WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from
contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of
practice. In case of malfunction or damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
WARNING: The following procedures are critical to the proper operation of the disconnect handle and switch. Failure to follow these steps can result in damage to the equipment and/or
serious injury or death to the operator.
Rod and Cable Operated Disconnect Switch Location.................................................................................................. 2
Rod Operated Switch Installation.......................................................................................................................................... 3
Connecting Rod Installation................................................................................................................................................ 3
Rod Adjustment Procedure................................................................................................................................................. 4
Enclosure Without Handle Cutout............................................................................................................................................. 8
Door Catch Bracket Installation.................................................................................................................................................. 9
Trailer Fuse Block and Phase Barrier Installation................................................................................................................10
Line Terminal Adapter Installation..........................................................................................................................................12
Fuse Clip and Fuse Installation.................................................................................................................................................13
A) For Rod Operated Switches, follow steps 1 - 5 below.
B) For Cable Operated Switches, follow steps 3 - 5 below.
IMPORTANT: When locating the 30A, 60A and 100A cable operated switch, verify that the minimum diameter for the loop of the cable between the switch mechanism and handle mechanism is
not less than 6 inches.
Any reduction to the diameter of the bend loop for the cable will reduce the eciency of the cable system, create additional drag and friction within the cable conduit and possibly decrease
system life.
1 Measure top hole of handle on enclosure.
2 Use template PN-254969 to locate handle holes on mounting plate.
Lay template on enclosure back plate. Align using the top hole on
IMPORTANT: Verify that the cable assembly does not interfere with any mechanical and moving parts. Keep the cable conduit a minimum of 1/2" from all heat sources and current carrying
terminals, fuses, transformers, etc.
IMPORTANT: When locating the 30A, 60A and 100A switch, verify that the minimum diameter for the loop of the cable between the switch mechanism and the handle mechanism is not less
than 6 inches.
1 Locate switch as to not pinch the cable or create
a bend less than 6" in diameter.
NOTE:
All bends must be
greater than 6" in
6" Diameter Min
diameter.
Do Not Pinch Cable
1 Tighten cable nuts onto switch
bracket.
Check for one
washer on each
side of the switch
bracket.
30-35 lb-in
(3.4-4 N-m)
2 Use washer and hitch pin to attach cable
pivot to switch mechanism cable slot.
Install pin as
shown. Do
not push past
second bend
on clip.
3 Remove drive bar for rod operation, washer
and hitch pin; discard.
Publication 1494U-IN001G-EN-P - November 2015PN-335193 DIR 10001182729 (Version 06)
• Some Enclosures with hinged flange panels may require additional flange support brackets to stiffen panel.
Consult your local enclosure manufacturer.
Locate Handle
1
Right Hand Flange
Drill Handle Holes
2
C
B
A
B
A
C
Top Handle Hole
Left Hand Flange
Top Handle Hole
To make slot drill (3) 1/2" diameter holes and remove burrs
NEMA
SIZE
30A, 60A
100A
Publication 1494U-IN001G-EN-P - November 2015PN-335193 DIR 10001182729 (Version 06)
Bulletin 1494U Disconnect Switch Component Accessory List
Disconnect Switch and Mechanism
(1494U-D30 shown)
Handle
15
(1494U-HM1 shown)
Connecting Rod
Cable-Operated Handle Mechanism
Fuse Block
(1494U-F30 shown)
Fuse Clip Kits
(1494U-FC30J shown)
Publication 1494U-IN001G-EN-P - November 2015PN-335193 DIR 10001182729 (Version 06)
Cable Handle Mechanism:
1494U-C313 (3 ft. Cable)
1494U-C314 (4 ft. Cable)
1494U-C315 (5 ft. Cable)
1494U-C316 (6 ft. Cable)
1494U-F30 (30A)
1494U-F60 (60A)
1494U-F100 (100A)
Includes:
Phase Barriers
1494U-PB31 (Field Installed) (Pkg Qty 2)
Bulletin 1494U Disconnect Switch Component Accessory List (Cont’d)
Auxillary Contacts
1494U-NO (1 N.O.)
1494U-NC (1 N.C.)
1494U-NOLV (1 N.O. Low Level)
1494U-NCLV (1 N.C. Low Level)
Aluminum Lugs
Copper Lugs
1494U-LC36 (30A - 60A)
1494U-LC100 (100A)
(Pkg Qty 3)
Multiport Lugs
1494U-LM31 (30A - 100A)
(Pkg Qty 3)
Line Terminal Adapters
1494U-ALT31 (Pkg Qty 2)
250V
600V
30/60/100A
Non-
Fusible
30A
30A
30A
60A
100A
30A
60A
100A
ComponentCat No.
1494U-LA36 (30A - 60A)
1494U-LA100 (100A)
(Pkg Qty 3)
(1494U-LA100 shown)
(1494U-LC100 shown)
Phase Barriers
1494U-PB31 (Pkg Qty 2)
Fuse Cover
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page