Allen 1747 CP3 Diagram

PC to SLC-5/4 Communications
Figure 1 Full Duplex Point-To-Point Communications
Point-to-point communication between PC and SLC-5/4 is a DTE to DTE communication link. As shown in Figure 1 either two DTE to DCE cables with interceding modems may be used or one DTE to DTE (null modem) cable may be used. The DTE-to-DTE cable is connect to one of the DB-9P connectors on the PC and to the DB-9P (Channel-0) connector on the SLC as illustrated in Figure 2.
Figure 2 DTE to DTE Connection
Configure PC to use DF-1 drivers.
Use 1747-CP3 or compatible cable with circuit shown Figure 3.
Set default communication speed to 1200 bps.
Use Channel-0 (DB-9P) connector on SLC-5/4
Use Com1, Com2, Com3, or Com4 (DB-9P) on PC
1747-CP3
The 1747-CP3 is a form of a null modem cable. Read the notes on Figure 3 and pay attention to note two. Note that pin 2 and pin 3 are interchange on the cable and pin 5 is feed straight through. The other line are only used if hardware handshaking is not or cannot be turn off.
Figure 3 1747-CP3
Baud Rate Selection
To set the baud rate can take up to three steps. The first step is to synchronize the baud rate of the SLC 500 and the PC. If the SLC and PC are already communicating you may skip this step.
Step 1:
Load RSLinx communication package
Start application and select communications
Then select configure driver
Choose the RS-232 driver DF-1 device
Click on add new if DF-1 driver is not present
Select autoconfig and the PC and SLC-5/4 will connect at 1200 bps (default) or the current baud
rate. Then select OK. The next step is to set the baud rate of the UART in the SLC 500. To perform this operation use the RSLogix 500 software and follow the steps in STEP 2.
Step 2:
Load RSLogix 500
Open an existing project (RSS) file or create a new project file by selecting New under File.
In the project Tree double click on Channel Configuration under Controller
Select the Chan-0 System tab
Select the new baud rate and then apply.
At this point you most likely have lost communication between the SLC 500 and the PC. This is because the SLC UART is now at the new baud rate and the PC is at the old baud rate. To change the PC’s Baud rate follow the steps in Step 3.
Step 3
Start RSLinx application or transfer focus if it is currently running.
Select communications
Then select configure driver
Choose the RS-232 driver DF-1 device if another is highlighted
Loading...
+ 1 hidden pages