A.J. Antunes & Co VZN-440H, 9700746 User Manual

Page 1
MANUFACTURING
9700726 9700746
System Tested and Certified by NSF
International and WQA against NSF/ANSI
Standard 42 and 53 for the reduction of:
Standard No. 42: Aesthetic Effects
Nominal Particulate Reduction Class I
Standard No. 53: Health Effects
Cyst Reduction & Turbidity Reduction as
verified and substantiated by test data.
System Tested and Certified by WQA
against NSF/ANSI Standard 372
for lead-free compliance
P/N 1011064 Rev. F 12/13
VZN WATER FILTRATION
VZN-420H, VZN-440H
Owner’s Manual
Page 2
VZN SERIES
TABLE OF CONTENTS
Owner Information ...............................................................2
General............................................................................... 2
Warranty Information .......................................................... 2
Service/Technical Assistance ............................................. 3
Important Safety Information ..............................................4
Specifications .......................................................................6
Dimensions......................................................................... 6
Electrical Ratings and Plug Configurations ........................ 6
Replacement Cartridges .................................................... 6
Electrical Cord & Plug Configurations ................................ 6
Performance Data Sheet ......................................................7
Filter Cartridge Capacities.................................................. 7
Performance Claims for Percent Reduction....................... 7
Operation ...............................................................................8
Overview ............................................................................ 8
Manual Flushing ................................................................. 8
Installation .............................................................................9
Unpacking .......................................................................... 9
Equipment Setup ................................................................ 9
Mounting the System ....................................................... 10
Alternative Vertical Mounting............................................ 10
Drain Valve Connection .....................................................11
System Inlet Connection .................................................. 12
Filtered Water Permeate Outlet Connection .................... 12
Inlet Water Plumbing ........................................................ 12
Installing a Bypass ........................................................... 13
Starting the Controller ...................................................... 13
Rinsing the Ultra Filter Cartridge...................................... 13
Sanitizing the System and Lines ...................................... 14
Maintenance ........................................................................15
Replacing the Ultra Filter Cartridge.................................. 15
System Sanitization .......................................................... 15
Changing the Interval Setting ........................................... 16
Resetting the Timer Program ........................................... 16
Check Permeate Tank Air Pre-Charge ............................. 16
Troubleshooting .................................................................17
Replacement Parts .............................................................18
Limited Warranty ................................................................20
OWNER INFORMATION
General
The VZN system is an innovative filtration system that uses proprietary multi-bore hollow fiber membranes as well as a carbon element to provide the latest innovation in filtration technology.
This manual provides the safety, installation, and operating procedures for the VZN water filtration system. All information contained in this manual should be read prior to installing and operating the system. Your VZN system is man­ufactured from the finest materials available and is assembled to strict quality standards. This system has been tested at the factory to ensure dependable trouble-free operation.
Warranty Information
Please read the full text of the Limited Warranty in this manual.
If the system arrives damaged, contact the carrier immedi­ately and file a damage claim with them. Save all packing materials when filing a claim. Freight damage claims are the responsibility of the purchaser and are not covered under warranty.
The warranty does NOT extend to:
• Damages caused in shipment or damage as result of improper use.
• Installation of electrical service.
• Normal maintenance as outlined in this manual.
• Malfunction resulting from improper maintenance.
• Damage from moisture leaking into electrical components.
• Damage from tampering with, removal of, or changing any preset control or safety device.
IMPORTANT! Keep these instructions for future reference. If the system changes
ownership, be sure this manual accompanies the equipment.
2
P/N 1011064 Rev. F 12/13
Page 3
OWNER INFORMATION (continued)
Service/Technical Assistance
If you experience any problems with the installation or opera­tion of your system, contact A.J. Antunes & Co. at 1-630-784- 1000, or toll free in the United States at 1-800-253-2991.
Fill in the information in the next column and have it handy when calling for assistance. The serial number is on the specification plate located on the system.
Purchased From:
Date of Purchase:
Model No.:
Serial No.:
Mfg. No.:
VZN SERIES
Suggested replacement period for the Ultra Filter Cartridge is approximately 3 years.
For sales in the state of Iowa:
Seller: Date:
Buyer: Date:
IMPORTANT
A.J. Antunes and Company reserves the right to change specifications and product
design without notice. Such revisions do NOT entitle the buyer to corresponding
changes, improvements, additions, or replacements for previously purchased equipment.
P/N 1011064 Rev. F 12/13
3
Page 4
VZN SERIES
IMPORTANT SAFETY INFORMATION
In addition to the warnings and cautions in this manual, use the following guidelines to safely operate the system:
• Read all instructions before using equipment.
• Install or locate the equipment only for its intended use as described in this manual.
• Do NOT use corrosive chemicals in this equipment.
• Do NOT operate this equipment if it has a damaged cord or plug; if it is not working properly, or if it has been damaged or dropped.
• This equipment should be serviced by qualified person­nel only. Contact A.J. Antunes & Co. for repair.
• Do NOT immerse cord or plug in water.
• Keep cord away from heated surfaces.
• This equipment should be supplied with only cold water.
• For installations in Massachusetts, the Commonwealth of Massachusetts Plumbing Code 248 CMR shall be adhered to. The use of saddle valves are not permitted. Please consult your local plumber.
The following warnings and cautions appear throughout this manual and should be carefully observed.
• Unplug the power cord before performing any service or maintenance on the unit.
• All electrical connections must be in accordance with local electrical codes and any other applicable codes.
• WARNING ELECTRICAL SHOCK HAZARD. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN SERIOUS INJURY OR DEATH.
- Do NOT modify the power supply cord plug. If it does not fit the outlet, have a proper outlet installed by a qualified electrician.
- Do NOT use an extension cord with this unit.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or a similarly quali­fied person.
• This equipment is to be installed to comply with the local plumbing code and any other applicable code.
• Water pressure must not exceed 100 psig (690 kPa). To reduce water pressure, install a water pressure regulator and set to suit the application.
• The trans membrane pressure (inlet pressure minus the permeate water pressure) must not exceed 45 psi (310 kPa).
• A ground fault circuit interrupter (GFCI) must be installed on the circuit to this system.
• When installed on metallic plumbing, a properly sized electrical bonding jumper must be installed across the inlet and outlet pipes serving this unit.
NOTE: If the inlet water pressure is less than 50 psig (345 kPa), it is recommended that a suitably-sized booster system (outlet pressure 60 psig - 100 psig max (414 kPa ­690 kPa max) be installed.
4
P/N 1011064 Rev. F 12/13
Page 5
IMPORTANT SAFETY INFORMATION (continued)
VZN SERIES
Protect from becoming dry
If the membrane dries out, irreversible damage to the Ultra Filter membrane may result. Protect the filter from becoming dry by keeping it wet and sealed at all times.
Protect from freezing
If the Ultra Filter membrane freezes during operation or stor­age, irreversible damage to the membrane and brittle cracking of the cartridge or housing may result.
Protect from direct sunlight or other UV sources
Avoid long-term exposure to direct sunlight or other UV sources. The Ultra Filter should be stored in a dark location.
Protect from high temperatures or abrupt variation in temperature
The maximum operating temperature is 100°F (38°C). Avoid abrupt variations in temperature. Any temperature variation should be made slowly.
Protect from rough handling or dropping
Mechanical damage, external breakage, and/or internal break­age of the filter can result if the system is dropped or bumped. Handle with care at all times during transportation and instal­lation.
Protect from organic solvents and concentrated acids
Prevent any and all contact of the membrane with strong sol­vents, solvents containing chlorine, or concentrated acids. Do NOT use strong solvents or concentrated acids on any plastic parts of the filter system. Examples of some solvents to avoid: acetone, methyl acetate (nail polish remover); hexane (spot removers); turpentine, toluene (paint thinners); dry cleaning solutions, insecticides.
CAUTION
This equipment is to be installed to comply with the basic plumbing code of the Building Officials and Code Administrators, Inc. (BOCA) and the Food Service Sanitation Manual of the Food and Drug Administration (FDA).
CAUTION
Water Flow Regulator Assemblies are NOT interchange­able. Operating the system with the wrong Water Flow Regulator or without a regulator can damage the sys­tem, cause personal injury, and voids the warranty!
CAUTION
All electrical connections must be in accordance with local electrical codes and any other applicable codes.
A ground fault circuit interrupter (GFCI) must be installed on the circuit to this system.
When installed on metallic plumbing, a properly sized electrical bonding jumper must be installed across the inlet and outlet pipes serving this unit.
Protect from abrasive material
The membranes must be protected from abrasive materials like shavings left in a pipe. Abrasive materials in contact with the membrane can cause irreversible damage to the mem­brane. All pipes must be flushed clean before installing the fil­ter. All plastic parts of the filter system must be protected from sharp objects like knives, sand paper, or other tools. Cutting or nicking a plastic part can weaken it and cause a leak. Do NOT use abrasive cleansers on any plastic parts.
Protect from water hammer
The system must be protected from shock, pressure surges, or pulsation that may occur inside water pipes. Water ham­mer occurs in pipes when a valve or faucet shuts quickly. Install a water hammer arrestor (pressure vessel containing compressed air separated from the water by a diaphragm) to reduce pressure shock.
P/N 1011064 Rev. F 12/13
5
Page 6
VZN SERIES
MAY VA RY
SPECIFICATIONS
Dimensions
VZN-440HVZN-420H
C
Model & Mfg. No.
VZN-420H
9700726
VZN-440H
9700746
A
Width
(A)
31"
(79 cm)
50"
(127 cm)
B
C
Depth
(B)
9"
(23 cm)
9"
(23 cm)
A
Height
(C)
15"
(38 cm)
15"
(38 cm)
B
Operating
Weight
40 lbs. (18 kg)
54 lbs. (25 kg)
CAUTION
All electrical connections must be in accordance with local electrical codes and any other applicable codes.
Electrical Ratings and Plug Configurations
Model & Mfg. No.
VZN-420H
9700726
VZN-440H
9700746
NOTE: Includes plug adaptors for US, Europe, Australia, and UK.
Volts Watts Amps Hertz
100–240 10 .08 50/60
100–240 10 .08 50/60
Replacement Cartridges
Replacement Part Number
VZN-420H L-420 Ultra Filter 7000411
VZN-440H L-440 Ultra Filter 7000412
Electrical Cord & Plug Configurations
Kit Model
Number
Description Configuration
DC Power Supply
100 - 240 VAC
0012146
Includes the
4 plug adaptors
below
NOTE: PLUG STYLE
A ground fault circuit interrupter (GFCI) must be installed on the circuit to this system.
When installed on metallic plumbing, a properly sized electrical bonding jumper must be installed across the inlet and outlet pipes serving this unit.
US
NEMA 1-15 (2 pin)
or NEMA 5-15
(3 Pin)
Euro
CEE 7/16
AS/NZS
3112 AUS
(2 Pin)
UK
BS 136 3
6
P/N 1011064 Rev. F 12/13
Page 7
PERFORMANCE DATA SHEET
VZN SERIES
Filter Cartridge Capacities
Maximum Operating Pressure 100 psig (690 kPa)
Maximum Operating Temperature 100°F (38°C)
Minimum Operating Temperature 40°F (4°C)
Maximum Trans Membrane Pressure 45 PSI (3.1 Bar)
pH Range 3-10
MWCO 100 kD
NSF/WQA Certified Rated Service Flow:
VZN-420H 7.9 gpm (30 l/m)
VZN-440H 13 gpm (49 l/m)
System Tested and Certified by NSF
International and WQA against NSF/ANSI
Standard 42 and 53 for the reduction of:
Standard No. 42: Aesthetic Effects
Nominal Particulate Reduction Class I
Standard No. 53: Health Effects
Cyst Reduction & Turbidity Reduction
as verified and substantiated by test data.
Performance Claims for Percent Reduction
Substance Influent
1
cyst
Turbidity 11 ± 1 NTU ≤ 0.5 NTU 99.1%
Particulate Class I
Particles 0.5 to <
1µm
1
based on the use of microspheres or Cryptosporium parvum oocysts
Challenge
Concentration
minimum
50,000/L
at least 10,000
particles /mL
Reduction
Requirement
99.95% 99.95%
≥ 85% N/A
Minimum
Reduction
%
System Tested and Certified by WQA
against NSF/ANSI Standard 372
for lead-free compliance
This system has been tested according to NSF/ANSI Standard 42 and 53 for reduction of the substances listed below. The concentration of the indicated substances in water entering the system was reduced to a concentration less than or equal to the permissible limit for water leaving the system, as specified in NSF/ANSI 42 or 53. While testing was per­formed under standard laboratory conditions, actual perfor­mance may vary.
NOTE: The NSF/WQA information provided applies to the Ultra Filter cartridge.
Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system. Systems certified for cyst reduction may be used on disinfected waters that may contain fil­terable cysts.
P/N 1011064 Rev. F 12/13
7
Page 8
VZN SERIES
OPERATION
Overview
The VZN system operates in two modes:
Normal Operation Mode
Flush Mode
During Normal Operation Mode, water enters the Inlet and flows through the Ultra Filter before exiting the Permeate Outlet as usable product water.
During Flush Mode, the Drain Valve opens and water enter­ing the Inlet flushes and cleans the Ultra Filter membrane by removing any debris collecting on the membrane wall.
The Drain Valve is only powered during Flush Mode.
NOTE: Do NOT unplug the power cord or turn off the sys­tem during Flush Mode. If there is a power outage or the system is unplugged, water will continue to be filtered but the system will NOT flush. This could cause the Ultra Filter to plug prematurely and may reduce the life of the filter.
The flush is automated by the Universal Pulse Controller to last 10 seconds and take place in one-hour intervals. This interval can be changed (see Changing the Interval Setting in the Maintenance section of this manual).
Ultra Filtration
Cartridge
Outlet
Solenoid
Inlet
(Automatic)
Figure 1. System Components
System
Flush
Valve
CAUTION
Changing the flush interval can cause the Ultra Filter to plug prematurely and may reduce the life of the filter. Consult the factory for more information.
Manual Flushing
A manual flush can be activated at any time by pressing the FLUSH button on the Universal Pulse Controller.
When the FLUSH button is pressed, the Flush LED on the controller flashes and the Drain Valve opens for 10 seconds. After flushing is complete, the Drain Valve will close, the Flush LED will stop flashing and the unit will automatically return to Normal Operation Mode.
NOTE: A manual flush will not affect the interval flush setting.
8
P/N 1011064 Rev. F 12/13
Page 9
INSTALLATION
VZN SERIES
Unpacking
1. Open the large box. It should contain:
A. Plate-mounted VZN system with Ultra Filter
Cartridge installed.
B. Padded envelope containing:
• Power Adaptor
• Adaptor Plugs
• Owner’s Manual
• Mounting Bracket
3. Remove all packing materials and protective coverings from the system.
4. Remove the information packet. Fill out and mail the warranty card immediately to prevent any delay in obtaining warranty coverage.
NOTE: If any parts are damaged, contact A.J. Antunes & Co. IMMEDIATELY at 1-800-253-2991 (toll free in the U.S. and Canada) or 1-630-784-1000.
Equipment Setup
GENERAL
When placing the system into service, pay attention to the following guidelines:
• Do NOT immerse cord or plug in water.
• Keep cord away from heated surfaces.
ELECTRICAL
The line voltage must match the voltage on the specification label. The plug on the power cord must match the appropriate outlet. Do NOT connect the system to a switched electrical outlet.
PLUMBING
NOTE: The system must be connected to the COLD water line. Do NOT connect the system to the hot water line.
The VZN system uses the following connections:
System Inlet 1" NPT
System Outlet (Product Water)
Drain 3/4" FNPT
1" NPT
It is recommended that ball valves be installed on the inlet and outlet of the system. This will aid in replacing cartridges and servicing the system.
When making a plumbing connection to the system, use a back-up wrench on the supporting plumbing. Always use a quality, approved pipe sealant or thread seal tape on pipe threads. Do NOT allow pipe sealant inside pipes.
Do NOT over tighten the connections. Use plastic fittings when connecting to the plastic connections of the system.
If soldered plumbing is used, do NOT apply heat to, or near, the filtration system. Use union (O-ring seal) connections for ease of installation and future servicing.
SUGGESTED TOOLS AND SUPPLIES FOR INSTALLATION
The following tools and supplies are suggested to help with the installation:
• Screwdriver • Adjustable Wrenches
• Drill with Bits • Level
• Tape Measure • Pipe Dope or Thread Seal Tape
• Two Gallon Bucket • Fresh, Unscented Liquid Chlorine Bleach
• Pipe Wrenches • Hose or pipe for drain line
• Ball Valves (for inlet, outlet, and bypass)
P/N 1011064 Rev. F 12/13
9
Page 10
VZN SERIES
INSTALLATION (continued)
CAUTION
Due to its weight and size, the VZN system MUST be mounted with the provided Mounting Bracket. Read the Mounting the System section before attempting to mount the VZN system. Use care when lifting heavy objects.
Mounting the System
NOTE: Use caution when lifting and mounting the sys­tem. The system MUST be mounted using the provided Mounting Bracket.
The VZN system comes with a Mounting Bracket. When mounting the system, pay attention to the following guidelines:
Allow sufficient access for cartridge replacement. VZN­420 units should be mounted with 20 inches to the left or right. VZN-440 units should be mounted with 40 inches to the left or right.
Mount the system near but NOT above an appropriate electrical outlet.
Mount the system near a drain for flushing operations.
Mount the system before all consumable water filtration processes.
Mount the system with the provided Mounting Bracket and hardware capable of supporting 120 lbs. or more.
Secure the Mounting Bracket into wall studs or with the appropriate heavy duty mounting hardware.
The system is pre-assembled to a Back Plate. The Back Plate has mounting holes across the bottom portion to secure the bottom of the system to the wall. Some of the bottom mount­ing holes may be obscured. Plan your mounting accordingly.
Alternative Vertical Mounting
The system can be mounted vertically if required. See Figure 2A for more details. Note the following when mounting a sys­tem vertically:
1. Install the Mounting Bracket horizontally as shown in Figures 2 and 2a.
2. The system must be mounted so the Solenoid Valve is located at the TOP (Figure 2a).
3. Allow sufficient access for cartridge replacement. VZN­420 units should be mounted with 20 inches above or below. VZN-440 units should be mounted with 40 inches above or below.
The system is
designed to hang from
Back Plate
(holes along bottom
for additional
mounting stability)
Figure 2. Mounting the System
Follow these steps to secure the Mounting Bracket to the wall and seat the VZN system:
1. Use a stud finder and level to attach the Mounting Bracket securely to the wall with the appropriate mounting hardware (Figure 2).
2. The Mounting Bracket is designed so that the VZN system can be lifted and hung on the Mounting Bracket. With assistance, lift the system and seat it onto the Mounting Bracket securely (Figure 2).
3. Secure the bottom portion of the VZN system to the wall using the holes provided. Make sure the mounting hardware secures the system into wall studs or use the appropriate mounting hardware.
Back Plate
(holes along right
for additional
mounting stability)
Solenoid
Valve
at Top
the Mounting Bracket.
Secure Mounting Bracket
to wall studs using
appropriate hardware.
The system is
designed to hang from
the Mounting Bracket.
Secure Mounting Bracket
to wall studs using
appropriate hardware.
4. With assistance, lift the system and seat it securely onto the Mounting Bracket vertically (Figure 2a).
5. When mounted vertically, the back plate has mounting holes across the right portion to secure the right side of the system to the wall.
10
Mounting
Holes
Figure 2a. Vertical Mounting
P/N 1011064 Rev. F 12/13
Page 11
INSTALLATION (continued)
Drain Valve Connection
The drain is for flushing particle buildup out of the system during self cleaning.
1. Cut a length of tubing (not supplied) so it reaches the drain from the Drain Valve.
2. Connect one end of the hose to the Drain Valve with an appropriate fitting (not supplied) (Figure 3).
3. Direct the other end of the hose to the drain (Figure 3).
When connecting the drain hose, pay attention to the follow­ing guidelines:
• The drain line plumbing must be able support the flow rate whenever the system flushes. This flow rate is dependent on the inlet water pressure, inlet pipe size, and system.
VZN SERIES
Example Drain Valve
Connection
Secure Hose
with Worm
Clamp
Direct Hose
to Drain
• The drain line leading out of the system must be as short as possible and slope downwards without any kinks or loops.
• The drain line plumbing must be positioned and secured at least 2 inches above the drain (Figure 4). This air gap protects the system from contamination in the event of a backed-up drain.
• The drain used must not be blocked or restricted.
• The drain used must be as large or larger than the drain line plumbing.
Figure 3. Drain Valve Connection
Secure
End
Drain
Drain Line
from System
Secure
End
Drain Line
from System
2” (5.1 cm)
minimum
Standpipe
P/N 1011064 Rev. F 12/13
Floor Drain
2” (5.1 cm)
minimum
Figure 4. Drain Line Plumbing
11
Page 12
VZN SERIES
INSTALLATION (continued)
System Inlet Connection
The System Inlet has a 1” NPT male thread at the Inlet (Figure 5). Do NOT overtighten fittings as this could cause the plastic to crack.
Use plastic fittings and a pipe thread sealant approved for use on PVC fittings when making connections.
Filtered Water Permeate Outlet Connection
The System Outlet has a 1” NPT male thread at the Outlet (Figure 5). Do NOT overtighten fittings as this could cause the plastic to crack.
Inlet
Use plastic fittings and a pipe thread sealant approved for use on PVC fittings when making connections.
Inlet Water Plumbing
A “T” or Cross Fitting with cap or plug (Not Supplied) should be installed at the System Inlet. This fitting can be used for draining and sanitizing the system and downstream plumbing (Figure 5a).
Before connecting the fitting to the System Inlet, the plumb­ing to the system must be flushed clear of all debris. Hold a bucket at the inlet water line and slowly open the Inlet Water Valve. Allow the pipe to flush until all debris is removed.
Outlet
Figure 5. Inlet and Outlet Connections
Sanitation
Plug
Inlet
T-Fitting
12
Figure 5a. Installing a T-Fitting for Sanitizing
P/N 1011064 Rev. F 12/13
Page 13
INSTALLATION (continued)
VZN SERIES
Water
Flow
Tee
Inlet Ball
Valve
(Manual)
Fully
Ported
Ball Valve
Water
Outlet Ball
Valve
(Manual)
Figure 6. Install Bypass
Flow
Installing a Bypass
It is recommended that an optional bypass be installed to help with replacing cartridges and servicing the system.
1. Install ball valves on the end of the Inlet and Outlet (Figure 6)
2. Install tees on the end of the plumbing leading to the Inlet and Outlet Ball Valves.
Rinsing the Ultra Filter Cartridge
The Ultra Filter Cartridge comes pre-installed in the VZN system. The Ultra Filter Cartridge must be rinsed before the system is used to remove any air and protective solution.
NOTE: Ultra Filter Cartridge must be rinsed to drain before use. Rinsing to drain removes storage solution and air. Do NOT rinse into carbon if present. Carbon life and/or performance may be affected.
1. Direct water from the System Outlet to a drain.
2. Open the Outlet Ball Valve.
3. Close the Inlet Ball Valve.
4. Slowly turn on the water supply to the VZN system.
5. Slowly open the Inlet Ball Valve. Air and water will come out of the Outlet Ball Valve.
6. Press the FLUSH button. The Drain Valve will open and air and water will come out of the drain line. Repeat six times to ensure all air and storage solution are flushed out of the Ultra Filter Cartridge.
7. Continue to allow water to run at full flow out of the Outlet Ball Valve for at least 15 minutes.
8. After 15 minutes, close the Outlet Ball Valve and allow the system to sit for 15 minutes without any water flow to release any trapped air from the Ultra Filter Cartridge.
9. Inspect the unit for any leaks, repairing as needed.
3. Connect the two tees by installing plumbing and a fully ported (preferably 1”) Ball Valve (Figure 6).
4. When the system is in use, open the Inlet and Outlet Ball Valves and close the Bypass Ball Valve.
5. When servicing is needed, close the Inlet and Outlet Ball Valves and open the Bypass Ball Valve.
Starting the Controller
1. Select the proper AC plug for your electrical outlet and install it onto the power supply.
2. Plug the appropriate end of the power cord into the controller.
3. Plug the other end of the power cord into the electrical outlet. The LEDs on the controller will light up.
4. The controller automatically enters Flush Mode and the Flush LED starts to flash.
5. When flushing is complete, the Flush LED will stop flashing and one or more LEDs will remain lit, indicating the unit has power and which interval is selected in the controller.
P/N 1011064 Rev. F 12/13
10. After 15 minutes, open the Outlet Ball Valve and wait for five minutes to flush out any remaining air.
11. Close the Outlet Ball Valve and redirect water from the System Outlet to service.
12. Press the FLUSH button to open the Drain Valve. Repeat six times to ensure any remaining air is flushed out of the system.
13. Open the closest downstream tap or faucet.
14. Slowly open the Outlet Ball Valve and allow water to run through the system and out the faucet for five minutes.
13
Page 14
VZN SERIES
INSTALLATION (continued)
Sanitizing the System and Lines
The plumbing must be sanitized to eliminate possible contam­ination that may have occurred during the installation process.
One ounce (30 ml) of liquid chlorine bleach (regular bleach, unscented 5.25 % - 6 % sodium hypochlorite) or Kay-5 sanitizer solution (Sodium Dichloro-s-Triazinetrione Dihydrate, 6%) or equivalent can be used to sanitize the plumbing.
The Kay-5 sanitizer solution is made by dissolving a 1 oz. packet of Kay-5 powder in 2 oz. (60 ml) of clean warm water. This can be done by removing 1 inch from the top of the Kay-5 packet and adding the 2 oz. of warm water to the pack­et. Mix with a coffee stirrer to dissolve. When added to the system, this will create a 60-100 ppm chlorine solution.
NOTE: Follow the handling and safety instructions supplied with the sanitizer.
1. Follow the steps in the Rinsing the Ultra Filter Cartridge in the Installation section of this manual.
2. Turn off the water to the system.
3. Open the faucet or tap closest downstream to the system.
4. Allow the system and plumbing to drain.
Flushing the Outlet Plumbing
To ensure that the highest quality water is produced from the system, the plumbing leading from the filter system must be flushed clear of all debris after the system is hooked up. After making the connection to the outlet of the filter system, open the faucet or tap closest to the filter system, then slowly open the Inlet Water Valve. Allow the pipe to flush until all debris is removed.
5. Remove the plug installed in the sanitizing "T" fitting at the inlet of the system. Allow the water to drain out of the system.
6. Pour the sanitizer into the inlet sanitation fitting using a cup or funnel. Be careful not to spill the sanitizer onto clothing or skin.
7. Reattach the plug on the sanitation fitting.
8. Slowly turn on the water supply to the system.
9. Allow water to flow through the system and out of the open faucet or tap until the smell of sanitizer is present.
10. Close the faucet or tap.
11. Let the system stand without water flow for at least 15 minutes to allow the sanitizer to sanitize the pipes.
12. After 15 minutes without water flow, open the faucet or tap.
13. Allow water to flow through the system until the presence of sanitizer is gone.
14. Open all other faucets and taps in line with the system to flush any remaining sanitizer from the plumbing.
15. Close all faucets and taps.
14
P/N 1011064 Rev. F 12/13
Page 15
Replacing the Ultra Filter Cartridge
VZN SERIES
MAINTENANCE
1. Turn off water to the system by closing the Inlet Ball Valve.
2. Press the FLUSH button to flush the system and relieve pressure. Repeat several times to ensure permeate tank is empty.
3. Locate the long hooked tubing on the right and discon­nect the long end from the tee by pushing the collet squarely against the face of the fitting.
4. With the collet pushed in place, pull the tubing from the fitting with your right hand.
NOTE: Water may drain from the tubing as it is removed.
NOTE: Make sure there is enough room next to the system to remove the cartridge.
5. Remove the Snap Ring (Figure 7) from the Ultra Filter Housing. Grab the raised lug with a pair of pliers and pull towards the center of the End Cap and away. The Snap Ring should lift out of its groove.
6. Remove the End Cap, End Cap O-Ring, and Cartridge (Figure 7) from the housing.
NOTE: If the Cartridge does not easily come out of the Housing, remove the opposite End Cap for assistance during Step 5.
7. Inspect the Large End Cap O-rings and End Cap O-ring for nicks or cuts. Replace as needed.
Snap Ring
End Cap
End Cap O-Rings
Cartridge
O-Ring
Ultra Filter
Housing
Ultra Filter
Cartridge
Cartridge
O-Ring
End Cap O-Rings
End Cap
Snap Ring
8. Lubricate all O-rings with a food-grade silicone lubri­cant. Apply a light coating of lubricant to the inside center tube at both ends of the new cartridge.
9. Record the serial number of the new cartridge. The cartridge serial number is engraved on one end of the outer tube (for example: 05K 12013).
10. Install the End Cap O-ring on the End Cap and insert the Large End Cap into the end of the new cartridge.
11. Position the new cartridge and End Cap at the housing and gently insert into the housing.
12. Press the End Cap into position until it is fully seated and the Snap Ring groove is visible.
13. Install the Snap Ring by guiding the non-lugged end into the groove first, pushing outward and working around the ring until it snaps into place.
NOTE: Make sure that the Snap Ring is fully seated before turning the water on.
P/N 1011064 Rev. F 12/13
Figure 7. Replacing the Ultra Filter Cartridge
14. Reattach the tubing that was removed in Steps 3 and 4. Be sure the tubing is pushed past the O-ring.
NOTE: Make sure the fitting is completely inserted onto the tubing past the O-ring. A loose connection results in leaking at the point of connection.
15. Rinse the new Ultra Filter Cartridge before placing the system back into operation. Follow the Rinsing the
Ultra Filter Cartridge and Sanitizing the System and Lines procedures in the Installation section of this
manual to complete the cartridge change.
16. When rinsing is complete, repressurize the system.
System Sanitization
The system and downstream plumbing should be sanitized every six months. When necessary, follow the procedure in Sanitizing the System and Lines in the Installation section of this manual.
15
Page 16
VZN SERIES
MAINTENANCE (continued)
Changing the Interval Setting
CAUTION
Changing the flush interval can cause the Ultra Filter to plug prematurely and may reduce the life of the filter. Consult the factory for more information.
Though not recommended, the interval setting on the Universal Pulse Controller can be changed. If the setting must be changed, use the chart below. Press and hold the corre­sponding button. After 5 seconds, the Button LED will turn on. After 10 seconds, the Flush LED will also turn on.
Flush
Interval
15 minutes A 10 seconds On On
30 minutes B 10 seconds On On
45 minutes C 10 seconds On On
1 hour A 5 seconds On Off
4 hour B 5 seconds On Off
6 hours C 5 seconds On Off
Button Hold Time
Button
LED
Flush
LED
Resetting the Timer Program
During the normal operation, the system will flush accord­ing to the set interval. It is possible the system will flush at a time of high water use. If this poses a problem, the controller can be reset. Unplug the power supply, wait for 5 seconds, and then plug the power supply in. When power is restored to the controller, it will automatically enter Flush Mode. The controller will then begin timing from the point when power is restored based on the interval setting selected.
Check Permeate Tank Air Pre-Charge
It is recommended the permeate tank air charge be checked every six months.
Tools and supplies required:
Air Pressure Gauge, 5‒40 psi range (0.3‒2.7 bar) with tire valve (Schrader Valve) connection
Source of compressed air (manual bicycle tire pump or air compressor)
CAUTION
Air pre-charge should only be checked and adjusted under zero system pressure. The system must be depressurized before checking the tank pre-charge. Do NOT adjust the tank air pre-charge with the system under pressure.
12 hours D 5 seconds On Off
24 hours D 10 seconds On On
Figure 8. Universal Pulse Controller
CAUTION
Be careful when adding air to the tank. Do NOT add too much air pressure to the tank.
1. Depressurize and make sure the Permeate Tank is fully drained.
2. Unscrew the protective cap from the air valve on the tank.
3. Use the pressure gauge to check the tank pre-charge for pressure.
NOTE: If any water comes out the air valve, the tank bladder has ruptured and the tank needs to be replaced.
4. The permeate tank should have a pressure of 28-31 PSI.
• To add pressure to the permeate tank, use a manual
bicycle tire pump or other source of compressed air.
• To release pressure from the permeate tank, press
the center pin on the air inlet valve.
5. Once the permeate tank is at 28-31 PSI, replace the protective cap on the air valve.
6. Pressurize system.
16
P/N 1011064 Rev. F 12/13
Page 17
Problem Possible Cause Corrective Action
Unit does not have power.
No water comes out of the filter system.
Low water flow comes out of the filter system.
Water tastes bad.
Flush runs continuously.
Flush runs too long.
Flush occurs at a time of high water usage.
Water splashes at drain during flush.
Water leaks at ends of the Ultra Filter cartridge after changing cartridge.
Water leaks from system fitting or connection.
VZN SERIES
TROUBLESHOOTING
The power cord is not plugged into the appropriate outlet or control box.
The unit is plugged into a switched electrical outlet.
Universal Pulse Controller is inoperable.
Transformer is defective.
Inlet/Outlet Ball Valves closed. Open the Inlet/Outlet Ball Valves.
System depressurized. Pressurize system.
Drain Valve is stuck open. Clean, rebuild, and/or replace the Drain Valve.
Rinse Ball Valve is open. Close the Rinse Ball Valve.
The system may be in a flush cycle. Wait for the flush cycle to end.
Inlet Strainer (if installed) is plugged. Clean or replace Inlet Strainer
Ultra Filter Cartridge is plugged. Replace Ultra Filter Cartridge.
See above. See above.
The inlet water pressure is too low. Boost the inlet water pressure.
The inlet flow restrictor may be plugged. Clean or replace the inlet flow restrictor.
Storage/shipping solution not completely flushed out of the system.
Biological growth in pipes. Sanitize plumbing.
Water condition changed. Consider installing additional filtration.
Broken capillaries in Ultra Filter Cartridge.
Drain Valve stuck open. Clean, rebuild, or replace the Drain Valve.
Controller sending continuous signals to valve.
Flush settings changed from factory setting.
Inoperable Universal Pulse Controller. Replace the Universal Pulse Controller.
The controller interval is set incorrectly or setting was lost due to power loss.
Drain line not positioned properly. Reposition the end of the drain line.
Drain not capable of handling high flow rate.
O-ring not lubricated. Lubricate O-ring with food grade lubricant.
O-ring is split, cut, or twisted. Replace O-ring.
Fitting broken or loose. Tighten or replace the fitting.
Not enough pipe thread sealant used.
Plug power cord into the appropriate outlet.
Plug the power cord into an unswitched outlet.
Contact your maintenance person or Authorized Service Agency.
Flush the system for a longer period of time; replace Carbon Element.
Replace Ultra Filter Cartridge.
Replace the controller.
Confirm flush settings; change back to factory settings.
Set interval.
Clean drain; find alternate drain.
Redo the fitting with the proper amount of seal­ant.
P/N 1011064 Rev. F 12/13
17
Page 18
VZN SERIES
REPLACEMENT PARTS
Replacement Parts can be purchased from an authorized dealer. Contact
A.J. Antunes & Co. at 1-630-754-1000 or toll free in the United States at 1-800-253-2991.
VZN-420H Systems
14
8
9
10
16
17
18
19
25
22
12
13
11
15
3
4
23
1
2
26
5
6
7
20
21
24
Item Part Description Qty. No.
1 0505872 VZN Back Plate 1 2 0012357 Universal Pulse Controller 1 3 4060438 36" Black Cable Tie 2 4 7000921 Permeate Tank Replacement Kit 1 5 0400381 Grommet, 1.75" OD x 1.197" ID 1 6 2190158 Female Connector, 3/4" CTS x 3/4" NPT 1 7 2010199 Tubing, Bent 90° 1 8 2180181 Lock Ring 2 9 2180230 End Cap 4" Quick Disconnect 2 10 7000413 O-ring Replacement Kit 1 11 2180201 Ultra Filter Housing 420 1 12 2070117 Nipple, Close 3/4" NPT 1 13 7000411 Ultra Filter Replacement Kit (Incl. #10) 1
10
9
20
8
19
Item Part Description Qty. No.
14 2190147 Nipple Hex, 1" 1 15 2180287 UFL Housing Clamp 2 16 3000116 Nut Retainer, 1/4"-20 4 17 3250154 Washer, Lock 1/4" 4 18 3250109 Screw, 1/4"-20 x 1/2" 4 19 2010198 Tubing, UFL Bent 180° 2 20 2190155 Union Tee 2 21 2010200 Tubing, UFL 1 22 4040189 Solenoid Valve, NC 3/4" NPT 1 23 0505871 VZN Mounting Bracket 1 24 2190154 Adaptor Stem 1" NPT 1 25 0021667 Flow Regulator Assy., 7.9 gpm 1 26 0012146 Power Adaptor 1
18
P/N 1011064 Rev. F 12/13
Page 19
VZN SERIES
REPLACEMENT PARTS (continued)
Replacement Parts can be purchased from an authorized dealer. Contact
A.J. Antunes & Co. at 1-630-754-1000 or toll free in the United States at 1-800-253-2991.
VZN-440H Systems
8
9
14
25
10
16
17
18
11
15
19
20
20
24
21
22
12
13
10
9
3
4
8
23
1
2
26
5
6
7
Item Part Description Qty. No.
1 0505872 VZN Back Plate 1 2 0012357 Universal Pulse Controller 1 3 4060438 36" Black Cable Tie 2 4 7000921 Permeate Tank Replacement Kit 1 5 0400381 Grommet, 1.75" OD x 1.197" ID 1 6 2190158 Female Connector, 3/4" CTS x 3/4" NPT 1 7 2010199 Tubing, Bent 90° 1 8 2180181 Lock Ring 2 9 2180230 End Cap 4" Quick Disconnect 2 10 7000413 O-ring Replacement Kit 1 11 2180202 Ultra Filter Housing 440 1 12 2070117 Nipple, Close 3/4" NPT 1 13 7000412 Ultra Filter Replacement Kit (Incl. #10) 1
P/N 1011064 Rev. F 12/13
19
Item Part Description Qty. No.
14 2190147 Nipple Hex, 1" 1 15 2180287 UFL Housing Clamp 2 16 3000116 Nut Retainer, 1/4"-20 4 17 3250154 Washer, Lock 1/4" 4 18 3250109 Screw, 1/4"-20 x 1/2" 4 19 2010197 Tubing, UFL Bent 180° 2 20 2190155 Union Tee 2 21 2010200 Tubing, UFL 1 22 4040189 Solenoid Valve, NC 3/4" NPT 1 23 0505871 VZN Mounting Bracket 1 24 2190154 Adaptor Stem 1" NPT 1 25 0021666 Flow Regulator Assy., 15 gpm 1 26 0012146 Power Adaptor 1
19
Page 20
LIMITED WARRANTY
Equipment manufactured by A.J. Antunes & Co. has been constructed of the finest materials available and manu­factured to high quality standards. These units are warranted to be free from defects in materials and workman­ship for a period of one year from date of purchase under normal use and service, and when installed in accor­dance with manufacturer’s recommendations*. The ultra filtration membrane cartridge is warranted under the same terms and conditions on a prorated basis for 24 months from date of purchase.
*To ensure continued proper operation of the units, follow the maintenance procedure outlined in the Owner’s Manual.
1. This warranty does not cover failures due to improper system installation, defects caused by improper storage or handling prior to placing of the equipment into service. This warranty does not include overtime charges or work done by unauthorized service agencies or personnel. This warranty does not cover normal maintenance, calibra­tion, or regular adjustments as specified in operating and maintenance instructions of this manual, and/or labor involved in moving adjacent objects to gain access to the Equipment.
2. A.J. Antunes & Co. reserves the right to make changes in design or add any improvements on any product. The right is always reserved to modify equipment because of factors beyond our control and government regulations. Changes to update equipment do not constitute a warranty charge.
3.
If shipment is damaged in transit, the purchaser should make a claim directly upon the carrier. Careful inspec­tion should be made of the shipment as soon as it arrives and visible damage should be noted upon the car­rier’s documentation. Damage should be reported to the carrier. This damage is not covered under this war­ranty.
4. THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR­POSE, EACH OF WHICH IS HEREBY EXPRESSLY DISCLAIMED. THE REMEDIES DESCRIBED ABOVE ARE EXCLUSIVE AND IN NO EVENT SHALL A.J. ANTUNES & CO. BE LIABLE FOR SPECIAL CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR THE BREACH OR DELAY IN PERFORMANCE OF THIS WARRANTY.
Prices and specifications are subject to change without notice.
Loading...