Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circu mstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circu mstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Page 3
Table of Contents
Basic Power Supply 5 A
TopicPageTopicPage
Additional Resources3Hold-up Time11
Terminology and Abbreviations4DC OK Relay Contact11
Product Overview5Efficiency and Power Loss12
Front Side and User Elements6Lifetime Expectancy and Mean Time between
Failur e (MTB F)
Protection Features6Functional Diagram13
Safety Features7EMC14
Installation Notes7Application Notes15
Terminals and Wiring7Specifications19
Installation Notes7Environment20
Input8Dielectric Strength21
DC-Input9Standards Compliance and Certifications22
Input Inrush Current9Approximate Dimensions and Weight23
Output10
13
Summary of Changes
Additional Resources
This manual contains new and updated information as indicated in the
following table.
Top icPag e
Corrected dimension information23
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Switched Mode Power Supply Technical Data, publication
1606-TD002
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
To order paper copies of technical documentation, contact your local
Allen-Bradley distributor or Rockwell Automation sales representative.
.
Rockwell Automation Publication 1606-RM055B-EN-P - February 20173
Page 4
Basic Power Supply 5 A
Terminology and
Abbreviations
TermDefinition
230V ACA figure with the unit (V AC) at the end is a momentary figure without any additional
tolerances included.
50 Hz vs. 60 HzAs long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz
mains frequency. AC 120V parameters are valid for 60 Hz mains frequency.
AC 230V A figure that is displayed with the AC or DC before the value represents a nominal
voltage with standard tolerances included. For example: DC 12V describes a 12V battery,
whether it is full (13.7V) or flat (10V)
Earth, GroundThis document uses the term “earth” which is the same as the U.S. term “ground”.
PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol.
PELVProtection by extra-low voltage
SELVSafety by extra-low voltage
4Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 5
Basic Power Supply 5 A
Product Overview
1606-XLB Basic Power Supplies are
compact, industrial grade power supplies that
focus on the essential features needed in
industrial applications.
The housing is made of a high-grade,
reinforced molded material, which permits
the units to be used in ambient temperatures
up to 70 °C (158 °F).
This power supply features a wide input
voltage range, which makes it suitable for
global use.
The addition of a DC-OK signal makes the
power supply ideal for many industry
applications such as: process, automation,
and many other critical applications where
preventive function monitoring can help to
avoid long downtimes.
The 1606-XLB120E power supply offers these features:
• 100…120V/200…240V AC auto-select input
• Cost that is optimized without compromising the quality or reliability
• Small width of 39 mm (1.54 in.) takes up less space on the DIN rail
• Efficiency up to 92.3%
• Full power between -10…+55 °C (14…131 °F)
• DC-OK relay contact included
•1-year warranty
Rockwell Automation Publication 1606-RM055B-EN-P - February 20175
Page 6
Basic Power Supply 5 A
Front Side and User Elements
Figure 1 - Front Side of DC-UPS
LetterDescription
AInput terminals - (screw terminals)
N, L - Line input
PE - Protective earth input
BOutput terminals - (screw terminals, two pins per pole)
+ Positive output
– Negative (return) output
COutput voltage potentiometer -
Guaranteed adjustment range: 24…28V
Fac tory set: 24 .1V
DDC-OK status indicator- (green) On, when the output voltage is >18V
EDC-OK Relay Contact (push-in terminals)
Protection Features
Attribute1606-XLB120E
Output protection Electronically protected against overload, no-load, and short circuits
Output overvoltage protection typ 31V DC
max 34V DC
Degree of protection IP 20 EN/IEC 60529 Caution: For use in a controlled
In case of an internal power supply anomal y, a redundant
circuit limits the maximum output voltage. In such a
case, the output shuts down and stays down until the
input voltage is turned off and on again for at least 1
minute or until the green status indicator went off.
environment according to CSA 22.2 No 107.1-01.
6Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 7
Safety Features
Basic Power Supply 5 A
Attribute1606-XLB120E
Input/output separation
double or reinforced insulation
Class of protectionIPE (Protective Earth) connection required
Isolation resistance> 100 MOhmInput to output, 500V DC
Tou ch cur ren t
(leakage current)
SELVIEC/EN 60950-1
PELVIEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41
typ 0.21 mA/0.46 mA 100V AC, 50 Hz, TN-,TT-mains/IT-mains
typ 0.30 mA/0.65 mA 120V AC, 60 Hz, TN-,TT-mains/IT-mains
typ 0.33 mA/0.72 mA 230V AC, 50 Hz, TN-,TT-mains/IT-mains
Figure 3 - Input Current vs. Output Load at 24VFigure 5 - Power Factor vs. Output Load
8Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 9
Basic Power Supply 5 A
20ms/DIV
Input current 20A/DIV
Input voltage 500V/DIV
Output voltage 20V/DIV
1ms/DIV
Ipeak = 33A
Input current 10A/DIV
DC-Input
Input Inrush Current
Figure 6 - Input Inrush Current, Typical Behavior,
230V AC Input, 24V 5 A Output, 40 °C (104 °F) Ambient
Do not operate the power supply with DC-input voltage.
A NTC inrush limiter limits the input inrush current after turn-on of the
input voltage.
AttributeAC 100VAC 120VAC 230VNotes
Inrush
current
Inrush
energy
max23 A peak27 A peak40 A peak40 °C (104 °F) ambient, cold start
typ18 A peak22 A peak33 A peak
typ13 A peak16 A peak30 A peak25 °C (77 °F) ambient, cold start
max0.4 A
2
s0.5 A
2
s1.5 A
2
s40 °C (104 °F) ambient, cold start
Figure 7 - Input Inrush Current, Zoom Into First Peak
230V AC Input, 24V 5 A Output, 40 °C (104 °F) Ambient
Rockwell Automation Publication 1606-RM055B-EN-P - February 20179
Page 10
Basic Power Supply 5 A
Output Voltage
0
024
4
8
12
28V
16
20
24
10A53167
intermittent
operation
8 9
continuous
current
Adjustment
Range
Output Current
A
.
.
.
1
3
2
/
2
6
4
V
a
c
B
.
.
.
8
5
/
1
8
7
V
a
c
A
B
Output
Attribute1606-XLB120ENotes
Output voltagenomDC 24V
Adjustment rangemin24…28Vguaranteed
max30V
(1)
at clockwise end position of potentiometer
Factory settingstyp24.1V±0.2 %, at full load, cold unit
Line regulationmax10 mV90…132/180…264V AC
Load regulationmax150 mVstatic value, 0 A .. 5 A .. 0 A
Ripple and noise
max100 mVpp20 Hz to 20 MHz, 50 Ohms
voltage
Output currentfor AC 110…120/220…240V mains voltages (includes AC 208V mains):
nom5 Aat 24V, below 55 °C (122 °F) ambient temperature
4.3 Aat 28V, below 55 °C (122 °F) ambient temperature
3.1 Aat 24V, at 70 °C (158 °F) ambient temperature
2.7 Aat 28V, at 70 °C (158 °F) ambient temperature
Derate linearly between +55 °C (122 °F) and +70 °C (158 °F)
for AC 100/200V mains voltages:
nom5 Aat 24V, below 55 °C (122 °F) ambient temperature
4.3 Aat 28V, below 55 °C (122 °F) ambient temperature
2.5 Aat 24V, at 70 °C (158 °F) ambient temperature
2.1 Aat 28V, at 70 °C (158 °F) ambient temperature
Derate linearly 50 …70 °C (122…158 °F)
Overload behaviorcontinuous currentoutput voltage > 10V DC, see Figure 8
Intermittentoutput voltage < 10V DC, see Figu re 8
Short Circuit currenttyp3.5 A
(2)
average (R.M.S.) current, load impedance 50mOhm
Output capacitancetyp2 050 μFincluded inside the power supply
(1) This is the maximum output voltage that can occur at the clockwise end position o f the potentiometer due to tolerances. It is not
guaranteed value that can be achieved. The typical value is about 28.5V.
(2) Discharge current of output capacitors is not included.
Figure 8 - Output Voltage vs. Output Current, R ms current, typFigure 9 - Intermittent Operation at Shorted Output, typ
10Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
60ms
360ms
9.2A
Page 11
Hold-up Time
0
25
50
125ms
85120155190230Vac
Input Voltage
Hold-up Time
75
100
a) 24V 2.5A typ.
b) 24V 2.5A min.
c) 24V 5A typ.
d) 24V 5A min.
a bc da
b
c
d
TypeAC 100VAC 120VAC 230V
24V, 2.5 Atyp64 ms108 ms105 ms
min54 ms91 ms88 ms
24V, 5 Atyp26 ms51 ms50 ms
min22 ms43 ms42 ms
Figure 10 - Hold-up Time vs. Input VoltageFigure 11 - Shut-down behavior, definitions
Zero Transition
Input
Voltage
Basic Power Supply 5 A
DC OK Relay Contact
Output
Voltage
Hold-up Time
- 5%
This feature monitors the output voltage that is produced by the power supply
itself. It is independent of a back-fed voltage from a unit that is connected in
parallel to the power supply output (for example, redundant application).
Attribute1606-XLB120E
Contact closesAs soon as the output voltage reaches 21.4V
Contact opensAs soon as the output voltage dips below 21.4V
Contact ratingsmax60V DC 0.3 A, 30V DC 1 A, 30V AC 0.5 Aresistive load
min1 mA at 5V DCminimum required load
Isolation voltageSee Dielectric Strength
Figure 12 - DC-OK Relay Contact Behavior
on page 21
Output Voltage
21.4V
open
closed
Rockwell Automation Publication 1606-RM055B-EN-P - February 201711
Page 12
Basic Power Supply 5 A
Efciency
0.5
86
87
88
89
90
91
92
85
93%
5A2 2.5413
a
c
b
Output Current
1.53.54.5
a) 100Vac
b) 120Vac
c) 230Vac
Power Losses
0
51A
0
2
6
8
10
12W
4
234
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
c
b
a
Efciency
90120
155
180230 260Vac
87
88
89
90
Input Voltage
91
92
93%
Efficiency and Power Loss
AttributeAC 100VAC 120VAC 230VNotes
Efficiencytyp90.7%91.2%92.3%at 24V, 5 A
Average
(1)
efficiency
Power lossestyp1.4 W1.5 W0.7 Wat 24V, 0 A
(1) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load
for 25% of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time
and with 100% of the nominal load for the rest of the time.
Figure 13 - Efficiency vs. Output Current, typFigure 15 - Power Losses vs. Output Current at 24V, typ
typ89.2%89.4%90.6%25% at 1.25 A, 25% at 2.5 A,
25% at 3.75 A. 25% at 5 A
typ7.0 W7.4 W6.0 Wat 24V, 2.5 A
typ12.3 W11.6 W10.0 Wat 24V, 5 A
Figure 14 - Efficiency vs. Input Voltage at 24V, 5 A, typFigure 16 - Power Losses vs. Input Voltage at 24V, 5 A
Power Losses
14W
12
10
8
6
90120
12Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
155
Input Voltage
180230 260Vac
Page 13
Lifetime Expectancy and
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectier
&
Inrush
Limiter
(NTC)
DC-ok
Relay
DC-ok
Contact
115/230V
Auto
Select
Mean Time between Failure
(MTBF)
Basic Power Supply 5 A
AttributeAC 100VAC 120VAC 230VNotes
Lifetime
expectancy
(1)
181 000 h194 000 h219 000 hat 24V, 2.5 A and 40 °C (104 °F)
511 000 h548 000 h621 000 hat 24V, 2.5 A and 25 °C (77 °F)
66 000 h68 000 h83 000 hat 24V, 5 A and 40 °C (104 °F)
188 000 h193 000 h234 000 hat 24V, 5 A and 25 °C (77 °F)
MTBF
SN 29500,
(2)
IEC 61709
MIL HDBK
217 F
1 065 000 h 1 147 000 h 1 379 000 hat 24V, 5 A and 40 °C (104 °F)
2 038 000 h 2 166 000 h 2 519 000 hat 24V, 5 A and 25 °C (77 °F)
681 000 h651 000 h645 000 hat 24V, 5 A and 40 °C (104 °F); Ground Benign GB40
872 000 h842 000 h839 000 hat 24V, 5 A and 25 °C (77 °F); Ground Benign GB25
165 000 h164 000 h168 000 hat 24V, 5 A and 40 °C(104 °F); Ground Fixed GF40
206 000 h205 000 h211 000 hat 24V, 5 A and 25 °C (77 °F); Ground Fixed GF25
(1) The Lifetime expectancy that is shown in the table indicates the minimum operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated
according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maxi mum
life of up to 15 years (131 400 h). Any number exceeding this value is a calculated theoretical lifetime w hich can be used to compare
devices.
(2) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of for example, 1 000 000 h means
that statistically one unit fails every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed
unit has been running for 50 000 h or only for 100 h.
Functional Diagram
Figure 17 - Functional Diagram
Rockwell Automation Publication 1606-RM055B-EN-P - February 201713
Page 14
Basic Power Supply 5 A
EMC
EMC ImmunityAccording to Generic Standards EN 61000-6-1 and EN 61000-6-2Criterion
Electromagnetic RF field EN 61000-4-380 MHz-2.7 GHz20V/mCriterion A
Fast transients (Burst)EN 61000-4-4input lines
output lines
DC-OK signal
4 kV
2 kV
2 kV
Criterion A
Criterion A
Criterion A
(coupling clamp)
Surge voltage on inputEN 61000-4-5L ->N
L ->PE, N ->PE
Surge voltage on output EN 61000-4-5+ ->-
+/- ->PE
2 kV
4 kV
500V
1 kV
Criterion A
Criterion A
Criterion A
Criterion A
Surge voltage on DC-OK EN 61000-4-5DC-OK signal… PE1 kVCriterion A
Conducted disturbanceEN 61000-4-60.15…80 M Hz20VCriterion A
Mains voltage dipsEN 61000-4-110% of 100V AC
40% of 100V AC
70% of 100V AC
0% of 200V AC
40% of 200V AC
70% of 200V AC
0V AC, 20 ms
40V AC, 200 ms
70V AC, 500 ms
0V AC, 20 ms
80V AC, 200 ms
140V AC, 500 ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion C
Criterion A
Voltage interruptionsEN 61000-4-110% of 220V AC (=0V)5000 msCriterion C
Voltage sagsSEMI F47 0706dips on the input voltage according to SEMI F47 standard
80% of 208V AC (166V AC)
70% of 208V AC (146V AC)
50% of 208V AC (104V AC)
80% of 120V AC (96V AC)
70% of 120V AC (84V AC)
50% of 120V AC (60V AC)
1000 ms
500 ms
200 ms
1000 ms
500 ms
200 ms
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion C
Powerful transientsVDE 0160over entire load range750V, 1.3 msCriterion A
(1) Criterion A: Power supply shows normal operation behavior withing the defined limits.
Criterion C: Temporary loss of function is possible. Power supply can shut down and restart by itself. No damage or hazard for the
power supply occurs.
(2) Below 4.5 A, Criterion C for currents above 5 A.
(1)
(2)
EMC EmissionAccording to Generic Standards: EN 61000-6-3, EN 610000-6-4
Conducted emission input lines EN 55011, EN 55022
FCC Part 15
CISPR 11, CISPR 22
Conducted emission output
(1)
lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 limits for DC power port according to EN
Radiated emissionEN 55011, EN 55022Class B
Harmonic input currentEN 61000-3-2Fulfilled for class A equipment
Voltage fluctuations, flickerEN 61000-3-3Fulfilled
This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device cannot
cause harmful interference, and (2) this device must accept any interference received, including interference that can
cause undesired operation.
(1) For information only, not mandatory for EN 61000-6-3.
(2) Tested with constant current loads, non-pulsing.
14Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Class B
61000-6-3 not fulfilled
(2)
Page 15
Basic Power Supply 5 A
Application Notes
Peak Current Capability
The unit can deliver peak currents (up to several milliseconds) which are
higher than the specified short-term currents.
This helps to start current demanding loads. Solenoids, contactors, and
pneumatic modules often have a steady state coil and a pick-up coil. The inrush
current demand of the pick-up coil is several times higher than the steady-state
current and usually exceeds the nominal output current. The same situation
applies when starting a capacitive load.
The peak current capability also verifies the safe operation of subsequent
circuit breakers of load circuits. The load branches are often individually
protected with circuit breakers or fuses. If there is a short or an overload in one
branch circuit, the fuse or circuit breaker need a certain amount of overcurrent
to open in a timely manner. This avoids voltage loss in adjacent circuits.
The extra current (peak current) is supplied by the power converter and the
built-in large sized output capacitors of the power supply. The capacitors get
discharged during such an event, which causes a voltage dip on the output. The
following two examples show typical voltage dips:
Figure 18 - Peak Load with 2x the Nominal Current for 50 ms, typFigure 19 - Peak Load with 5x the Nominal Current for 5 ms, typ
24V
10A
0A
10ms/DIV
10 A Peak load (resistive) for 50 ms
Output voltage dips from 24V to 17V.
Output
Voltage
17V
Output
Current
Peak Current CapabilityVoltage DipPeak Load
Peak current voltage dips typ24…17Vat 10 A for 50 ms, resistive load
Back Feeding Loads
24V
25A
0A
typ24…13Vat 25 A for 2 ms, resistive load
typ24…9Vat 25 A for 5 ms, resistive load
25 A Peak load (resistive) for 5 ms
Output voltage dips from 24V to 9V.
1ms/DIV
Output
Voltage
9V
Output
Current
Loads such as decelerating motors and inductors can feed voltage back to the
power supply. This feature is also called return voltage immunity or resistance
against Back- E.M.F. (Electro Magnetic Force).
Rockwell Automation Publication 1606-RM055B-EN-P - February 201715
Page 16
Basic Power Supply 5 A
This power supply is resistant and does not show malfunctioning when a load
feeds back voltage to the power supply. It does not matter whether the power
supply is on or off.
The maximum allowed feed-back-voltage is 35V DC. The absorbing energy
can be calculated according to the built-in large sized output capacitor that is
specified in Output on page 10
.
External Input Protection
The unit is tested and approved for branch circuits up to 30 A (UL) and 32 A
(IEC). An external protection is only required if the supplying branch has an
ampacity greater than this. Check also local codes and local requirements. In
some countries local regulations might apply.
If an external fuse is necessary or utilized, minimum requirements need to be
considered to avoid nuisance tripping of the circuit breaker. A minimum value
of 10 A, B-characteristic or 6 A, C-characteristic breaker should be used.
Parallel Use to Increase Output Power
Do not use the power supply in parallel to increase the output power.
Parallel Use for Redundancy
Power supplies can be paralleled for redundancy to gain higher system
availability. Redundant systems require a certain amount of extra power to
support the load in case one power supply unit fails. The simplest way is to put
two power supplies in parallel. This is called a 1+1 redundancy. In case one
power supply unit fails, the other one is automatically able to support the load
current without any interruption.
This simple way to build a redundant system does not cover failures such as an
internal short circuit in the secondary side of the power supply. In such a case,
the defect unit becomes a load for the other power supplies and the output
voltage cannot be maintained any more. This can only be avoided by utilizing
decoupling diodes that are included in the redundancy module.
Recommendations for building redundant power systems:
– Use the DC-OK signal contact to monitor the individual power
supply units.
– Use separate input fuses for each power supply.
– Use separate mains systems for each power supply whenever it is
possible.
– It is desirable to set the output voltages of all units to the same value
(± 100 mV) or leave it at the factory setting.
16Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 17
Basic Power Supply 5 A
Unit A
AC
DC
Unit B
AC
DC
-
+
-
+
Load
+
-
Earth
(see notes)
Series Operation
Power supplies of the same type can be connected in series for higher output
voltages. It is possible to connect as many units in series as needed, providing
the sum of the output voltage does not exceed 150V DC. Voltages with a
potential above 60V DC are not SELV any more and can be dangerous. Such
voltages must be installed with a protection against touching.
Earthing of the output is required when the sum of the output voltage is above
60V DC.
Avoid return voltage (for example, from a decelerating motor or battery) which
is applied to the output terminals.
Keep an installation clearance (left/right) of 15 mm (0.59 in.)between two
power supplies and avoid installing the power supplies on top of each other.
Pay attention that leakage current, EMI, inrush current, harmonics increase
when using multiple power supplies.
Figure 20 - Series Operation
Inductive and Capacitive Loads
• No limitations for inductive loads.
• No limitations for capacitive loads in combination with an additional
resistive type of load.
• Limitations apply for capacitive loads in combination with constant
current type of loads:
– 20 mF Max with an additional 2.5 A constant current load and
– 10 mF max with an additional 5 A constant current load.
Charging of Batteries
Do not use the power supply to charge batteries.
Rockwell Automation Publication 1606-RM055B-EN-P - February 201717
Page 18
Basic Power Supply 5 A
Operation on Two Phases
The power supply can also be used on two-phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying voltage is
+10%
below 240V
Figure 21 - Operation on Two Phases
.
Power Supply
L
Fuse
N
PE
AC
internal
fuse
DC
L3
L1
max.
+10%
240V
L2
Use in a Tightly Sealed Enclosure
When the power supply is installed in a tightly sealed enclosure, the
temperature inside the enclosure is higher than outside. In such situations, the
inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the
temperature rise inside the enclosure.
The power supply is placed in the middle of the box; no other heat producing
items are inside the box.
•Enclosure
– Rittal Type IP 66 Box PK 9516 100
–Plastic
– 110 x 180 x 165 mm (4.33 x 7.09 x 6.50 in)
•Input
– 230V AC
AttributeCase ACase B
(1)
Load
Temperature inside the box
Temperature outside the box24.4 °C (75.9 °F)24.2 °C (75.6 °F)
Temperature rise17.1K14.5K
(1) Load is placed outside the box.
(2) In the middle of the right side of the power supply with a distance of 1 cm (0.39 in.).
18Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
(2)
24V, 5 A24V, 4 A (=80 %)
41.5 °C (106.7 °F)38.9 °C (102 °F)
Page 19
Specifications
Basic Power Supply 5 A
Attribute1606-XLB120ENotes
Output voltage DC 24V
24…28V DCAdjustment range
Output for AC 110…120/
220…240V mains:
for AC 100/200V mains: 5.0...4.3 A
Output ripple < 100 mVpp 20 Hz to 20 MHz
AC Input voltage AC 100…120V/
Mains frequency 50…60 Hz ±6 %
AC Input current 1.72 A/1.05 A at 120/ 230V AC
Power factor 0.64/0.54 at 120/ 230V AC
AC Inrush current22 A/33 A peak at 120/ 230V AC, 40 °C (140 °F)
Efficiency 91.2 /92.3% at 120/ 230V AC
Losses 11.6 W/10.0 W at 120/ 230V AC
Temp. range -10… +70 °C
Derating 3 W/°C 55…70 °C (131… 158 °F)
Hold-up time 51 ms/50 ms at 120/ 230V AC
Dimensions 39 x 124 x124 mm
Weight 370 g/0.81 lb
(1) 50…70 °C (122…158 °F) for AC 100 V/ 200V mains
5.0...4.3 A
3.1...2.7 A
2.5...2.1 A
200…240V
(14… 158 °F)
(1.53 x 4.88 x 4.88)
at 24…28V, <55 °C (122 °F)
at 24…28V, <70 °C (158 °F)
at 24…28V, <50 °C (122 °F)
at 24…28V, <70 °C (158 °F)
±10% Auto-Select
operational
W x H x D
(1)
Rockwell Automation Publication 1606-RM055B-EN-P - February 201719
Page 20
Basic Power Supply 5 A
Allowed Output
Current at 24V
0
020004000
6000m
1
2
3
4
5
6A
Altitude
A
.
.
.
T
a
m
b
<
5
5
°
C
B
.
.
.
T
a
m
b
<
4
5
°
C
C
.
.
.
T
a
m
b
<
3
5
°
C
A
B
C
Environment
Attribute1606-XLB120ENotes
Operational temperature
(1)
-10… +70 °C (14… 158 °F)reduce output power according to Figure 22
Storage temperature-40… +85 °C (-40… 185 °F)for storage and transportation
Output derating
Humidity
Vibration sinusoidal
(2)
(3)
3W/°C (55…70 °C 131…158 °F)
3W/°C (50…70 °C; 122…158 °F)
5...95% r.h.IEC 60068-2-30
(4)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
for AC 110-120/220-240V mains systems
for AC 100/200V mains systems
IEC 60068-2-6
2 hours/axis
(5)
Shock
30g 6ms, 20g 11ms
IEC 60068-2-27
3 bumps/direction, 18 bumps in total
Altitude0…2000 m (0…6 560 ft.)without any restrictions
2000…6000 m (6 560… 20 000 ft.)reduce output power or ambient temperature,
see Figure 22 IEC 62103, EN 50178,
overvoltage category II
Altitude derating7.5W/1000m or 5 °C/1000m> 2000 m (6500 ft.), see Figu re 23
Overvoltage categoryIIIIEC 62103, EN 50178, altitudes up to 2000m
IIaltitudes from 2000m to 6000m
Degree of pollution2IEC 62103, EN 50178, not conductive
LABS compatibilityThe unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
(1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below
the unit.
(2) For AC 208V mains use AC 200…220V values.
(3) Do not energize while condensation is present.
(4) Tested on a DIN Rail with a thickness of 1.3 mm.
(5) Tested on a DIN Rail with a thickness of 1.3 mm.
Figure 22 - Output Current vs. Ambient TemperatureFigure 23 - Output Current vs. Altitude
20Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Allowable Output Current at 24V
5.0A
4.0A
3.1A
2.5A
2.0A
1.0A
a) AC 110-120/ 220-240V mains
b) AC 100/ 200V mains
0
Ambient Temperature
-10 0+20 +40
a
b
+70°C
+55
+50
Page 21
Basic Power Supply 5 A
DA
C
B
B
*)
N
L
InputDC-ok
Earth, PE
Output
-
+
B*) When testing input to DC-OK ensure that
the max. voltage between DC-OK and the
output is not exceeded (column D). We
recommend connecting DC-OK pins and the
output pins together when performing the test.
Dielectric Strength
The output voltage is floating and has no ohmic connection to the ground.
Type and factory tests are conducted by the manufacturer. Field tests can be
conducted in the field using the appropriate test equipment, which applies the
voltage with a slow ramp (2 s up and 2 s down). Connect all input-terminals
together and all output poles before conducting the test. When testing, set the
cutoff current settings to the value in the following table.
ABCD
Type test60 s2500V AC3000V AC1000V AC500V AC
Factory test5 s2500V AC2500V AC500V AC500V AC
Field test5 s2000V AC2000V AC500V AC500V AC
Cutoff current setting> 10 mA> 10 mA> 15 mA> 1 mA
Figure 24 - Dielectric Strength
To meet the PELV requirements according to EN60204-1 § 6.4.1, we
recommend that either the + pole, the – pole or any other part of the output
circuit be connected to the protective earth system. This helps to avoid
situations in which a load starts unexpectedly or cannot be switched off when
unnoticed earth faults occur.
Rockwell Automation Publication 1606-RM055B-EN-P - February 201721
Page 22
Basic Power Supply 5 A
Standards Compliance and
Certifications
EC Declaration of Conformity The CE Marking indicates conformance with the low voltage directive and
UL 508Listed for use as Industrial Control Equipment ;U.S.A. (UL 508) and Canada
UL 60950-1Recognized for use as Information Technology Equipment,
RCM Declaration of Conformity C-tick is for products intended for sale and use within the Australian
EACEAC is for products intended for sale and use within the Russian market.
EMC Directive. EN 60950-1, EN 61000-6
(C22.2 No. 14-15); File: E56639
U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950); File: E 168663.
market.
22Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 23
Approximate Dimensions
128.95
(5.08)
and Weight
Basic Power Supply 5 A
Attribute1606-XLB120E
Width39 mm (1.54 in.)
Height125 mm (4.92 in.)
(1)
Depth
128.95 mm (5.08 in.)
Weight370 g (0.81 lb)
DIN RailUse 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15 mm.
Plastic Material of HousingFlame retardant Polycarbonate (PC) - UL94-V0 Vicat softening temperature specified
with 149 °C according to ASTM D1525
Installation ClearancesKeep the following installation clearances: 40 mm on top, 20 mm on the bottom, 5
mm on the left and right sides are recommended when the device is loaded
permanently with more than 50% of the rated power. Increase this clearance to 15 mm
in case the adjacent device is a heat source (for example, another power supply).
(1) The DIN rail height must be added to the unit depth to calculate the total required installation depth.
Dimensions are in mm (in).
Figure 25 - Front View
Figure 26 - Side View
39
(1.54)
125
(4.92)
Rockwell Automation Publication 1606-RM055B-EN-P - February 201723
Page 24
Basic Power Supply 5 A
Notes:
24Rockwell Automation Publication 1606-RM055B-EN-P - February 2017
Page 25
Page 26
Rockwell Automation Support
Use the following resources to access support information.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf
.
Technical Support Center
Knowledgebase Articles, How-to Videos, FAQs, Chat, User
Forums, and Product Notification Updates.
https://rockwellautomation.custhelp.com/
Local Technical Support Phone NumbersLocate the phone number for your country.http://ww w.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes
Find the Direct Dial Code for your product. Use the code to
route your call directly to a technical support engineer.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Allen-Bradley, Rockwell Automation, and Rockwell Softwa re are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respec tive companies.