Allegion LP150, LP250, LP150B, LP250B, LP250RDB4 Installation Instructions

*829767-00*
LP150, LP250
829767-00
Power Supply
LP150B, LP250B
Installation Instructions
LP250RDB4
The LP150/LP250 is a power-limited power supply and battery charger that will convert 120 VAC / 60Hz input into eld-selectable 12 VDC or 24 VDC Class 2 rated outputs (one continuous, one switchable). It is intended for use in applications with UL listing requirements (see specications below for specic listings).
This instruction covers:
LP150 PS cabinet + board (1.5A), battery wire kit, keylock LP250 PS cabinet + board (2.5A), battery wire kit, keylock LP250RDB4 PS cabinet + board (2.5A), battery wire kit, keylock, RDB4 board *
Keylock
LP150B PS board only (1.5A), 4 mounting screws LP250B PS board only (2.5A), 4 mounting screws
PS board
RDB4 board included
PS150/250
Power Supply
with hinged cover
+ Board
Battery Wire Kit
*
RDB4
with LP250RDB4 only
and is covered in
separate instruction
PS150/250 Specications:
Input LP150: 120 VAC, 1A, 60Hz LP250: 120 VAC, 1.2A, 60Hz Output LP150: 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 1.5A, Class 2 rated
LP250 (LP250RDB4): 12 VDC (13.2V nominal) or 24 VDC (26.4V nominal), 2.5A, Class 2 rated Output Protection DC OUT and CONTROL OUT are protected from overload or shorts via self-resetting electronic protection circuit Battery Protection PTC
Environment 32°-120° F (0°- 49° C), up to 85% relative humidity, indoor use only, protected area Compliance UL294, UL603, Access control performance levels: Attack: I, Line security: I, Endurance: IV, Standby power: III
(LP150) and II (LP250/LP250RDB4), CSA22.2 NO. 205, CSFM, FCC Battery Backup Requires 12V, 7AH max. rechargeable sealed lead acid battery: (1) for 12V, (2) for 24V output.
Battery maximum dimensions: 3-3/4” H x 6” W x 3” D
See typical backup times in Section 2
See Section 8 for maintenance of battery Control Input / Output Input: Normally closed, requires dry contact rated at 24 VDC, 10mA
Output: Powered NC/NO contacts rated at 24 VDC, 2.5A AC Status Indicator: Green LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A DC Output Status Indicator: Red LED Battery Status Indicator: Red LED
Relay contacts: NO/NC contacts rated at 24 VDC, 1A Enclosure 13” H x 12-5/8” W x 3-1/4” D (8 knockouts, 1/2” or 3/4”)
Denitions:
Normally closed contacts (NC) Normally open contacts (NO)
FSE - Fail secure (needs power to unlock)
FACP - Fire Alarm Control Panel ACC - Access Control Contacts FS - Fail safe (needs power to lock)
See Section 10 for an explanation of the Warnings and Cautions used in this booklet.
1 Installation Overview
Wiring methods shall be applied in accordance with the National Electric Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction.
WARNING
To avoid risk of electric shock, turn off AC power before
installing or servicing LP150/LP250 power supply.
1. Mount unit in a protected area per Section 2.
2. Select voltage (12 or 24 VDC) per Section 3.
3. Connect AC power per Section 3.
Connect the earth ground to the green/yellow cabinet wire and line (L) and neutral (N) to the appropriate terminals on the AC terminal block.
Measure output voltage before connecting devices to prevent damage.
4. Disconnect AC power and nish all wiring per Sections 4 and 6.
5. Install battery backup (if required) per Sections 2 and 3. If AC input goes o󰀨 and battery backup is not being used, all devices connected to the power supply will be unpowered.
6. AC status may be required for Battery Backup systems (Section 3).
7. Secure cover with screws or keylock when complete per Section 7.
8. For maintenance and troubleshooting, see Sections 8 and 9.
2
2 Mounting
CAUTION
Product intended for indoor use only and within
the temperature range specified. Mount unit in a
protected area. Do not install in locations with
exposure to rain or water.
Enclosure mounting screws not provided
Mounting Hole
Dimensions
10¹⁵⁄₁₆"
11¹⁄₈"
Enclosure
Dimensions
12⁵⁄₈"
Mount in upright position
13"
Cover not shown for clarity
Battery mounting to be as shown
3¹⁄₄"
Battery Backup
Time
BACKUP TIME (HOURS)LOAD
CURRENT
(AMPS)
0.2
0.5
1.5
2.5
LP150
19
11
2
LP250
19
11
2
1.25
Calculated battery backup time based on charging time of 48 hours at a temperature of 77° F (25° C).
3
3 Power Supply Board - Features and Operation
120VAC, 60Hz
input voltage
AC
STATUS
120VAC
green LED
DC
red LED
BAT
red LED
BAT
STATUS
L: Line, hot G: Ground N: Neutral
NC to C: open NO to C: closed NC to C: closed NO to C: open
off on
off on
off
on
NC to C: open NO to C: closed
NC to C: closed NO to C: open
Hot
Neutral
Earth Ground
Non power-limited, Class 1
Green/Yellow
120VAC NOT present on input
120VAC present on input
120VAC NOT present on input 120VAC present on input
DC output off or shorted/overload DC output on (12 or 24V)
Battery not connected or battery low Battery connected and charging or providing battery backup
Battery not connected or battery low Battery connected and charging or providing battery backup
120VAC
L
G
N
WARNING
Must be connected via rigid conduit.
WARNING
Keep power-limited wiring separate from non power-limited wiring.
Minimum 1/4" spacing must be provided.
CAUTION
When installing, route field wiring away from sharp projections, corners, and
NC
C
NO
AC STATUS
NC
C
NO
BAT STATUS
IN
C
CONTROL IN
internal components. Deburr all conduit fittings.
BATDC
24V 12V
LP150 LP250
CONTROL
4
CONTROL OUT
NC to DC-: 0V NO to DC-: DC+ out NC to DC-: DC+ out NO to DC-: 0V
24VDC
BATTERY
CONFIGURATION
12VDC
BATTERY
CONFIGURATION
CONTROL IN
IN to C: open contacts
IN to C: closed contacts
Black
Yellow
12V
BATTERY
BATTERY
BATTERY
12V
12V
OR
CONTROL
OUT
Red
Black
Red
NO DC- DC- DC+NC
Non power­limited
BAT- BAT+
DC OUT
DC
OUTPUT
VOLTAGE
SELECT
Switch moved to
24V
left position Switch moved to
12V
right position
24V
CAUTION
Confirm polarity to avoid damage to unit.
12V
4 Typical Wiring
FS & FSE device connected to
PS board with FACP override
FACPACC
CONTROL
IN
IN
C
NC
LP150/250
Operation:
1. CONTROL IN controls the operation of devices connected to the NO or NC terminals.
2. Opening of the FACP contacts will unpower the CONTROL OUT NC contacts and power the NO contacts.
3. DC OUT is always powered regardless of the state of the FACP contacts.
CONTROL
OUT
DC
OUT
NO
DC-
DC+
DC-
+
E-STRIKE
FSE
+
FSE device using open input
control contacts
ACC
CONTROL
IN
IN
C
+
MAGLOCK
CONTINUOUS
DC OUTPUT
FS
NC
LP150/250
Operation:
1. CONTROL IN controls the operation of the strike connected to the NC terminal.
2. Closing the ACC contacts will apply power to the FSE strike to unlock it.
CONTROL
OUT
DC
OUT
NO
DC-
DC+
DC-
+
E-STRIKE
FSE
+
CONTINUOUS
DC OUTPUT
5
Loading...
+ 11 hidden pages