Akerstroms Bjorbo CU96 Users Manual

INSTALLATION INSTRUCTION REMOTUS 96XX 92 3161-000 Ver. C0 Page 1(3)
The following guide shall be used when installing Åkerströms Remotus CU9600 system, in order to obtain a completely reliable operation. The installation shall be done by a competent person.
1. MOUNTING
The permanent installation of the building must submit fuses which protect the equipment and wiring from over-current and short-circuit. In detail the regular power supply of the equipment and all relay-contacts must be fused. All that fuses are used as separation devices. They must be easily accessible, must submit a contact-gap of at least 3,0 mm and has to be placed in the line pole (L).
After the installation of the equipment, the installed cables must be bound together (e.g. by using a cable binder) very close to the terminal blocks.
1.1 AERIAL PLACEMENT
The antenna for the receiver shall be placed as open as possible. Further information can be found in drawing 90 8473-000.
Aerial connector
Connector for MC 1
Connector for MC 2
Connector for Voltage supply 12-24VDC
Ground screw for shield connection.
Connector for Profibus DP.
020320
S-780 45 BJÖRBO, PHONE +46 241 – 250 00, FAX. +46 241 - 232 90
INSTALLATION INSTRUCTION REMOTUS 96XX 92 3161-000 Ver. C0 Page 2(3)
Equipotientiaial
1.2 CONNECTION CABLE
Connection cable for power supply and main contactor (MC):
The cable shall have a CONCENTRIC SHIELD e.g. ÖLFLEX or similar and with a cable area of 0,75-1mm². We recommend grounding the cable the same way as the cable for Profibus (according to the figure below). Voltage supply: 24 VDC (11-35 VDC) Power consumption: Max 9W
Connection cable for Profibus:
We recommend the following cable type (Type A). Type A is in particular suitable for high data rate (>500kbit/s). Technical specification: Impedance: 35 up to 165 Ohm at frequencies from 3 to 20MHz Cable capacitance: <30pF by each meter Cable area: >0,34mm², similar to AWG 22 Cable type: Twisted pair. 1x2 or 2x2 or 2x4 wires Resistance: <110 Ohm by each km. Signal attenuation: Max. 9dB over entire length Shield: Double shield i.e. shield cover and shield foil Max Bus length: 200 m at 1500 kbit/s, up to 1,2 km at 93,75 kbit/s
Place the cable for PROFIBUS separated from the cable for power supply.
Master
Equipotientiaial rail
Data cable
Follower
rail
Equipotientiaial cable
Follower
Equipotientiaial rail
Data cable
It is recommended to connect the shield on both sides low inductively with the protective ground. Preferably the connection between shield and protective ground is made via the metal cases. It should be noticed that this is not the optimal solution. In such a case it is better to bare the cable shield at an appropriate point and to ground with a cable as short as possible to the metallic structure of the cabinet. This could be achieved with a ground screw in front of the CU96XX receiver. If the machine parts NOT have the same ground potential, a equalization cable with great area (e.g. 16mm²) most be connected between the parts and to the central protective ground.
020320
S-780 45 BJÖRBO, PHONE +46 241 – 250 00, FAX. +46 241 - 232 90
INSTALLATION INSTRUCTION REMOTUS 96XX 92 3161-000 Ver. C0 Page 3(3)
Any modification to the equipment not expressively authorized by the party responsible for compliance could void the user's authority to operate the equipment.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
FCC note: The equipment user is required by the radio service rules to obtain a licence before operating the equipment.
1.3 CONNECTION EXAMPLE FOR THE MAIN CONTACTOR The maximum switching capacity of the relay contacts is 8A/250VAC at cosϕ=1.
Current loops that contains the relay contacts shall have a protection fuse rated 6 A.
1.3.1 Principal connection of the main contactor
Main contactor control from receiver MC1 MC2
Possible ON-
function from PLC
Main contactor
Switch
Receiver
PROFIBUS DP
The receiver functions as a Profibus DP slave and have the identity 0x0765. This is fixed and corresponds to the unit function as a Profibus DP slave.
16 byte consistent data in. The last byte is a checksum total for the 15 preceding bytes.
16 byte consistent data out.
On the Profibus board there are two rotary switches on which you can adjust the Profibus DB slave address. The default address is 55. A diskette with TYPE- and GSD-files are included with each delivery.
020320
S-780 45 BJÖRBO, PHONE +46 241 – 250 00, FAX. +46 241 - 232 90
PRODUCT DESCRIPTION REMOTUS CU9600 92 3159-980 Rev. F Page 1(16)
Written by: Bengt Edström, Henrik Hedlund Approved by: Tomas Bustad Date: 02.10.24
R A D I O L I N K S Y S T E M
R E M O T U S C U 9 6 0 0
R E C E I V E R
for serial communication and fieldbuses
Datum: 02.10.24
780 45 BJÖRBO, TEL. + 46 241 25 000, TELEFAX. +46 241 232 90
PRODUCT DESCRIPTION REMOTUS CU9600 92 3159-980 Rev. F Page 2(16)
CONTENTS
1. SPECIFICATION
2. CONSTRUCTION
3. FUNCTION DESCRIPTION
3.1 Security
3.1.1 DUAL channel approach.
3.1.2 Check of output devices.
3.1.3 Under voltage protection.
3.1.4 Over voltage protection.
3.1.5 Watch-dog
3.1.6 Test of all system code (FLASH EPROM).
3.1.7 Test of safety relevant code (FLASH EPROM).
3.1.8 Test of PLC-program (FLASH EPROM)
3.1.9 Test of data memory (RAM).
3.1.10 CPU-test
3.1.11 Software reset.
3.1.12 Main contactor
3.1.13 Emergency stop
3.1.14 Disturbed message
3.2 System configuration
3.2.1 Unit address
3.2.2 Selection of persistent functions
3.2.3 Manipulator decoding
3.2.4 Disconnect delay, brake lifter
3.2.5 Multi-operator and multi-crane operation
3.2.6 Settings for Profibus DP
3.3 Indications
3.4 Two-way communikation (duplex)
3.5 Communication with other equipment
3.6 Dipswitches
3.7 Test mode
3.7.1 Runtime information
3.8 Monitor
4. MESSAGE CHECK
5. CONNECTIONS Appendix.
1 Description of the PLC system (90 8075-000). 2 Description of the MONITOR (90 8069-000).
Datum: 02.10.24
780 45 BJÖRBO, TEL. + 46 241 25 000, TELEFAX. +46 241 232 90
PRODUCT DESCRIPTION REMOTUS CU9600 92 3159-980 Rev. F Page 3(16)
1. SPECIFICATION
o Part of the family REMOTUS 9000 and are therefore compatible with other units. o Connects as a slave to fieldbus PROFIBUS DP. Max 16 byte out (120 functions
include checksum) and 16 byte in.
Designed to fulfil security category 3 or category 5 (according to EN 954-1) by using
way of double microprocessor-channels (redundancy).
o Double security circuits (3 MC-relays). o Build-in powerful PLC-system. o 14 bits address, which permits 16 384 different addresses. o Selectable decoding of manipulators. o Advanced multi-operator and multi-crane operator thanks to built-in PLC. o One serial asynchronous communication channel for communication with scales,
position transmitters etc.
o Built-in monitor for test- and parameter settings. o Indications for different functions in the system (status, outputs). o Statistics functions programmable with built-in PLC. o User-defined log function stores history.
Datum: 02.10.24
780 45 BJÖRBO, TEL. + 46 241 25 000, TELEFAX. +46 241 232 90
Loading...
+ 13 hidden pages