Attribute 1606-XLB240E Notes
Operation al temperature
(1)
-25… +70 °C (14...158 °F) reduce output power, see Figure 21.
Storage temperature -40… +85°C (-40…185 °F) for storage and transportation
Output derating 6W/°C 50°…70 °C (131…158 °F)
(2)
Humidity
Vibration sinusoidal
5...95% r.h. IEC 60068-2-30
(3)
2…17.8 Hz: ±1.6 mm (0.06 in.);
IEC 60068-2-6
17.8…500Hz: 2 g 2 hours/axis
(4)
Shock
30 g 6ms, 20 g 111ms
IEC 60068-2-27
3 bumps/direction, 18 bumps in total
Altitude 0…2000 m (0…6 560 ft) without any restrictions
2000…6000 m (6 560… 20,000 ft) reduce output power or ambient temperature,
see Figure 22. IEC 62103, EN 50178, overvoltage category II
Altitude derating 15 W/1000 m or 5 °C/1000 m > 2000 m (6500 ft), see Figure 22 .
Overvoltage category III IEC 62103, EN 50178, altitudes up to 2000 m
II altitudes from 2000 m to 6000 m
Degree of pollution 2 IEC 62103, EN 50178, not conductive
LABS compatibility The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
(1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2 cm (0.79 in.)
below the unit. (2) Do not energize while condensation is present. (3) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.) (4) Tested on a DIN Rail with a thickness of 1.3 mm (0.05 in.)
Figure 21 - Output Current vs. Ambient Temperature Figure 22 - Output Current vs. Altitude
20 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 21
Basic Power Supply 10 A

Dielectric Strength

The output voltage is floating and has no ohmic connection to the ground. Type and factory tests are conducted by the manufacturer. Field tests can be conducted in the field using the appropriate test equipment, which applies the voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals together and all output poles before conducting the test. When testing, set the cutoff current settings to the value in the following table.
ABCD
Type test 60 s 2500V AC 3000V AC 1000V AC 500V AC
Factory test 5 s 2500V AC 2500V AC 500V AC 500V AC
Field test 5 s 2000V AC 2000V AC 500V AC 500V AC
Cutoff current setting > 15 mA > 15 mA > 20 mA > 1 mA
Figure 23 - Dielectric Strength
Input DC-ok
L
N
Earth, PE
*)
B
B
C
DA
Output
+
-
To meet the PELV requirements according to EN60204-1 § 6.4.1, we recommend that either the + pole, the – pole or any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in which a load starts unexpectedly or cannot be switched off when unnoticed earth faults occur.
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 21
Page 22
Basic Power Supply 10 A

Standards Compliance and Certifications

EC Declaration of Conformity The CE Marking indicates conformance with the low voltage and EMC
UL 508 Listed for use as Industrial Control Equipment ;U.S.A. (UL 508) and Canada
UL 60950-1 Recognized for use as Information Technology Equipment,
RCM Declaration of Conformity C-tick is for products intended for sale and use within the Australian
EAC EAC is for products intended for sale and use within the Russian market.
Directive. EN 60950-1, EN 61000-6
(C22.2 No. 14-15); File: E56639
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); File: E 168663.
market.
22 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 23
Approximate Dimensions
49
(1.93)
125
(4.92)
124
(4.88)
116.65 (4.59)
and Weight
Attribute Value
Width 49 mm (1.93 in.)
Height 124 mm (4.88 in.)
Depth
Weight 540 g (1.21 lb)
DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm (0.30 or 0.59 in.).
Plastic Material of Housing
Installation Clearances Keep the following installation clearances: 40 mm (1.57 in.) on top, 20 mm (0.79 in.) on the bottom,
(1) The DIN rail height must be added to the unit depth to calculate the total required installation depth.
Basic Power Supply 10 A
(1)
124 mm (4.88 in.)
Flame ret ardant Polycarbo nate (PC) - UL9 4-V0 Vicat soft ening temperature specified with 149 °C (300 °F ) according to ASTM D1525
5 mm (0.20 in.) on the left and right sides are recommended when the device is loaded permanently with more than 50 % of the rated power. Increase thi s clearance to 15 mm (0. 59 in.) in case the adjacent device is a heat source (for example, another power supply).
Dimensions are in mm (in.).
Figure 24 - Front View
Figure 25 - Side View
Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 23
Page 24
Basic Power Supply 10 A
Notes:
24 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016
Page 25
Page 26
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf
.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
http://www.rockwellautomation.com/global/support/direct-dial.page
Literature Library
Installation Instructions, Manuals, Brochures, and Technical Data.
http://www.rockwellautomation.com/global/literature-library/overview.page
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
http://www.rockwellautomation.com/global/support/pcdc.page
.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Automation, and Rockwell Softwa re are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respec tive companies.
Publication 1606-RM056A-EN-P - December 2016
Copyright © 2016 Rockwell Auto mation, Inc. All rights reserved. Pr inted in the U.S.A.
Loading...