Alarko CGS2-100, CGS2, CGS2-250, CGS2-150, CGS2-200 User Manual

...
CGS 2 and CGS 3
LIQUID / GASEOUS FUEL
STEEL BOILER
USER MANUAL
Code No: A.4.1.8 Revision: 250718
CGS 2 and CGS 3
LIQUID / GASEOUS FUEL
STEEL BOILER
Installation, Commissioning,
Operation and Maintenance Manual
Table of Contents
Introduction
07
Declaration of Conformity
08
Notices
09
Warranty and Service
11
Operating Conditions
12
Boiler Water Temperature and Room Temperature
13
Settings
Main Parts of the Boiler (CGS2)
16
Main Parts of the Boiler (CGS3)
17
Installation
18
Safety Systems
21
Burner Selection
26
Burner Installation
26
Suitable Fuels
28
Flue Gas System
28
Heating System Filling and Feeding Water
29
Features Oxygen Corrosion
30
Commissioning
31
Start Up and Stop
34
Maintenance and Service
36 Boiler Control Boards
39
Appendices
40
Standard Electrical Diagram
47
Ecopanel 7/21 and 12/311 Electrical Diagram
48
Heating Control Panel SDC Easy Operation Guide
49 Boiler Label Information
59
Technical Specifications Table
60
Burner Selection Table
62
Burner Gas Line Diagram
65
Control and Commissioning Form
66
CGS Steel Boiler Flue Information
67
7
INTRODUCTION First of all, thank you for choosing the brand, ALARKO.
In this manual, you will find the INSTALLATION, OPERATION and MAINTENANCE information on ALARKO's Steel Body Heater Boilers. Please read this guide carefully for highly efficient and economic operation of your device for a long time without any problems.
Except as described in this manual, DO NOT TOUCH any part or setting of your device for reasons such as operation, adjustment or maintenance.
Have your device installed by ALARKO CARRIER Authorized Dealers. Our Authorized Dealers and Services will provide you with the necessary
information about how to use and maintain the device after they have placed, made connections of and put into operation of your device. You can ask the issues you don't understand over and over again. Our experts will be happy to answer your questions.
For more detailed information about your device, please contact our Customer Services Hotline at 444 0 128 in order to reach the product brochure and access the ALARKO CARRIER authorized dealers and services, when necessary.
8
DECLARATION OF CONFORMITY
Our boilers with a capacity of up to 1,000 kW are manufactured in accordance with the following rules and have the right to bear the CE marking.
EN 303-1
EN 303-3
Directive 2009/142/EC on Appliances Burning Gaseous Fuels
Our boilers with a capacity of 1,000 kW and above are manufactured in accordance with the following rules and have the right to bear the CE marking.
EN 303-1
EN 303-3
EN 12953
Directive 2009/142/EC on Appliances Burning Gaseous Fuels
The materials used in our products are designed to provide safe and proper performance for our applications and are selected to withstand the chemical, mechanical and thermal effects to which they may be exposed during the expected lifetime.
There is no soft soldering on gas bearing parts.
The security of the changeable settings is ensured.
Asbestos materials are not used.
There are no parts in contact with the food and/or water used for sanitary
purposes in our boilers.
Used parts are CE-marking approved.
Installation and user information, nameplate and packaging information
have been written in the official language of the country where the boiler is to be used, the national rules of the country concerned have been considered.
The electrical materials used are suitable for directives on low voltage. The electrical materials used are suitable for Directives on Electromagnetic
Compatibility.
9
NOTICES
The boiler must be installed and operated in a closed space outside the living areas, only in a well-ventilated and non-freezing risk.
The design, installation, commissioning and maintenance of the heating system must be carried out by professional personnel trained in this field (by Alarko Carrier Authorized Service), in accordance with this manual and the local rules and applicable standards, regulations, or according to the EEC directives and European norms (EN) in the absence of those specified above.
If the boiler is installed and used outside of the operating conditions specified in this manual, it may cause accidents such as fire, explosion or the like, which could result in loss of property or loss of life.
The boiler is designed for hot water use only (below boiling temperature). The system operating temperature and pressure must comply with the values specified on the boiler's nameplate and in this manual. The heat transfer medium is water.
Boilers must only be used with gaseous or liquid fuels specified in this manual and on the boiler's nameplate.
Boilers must only be used with EN 676 (gaseous fuel) or EN 267 (liquid fuel) certified burners to operate in accordance with the Directive (92/42/AT) on Efficiency Requirements for Boilers and the Directive 2009/142/EC on Appliances Burning Gaseous Fuels.
This is a B23 type boiler, so the boiler must be connected to a flue with sufficient draught in accordance with the regulations, and there should be no flue gas leakage into the boiler room.
During the operating period of the boiler, a pump with suitable values must perform circulation continuously.
The filling and feeding water must comply with the specifications given in this manual. Lime-free, clean and non-corrosive water use is necessary in terms of economic operation and long service life of the system.
Never close the boiler room ventilation for safe and efficient use. Fresh air is needed for good combustion. It is necessary to be able to expel the gases that can emerge from combustion and that may leak from fuel to the environment.
Install the boilers on a base which is at least 15 cm above the ground, parallel to the ground, non-flammable, with sufficient strength.
Boilers should not be installed and put into operation in the environments with flammable gases and materials. In order to prevent the boiler from being damaged, it should be avoided to leak dense dust or halogen hydrocarbons (solvents, spray
10
gases, adhesives, etc.) into the combustion air. The humidity of the boiler room must not be high.
In liquid or gaseous burners, ignition is automatic and there are many additional safety controls. Do not attempt to manually switch on the burners or to operate the system manually by disabling the controls. All control equipment must be kept working continuously at the specified limits. In the event of any malfunction, do not operate the system and contact your authorized service.
The boiler room should not be used for any other purposes and should not have any open connection to living spaces. The door must be airtight, fire-resistant and self-closing.
If the boiler temperature rises above 90 °C, do not feed cool water into the
system for rapid cooling. This could cause an explosion. Allow the boiler to cool down to 40 °C naturally before the feeding water is added.
If any part of the boiler is submerged, do not put it into operation. Contact your authorized service immediately.
Do not touch the window box, flue and fume cupboard and its surrounding areas. These areas may be very hot and cause serious injury.
It is recommended to install an emergency stop switch in a suitable place outside the boiler room. This switch must be able to stop the combustion process or fuel supply. It is useful to specify it with a nameplate.
When starting up a newly installed system, initial checks and commissioning must be performed by the Alarko Carrier Authorized Service. Maintenance is the responsibility of the user and must be performed by an authorized service.
If you wish to change fuel in the future, please contact your authorized service. Fuel change requires replacement of some parts and new adjustments. Do not carry out fuel change by yourself or unauthorized persons.
This is not a condensing-type boiler, make sure that there is no long-term condensation in the boiler.
If the system is to be put into operation with a heavy gaseous fuel (such as LPG) and the boiler room is below ground level, additional measures should be taken. The fuel that can be leaked into the boiler room must be able to be expelled automatically in a safe area outside the boiler room through an ex-proof mechanical system (ventilation) and the fuel line must be cut automatically when the fuel leakage reaches a certain level.
If the system is to be commissioned with liquid fuel, the turbulators in the smoke ducts must be removed. Turbulators are for use with gaseous fuel. Since the turbulators are not used, the boiler efficiency will decrease by 2-5%.
Do not touch any part of the boiler and the burner for the purpose of adjustment or maintenance, except as described in this manual.
When gaseous fuel is used, the boiler must have an automatic cutter (solenoid valve) on the fuel supply line and this device must be associated with a warning system.
The condensate coupling under the Boiler Rear Fume Cupboard must be connected to the drain with a siphon.
Rear fume cupboard
condensate coupling
drain
siphon
WARRANTY AND SERVICE
So long as the principles, notices and all applicable standards (EN norms, directives and principles should be applied where those principles are not applicable) mentioned in this manual are abided by, your device is warranted for 2 (two) years from the date of sale against material and manufacturing defects.
The Product’s Warranty Certificate shall be filled in by the authorized service from whom you purchase the products and sent to the ALARKO-CARRIER. Please follow.
ALARKO CARRIER Authorized Services are at your service at any time, even in the slightest problems. You can find authorized service addresses in the Authorized Service Address Booklet supplied with your device.
Any defects arising from improper installation, maintenance or use shall not be covered by the warranty.
Malfunctions resulting from the heat transfer parts of the boiler coated with lime and/or similar foreign materials and the corrosion are not covered by the warranty.
The minimum service life determined by the Ministry of Industry and Trade for these devices is 15 (fifteen) years. Manufacturer and reseller companies undertake to provide service and spare parts for the device within this period.
If you encounter any problems, you can call the Customer Hotline at 444 0 128 with local call rate from anywhere in Turkey, and you can also reach Alarko Carrier Customer Services Department via e-mail at info@alarko-carrier.com.tr.mailto:info@alarko-carrier.com.tr
12
OPERATING CONDITIONS
Boilers are designed to produce hot water. They must be installed in a hot water heating system suitable for boiler performance.
Standard operating temperature is between 55 and 90 °C (special order is required for temperatures up to 105 °C). Standard operating pressure is 3 bar
(special order is required for pressure levels above this). These boilers are not suitable for use as a direct water heater. In case of
potable or clean hot water needs, a closed circuit heat exchanger suitable for the system must be installed.
These boilers are suitable for operating with liquid and gaseous fuels. Consult our authorized dealers for the fuels you can use. If you want to change the fuel that has been commissioned for the first time, contact our authorized services.
The boiler can be used in both open and closed expansion systems. A suitable expansion system in the system should work actively at all times.
In the 2nd transition pipe in CGS2 boilers and 3rd transition pipe in CGS3 boilers, there are turbulators to increase the heat transfer to the water. Never remove these turbulators, this will cause loss of efficiency in the boiler and may damage the boiler.
This is not a condensing-type boiler, so make sure that there is no condensation in the boiler.
These boilers are suitable for operating with liquid and gaseous fuels. Consult our authorized dealers for the fuels you can use. If you want to change the fuel that has been commissioned for the first time, contact our authorized services.
13
BOILER WATER TEMPERATURE AND ROOM TEMPERATURE SETTINGS
Boiler can be operated with Standard Panel or Eco-panel. Temperature Settings of Boilers Operated with Standard Panel:
The user cannot adjust the room temperature, can only adjust the temperature of the boiler water. He adjusts the boiler water temperature in the boiler thermostat on the panel. As the outside temperature changes, he must also change the thermostat setting.
Temperature Settings of Boilers Operated with Eco-panel: The user determines the desired room temperatures and time program and saves them to the eco-panel. The boiler then operates automatically depending on the outside temperature. With the tests to be carried out in 1 or 2 weeks, it should be determined whether the values determined at the beginning are suitable for the conditions of the building and suitable values for building should be found.
As long as it is not changed by the user, the eco-panel works according to the factory settings. The factory settings are as follows;
Factory Settings
User Setting
Comfort room temperature
20 °C
Economy room temperature
16 °C
Working hours at comfort temperature
06:00 - 22:00
Working hours at economy temperature
22:00 - 06:00
Heating curve (if building with radiator)
1,5
Heating curve (if building with underfloor heating)
1,0
14
Heating curves are the graphs in which the boiler water temperature is determined depending on the desired room temperature and the outside temperature.
Boiler water temperature
(
o
C)
Outside temperature
Room temperature (oC)
15
When the room temperature is changed, the curves move in parallel. In the
following example, if the room temperature is desired to be 25 °C or 15 °C, the
way of change of the heating curve of 1,5 is indicated by dashed lines.
Curve of 1,5 for
25 °C room
temperature
Curve of 1,5 for
20 °C room
temperature
Curve of 1,5
for 15 °C room
temperature
Boiler water temperature
(
o
C)
Outside temperature
Room temperature (oC)
16
MAIN PARTS OF THE BOILER
CGS2 SERIES BOILERS
INTRODUCTION PARTS OF CSG2 BOILERS:
1. Boiler flow flange
9. Front fume cover
2. Boiler return flange
10. Rear fume cupboard
3. Flow safety connection
11. Fume transition pipes
4. Return safety connection
12. Flue connection outlet
5. Hydrometer connection
13. Cleaning cover
6. Thermometer connection
14. Blowout cover
7. Condensate drain connection
15. Carrier frame
8. Burner connection cover
16. Boiler feet
17.
CGS3 SERIES BOILERS
FRONT VIEW
SIDE VIEW
INTRODUCTION PARTS OF CSG3 BOILERS:
1. Boiler flow flange
10. Burner connection
2. Boiler return flange
11. Front fume cover
3. Flow safety connection
12. Rear fume cupboard
4. Return safety connection
13. Flue connection outlet
5. Hydrometer connection
14. Cleaning cover
6. Thermometer connection
15. Blowout cover
7. Condensate drain connection
16. Carrier frame
8. III. Fume Extractor Pipes
17. Boiler feet
9. II. Fume Extractor Pipes
INSTALLATION
The design, installation and commissioning of the heating system must be carried
out
in accordance with the applicable standards, regulations and the warnings in this
manual.
In cases where there are no local standards, regulations or inadequate standards
and regulations,
EEC directives and European norms (EN) should be applicable.
The control and commissioning of the entire system must be carried out by Alarko Carrier Authorized Services.
The boiler must be installed in a closed area, except for living areas, which are well ventilated and where there is no risk of freezing in accordance with the rules. Top and bottom ventilation systems must comply with local regulations.
Boilers must only be used with EN 676 (gaseous fuel) or EN 267 (liquid fuel) certified burners to operate in accordance with the Directive (92/42/AT) on Efficiency Requirements for Boilers and the Directive 2009/142/EC on Appliances Burning Gaseous Fuels.
This is a B23 type boiler, so the boiler must be connected to a flue with sufficient draught in accordance with the regulations, and there should be no flue gas leakage into the boiler room.
All equipment and control system of the heating system should be able to provide the specified heating loads according to the external climatic conditions and the desired internal temperature. It should be able to protect the heating system against freezing and humidity when normal operating conditions (comfort temperature level) are not required.
The equipment for the control and safety systems of the heating system must comply with the applicable TS standards, and, where insufficient, the instructions in EN 12828 and this manual must be observed.
The heating system must also have at least one circulation pump complying with the system requirements and this pump must be kept in operation as long as the burner is operating.
An effective installation circuit must be installed to protect the boiler from flue gas condensation. The condensation return water temperature should be kept above the condensation value by a system such as condensation by pass pump, 3-way valve system.
The first filling water and then the feeding water should have the properties specified in this manual. The use of water with proper properties is necessary for the longevity of the system and its economic operation. Extremely soft water causes corrosion, extremely hard water causes limestone, so water with proper values should be used.
18
19
Install the boilers on a base which is at least 10 cm above the ground, parallel
to the ground, non-flammable, with sufficient strength. The base dimensions table is attached.
Boilers should not be installed and put into operation in the environments with
flammable gases and materials. In order to prevent the boiler from being damaged, it should be avoided to leak dense dust or halogen hydrocarbons (solvents, spray gases, adhesives, etc.) into the combustion air. The humidity of the boiler room must not be high.
The boiler room should not be used for any other purposes and should not
have any open connection to living spaces. The door must be airtight, fire-resistant and self-closing.
It is recommended to install an emergency stop switch in a suitable place
outside the boiler room. This switch must be able to stop the combustion process and fuel supply. It is useful to specify it with a nameplate.
If the system is to be put into operation with a heavy gaseous fuel (such as
LPG) and the boiler room is below ground level, additional measures should be taken. The fuel that can be leaked into the boiler room must be able to be expelled automatically in a safe area outside the boiler room through an ex-proof mechanical system (ventilation) and the fuel line must be cut automatically when the fuel leakage reaches a certain level.
If the system is to be commissioned with liquid fuel, the turbulators in the
smoke ducts must be removed. Turbulators are for use with gaseous fuel. Since the turbulators are not used, the boiler efficiency will decrease by 2-5%.
All electrical connections must be made according to current standards and
according to the diagrams given in this manual. Please pay special attention to the grounding of all electrical appliances in the boiler room. Never use fuel or water pipes as ground connections.
Boiler flue connections should be made according to standards. The boiler
position should be selected so that the distance between the boiler and flue and the number of elbows is minimum. Flue ducts should not be directed downwards and vertical elbow turns should be avoided. Smoke ducts and flue should be heat insulated. Tables for the selection of flue height and diameter are given in the appendix. These tables can be used under certain conditions, in systems other than these conditions, a flue calculation must be made according to the norms (TS 2165).
There should be no manual shut-off systems (such as valves) between the
boiler and the safety and control systems. A lock valve can only be fitted to the connection of the closed expansion tank for maintenance and pre-pressure checks. Accidental closure of this valve should be strictly prevented.
20
After the installation of the heating system, all system equipment connections (water, fuel, flue gas lines, electricity) must be checked for leakage.
CGS2 and CGS3 boilers have a condensate outlet. This outlet must be connected to a suitable conduit via a siphon to prevent liquid gas leakage.»
Condensate discharge must comply with applicable regulations.
The weight of the flue gas ducts must not get carried by the boiler's flue gas connection point and a flanged or leak-tight connection must be used for easy maintenance.
The total weight of the large and heavy burners should not get carried by the boiler front cover, and the weight of the burner should get carried by the ground with the help of a suitable adjustable support.
The length of the burner connection bolts should not exceed the total thickness of the burner flange, gasket and adapter plate.
If the gap between the burner barrel and the boiler refractory is more than 10 mm, this area must be filled tightly with 1200 °C resistant ceramic fiber
material.
The responsibility for the installation and commissioning of the control and safety system of the heating system in compliance with the applicable standards and regulations is in the units that implement the system project, installation and operation. The minimum information is given as a preliminary reference in accordance with the standards in force at the date of the preparation of the installation part of this manual.
For the types with 800.000 kcal/hr and under, they have a prismatic cabinet for closing the thermal insulation. Cabin steel plates are delivered separately and our authorized service department assembles them.
For the types with 1.000.000 kcal/hr and above, insulation closure sheet plates are rolled and packed and put in the combustion chamber. Our
authorized service assembles them as shown in the following pictures 1-2-3-4.
21
SAFETY SYSTEMS
In the heating system, safety precautions must be taken against exceeding the maximum operating temperature and the maximum operating pressure. The safety precautions must be taken based on the power, type, energy source and controller of the heat transfer system (e.g. automatic control or manual operation) of the heating system. It is the responsibility of the designer, the installer and the units putting it into operation to take the necessary safety precautions, select, install and adjust the safety and operating equipment correctly. If they are inadequate for the applicable standards and regulations, they must comply with EN 12828.
Minimum Safety Equipment Required in Systems with Closed Expansion Tank
Protection against exceeding the maximum operating temperature;
Each boiler control circuit must have at least one manual reset limit thermostat. After stopping the limit thermostat burner and/or fuel supply, the boiler water
temperature should not increase by more than 10K. The limit temperature control thermostat must comply with EN 60730-2-9 and/or bear CE-marking.
All Alarko Carrier optional boiler control panels have a manual reset limit thermostat. If the optional control panel is not supplied, this controller must be supplied and installed by the installer.
Protection against exceeding the maximum operating pressure;
Each boiler control circuit must have at least one pressure relief valve. The pressure relief valve must protect the system from high pressure by opening before the boiler exceeds its operating pressure and the system pressure should never exceed 10% of the operating pressure when it is opened. The pressure relief valve assembly should be done so that the pressure drop on the inlet pipe side should not be more than 3% and the pressure drop on the outlet pipe side should not be more than 10%.
The pressure relief valve is not included in the standard equipment supplied with the boiler. It is the responsibility of the project and assembly units to properly connect the pressure relief valve with the correct diameter and pressure value to the system. The relief valve must be connected to the connection point below the water flow flange without any cut-off valve, and water discharge should be done in a safe area. Boilers with a capacity above 300 kW must have a suitable size blow-off valve at the relief valve outlet line (see EN 12828). Safety valves must comply with prEN 1268-1 standard. The relief valve diameters should be selected according to the boiler capacity, but the selection diameter may not be less than DN 15.
22
For boilers with a capacity more than 300kW; high pressure protection system must have at least 1 pressure limit switch (pressure switch) as well as relief valve. This switch must be tripped before the pressure relief valve and lock the burner and/or the fuel line by disabling them. The pressure switches should not have automatic reser function and should not automatically reset itself even if the pressure drops and falls within the normal range.
The pressure limit switch is not included in the standard equipment supplied with the boiler. It is the responsibility of the project and assembly units to properly connect the pressure limit switch with manual reset with the correct diameter and ampere value to the system. Pressure limit switch and pressure relief valve can be connected in series to a collector to be installed on a line from the connection point below the boiler water flow flange, without any cut-off valve.
Protection against low water level/pressure;
Closed expansion systems must be protected against operation at low water level. The heat transfer surfaces of the hot water boilers that continue to operate at low water level can overheat and the boiler may become vaporous, which is a danger that could cause boiler explosions. Low water level protection methods include low pressure switch, water flow switch, water level switch. The low water level controller is not included in the equipment supplied with the boiler and the project and assembly units are responsible for the selection and installation of the equipment.
Closed expansion tank;
In closed heating systems, the water which is in the system as the heat carrier tries to expand and increase inherently when heated, this causes the pressure increase due to the fact that there is no volume change in closed systems. In closed heating systems, an expansion tank capable of meeting this increase in volume and holding at least a certain amount of reserve water must be connected to the system. In the system which is widely used today, the closed expansion tanks with membrane perform this function. EN 12828 standard can be used when selecting closed expansion tanks with membrane type, but manufacturers' selection calculations and installation criteria of closed expansion tanks with membrane are prioritized.
In the case of water expansion at the highest possible temperature in the system, the expansion tank volume and the size of the connecting pipe to the boiler should be selected so as not to increase the system pressure (without activating the pressure limit switch and relief valve). When installing the expansion tank, frost protection should be considered. It is recommended to connect the expansion tanks with membrane to the connection near the boiler return water flange. Manual shut-off equipment must not be used in the connection line between the expansion tank and the boiler. Only for the purpose of maintenance, repair, pre-gas pressure control of the expansion tank, it is appropriate to use lock-type valves
23
(cannot be closed by anyone other than authorized persons). The closed expansion tank is not included in the equipment supplied with the
boiler and the project and assembly units are responsible for the selection and installation of the equipment.
Minimum Controllers Required in Systems with Closed Expansion Tank
For safe and economic operation of closed expansion systems, the following controllers must be available in the system.
Water temperature controller (Boiler thermostat);
There must be a controller which controls and regulates the water temperature required by the heating system. This temperature cannot be above the adjustable maximum setting temperature of the controller, boiler operating temperature. For standard CGS2 and CGS3 boilers max. 90°C. All optional boiler control panels have a water temperature controller (Boiler thermostat). If the optional control panel is not supplied, this controller must be supplied and installed by the installer. The temperature control thermostat must comply with EN 60730-2-9 and/or bear CE-marking.
Water temperature gauge (thermometer);
The boiler must be more than 20% of its maximum operating temperature. The boiler must be installed in the flow line (the water temperature gauge in the boiler return line is not required by the standards but is recommended by us). All optional boiler control panels have a water temperature gauge (Boiler thermometer). If the optional control panel is not supplied, water temperature gauge must be supplied and installed by the installer.
Water pressure gauge (manometer);
A monometer must be connected to the boiler flow line to show 50% more pressure than the operating pressure in the heating system. All optional boiler control panels have a water temperature gauge (Boiler monameter 4 bar). If the optional control panel is not supplied or when the system pressure is above 2.5 bar, water pressure gauge must be supplied and installed by the installer.
System water level and pressure regulation system;
A regulation to keep the heating system water level and pressure at operating values must be installed in the system. According to the prEN 806-2: It is sufficient to connect the boiler water filling line to the cold water network with 1 pressure reducer, 1 check valve,
24
1 filter, 1 cold water meter and 2 ball valves. There must be a ventilation system suitable for the total boiler capacity in the
boiler room in order to be able to expel toxic, explosive gases that may occur in the boiler room and ensure an efficient and low emission combustion. It must be ensured that this ventilation system is functional as long as the boiler is active. Ventilation calculations must be calculated according to the local directives.
Minimum Safety Equipment Required in Systems with Open Expansion Tank
Open expansion tanks;
Boilers used with expansion systems open to the atmosphere must be connected to an expansion tank which is located at the highest point of the whole heating system and open to the atmosphere with a suitable capacity.
They must be dimensioned to meet the water expansion at the highest possible temperature in the system, and the expansion tank must comply with these requirements when dimensioning pipe connections. When installing the expansion tank and connecting pipes, frost protection should be considered. Expansion tanks open to the atmosphere must be connected to the connection located under the boiler flow and return water flange. Manual shut-off equipment must not be used in the connection line between the expansion tank and the boiler. There should be a ventilation outlet and overflow pipe which can not be closed in the expansion tanks open to the atmosphere. The overflow pipe should be dimensioned to drain the maximum flow rate of the water entering the system, a practical selection method; The overflow pipe diameter can be provided by selecting it as 1 DN larger than the filling pipe diameter.
Expansion tanks, safety pipes and overflow pipes must be protected against freezing. The sample reference assembly diagram is presented in the appendices.
Open expansion tank pipelines;
The boilers must be connected to the expansion tanks open to the atmosphere without any valve between the pipes with sufficient diameter from both the safety flow (expansion) and safety return (supply) lines. The expansion tank must be open to the atmosphere. The safety flow pipe must be connected from the upper part of the expansion tank, the safety return pipe from the lower part of the expansion tank, and the overflow pipe at the calculated maximum expansion level. It should not be possible to close the safety pipe or the supply and expansion pipe.
25
The smallest internal diameter of the open safety pipe and the supply and expansion pipes can be calculated as follows:
Safety flow (expansion) pipe: dG= 15+1.4 b 9 mm (but it cannot be smaller than 19 mm).
Safety return (supply) pipe: dD= 15+1.0 b d
m m
9 : It is the boiler's
nominal heat output in kW. (do not forget symbols)
Operational requirements of open expansion systems;
For safe and economic operation of open expansion systems, the following controllers must be available in the system.
Water level gauge;
The hydrometer must be connected to the system to show the water level in the heating system as a meter water column.
Water temperature gauge (thermometer);
The boiler must be more than 20% of its maximum operating temperature. The boiler must be installed in the flow line (the water temperature gauge in the boiler return line is not required by the standards but is recommended by us). All optional boiler control panels have a water temperature gauge (Boiler thermometer). If the optional control panel is not supplied, water temperature gauge must be supplied and installed by the installer.
Water temperature controller (Boiler thermostat);
There must be a controller which controls and regulates the water temperature required by the heating system. This temperature cannot be above the adjustable maximum setting temperature of the controller, boiler operating temperature. For standard CGS2 and CGS3 boilers max. 90°C. All optional boiler control panels have a water temperature controller (Boiler thermostat). If the optional control panel is not supplied, this controller must be supplied and installed by the installer.
There must be a ventilation system suitable for the total boiler capacity in the boiler room in order to be able to expel toxic, explosive gases that may occur in the boiler room and ensure an efficient and low emission combustion. It must be ensured that this ventilation system is functional as long as the boiler is active. Ventilation calculations must be calculated according to the local directives.
26
BURNER SELECTION
Boilers must be put into operation with EN 676 (gaseous fuel) or EN 267 (liquid fuel) certified burners to operate in accordance with the directive (92/42/AT) on efficiency requirements for boilers and the directive 2009/142/EC on appliances burning gaseous fuels.
When selecting a burner suitable for the boiler; boiler capacity, boiler gas side counter pressure, boiler combustion chamber dimensions, burner barrel diameter and connection flange dimensions should be taken into account (EN 303-1, EN 303-3). The material of the combustion head of the burner should be suitable for at least 500 °C operating temperature.
The combustion chamber dimensions of and the boiler gas side counter pressure of the CGS2 and CGS3 boilers are in compliance with the applicable TS EN standards.
BURNER INSTALLATION
The burner must be connected to the boiler body by using the burner adapter plate available on the front cover as standard. Actions to be made are as follows:
1. Remove the burner adapter plate bolts and remove the adapter plate from the boiler cover. Figure: x
Figure: x
Burner Adapter Plate
Burner Adapter Plate
Burner Gasket
2. Open the barrel inlet hole in the burner adapter plate.
3. Mark the holes of the flange to be used to mount the burner to the boiler on the adapter plate.
4. There are three options for fixing the burner flange to the adapter plate;
4.1. Fastening to the adapting plate with a bolt (Figure xx): Drill holes in marked areas. Then fit the "burner adapter bolts" into these holes with their ends facing outside of the burner and with their heads in between the adapter plate and the boiler cover. After passing the holes of the flange through these stud bolts,
27
tighten them with nut. The gasket thickness between the adapter plate and the burner cover is 10 mm. The heads of the bolts have 8 mm or less thickness in general. Accordingly, the bolt heads between the plate and the cover will not cause an extra thickness.
Burner Adapter Plate
Burner Gasket
Figure: xx
4.2. Threading the adapter plate: You can weld bolts to marked areas. Then pass the holes of the flange through these bolts and tighten them with nut.
4.3. Welding the bolt to the adapter plate: You can thread the areas you marked with a guide. After aligning the flange holes, you can tighten them using bolts. In this case, the outer end part of the bolt to be inserted on the adapter plate should be maximum 8-9 mm. If it is longer, its end touches the coiler cover and bolts cannot be tightened.
The length of the combustion head of the burner shall be at least as to reach the front part of the boiler combustion chamber. If the length of the combustion head is too long or too short, get approval from the boiler manufacturer for trouble-free operation.
If the gap between the burner combustion head diameter and the refractory in the boiler front cover is more than 10 mm, fill the remaining gap firmly with the heat insulation material supplied with the boiler.
The burner flange connection must always be mounted so as not to cause any gas leakage. If this cannot be achieved, there will be toxic gas leakage in the boiler room and these hot gases will cause permanent damage to the boiler front cover.
The burner capacity must be suitable for the boiler capacity. If a 2-stage or modulating controlled burner is used, the 1st stage setting should be minimum 60% of the boiler capacity. However, if continuous condensation is observed in the boiler, the 1st stage setting should be adjusted to higher levels or anti-condensation system settings should be changed.
The total weight of the large and heavy burners should not get carried by the boiler front cover, and the weight of the burner should get carried by the ground with the help of a suitable adjustable support.
28
SUITABLE FUELS
CGS2 and CGS3 boilers are only suitable for liquid and gaseous fuels. Liquid fuels: Light, Medium and Heavy oils (Observe the burner manufacturer's
instructions and local government restrictions). Gaseous fuels: Natural gas, LPG, Air gas (all gaseous fuels in accordance with
TS 11395 EN 437) (Observe the burner manufacturer's instructions and local government restrictions).
For all other fuels, contact Alarko Carrier experts.
FLUE GAS SYSTEM
CGS2 and CGS3 series boilers are B23 type boilers. The flue gases must be used with a flue system with sufficient draught so that there is no gas leakage to the boiler room. Flue calculations must be carried out according to TS EN 11389 EN 13384-1. The inner diameter, height, material and heat insulation of the flue should be based on the flue gas properties and should not cause dangerous high and low pressures.
If the system is to be commissioned with liquid fuel, the turbulators in the smoke ducts must be removed. Turbulators are for use with gaseous fuel. Since the turbulators are not used, the boiler efficiency will decrease by 2-5%.
There must be a draught between 0 and - 0.3 mbar at the flue gas outlet of the boiler. For reference, some tables related to this matter are given in the appendix.
The effective flue height is the difference in height between the boiler flue outlet and the end point of the flue.
Pre-constraint values for using the flue diagrams in the appendix; The length of the flue gas ducts between the boiler and the flue should not exceed the % of the effective flue height. However, it should be noted that it is not longer than
7m, and not less than 0.6m. A maximum of 2 elbows with 90° can be found in
the flue gas ducts (avoid sharp turns). The inclination of the flue gas ducts should not be downwards. The
recommended elevation angle is 10° upwards. The weight of the flue gas ducts must not get carried by the boiler's flue gas
connection point and a flanged or leak-tight connection must be used for easy maintenance.
29
BOILER WATER PROPERTIES
The properties that should be in boiler water are below. Other parameters not specified in the table must comply with "TS 377-10 EN12953-10, January 2006, TSE, Cylindrical boilers requirements for feeding water and boiler water quality" standard.
Parameter
Unit
Boiler Water
Boiler Supply Water
Appearance
-
Clean, stable, no
foam (*)
Clean and it should not
contain suspended
particles (*)
Conductivity (at 25 °C)
Microsienens/cm
Up to 1.500 (*)
-
Total hardness 175.000 kcal/hr
and below
French hardness
Up to 20 (**)
Up to 0,5 °Fr (*)
Total hardness 175-500.000
kcal/hr
French hardness
Up to 15 (**)
Up to 0,5 °Fr (*)
Total hardness 500.000 kcal/hr
and above
French hardness
Up to 0,2 (**)
Up to 0,5 °Fr (*) Total hardness, Cascade system
French hardness
Up to 0,2 (**)
-
(*) TS 377-10 EN12953-10, January 2006, TSE, Cylindrical boilers requirements for feeding water and boiler water quality (**) VDI 2035 – Part 1, December 2005, Association of German Engineers, Prevention of damage in water heating installations, Scale formation in drinking water
If the heating system includes units made of material other than steel (e.g.
aluminum radiator - copper pipe), these units may require lower pH and conductivity, but the protection of the boiler is a priority in the system and the above values must be observed.
Organic substances usually consist of various compounds. It is difficult to
predict the effect of such mixtures and each component of them on the boiler in advance. Organic substances can be separated into components to form carbonic acid or other acidic components and cause wear or perforation. This can also lead to foaming and the accumulation of
substances such as limestone, which should be as little as possible. Note: During the economic lifetime of the boiler, the total amount of feed water used cannot be more than 3 times the water of the entire system.
30
OXYGEN CORROSION
The presence of oxygen in the boiler water causes corrosion. The oxygen from the first filling water or the next two fillings of water to the boiler generally does not cause much damage. The main damaging factors are below;
a) Continuous supply of fresh water to the system b) Using plastic pipes without oxygen barrier c) Using an open expansion tank d) Air entering from vacuum-forming areas
If it is not possible to remove the above factors in the heating installation, the boiler and the installation must be separated from each other by a plate heat exchanger.
Damages caused by the presence of oxygen in the boiler water are not covered by the warranty.
31
COMMISSIONING
Installation control and first operation must be carried out by Alarko Carrier Authorized Services and necessary documents must be recorded. Otherwise, the manufacturer and/or the dealer shall not accept any liability for any matter and the product is deemed to be out of warranty.
Before starting the first operation, please check the following matters;
The availability of the installation, commissioning, operating, maintenance and repair of the heating system equipment in the boiler room.
Compliance of the system requirements and equipment with the values indicated on the boiler label. Fuel type and pressure, boiler - burner capacity, electrical energy values, filling water properties, expansion system existence and adequacy, selection of operating pressure and temperature according to the system requirements... etc.
Existence and adequacy of boiler room ventilation. The ventilation is not blocked by any obstruction.
The flue gas ducts and the flue are adequate and installed correctly.
Ensure that all system controls and safety equipment are available,
have the correct properties, and are installed correctly and that they are all operating in the desired range of values.
Fuel type and burner capacity are selected correctly according to boiler and heating system requirements.
If gaseous fuel is used, the turbulators are present complete in the boiler and have been placed correctly.
If liquid fuel is used, the turbulators have been removed.
There is no forgotten foreign material in the boiler combustion chamber.
Boiler front cover, back cover, burner adapter plate, window box seals
are intact and installed correctly.
The gap between the burner barrel and the cover refractory is insulated, the suitability of the length of the burner connection bolts.
Check that if the burner is heavy, a carrier support is placed under it, and that flue ducts load is not carried by the boiler smoke outlet.
In the installation criteria, the warnings specified in this manual and the applicable standards and regulations are taken into account.
32
Before the boiler is not put into first operation, all heating system components (water and fuel side) must be cleaned from foreign materials and the system should be blown (filled and quickly drained) several times. Make sure that there are no foreign materials .
Before starting to fill the system with water, in closed expansion systems, check the closed expansion pre-pressure and make sure it is in accordance with the system requirements.
Turn all valves required for filling to the open position. Check that the properties of the filling water correspond to the specified values. Carry out filling process very slowly. The filling rate must be performed at a flow
rate appropriate to the capacity of the air outlet elements of the system, otherwise air may be trapped at many points in the system.
In open expansion systems, fill up to the appropriate water level (until the water from the messaging tube) and in closed expansion systems, fill up to the pre-calculated pressure value.
If there is a low water level safety system in the system, check the function and setting values of the selected low water level control system without filling the system completely.
Deaerate all possible points of the system. Switch on the circulation pump and check that it operates in the correct direction
and circulates the water. Deaerate the system again. If the water level/pressure has dropped, supply
water again. In open expansion systems, tick up the lower pressure from the water level
indicator and inform the user about the minimum water level. In closed expansion systems, tick up the water pressure lower and upper limit
values and inform the user. In closed expansion systems, if the water pressure relief valves are not set as
default and certified, increase the system pressure slowly and adjust the pressure relief valve and other pressure control elements to the pre-calculated values. Make sure that all pressure safety systems operate at the required values.
Check that there is no water leakage from all elements in the heating system. Check the presence and accuracy of all other control and safety devices in the system and adjust the presets.
Before commissioning the burner, check the fuel properties (according to the type of fuel; pressure, temperature) and the fuel lines for leakage and discharge air from the fuel line.
33
Adjust the burner presets. Before starting the burner, make sure that all heating system is filled with water,
valve positions, water and fuel side are completely deaerated, and all control and safety element elements in the heating system are correctly pre-adjusted.
Start the burner, make the capacity and combustion adjustments. In two-stage and modulating burners, the minimum combustion setting should not be less than 60% of the boiler capacity.
Check the flue gas values with the analyzer and check that the flue emissions comply with the applicable restrictions. The values such as SCO, NOx, sootiness, CO2 or O2, flue gas temperature must be checked.
The reference values are given below (applicable standards and regulations are prioritized, may differ from this table).
Fuel
Sootiness Degree (Rinqelmann)
Heat loss % with waste gas
% C0
2
co
(mg/kWh)
NO
x
(mg/kWh)
Gaseous
(1)
(9)
> 10
<< 100 (1070)
<? 170 (260)
LPG
(1)
(9)
> 10
<<100 (1070)
<< 230 (260)
Diesel
______ (1) ______
___ (11) ____
> 13
<<110 (110)
<< 250 (250)
Note: Flue emission values must be in accordance with applicable regulations. The values given in parentheses are taken from the "Regulation on Control of Air Pollution Due to Heating" of Turkish Ministry of Environment and Forestry.
After adjusting the burner, continue to burn the burner and check that the 1st and, if any, 2nd stage thermostats are working correctly for several times.
Then heat all the water in the heating system up to 85-90 °C and deaerate the entire system again. In the first filling process, there is melted air in the cold water (10-25 °C) and this air can only be released by heating the system and disposed out of the system.
Check the setting and function of all control and safety devices again. Record the system setting parameters.
Call the person(s) who will start the heating system; Please describe all necessary system information for a correct and safe operation and give detailed information about the issues that need to be done in a potentially hazardous situation.
34
START UP AND STOP
For economic and safe use, please read this installation, commissioning, operation and maintenance manual before starting. Improper installation, commissioning, operation and maintenance may result in accidents, fire, or explosion, which could result in injury, loss of property or life.
Preliminary checks to be made before operation;
Before operating the system, ensure that there is no fuel leakage in the application area. Visual inspection of liquid fuel lines may be sufficient. In gas-fired systems, heavy gas leakage can be understood from different odors in the environment. If a gas such as LPG which is heavier than air is used, the odor control at the ground level must be carried out.
ACTIONS TO BE MADE IF YOU SMELL GAS OR NOTICE LEAKAGE:
Do not activate the system.
Do not start fire.
Do not touch any electrical unit including plugs, light switch.
Do not smoke.
Do not use any phones in the building where the leak occurs.
Close the main fuel valve entering the building.
Warn and evacuate other people in the building.
Contact your local authorities through your neighbor's phone
immediately.
If you have not detected any fuel leakage;
Check the water system level or pressure. Make sure that there are no obstructions in front of the ventilation covers. Ensure that there is no leakage in the water, flue gas lines.
Check the valve positions and ensure that all water valves are in the correct position. Make sure that all service, maintenance, replacement, dismantled parts are securely closed and/or installed correctly.
Make sure that there is no flammable material in the boiler room. If you have not used the heating system for a long time, make sure that the
water in the system is not frozen.
35
Start Up
Standard control panel;
Turn on the main burner switch (if equipped and in the closed position). Turn on the control panel switch.
Adjust the boiler thermostats to the desired level. (If there is a 2nd stage thermostat, set it to 7 °C below the degree of the 1st stage thermostat).
Switch on the circulation pump. The burner will be activated after finishing the standard automatic control functions. If the burner does not switch on and the fault lamp on the burner is illuminated,
reset it by pressing. Call your authorized dealer if it is not activated when you try it for 3 times.
(Visually check that there is no leakage of combustion gases from the boiler front and rear cover area and from the flue connections after each commissioning).
Stop
Standard control panel;
a) If there is a 2nd stage thermostat in your control panel, first set the 2nd stage thermostat to minimum (If the thermostat is operating normally, the burner will immediately switch to 1st stage operation. This function is a practical way to control the 2nd stage thermostat). If the control panel is single stage, start from the section ”b“. b) Set the boiler thermostat to minimum (If the boiler thermostat is working normally, the burner will stop immediately. This function is a practical way to control the boiler thermostat). Turn off the burner control main switch. Turn off the main fuel valve.
For long-term shutdowns: you can stop the circulation pump, but keep in mind that the water in motion is more difficult to freeze. If you shut the system off for a long period in winter, make sure that the heating system and other parts are protected against frost.
If there is another type of control panel, refer to the relevant manual.
36
MAINTENANCE AND SERVICE
Do not interfere with any part of the heating system while the system is running. Before starting maintenance, servicing, cleaning, please stop the burner, close the fuel valves, switch off the system's electrical power supply at the main switch and wait until all parts of the boiler cool down.
Natural gas is a clean energy source, does not cause excessive smoke and dust, but in order to prolong the lifetime of the system and increase its efficiency, please call your authorized service for each burning season or at least once a year to have them make followings;
Cleaning of boiler heat transfer surfaces
Control of combustion parameters, burner settings
Control of safety and control devices
Proper flue draught and, if necessary, flue cleaning
Leakage control in water, fuel and flue gas lines
Cleaning of filters in gas lines and water lines.
If the system is operating with liquid fuel, the boiler heat transfer surfaces should be cleaned at least once a month (The cleaning frequency depends on the operating characteristics and combustion parameters. The need for cleaning may occur in much shorter times due to some factors such as poor combustion setting or the use of a bad fuel, insufficient flue draught. The occurrence of soot with a thickness of 1-2 mm on heat transfer surfaces causes excessive drop in system efficiency, thus, keep the boiler heat transfer surfaces clean.
Cleaning of heat surfaces;
Stop the burner.
Stop the circulation pump.
Turn off the main power supply.
Switch off the fuel line, disconnect the connection from the coupling if
necessary.
Allow the boiler to cool down (at least 2 hours).
Open the front cover of the boiler. First remove the clamping parts
on the opening side of the boiler cover, then loosen the clamps on the hinge side until the cover is at least 10-15 mm away from the boiler.
Make sure that the boiler's front cover refractory and turbulators are
cooled.
Remove the turbulators.
37
Clean the combustion chamber and 2nd transition pipes with a pipe brush.
Open the cleaning cover on the back cover and remove any sooting
from the fume cupboard.
Check the front cover refractory.
Check the sealing elements of the front and rear cover combustion
gases.
Reassemble and tighten cleaning cover at the rear cover with care to
the sealing element.
Put the turbulators back. All pipes must have a turbulator.
Close the front cover. Visually check the cover gas insulating gasket
and refractory.
If removed, reassemble the fuel line.
Open the fuel line.
Carry out a fuel leakage check on the disassembled area (Never use
fire)
Switch on the main power supply.
You can put the system into operation again (If the fuel line is removed,
the burner may not start in the first 1-2 attempts; it will be activated when the air in the fuel line is bled).
Call your authorized service at least once a year to have them to control
of the combustion parameters, safety and control devices. Call your authorized service at least once a year to have them to control of the combustion parameters, safety and control devices.
When the burner failures, please check the following before calling the authorized service.
Is there required power supply in boiler and burner control panels?
Are the fuel valves open?
Are the main power switches on the boiler and burner control panel open?
Is the boiler water temperature below the temperature at which the
boiler thermostat is set?
Is the fuel available within the limits given? (Min. gas pressure or fuel
level in fuel tank)
Is the system water level or pressure within normal limits?
Did you manually reset the limit temperature stop thermostat?
Please do not change the setting of any safety devices.
38
Refer to the burner manual for additional checks.
Reset the burner fault switch up to 3 times and call the authorized service if
there is still no ignition. In closed expansion systems operated with an expansion tank with membrane, the tank gas pressure must be checked regularly by an authorized service. If the pre-filling gas pressure is lower than the specified, the system pressure will rise abnormally and this may cause an explosion. In closed expansion systems operated with an expansion tank with membrane, the tank gas pressure must be checked regularly by an authorized service. If the pre-filling gas pressure is lower than the specified, the system pressure will rise abnormally and this may cause an explosion. If there is a fuel, flue gas or water leakage in any part of the heating system, stop the system immediately and contact your authorized service or the responsible authority. If any of the flue gas gaskets have been damaged and the flue gas leakage is present, switch off the burner and please call your authorized service for repair or replacement. Periodically analyze the feed water to prevent deposits (such as limestone) and corrosion. Deposits such as limestone can lead to reduced system efficiency in the short term and permanent damage to the boiler in the long term. Check your safety and control devices periodically. Wet rotor pumps not operated for long-term (summer period) may have a locking problem due to corrosion. Operate the wet rotor pumps in the system once a month for 5 minutes to prevent locking. The frequent need for feed water and the frequent drop in the system water pressure/level indicate that there is water leakage in the heating system. It must be solved immediately. Never drain the system if it is not necessary. In empty systems, wear is much faster. New water filling means adding new undesirable substances and oxygen to the system. All these reasons shorten the life of the boiler and cause loss of efficiency. The water level and/or pressure of the system should be checked at least once a month. After initial installation, more frequent checks may be required until the system become stable. The burner should be checked regularly. Observe the maintenance periods specified in the burner manual. It is recommended to add oil to the section where the sensor of the heat thermostat is placed. Check oil level at least once a year and add oil if reduced. The liquid oil to be added allows the temperature sensors to react more quickly and accurately.
Flue must be cleaned periodically according to local regulations.
39
If the system shuts down for a long time in winter, necessary precautions should be taken against frost.
Fuel and water filters must be cleaned periodically according to system requirements.
BOILER CONTROL PANELS Standard Panel (PS)
1. Control Panel Fuse (6 Av)
2. Safety Limit Thermostat (100 °C)
3. Boiler Temperature Gauge (30-120°C)
4. Main Control Switch
5. Control Panel Energy Lamp,
Pump Running Lamp
6. Limit Thermostat Fault Lamp
7. First and Second Stage Thermostats
Eco-panel (PE 7/21 or PE 12/31)
1.
Control Panel Fuse (6 A)
2.
Safety Limit Thermostat (100 °C)
3.
Boiler Temperature Gauge (0-120°C)
4.
Main Control Switch (0/1)
5.
Control Panel Energy Lamp, Pump Running Lamp
6.
Limit Thermostat Fault Lamp
7.
Eco-panel (PE 7/21 or PE 12/31)
8.
First and Second Stage Thermostats (30-85°C/7K)
40
APPENDICES
NOTE: IN BOILERS OF UP TO CG
S 1250,
1=FLOW AND 2=RETURN, IN BOILERS OF
UP TO CGS 1250 AND ABOVE, 1=RETURN
AND 2=FLOW.
Heating system Circulation pump By pass pump Open expansion tank 3-way valve Safety (limit) thermostat Boiler thermostat Thermometer (0
-120 C)
Manometer (6 bar) Max. pressure limiter Min. pressure limiter Relief valve Blow-off valve Lock valve Pressure regulator Check valve (non
-return valve)
Cold water meter Automatic filling system Drain valve HS
SP
ACP
MET
3WV
TC,
TC
Tl
P,
SPL1
SPL2
sv
FT
IV
PR
cv M ARFS
DV
SAFETY
EQUIPMENT AND HYDRAULIC
DIAGRAM FOR SYSTEMS WITH CLOSED EXPANSION TANK
BOILER
41
NOTE: IN BOILERS OF UP TO CGS 1250,
1=FLOW AND 2=RETURN, IN BOILERS OF
UP TO CGS 1250 AND ABOVE,
1=RETURN AND 2=FLOW.
Heating system Circulation pump By pass pump Open expansion
tank
3-way valve Safety (limit) thermostat Boiler thermostat Thermometer Hydrometer Low pressure switch Lock valve
Valve
Pressure regulator Check valve (non
-return valve)
Drain valve Safety flow pipe Safety return pipe Overflow pipe Ventilation pipe
HS
SP
BPP
OEC
3WV
TCL
TC
Tl
HM
WLI
LV v PR
CV
DV
GB
DB
TB
HB
SAFETY EQUIPMENT AND HYDRAULIC
DIAGRAM FOR SYSTEMS WITH OPEN
EXPANSION TANK
BOILER
42
BURNER INSTALLATION
NOTICE
If the gap between the burner barrel diameter and the boiler cover refractory is more than 10 mm, fill the gap tightly with 1
200 C
degree ceramic fiber supplied with the boiler.
2.Observe the size of the
burner connection bolts.
Bolt length should not exceed the total thickness of the burner connection flange,
gasket and burner adapter plate. 3. The burner barrel pipe should pass the inner alignment of the cover at a distance of 50
-
100 mm.
Burner adapter plate
Burner barrel insulatio
n
Ceramic wool
Rock wool
Rock wool
Ceramic wool
must be 50
-
100 mm
43
BOILER BASE DIMENSIONS CGS 2 and CGS 3 100-800 BOILERS
Model
B(mm)
C(mm)
CGS2-80
660
900
CGS2-100
770
1050
CGS2-125
770
1050
CGS2-150
770
1050
CGS2-200
890
1260
CGS2-250
890
1260
CGS2-300
990
1500
CGS2-350
990
1500
CGS2-400
1090
1770
CGS2-450
1090
1770
CGS2-500
1180
1770
CGS2-600
1180
1770
CGS2-700
1310
1970
CGS2-800
1310
1970
Model
B(mm)
C(mm)
CGS3-100
680
1050
CGS3-125
680
1150
CGS3-150
680
1300
CGS3-175
750
1300
CGS3-200
750
1400
CGS3-250
750
1450
CGS3-300
750
1500
CGS3-350
880
1560
CGS3-400
880
1670
CGS3-450
880
1750
CGS3-500
960
1860
CGS3-600
1050
1900
CGS3-700
1050
2000
CGS3-800
1090
2130
CGS 3, 1000-3000 BOILERS
Model
B(mm)
C(mm)
CGS3-1000
1100
2000
CGS3-1250
1100
2000
CGS3-1500
1280
2300
CGS3-1750
1280
2500
CGS3-2000
1280
2550
CGS3-2500
1440
2600
CGS3-3000
1440
2800
44
BOILER LAYOUT
A: Burner leng
th
B: Min. 600 mm W: Min.(
A+100)mm.
D: L/2 + 500 L: Boiler length H: Boiler room height should be at least (Boiler height + 12000) mm.
Note: These dimensions are recommended reference values. They may vary according to local
standards.
45
Rated Heat Power (kW)
FOR SQUARE SECTION (PLEVVA)
Effective Flue System Height (m)
Inner Diameter
46
Rated Heat Power (kW)
CIRCULAR SECTION (SCHIEDEL)
Effective Flue System Height (m)
47
STANDARD PANEL ELECTRICAL DIAGRAM
PHASE ENERGY
NEUTRAL ENERGY
GROUNDING ENERGY
1ST STAGE THERMOSTAT OUTLET
2ND STAGE THERMOSTAT INLET
2ND STAGE THERMOSTAT OUTLET
NEUTRAL
RESET INLET
RESET OUTLET
IL : ON-OFF SWITCH TS : SAFETY THERMOSTAT TC-1 : 1ST STAGE THERMOSTAT TC-2 : 2ND STAGE THERMOSTAT L1 : FAULT LAMP L2 : 1ST STAGE THERMOSTAT RUNNING LAMP L3 : 2ND STAGE THERMOSTAT RUNNING LAMP F : 6.3 AMP FUSE
48
ECO-PANEL 7/21 AND 12/31 ELECTRICAL DIAGRAM
ECO-PANEL EXTERNAL AIR COMPENSATION WITH FIRST AND SECOND STAGE
BOILER CONTROL PANEL
BURNER
AA : ON-OFF SWITCH LT : SAFETY LIMIT THERMOSTAT PL : PUMP LAMP (1ST MIXTURE ZONE) AL : LIMIT FAULT LAMP KT1 : 1ST STAGE BOILER THERMOSTAT 16-17-18 : 2ND STAGE BOILER THERMOSTAT G : SENSOR JOINT TERMINALS N: NEUTRAL L: PHASE AF : OUTDOOR AIR SENSOR
WF/KF : BOILER SENSOR SF : BOILER SENSOR VF1 : MIXTURE CIRCUIT SENSOR (1ST ZONE) VF2 : MIXTURE CIRCUIT SENSOR (2ND ZONE) P2 : 2ND ZONE MIXTURE CIRCUIT PUMP 13-14 : 2ND ZONE 3-WAY VALVE ON-OFF PHASES P1 : 1ST ZONE MIXTURE CIRCUIT PUMP 7-8 : 1ST ZONE 3-WAY VALVE ON-OFF PHASES BP : BOILER PUMP DP : DIRECT CIRCUIT PUMP
49
ECO-PANEL 7/21 AND 12/31 EASY OPERATION GUIDE
Controller
1 "Manual operation" / "Emission measurement" button
(It is not included in remote controlled heating system
control panel) 2 "Operating mode" button (Basic indicator) 3 "Time Programs" / "Holiday programs button" 4 "System information" button 5 Display 6 Snap-in cover for service connector 7 "Day room temperature" button 8 "Economy temperature" button 9 "Domestic water temperature" button (KSS) 10 Entry button (push/turn) 11 Symbols of operating modes (Heating programs)
Entry button (push/turn) - General functions
Nominal values and parameters selected using the entry button can be changed and then saved by pressing it. Various programs can be selected by turning the entry button.
Right The setting value increases. turn (+):
Left The setting value decreases. turn (-): Pressing: the selected and displayed
value is applied
Hold down: Switch to the programming section,
return to previous selection
50
Flashing indicators on the display
In this manual, flashing indicators on the display are shown as follows:
Standard Display View
Day, date, time, boiler water temperature The cursor on the operating modes indicates the active operating mode which is active at that moment.
Special indicators
Ice crystal symbol: System frost protection active
Parasol symbol: Summer mode active (Heating system off, KSS running as programmed)
Error Message (Ex. KSS) appears alternately with the standard indicator. Contact an authorized service!
Emission measurement
(In heating system control panels, for service only)
press the button.
Current boiler water temperature Time elapsed after activation
51
After pressing the button, the boiler tries to reach the maximum temperature value set. The emission measurement time is limited to 20 minutes and must be reactivated if necessary.
Cancel: Press the button or wait for the countdown to end.
Manual operation
press and hold the button for approximately 5 seconds.
Boiler water temperature: Current actual value desired setting value (flashes)
Set the boiler water temperature to the desired value
Automatic recommissioning:
press the button.
Setting the day room temperature
press the button.
Changing the temperature:
Setting range: 5 to 30 °C
Application of change:
or
or
automatic depending on the duration of the set information.
Setting the economy temperature
press the button.
Changing the temperature:
Setting range: 5 to 30 °C
Application of change:
or
or
automatic depending on the duration of the set information.
52
INFORMATION: In operating mode 2, first select the corresponding heating circuit
and confirm it by pressing the enter button before setting the day and night room temperatures.
Setting the domestic water temperature
press the button.
Changing the temperature:
Setting range:
5 °C to maximum domestic
water temperature
Application of change:
or
or
automatic depending on the duration of the set information.
Heating curves
The heating power through the heating curves is adapted based on the structural properties of the building from the relevant outside temperature.
Correction of vertical fluctuations in the heating curve
Entering the menu:
Press and hold this button for about
3 seconds.
Selecting the heating circuit:
DD= Direct heating circuit KD1 = Mixture Circuit 1 KD2 = Mixture Circuit 2
Application of change:
Correction of characteristic curve:
Room temperature too high:
Decrease the setting value
Room temperature too low: Increase the setting value
53
ATTENTION
Make corrections only after long evaluation periods and in small steps.
Termination (Return to standard screen):
press the button.
Operating Modes
After pressing this button, the following operating
modes can be selected with the entry button:
1. Short term program:
OUTSIDE Heating when not at home RETURN HOME Stopping the operation for short time.
PARTY END At the specified date, the heating time is
extended to the set time.
2. Automatic programs:
Automatic heating process according to operating hours program.
According to the working hours program, only domestic water is active; The heating system is disabled for frost protection.
AUTOMATIC
SUMMER
3. Continuous programs:
HEATING
ECO HEATING
Continuous heating operation without time limit. Continuous heating operation in economic operating mode without time limit.
Disabling the heating system and domestic water for frost protection.
STANDBY
Selecting program
After pressing button <0, the last selected program appears flashing. All other programs can be selected via the entry button by placing the symbol (quadrangular) located on the upper part of the operating symbols on the related symbol.
The selected program is activated by pressing the entry button.
54
Example: Press the Automatic program
button and select the option AUTOMATIC.
Application of change:
or
When selecting a time adjusted program, the time information such as the return date (HOLIDAY), the return time (OUTSIDE, RETURN HOME) or extended heating operation (PARTY END) can be entered.
Example: Press the Party program
button and select the option PARTY END.
Application of change:
or
Changing the time:
Application of time:
or
4. Holiday programs
Holiday programs can be selected by pressing button
HOLIDAY
Disabling the heating system for frost protection or low power operation of the heating system during the holiday period. The domestic water temperature is disabled for frost protection.
Example: Press the holiday programs
button, select the option HOLIDAY and confirm by pressing
Select the holiday block E.g. HOLIDAY 01) and
confirm with it.
55
Changing year and date:
Application of time:
Entering Date:
Application of time:
System information
After pressing this button, all system temperatures and operating states of all system components can be queried respectively using the entry button.
Pressing:
System temperatures (Set values) Turning:
System temperatures (Actual values)
Functions and values of variable inputs
Meters and consumption data
Heating circuit information, e.g.
Program type (HOLIDAY, OUTSIDE, RETURN HOME, PARTY END, AUTOMATIC etc.)
Current operating hours programs (P1 or P1-P3 depending on activation)
Operating Mode (Daytime operation, low power operation, disabling operation)
Heating circuit depending on the model of the device (DD = Direct heating circuit, KD1= Mixture Circuit 1, KD2= Mixture Circuit 2, KSS= Domestic Water Circuit)
Related heating circuit pump status (OFF-ON)
Related Valve motor status (ON-STOP-OFF)
Boiler status (OFF-ON)
Status and functions of variable outputs
56
INFORMATION: System information appears suitable according to
the device model used.
Changing Time Programs
Entering to the "Time programs" menu press this button.
(For more information, see. SDC/DHC User Manual, TR2H-0220)
Each setting value flashing on the screen is corrected with the entry button and applied by pressing the entry button. Returning to the previous selection is made by pressing the button. By pressing the return to the standard screen button or according to the set duration of information, it is made automatically.
1. Selecting the circuit, Restoring and
copying of standard programs
Setting range: Direct heating circuit (DD), Mixture
circuit 1 (KD1), Mixture circuit 2 (KD2), Domestic water circuit (KSS), standard programs, copying of heating circuits
Continue:
2. Selecting the Time Program
Prerequisite: It is set as Parameter 02 = P1-P3 in the "system parameters" menu.
Setting range: P1,P2, P3 Continue:
57
3. Day and heating cycle selection, copying
(Block creation)
Ayar sırası: Monday 1st Cycle - Monday 2nd Cycle,
Tuesday 1st Cycle - Tuesday 2nd Cycle ... Sunday 2nd Cycle, copy to each days (Monday, Sunday), weekday block (1-5), weekend block (6-7), entire week (17).
INFORMATION: When the second cycle is also completed,
a third cycle is available for use.
Continue:
4. Start of heating (Activation time)
Setting range: Between 0.00 - 24.00 hours INFORMATION: The activation time is shown in the
top clock tab via a flashing section.
Continue:
5. End of Heating (Deactivation time)
Setting range: Between 0.00 - 24.00 hours INFORMATION: The deactivation time is shown in the
top clock tab via an additional flashing section.
Continue:
58
6. Cycle temperature for selected heating cycle
on selected day
Setting range: For heating circuits (DD, KD1, KD2):
5 to 30 °C For domestic water temperature (KSS):
10 to 80 °C (or maximum domestic water
temperature)
. ATTENTION
When the desired daytime room temperature or domestic water temperature is changed using the buttons or all the relevant cycle temperatures are changed accordingly and at the same value!
Continue:
7. Day and heating cycle
selection, copying (Block creation)
If necessary, select the next heating cycle or day as described in Step 3 below and adjust accordingly.
59
BOILER LABEL INFORMATION 1ST BOILERS WITH A CAPACITY OF UP TO 1000 KW:
www.alarko-carrier.com.tr
Email: info@alarko-carrier.com.tr
İSTANBUL: GOSB-GebzeOrganize Sanayi Bölgesi Ş.Bilgisu Cad. Gebze 41480 KOCAELİ Phone: (0262) 648 6000 Fax: (0262) 648 6101 ANKARA: Sedat Simavi Sok.
No:48, Çankaya 06550 ANKARA Phone: (0312) 409 5200 Fax:(0312) 440 7930 İZMİR: Şehit Fethibey Cad. No:55 Kat:13, Pasaport 35210 İZMİR Phone: (0232) 483 2560 Fax:
(0232) 441 5513 ADANA: Ziyapaşa Bulvarı, No: 19/5-6, 01130 ADANA Phone: (0322) 457 6223 Fax: (0322) 453 0584 ANTALYA: Mehmetçik Mahallesi, Aspendos Bulvarı,
No: 79/5 ANTALYA Phone: (0242) 322 0029 Fax: (0242) 322 8766
NAME OF THE PRODUCT
HOT WATER BOILER
FLUE TYPE: MODEL TYPE:
STANDARD
EN 303-1, EN 303-3
CAPACITY
kcal/h
FUEL CATEGORY
MAX. OPERATING PRESSURE
bar
DATE OF MANUFACTURE
MAX. OPERATING TEMPERATURE
°C
SERIAL NO
2ND BOILERS WITH A CAPACITY OF 1000 KW AND ABOVE:
www.alarko-carrier.com.tr
Email: info@alarko-carrier.com.tr
İSTANBUL: GOSB-GebzeOrganize Sanayi Bölgesi Ş.Bilgisu Cad. Gebze 41480 KOCAELİ Phone: (0262) 648 6000 Fax: (0262) 648 6101 ANKARA: Sedat Simavi Sok.
No:48, Çankaya 06550 ANKARA Phone: (0312) 409 5200 Fax:(0312) 440 7930 İZMİR: Şehit Fethibey Cad. No:55 Kat:13, Pasaport 35210 İZMİR Phone: (0232) 483 2560 Fax:
(0232) 441 5513 ADANA: Ziyapaşa Bulvarı, No: 19/5-6, 01130 ADANA Phone: (0322) 457 6223 Fax: (0322) 453 0584 ANTALYA: Mehmetçik Mahallesi, Aspendos Bulvarı,
No: 79/5 ANTALYA Phone: (0242) 322 0029 Fax: (0242) 322 8766
NAME OF THE PRODUCT
HOT WATER BOILER
FLUE TYPE:
MODEL TYPE:
STANDARD
EN 303-1, EN 303-3, EN 12953
CAPACITY
kcal/h
FUEL CATEGORY
MAX. OPERATING PRESSURE
bar
DATE OF MANUFACTURE
MAX. OPERATING TEMPERATURE
°C
SERIAL NO
60
CGS2
-800
800
930
863
1004
92,7 90 2,8
0,20
2025
1012 190
120 1505 903 * These values are given according to 10% CO2 in natural gas. It was calculated at the boiler water temperature of 75 °C and
the combustion air temperature of 20 °C. 30% of the rate
d power was taken
as a partial load. If there is a change in the partial load, the calculation must also be performed.
CGS2
-700
700
814
755
878
2,6
0,18
NW100 NW100
1755
794 1317 790
CGSK2
-60
0
600
698
647
753
2,8
0,16
NW100 NW100
1485
691 1130 678
CGS2
-500
500
582
539
627
2,3
0,16
NW100 NW100
1350
652 942 565
CGS2
-450
450
523
485
565
2,2
0,15
1 1/2" 1 1/2" 1250
630 847 508
CGS2
-400
400
465
431
502
2,2
0,15
1 1/2" 1 1/2" 1125
608 753 452
CGS2
-350
350
407
378
439
2,0
0,15
1 1/2" 1 1/2" 990
394 660 396
CGS2
-300
300
349
324
376
1,4
0,14
1 1/2" 1 1/2" 790
347 566 340
CGS2
-250
250
291
270
314
1,6
0,14
1 1/2" 1 1/2" 712
293 471 283
CGS2
-200
200
233
216
251
1,4
0,12
1 1/2" 1 1/2" 552
234 378 227
CGS2
-150
150
174
162
188
1,2
0,10
1 1/4" 1 1/4" 447
139 284 170
CGS2
-125
125
145
135
157
0,6
0,10
407
151 237 142
CGS2
-100
100
116
108
125
0,6
0,06
352
141 188 113
Unit
kcal/h x 1000
kcal/h x 1000
bar
mbar
mbar mSS
inch
inch
inch
inch
gr/sec
gr/sec
Pa, mbar
Efficie
ncy
Maximum operating pressure Maximum operating temperature
Recommended flow rate (At recommended flow rate) Water flow to the installation Water return from the installation Safety flow connection Safety return connection Weight of boile
r (without water)
Boiler water volume Flue gas values * Full load Partial load Full load Full load Partial load Partial load Flue gas required delivery
pressure
Flue gas
temperature
Flue gas flow
rate
TECHNICAL TABLES-1. BOILERS WITH A CAPACITY OF UP TO 1000 KW:
61
CGS3-800
800
930
863
1004
92,7
5,0
0,18
NW100 NW100
1890
1290 * 185
130 1505 903 * These values are given according to 10% CO2 in natural gas. It was calculated at the boiler water temperature of 75 °C and
the combustion air temperature of 20 °C. 30% of the rated power was taken as a
partial load. If there is a change in the partial load, the calculation must also be performed.
CGS3-750
750
872
809
941
92,7
4,5
0,16
NW100 NW100
1780
1190
185
130 1411 847 CGS3-700
700
814
755
878
92,7
4,2
0,14
NW100 NW100
1700
980
185
130 1317 790 CGS3-650
650
756
701
816
92,7
4,0
0,12
NW100 NW100
1620
950
185
130 1220 732 CGS3-600
600
698
647
753
92,7
3,8
0,12
NW100 NW100
1550
920
185
130 1030 618 CGS3-550
550
640
593
690
92,7
3,0
0,10
NW100 NW100
1490
850
185
130 1035 621 CGS3-500
500
582
539
627
92,7
2,8
0,10
NW100 NW100
1350
800
185
130 942 565 CGS3-450
450
523
485
565
92,7
2,4
0,08
NW80 NW80 1 1/2" 1 1/2" 1185
740
185
130 847 508 CGS3-400
400
465
431
502
92,7
2,0
0,08
NW80 NW80 1 1/2" 1 1/2" 1108
700
185
130 753 452 CGS3-350
350
407
378
439
92,7
1,8
0,08
NW80 NW80 1 1/2" 1 1/2" 950
600
185
130 660 396 CGS3-300
300
349
324
376
92,7
1,8
0,07
NW80 NW80 1 1/2" 1 1/2" 880
525
185
130 566 340 CGS3-250
250
291
270
314
92,7
1,4
0,07
NW65 NW65 1 1/2" 1 1/2" 805
460
185
130 471 283 CGS3-200
200
233
216
251
92,7
1,2
0,06
NW65 NW65 1 1/4" 1 1/4" 650
440
185
130 378 227 CGS3-175
180
209
194
226
92,7
1,2
0,06
NW65 NW65 1 1/4" 1 1/4" 605
420
185
130 332 199 CGS3-150
150
174
162
188
92,7
1,0
0,06
NW65 NW65
500
375
185
130 284 170 CGS3-125
125
145
135
157
92,7
1,0
0,05
NW50 NW50
450
280
185
130 237 142 CGS3-100
100
116
108
125
92,7
0,9
0,05
NW50 NW50
390
250
185
130 188 113 Unit
kcal/h x 1000
kcal/h x 1000
bar
mbar
mbar mSS
inch
inch
inch
inch
gr/sec
gr/sec Pa, mbar
Efficiency Maximum operating pressure Maximum operating temperature
Recommended flow rate (At recommended flow rate) Water flow to the installation Water return from the installation Safety flow connection Safety return con
nection
Weight of boiler (without water) Boiler water volume Flue gas values * Full load Partial load Full load Full load Partial load Partial load Flue gas required delivery pressure
Flue gas
temperature
Flue gas flow
rate
62
BURNER SELECTION FOR STEEL BOILERS TABLE -260713 1. BOILERS WITH A CAPACITY OF UP TO 1000 KW:
Natur
al
Gas
Burne
r
300
mbar
Flange
Diamet
er
(mm)
190
190
190
190
190
180
190
190
190
256
190
190
190
190
190
190
190
190
256
Note: The burner to be use
d must be checked whether it can pass through the burner hole of the boiler, if the hole is small, it should be
reported during the order to request the appropriate hole to be drilled.
Modulating
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M-1 1/4" MBC 300 ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 77/M
-1 1/4" MBC 300
ALG 94/M
-1 1/4" MBC 300
ALG 94/M
-1 1/4" MBC 300
ALG 120/M
-2" MBC 700
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC
300
ALG 60/M
-1 1/4" MBC 300
ALG 77/M
-1 1/4" MBC 300
ALG 94/M
-1 1/4" MBC 300
ALG 94/M
-1 1/4" MBC 300
ALG 120/M
-2" MBC 700
Flange
Diamet
er
(mm)
115
155
155
155
155
190
190
190
115
155
155
155
155
190
190
190
Two Stage
ALG 16/2
-1/2"
ALG 27
/2-3/4"
ALG 27/2
-3/4"
ALG 36/2
-3/4"
ALG 36/2
-3/4"
ALG 60/2
-3/4"
ALG 60/2
-3/4"
ALG 60/2
-3/4"
ALG 16/2
- 1/2"
ALG 27/2
- 3/4"
ALG 27/2
- 3/4"
ALG 36/2
- 3/4"
ALG 36/2
- 3/4"
ALG 60/2
- 3/4"
ALG 60/2
- 3/4"
ALG 60/2
- 3/4"
Flange
Diamet
er
(mm)
115
115
Single
Stage with
Damper
Motor
ALG 16DM
-1/2"
ALG 16DM
-1/2"
21
mbar
Flange
Diamete
r (mm)
190
190
190
190
190
190
190
190
256
190
190
190
190
190
190
190
190
256
Modulating
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-2" MBC 700
ALG 60/M
-2" MBC 700
ALG 77/M
-2" MBC 700
ALG 94/M
-2" MBC 1200
ALG 94/M
-2" MBC 1200
ALG 120/M
-2" MBC 1200
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MBC 300
ALG 60/M
-1 1/4" MB
C 300
ALG 60/M
-2" MBC 700
ALG 60/M
-2" MBC 700
ALG 77/M
-2" MBC 1200
ALG 94/M
-2" MBC 1200
ALG 94/M
-2" MBC 1200
ALG 120/M
-2" MBC 1200
Flange
Diamet
er
(mm)
115
155
155
155
155
190
190
190
115
155
155
155
155
190
190
190
Two Stage
ALG 16/2
-3/4"
ALG 27/2
-3/4"
ALG 27/2
-1"
ALG 36/2
-1 1/2"
ALG 36/2
-1 1/2"
ALG 60/2
-1 1/2"
ALG 60/2
-1 1/2"
ALG 60/2
-2"
ALG 16/2
-3/4"
ALG 27/2
-3/4"
ALG 27/2
-1"
ALG 36/2
-1 1/2"
ALG 36/2
-1 1/2"
ALG 60/2
-1 1/2"
ALG 60/2
-1 1/2"
ALG 60/2
-2"
Flange
Diamet
er
(mm)
115
115
Single
Stage with
Damper
Motor
ALG 16DM
-1"
ALG 16DM 1"
Boiler
Outp
ut
Pow
er
(kW)
116
145
174
232
290
349
407
465
581
698
814
930
116
145
174
232
290
349
407
465
581
698
814
930
Type
CGS2
-100 CGS2-125
CGS2
-150
CGS2
-200
CGS2
-250
CGS2
-300
CGS2
-350
CGS2
-400
CGS2
-500
CGS2
-600
CGS2
-700
CGS2
-800
CGS3
-100
CGS3
-125
CGD3
-150
CGS3
-200
CGS3
-250
CGS3
-300
CGS3
-350
CGS3
-400
CGS3
-500
CGS3
-600
CGS3
-700
CGS3
-800
63
BURNER SELECTION TABLE FOR STEEL BOILERS-260713
Flange
Diamete
r (mm)
Modulating
Flange
Diamet
er (mm)
132
132
132
132
162
162
162
162
162
185
185
230
132
132
132
132
162
162
162
162
162
185
185
230
Fuel Oil Burner
Two Stage
ALF 24/2
-T
ALF 24/2
-T
ALF 24/2
-T
ALF 24/2
-T
ALF 42/2 ALF 42/2 ALF 42/2 ALF 65/2 ALF 65/2 ALF 80/2 ALF 80/2 ALF 130/2 ALF 24/2
-T
ALF 24/2
-T
ALF 24/2
-T
ALF 24/2
-T
ALF 42/2 ALF 42/2 ALF 42/2 ALF 65/2 ALF 65/2 ALF 80/2 ALF 80/2 ALF 130/2
Flange
Diamet
er (mm)
132
Note: The burner to be used must be checked whether it can pass through the burner hole of
the boiler, if the hole is small, it should be reported during the order to request the appropriate
hole to be drilled.
Single
Stage with
Damper Motor
ALF 12DM
-T
Flange
Diamet
er (mm)
132
132
132
132
162
162
162
185
185
132
132
132
132
162
162
162
185
185
Single Stage
ALF 12 ALF 24 ALF 24 ALF 24 ALF 42 ALF 42 ALF 42 ALF 65 ALF 65
ALF 12 ALF 24 ALF 24 ALF 24 ALF 42 ALF 42 ALF 42 ALF 65 ALF 65
Flange
Diamet
er (mm)
145
160
165
165
165
165
184
184
230
145
160
162
162
162
162
184
184
230
Diesel Burner
Two Stage
ALM 30/2 ALM 40/2 ALM 60/2 ALM 60/2 ALM 60/2 ALM 60/2 ALM 76/2 ALM 76/2 ALM 125/2
ALM 30/2 ALM 40/2 ALM 60/2 ALM 60/2 ALM 60/2 ALM 60/2 ALM 76/2 ALM 76/2 ALM 125/2 Flange
Diamet
er (mm)
110
135
135
145
162
162
162
162
184
110
135
135
145
162
162
162
162
184
Single
Stage
ALM 14 ALM 22 ALM 22 ALM 30 ALM 50 ALM 50 ALM 50 ALM 50
ALM 59
ALM 14 ALM 22 ALM 22 ALM 30 ALM 50 ALM 50 ALM 50 ALM 50 ALM 59
Outp
ut
Pow
er
(kW)
116
145
174
232
290
349
407
465
581
698
814
930
116
145
174
232
290
349
407
465
581
698
814
930
Boiler
Type
CGS2
-100
CGS2
-125
CGS2
-150
CGS2
-200
CGS2
-250
CGS2
-300
CGS2
-350
CGS2
-400
CGS2
-500
CGS2
-600
CGS2
-700
CGS2
-800
CGS3
-100
CGS3
-125
CGD3
-150
CGS3
-200
CGS3
-250
CGS3
-300
CGS3
-350
CGS3
-400
CGS3
-500
CGS3
-600
CGS3
-700
CGS3
-800
64
1ST BOILERS WITH A CAPACITY OF 1000 KW OR ABOVE:
Boiler
Natural Gas Burner
Diesel
Burner
Fuel Oil Burner
Type
Output Power (kW)
21 mbar
300 mbar
Modulating
Flange
Diamet
er
Modulating
Flange
Diame
ter
Two
Stage
Flange
Diame
ter
Two
Stage
Flange
Diame
ter
Modulating
Flange
Diame
ter
CGS3-1000
1.163
ALG 200/M MBC 1900
256
ALG 200/M-M BC 700
256
240
ALM 125/2
230
ALF 130/2
230
CGS3-1250
1.453
ALG 200/M MBC 3100
256
ALG 200/M-M BC 700
256
240
ALM 174/2
230
ALF 180/2
230
RMS9 VMDU
278
CGS3-1500
1.744
ALM 174/2
230
ALF 180/2
230
RMS9 VMDU
278
CGS3-1750
2.034
L9 VZDU
278
MS9 VZDU
278
RMS9 VMDU
278
CGS3-2000
2.325
L9 VZDU
278
MS9 VZDU
278
RMS9 VMDU
278
CGS3-2500
2.907
L9 VZDU
278
MS10 VZDU
278
RMS10 VMDU
278
CGS3-3000
3.488
L10 VZDU
278
MS10 VZDU
278
RMS10 VMDU
278
Note: The burner to be used must be checked whether it can pass through the burner hole of the boiler, if the hole is small, it should be reported during the order
to request the appropriate hole to be drilled.
65
GAS LINE
The required and optional elements for the use of the gas line in the burners are shown below.
Sectional Gas Line (2-Stage)
Multi-block Gas Line (2-Stage)
MB - ZRDLE or MBC1200 VEF
1ST Ball Valve
9. Multi-block Valve
2ND Flexible Coupling (Optional)
10. Gas Sealing Unit (optional for small capacity burners
3. Gas Line Inlet Pressure Measuring Point
of less than 1200 kW)
4. Gas Filter
11. Air Pressure Switch
5. Minimum Gas Pressure Switch
12. Burner Gas Pressure Measuring Point
6. Safety Solenoid Valve
13. Burner
7. Gas Pressure Regulator
14. Regulator Output Pressure Measuring Point
8. Operating Solenoid Valve
15. Gas Line Output Pressure Measuring Point
66
LIQUID OR GASEOUS FUEL BOILER CONTROL AND COMMISSIONING FORM
Customer name, address
Phone and fax number Authorized dealer name
Authorized dealer
Installer company
Installer company phone
Authorized service
Authorized service
Product model and type
Product serial no
Invoice date
Invoice no
Warranty certificate no
Suitable for gas, certificate
Burner model
Burner serial no
INSTALLATION CONTROL
Yes
No
Yes
No
BOILER ROOM
Boiler room layout is adequate
Water system connections are adequate
Electrical installation is
Ventilation is adequate
BOILER
Electrical control board suitable is adequate
Boiler sections installation is adequate (if casting)
Boiler safety thermostat is adequate
Expansion tank connection is adequate
Boiler relief valve is adequate
Operation of pumps is adequate
Boiler base is adequate
System is watered, deaerated
WATER SYSTEM
A drain valve at the bottom of the installation is available
A bleed valve on radiators is available
An air purge valve at the top of the installation is available
BURNER SYSTEM
Burner installation is adequate
The entrance of the barrel into the boiler is adequate
A carrier support under the burner is available, adequate
..................... cm
CLOSED EXPANSION TANK
Connection diameter is adequate ................ finger
No valve in the connection line to the boiler
Tank volume is adequate, ................ liter
Gas pressure was measured when the tank was
FLUE SYSTEM
Boiler flue connection is adequate
Number of elbows and angles are adequate
Flue cross section is
Insulated, adequate
COMMISSIONING
Burner authorized service operated the burner
Radiator temperatures checked
On / Off switch checked
Flue draught checked
Burner thermostats working
2
Circulation pumps operated
Heated radiator is adequate, .............. meter
IMPORTANT NOTICES
Have your authorized service checked your equipment at least once a year. Faults that may occur due to misuse, faults in the electrical system, voltage imbalance,
unauthorized persons intervention, lack of maintenance, frost and usage error are not covered by the warranty.
CONCLUSION
The equipment has been put into operation, the operating manual and warranty certificate have been delivered
and the instructions for use has been given.
Yes
No
Authorized service (Name, signature, date)
........./........... / ...................
Customer (Name, signature, date)
........ / .......... / ...................
EXPLANATION
67
CGS STEEL BOILER FLUE INFORMATION
Rated Thermal
Power / Rated
Capacity (kW)
Ignition Thermal Power / Rated Thermal Load
(kW)
CO2 Amount
(%)
Waste Gas Flow
(g/sec)
Waste Gas
Temperature
(°C)
Pressure
Required
to be in
Flue
(mbar)
Flue Outlet
Diameter (mm)
Full
Load
Partial
Load
Full
Load
Partial
Load
Full
Load
Partial
Load
Full
Load
Partial
Load
Full
Load
Partial
Load
Full
Load
Partial
Load
Full
Load
Partial
Load
CGS 2-100
116
35
125
38
10
10
47
28
190
120
-0,1; 0
-0,1; 0
200
200
CGS 2-125
145
44
157
47
10
10
60
35
190
120
-0,1; 0
-0,1; 0
200
200
CGS 2-150
174
52
188
56
10
10
71
42
190
120
-0,1; 0
-0,1; 0
200
200
CGS 2-200
233
70
251
75
10
10
95
57
190
120
-0,1; 0
-0,1; 0
200
200
CGS 2-250
291
87
314
94
10
10
117
71
190
120
-0,1; 0
-0,1; 0
200
200
CGS 2-300
349
105
376
113
10
10
141
85
190
120
-0,1; 0
-0,1; 0
250
250
CGS 2-350
407
122
439
132
10
10
165
99
190
120
-0,1; 0
-0,1; 0
250
250
CGS 2-400
465
140
502
151
10
10
188
113
190
120
-0,1; 0
-0,1; 0
250
250
CGS 2-450
523
157
565
170
10
10
212
127
190
120
-0,1; 0
-0,1; 0
250
250
CGS 2-500
582
175
627
188
10
10
235
141
190
120
-0,1; 0
-0,1; 0
300
300
CGS 2-600
698
209
753
226
10
10
282
170
190
120
-0,1; 0
-0,1; 0
350
350
CGS 2-700
814
244
878
263
10
10
330
198
190
120
-0,1; 0
-0,1; 0
350
350
CGS 2-800
930
279
1004
301
10
10
376
226
190
120
-0,1; 0
-0,1; 0
350
350
CGS 3-100
116
35
125
38
10
10
47
28
190
120
-0,1; 0
-0,1; 0
150
150
CGS 3-125
145
44
157
47
10
10
60
35
190
120
-0,1; 0
-0,1; 0
150
150
CGS 3-150
174
52
188
56
10
10
71
42
190
120
-0,1; 0
-0,1; 0
150
150
CGS 3-200
233
70
251
75
10
10
95
57
190
120
-0,1; 0
-0,1; 0
200
200
CGS 3-250
291
87
314
94
10
10
117
71
190
120
-0,1; 0
-0,1; 0
200
200
CGS 3-300
349
105
376
113
10
10
141
85
190
120
-0,1; 0
-0,1; 0
250
250
CGS 3-350
407
122
439
132
10
10
165
99
190
120
-0,1; 0
-0,1; 0
250
250
CGS 3-400
465
140
502
151
10
10
188
113
190
120
-0,1; 0
-0,1; 0
250
250
CGS 3-450
523
157
565
170
10
10
212
127
190
120
-0,1; 0
-0,1; 0
250
250
CGS 3-500
582
175
627
188
10
10
235
141
190
120
-0,1; 0
-0,1; 0
300
300
CGS 3-600
698
209
753
226
10
10
282
170
190
120
-0,1; 0
-0,1; 0
300
300
CGS 3-700
814
244
878
263
10
10
330
198
190
120
-0,1; 0
-0,1; 0
350
350
CGS 3-800
930
279
1004
301
10
10
376
226
190
120
-0,1; 0
-0,1; 0
350
350
CGS 3-1000
1163
349
1255
377
10
10
465
280
190
120
-0,1; 0
-0,1; 0
400
400
CGS 3-1250
1454
436
1568
470
10
10
582
349
190
120
-0,1; 0
-0,1; 0
400
400
CGS 3-1500
1745
524
1882
565
10
10
698
418
190
120
-0,1; 0
-0,1; 0
450
450
CGS 3-1750
2035
611
2196
659
10
10
814
488
190
120
-0,1; 0
-0,1; 0
450
450
CGS 3-2000
2326
698
2509
753
10
10
930
558
190
120
-0,1; 0
-0,1; 0
500
500
CGS 3-2500
2908
872
3137
941
10
10
1163
698
190
120
-0,1; 0
-0,1; 0
600
600
CGS 3-3000
3489
1047
3764
1129
10
10
1395
838
190
120
-0,1; 0
-0,1; 0
600
600
Note: The partial load is considered to be 30% of the full load capacity.
İSTANBUL : GOSB - Gebze Org. S an. Bölgesi, Ş. Bilgisu Cad. 41480 Gebze-KOCAELİ
Phone: (0262) 648 60 00 - Fax: (0262) 648 60 08
ANKARA : Sedat Simavi Sok. N o: 48, 06550 Çankaya - ANKARA Phone: (0312) 409 52
00 - Fax: (0312) 440 79 30
İZMİR : Şehit Fethibey Cad. No:55, Kat:13, 35210 Pasaport - İZMİR Phone: (0232)
483 25 60 - Fax: (0232) 441 55 13
ADANA : Ziyapaşa Bulvarı Çelik Ap. No : 25/5-6, 01130 ADANA Phone: (0322) 457 62
23 - Fax: (0322) 453 05 84
ANTALYA : Mehmetçik M ahallesi Aspendos Bulvarı No: 79/5 - ANTALYA Phone: (0242)
322 00 29 - Fax: (0242) 322 87 66 MDH : 444 0 128
web: www.alarko-carrier.com.tr e-mail: info@alarko-carrier.com.tr
Loading...