Albion MAINSFLOW INSTALLATION GUIDE

September 2004
T H E R M A L S T O R E U N I T S
F O R U S E R G U I D E S E E
P A G E S 1 2 T O 1 4
INSTALLATION GUIDE
®
MAINSFLOW
THERMAL STORE UNITS
PLEASE LEAVE IN POCKET
PROVIDED ON THE UNIT
FOR USER GUIDE SEE
PAGES 12 TO14
C
O
O
M
T
D
E
N
G
I
S
E
D
THERMAL STORE
SPECIFICATION
P
L
Y
W
I
T
H
IMPORTANT
Please ensure that all installations meet current by-laws
and comply to best industry practice.
Follow component manufacturer's guidelines. This booklet
is published as a guide only, Albion cannot accept
responsibility for errors or ommissions.
MAINSFLOW CASED CONTRACTOR UNIT
INDIRECT DIRECT
A
C
B
D
DOMESTIC
HOT OUT
E
DOMESTIC
JH
A Warning pipe (Installer to fit) B Ball float (Supplied) C Primary Coil/ Boiler Tappings D Blending valve E Expansion vessel F Service valve G 3.0 bar pressure reducing valve H Drain Point J Thermostat connection K Radiator circuit tappings
COLD OUT
F
G
COLD
MAINS
A
C
C
B
D
DOMESTIC
HOT OUT
E
G
F
K
J
K H
DOMESTIC COLD OUT
COLD
MAINS
1
INTRODUCTION
The Albion Mainsflow operates on the Thermal Store principle eliminating the need for cold water storage in the loft and producing mains pressure hot water to all taps and shower facilities at high flow rates in accordance with BS6700.
The Mainsflow Thermal Store principle reverses the traditional operation of the cylinder in the heating system. The store of water is heated from the boiler, DIRECTLY to the store or INDIRECTLY via a second coil. The secondary (domestic) water is provided through a multi-tube heat exchanger, fed from the main.
Mainsflow DIRECT (single coil) must be fitted in open vented mode, preferably in twin pump configuration (See page 2, diagram 1).
Mainsflow INDIRECT (twin coil) units can be used with sealed system boilers i.e. a fully sealed heating system, or with more traditional open vented systems, where flexible siting is required
- the store being static. The Indirect is usually fitted into a Y plan system. (See page 2, diagram 2).
Mainsflow Indirect can also be used in central boiler schemes linking several cylinders to a single boiler or buffer store.
Mainsflow Indirect Cased Contractors are corrosion proofed and guaranteed for five years. The corrosion proofer is supplied inside the unit as a soluble crystal. It will not degrade and will dilute in hot water.
For Direct Units or if you re-commission after use, please add new inhibitor eg. Fernox MBI or MB2 or Sentinel X100. Follow manufacturers' instructions to maintain guarantees.
2
TYPICAL SCHEMATIC LAYOUTS
The Mainsflow units have been engineered to ensure maximum efficiency from fully pumped systems.
They are not for use in systems with gravity flow and return pipes. In addition each system is insulated with Albion's unique 100%
CFC free foam and cased in a smart white appliance finish.
DIRECT MAINSFLOW TWIN PUMP
INDIRECT MAINSFLOW 'Y' PLAN/SEALED SYSTEM
COLD MAINS
PUMP
1
PUMP 2
SPACE
HEATING
HOT
ROOM
THERMOSTAT
COLD
BOILER
STORE
THERMOSTAT
PROBE TYPE
BLENDING
VALVE
EXPANSION
VESSEL
HOT
COLD
BY-PASS
SPACE HEATING
BOILER
*FEED/EXPANSION - OPEN VENTED ONLY
STATIC STORE
POTABLE
WATER
COLD MAINS
GAS OR OIL
BOILER,
SEALED OR
*OPEN VENTED
PRIMARY
WATER
DIVERTER
VALVE
STORE
THERMOSTAT
PROBE TYPE
BLENDING
VALVE
EXPANSION
VESSEL
Diagram 1
Diagram 2
3
COLD SUPPLY
Mainsflow units are designed to provide hot water directly from the rising main. Output performance is directly related to the adequacy of the incoming mains supply. When choosing Mainsflow, installers and specifiers must take into account flow rates and pressure. The units are designed to deliver hot water at given flow rates and it is therefore important to ensure that the mains supply into the property is adequate, ie a minimum of 2 bar pressure at 20 litres per minute for single bathroom
applications and appropriately for larger installations.
The supplied pressure reducing valve must be fitted. It is recommended that some cold outlets are connected direct to the mains (kitchen, utility and outside taps) prior to the pressure reducing valve. The pressure reducing valve needs to be as far upstream from the cylinder as possible. The Mainsflow multi-tube heat exchangers are such that scale deposition will be minimised. However, in areas where concentration of CaCO
3
is greater than 200mg/l it is recommended that suitable in line scale eliminators are fitted. If fitted, a by-pass pipe must be installed so that the system can build up a natural patina for protection prior to using a proprietary scale eliminator. Consult the manufacturers' guidelines.
INSTALLATION
Albion Mainsflow units should be sited to enable access and removal of all plumbing connections and components including the unit and overflow pipes. The units should be positioned on a flat base capable of supporting
them when full up to 300kg (250 litre model).
Where Mainsflow Direct model is used care must be taken to ensure that the unit is sited to ensure sufficient head for trouble free operation of the system. They must be sited with the water level at least 500mm above the top of the highest radiator or highest point in the primary circuit*. Care must always be taken to allow a clearance of 200mm between the top of all combination units and the ceiling to allow access to the ball valve for
servicing and adjustment.
The Mainsflow Indirect can be sited anywhere within the property as the store is static, taking care to discharge pipes effectively.
* Check boiler minimum head requirements.
4
PIPE SIZING
To enable effective distribution of the available supply it is important in any mains pressure system that pipe sizing is in accordance with BS6700. As an indication the following pipe connections are necessary. Mains supply to the dwelling 22mm (25mm MDPE). Mains cold supply to the Mainsflow should be run in 22mm copper.
The hot water draw-off should be 22mm to the bath tap branch. The tee-offs to the basins/sinks should be in 10mm, whilst
the tee-offs to the showers should be 15mm. Primary flow and return pipework should be a minimum of 22mm and sized to 28mm or 35mm according to the boiler manufacturers' instructions. By-pass pipework must be strictly in accordance with boiler manufacturers' requirements.
Cold feed to heat exchanger 22mm.
Expansion tank discharge pipework 22mm copper or 22mm plastic solvent weld.
1.)
2.)
MAINSFLOW SIZING
A GUIDE TO SIZING YOUR MAINSFLOW CASED CONTRACTOR
MODEL
MFT140 CON
Specify DIRECT
or INDIRECT
MFT170 CON
Specify DIRECT
or INDIRECT
MFT200 CON
Specify DIRECT
or INDIRECT
MFT250 CON
Specify DIRECT
or INDIRECT
APPLICATION
(TO BS6700)
Single bath and en-suite shower
2/3 bed property
Two baths
2/3 bed property
Three bath
4 bed property
Three baths and two
en-suite showers
5 bed property
CYLINDER
SIZE
1280 x 560
1500 x 560
1700 x 560
2200 x 560
BOILER
(x 1000 BTU)
40
60
80
100
SIZING
(kW)
12 kW
18 kW
24 kW
30 kW
WEIGHT (EMPTY)
35kg
37kg
39kg
41kg
WEIGHT
(FULL)
175kg
217kg
249kg
291kg
5
Loading...
+ 14 hidden pages