Alfa Laval CC 352, CC 353, CC 354, CC 401, CC 403 Instruction Manual

...
Optigo CC
Instruction manual
ORIGINAL INSTRUCTIONS
AHE00047EN
Contents
1 Important information..............................................................................3
2 Product description................................................................................. 4
3 Product labels.......................................................................................... 7
4 Unpacking and lifting............................................................................ 10
4.1 Unpacking................................................................................................................................... 10
4.2 Lifting...........................................................................................................................................12
5 Installation...............................................................................................15
5.1 Mounting dimensions..................................................................................................................15
5.2 Mounting bracket........................................................................................................................ 17
5.3 Technical spaces........................................................................................................................ 18
5.4 Refrigerant connections..............................................................................................................19
5.5 Hotgas connection (optional)......................................................................................................19
5.6 Drain line.....................................................................................................................................20
5.7 Electrical connections.................................................................................................................21
5.7.1 Electrical connections 1-phase AC fan motors.............................................................22
5.7.2 Electrical connections 3-phase AC fan motors.............................................................23
5.7.3 Electrical connections 1-4 EC fan motors 1-phase (2-speed, CC250 only).................. 24
5.7.4 Electrical connection for 1-4 EC fan motors 1-phase with 0-10V speed regulation..... 25
5.7.5 Electrical connection for 1-4 EC fan motor 3-phase with 0-10V speed regulation...... 27
5.7.6 Electrical connection for electric defrost CC400 & CC500........................................... 28
5.7.7 Electrical connection for electric defrost CC250 & CC350........................................... 29
5.7.8 Electric defrost capacities............................................................................................. 29
6 Maintenance............................................................................................33
6.1 Fan replacement.........................................................................................................................33
6.2 Driptray........................................................................................................................................33
6.3 Side covers................................................................................................................................. 34
6.4 Coil heater elements replacement..............................................................................................34
6.5 Driptray heater elements replacement....................................................................................... 35
7 Spare parts............................................................................................. 37
1 Important information
Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB. Alfa Laval reserves the right to change specification without prior notification.
1.1 Disclaimer
This Instruction Manual applies to all Alfa Laval Optigo CC air cooler products and is supplied in combination with the Alfa Laval Air Cooler Product Manual AHE00042. Both manuals must be carefully examined and instructions should be followed up at all times. Alfa Laval does not accept liability for any damage resulting from non-compliance to the instructions as given in the manuals and order-related documents.
1.2 Intended use
Air coolers are partly completed machinery according to Machine Directive 2006/42/EC and intended for incorporation in cooling systems. Declarations of Incorporation are available on www.alfalaval.com. The units may not be put into operation until the conformity of the complete machine or cooling system has been declared according to the following standards and directives:
Pressure Equipment Directive 2014/68/EU
Machine Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
Electrical Equipment of Machines IEC 60204-1
Electro Magnetic Compatibility 2014/30/EU
Any applicable local or national legislation
1.3 Where to find product information
Detailed technical data for individual product models are available in order related documents, on the product label and in product data sheets. Comprehensive technical information for all Alfa Laval air heat exchanger products is available on-line on www.alfalaval.com. This includes:
Product manuals
Instruction manuals
Product leaflets & brochures
Product data sheets (selection software)
Dimensional drawings
Electrical wiring diagrams
Certificates
Optigo CC
Alfa Laval offers world-wide service and support in over 55 countries. In case of any questions or uncertainty please contact your local Alfa Laval representative. Contact addresses are available at www.alfalaval.com.
AHE00047EN 3 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
2 Product description
2.1 General information and application
Optigo CC are commercial single discharge unit coolers for general application in small to medium-sized cooling, freezing and working rooms. Coolers are available in draw-through (CC) and blow-through design (CCB). A wide range of models make them especially suitable for refrigerated working, processing and storage rooms. Dedicated ranges for HFO/HFC refrigerants (E), brine (W) and CO2 (X). A selection of Optigo CC coolers is available from stock.
Refrigerants: HFO/HFC DX (E), CO2 DX (X) and brine (W)
Room temperatures: +10 to -30 °C
Capacity (SC2): 1 up to 55 kW (SC2)
Air volumes: 770 up to 30000 m3/h
Model Refrigerant Design pressure Test pressure
CC(B) E HFO/HFC 40 bar 57 bar
CC X CO2 80 bar 114 bar
CC(B) W Brine 10 bar 14.3 bar
2.2 Standard configuration
Internally grooved Cu tubes and aluminium fins, smooth tubing for brine applications and dedicated thicker tubes for CO2 application. Tube pitch is staggered. All HFO/HFC DX models fitted with a T­connection to improve the refrigerant distribution and for hotgas defrost in coil.
Optigo CC coolers are available with 1 to 4 fans fitted with AC or EC fan motors in two fan speed executions (noise levels) H/L. Fan diameters 250, 300, 350, 400 or 500 mm drawing or blowing through the coil. Integrated thermo contacts (Clixon) standard for 3-phase AC motors. All single phase motors protected by an integrated internal overload switch. Electronically integrated overload protection for EC fan motors.
All casing parts made of durable sheet metal, epoxy coated RAL 9002. Top plate corrosion resistant Magnelis®.
All models fitted with hinged side panels and aluminium driptray. Driptray is adjustable for perfect leveling. Removable internal driptray for inspection and cleaning.
Hinged side panels and driptray, drain(s) 1½" BSP external
Fitted with schräder valve on the suction connection for testing purposes.
Sufficient room for fitting the expansion valve inside.
Stickers indicate fan direction and refrigerant in/out.
Optigo CC251-403 models are delivered in wood-reinforced cardboard boxes, CC404-504 and CCB models in wooden crates. All packings suitable for safe stacking.
AHE00047EN 4 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
2.3 Options
Electric defrost
For cold rooms with room temperatures below 4 °C and where frost build-up is likely, the application of a defrosting system is advised. Electric defrost for Optigo CC consists of stainless steel heater elements. The defrost elements are connected to separate terminals in the terminal box. Available defrost systems are:
Electric defrost in coil (standard E1, heavy E2)
Electric defrost in driptray (HD)
Hotgas defrost in driptray (HG)
Electric defrost in driptray & hotgas in coil
Driptray insulation 12 mm + cladding (IS)
Shut-up sock (S)
Airsock adapter ring (SR). Available for CC400 and CC500 draw-through models only.
Coil protection
Pre-coated aluminium fins (EP)
Cataphoresis treatment (CA)
Stainless steel casing and frame (SSC)
Fan ring heater (FRH)
Re-heating coil (RH)
Switch on/off (SW)
Fan motors wired to connection box (CB)
2.4 Code description
CC B E H E 50 1 .2 A S 230V BO SS E EP - 7.0 CU IS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
AHE00047EN 5 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
1. Commercial unit cooler
2. Air direction (default=draw through, B=blow through)
3. Refrigerant system (E= HFO/HFC DX, X=CO2 DX, W=brine)
4. Fan speed (H=high speed, L=low speed)
5. Fan motor type (blank=AC, E=EC)
6. Fan diameter (25=250, 30=300, 35=350, 40=400, 50=500 mm)
7. Number of fans (1 to 4)
8. CC version
9. Tube rows code (A, B, C)
10.No. of phases (S= 1, T=3)
11.Motor voltage
12.Packing (BO=box, CR=crate)
13.Casing material (PC=powder coated, SS= stainless steel)
14.Defrost system (A=air defrost, E=electric defrost, HG=hotgas, HG+E= hotgas + electric defrost in
driptray)
15.Fin material (AL=aluminium, EP=epoxy coated aluminium, CA=cataphoresis)
16.Fin spacing (4, 5.5, 7, 10, 12 mm)
17.Tube material (CU=copper)
18.Options
AHE00047EN 6 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
3 Product labels
1. Product label
WARNING
READ INSTRUCTION MANUAL BEFORE
INSTALLATIONS OPERATIONS AND MAINTENANCE
TO AVOID INJURIES OR DAMAGE
Country of origin Italy
Manufactu rer: Manuf. Date:
AIR HEX ALONTE S.R.L. - Italy 04 / 2019
Model: O.A. 1100186 CCEH502.2BD 400V CR PCE CA 5.5 CU
Item ID: 3289208322 Serial no. AP 2003621
Unit Net Weight: 190 Kg ±5% Sn
Motorfan data: Vn: 3~400V f: 50 H z
EXAMPLE
Model Refer to Code description
Item ID, Serial no. Communicate these when ordering spare parts as
they identify the unit
O.A. Order Acknowledgement number
Unit Net Weight Check before any lifting operation to ensure that
proper lifting tools are used
2. Product label - coil
WARNING
READ INSTRUCTION MANUAL BEFORE
INSTALLATIONS OPERATIONS AND MAINTENANCE
TO AVOID INJURIES OR DAMAGE
Manufactu rer: Manuf. date:
AIR HEX ALONTE S.R.L. - Italy 04 / 2019
Model: O.A. 1100186 CCEH502.2BD 400V CR PCE CA 5.5 CU
Item ID: 3289208322 Serial no. AP 2003621 Sn
Coil PED data: I Max DN: 38 mm Fluid G roup 2 Coil Ts: +125/-60 °C Ps: 40 bar Pt: 57 bar Test Date: 04-2019
EXAMPLE
Model Refer to Code description
AHE00047EN 7 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
Item ID, Serial no. Communicate these when ordering spare parts as
they identify the unit
Max DN Maximum diameter of the distributor tube
Fluid Group According to PED
Coil Ts Range of operating temperatures for the coil
Ps Design pressure
Pt Test pressure
Test date Date on which the coil has been pressure tested
in the factory
3. Nitrogen precharge warning
Units are delivered from the manufacturer with an overpressure. Check pressure on the Schrader valve. With unpressurised unit: imme- diate report to manufacturer and note on the bill of delivery.
4. In
5. Out
Refrigerant connections inlet and outlet.
6. Fan motor
Fan motor item number
7. Electrical warning
Electrically powered component. Switch off power supply before any maintenance or installation activity.
8. Fan direction
Sticker indicates fan rotation direction.
9. Moving parts
AHE00047EN 8 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
Warning: moving parts.
Switch off power supply before any maintenance or installation activities.
10.Eurovent
Sticker is applied when the product is included in the Eurovent Certify All program.
AHE00047EN 9 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
4 Unpacking and lifting
Always follow guidelines and instructions as given in the air cooler product manual AHE00042.
Optigo CC air coolers are delivered on a wooden pallet, either covered with a wooden folding box or a wooden reinforced crate. Handling and positioning can take place manually (smaller models) or with use of a forklift. When more than one cooler units are delivered in a single shipment, packed air coolers may be stacked during transportation.
Respect the maximum number of stacked air cooler units.
max. units floor stacking 251-254 : 5 301-403 : 4 404-504 : 2
max. 2
In order to avoid damage to the air cooler or falling of the unit, ensure that the lifting forks fully cover the support pallet.
A
4.1 Unpacking
Folding box (CC251-403)
Place the unit on the ground. Unscrew the fixings from the top of the box and remove the cover.
AHE00047EN 10 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
Unscrew the fixings from the bottom of the box and remove it. Remove the fixing screws from the lower support pallet.
Wooden crate (CC404-504 & CCB301-504)
Place the unit on the ground and loosen the fixing materials from the top crate. Remove top crate . Remove fixing screws to lower support pallet.
AHE00047EN 11 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
4.2 Lifting
CC 250/350 & CCB300/350
Unpacked models 250/300/350 must be turned before mounting.
Manually turn the air cooler into mounting position on a second wooden pallet. Use adequate protective material to prevent the driptray from damaging. The cooler is now ready to be lifted into mounting position.
CC400/500 & CCB400/550
Unpacked models 400/500 are in mounting postion. Remove driptray (supplied unmounted).
For CC400/500, turn mounting brackets into correct position and secure with supplied fixing materials.
The cooler is now ready to be lifted into mounting position.
AHE00047EN 12 Alfa Laval is a trademark registered and owned by Alfa Laval Corporate AB.
Alfa Laval reserves the right to change this specification without prior notification.
Loading...