Airwell AWSI-HGF018-H11, AWSI-HHF012-H11, AWSI-HHF018-H11, AWAU-YGF018-H11, AWAU-YGF009-H11 Service Manual

...
HGF / HHF Series
Indoor Units Outdoor Units
AWSI-HGF009-H11 AWSI-HHF009-H11 AWAU-YGF009-H11 AWSI-HGF012-H11 AWSI-HHF012-H11 AWAU-YGF012-H11 AWSI-HGF018-H11 AWSI-HHF018-H11 AWAU-YGF018-H11 AWSI-HGF024-H11 AWSI-HHF024-H11 AWAU-YGF024-H11
REFRIGERANT
R410A HEAT PUMP
SM HGFHHF 1-A.1 GB
March- 2011
Version:2
LIST OF EFFECTIVE PAGES
A SM HGFHHF 1-A.1 GB
LIST OF EFFECTIVE PAGES
Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page
(when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
Dates of issue for original and changed pages are:
Original ....... 01 ........ 27 Dec, 10
Updated...... 02 ........ 04 Mar, 11
Total number of pages in this publication is 75 consisting of the following:
Page No.
Revision No. #
Page
No.
Revision No. #
Page
No.
Revision No. #
Title........................... 1
A .............................. 1
i................................. 1
1-1 - 1-4…………….. 1 2-1 - 2-4…………….. 1 3-1…………………… 1 4-1 - 4-2…………….. 1 5-1 - 5-10……………. 1 6-1 - 6-4……………… 1 7-1 - 7-1……………… 1 8-1 - 8-4……………… 1 9-1……………………. 1 10-1………………….. 1 11-1 - 11-8…………... 1 12-1 - 12-2…………...1 13-1 - 13-18…………. 1 14-1………………….. 1
* Zero in this column indicates an original page.
TABLE OF CONTENTS
SM HGFHHF 1-A.1 GB i
Table of Contents
1. INTRODUCTION ............................................................................................................................. 1-1
2. PRODUCT DATA SHEET............................................................................................................... 2-1
3. RATING CONDITIONS ................................................................................................................... 3-1
4. OUTLINE DIMENSION ................................................................................................................... 4-1
5. PERFORMANCE DATA ................................................................................................................. 5-1
6. SOUND LEVEL CHARACTERISTICS ........................................................................................... 6-1
7. ELECTRICAL DATA....................................................................................................................... 7-1
8. WIRING DIAGRAM......................................................................................................................... 8-1
9. REFRIGERATION DIAGRAMS...................................................................................................... 9-1
10. TUBING CONNECTIONS............................................................................................................... 10-1
11. CONTROL SYSTEM....................................................................................................................... 11-1
12. TROUBLESHOOTING.................................................................................................................... 12-1
13. EXPLODED VIEW & SPARE PART LIST...................................................................................... 13-1
14. APPEDDIX ...................................................................................................................................... 14-1
INTRODUCTION
1. INTRODUCTION
1.1 General
HGF/HHF//YGF series is monosplit fixed speed air conditioner designed for residential buildings. The IDU HGF/HHF is a high-wall mounted type indoor with modern appearance. Following models are included:
z AWSI-HGF009-H11 / AWSI-HHF009-H11 // AWAU-YGF009-H11
z AWSI-HGF012-H11 / AWSI-HHF012-H11 // AWAU-YGF012-H11
z AWSI-HGF018-H11 / AWSI-HHF018-H11 // AWAU-YGF018-H11
z AWSI-HGF024-H11 / AWSI-HHF024-H11 // AWAU-YGF024-H11
Different appearance styles are used in HGF and HHF indoors.
1.2 Main Features
The unit benefits from the most advanced technological innovations, namely:
R410A models
Microprocessor control and indoor LED display
Energy efficiency class A in cooling mode for all models
Max allowing tubing distance of 25m.(For model HGF/HHF018-024)
Up to 10 m vertical high between indoor and outdoor units
Cooling operation at outdoor temperature up to 46ºC.
Easy installation and service.
Sleep mode from remote control to save energy
ON/OFF timer and clock display
Vertical auto swing with motorized flap (any position stop)
Intelligent Deicing
Memory from power failure
Rapid cooling/heating
I-Feel function
Cold air prevention in heating
Clean function (Blow dry)
Self diagnostic (Error indications) for ease of maintenance
SM HGFHHF 1-A.1 GB 1-1
INTRODUCTION
1-2 SM HGFHHF 1-A.1 GB
1.3 Indoor Unit
The indoor unit is wall mounted, and can be easily fitted to many types of residential locations. It includes:
LED display
Variable speed with PG motor
Motorized flap
High efficiency filtration to ensure a best Air Quality : Advanced filtering combine
mechanical, Photo-catalytic + Bi-anti bacterial and observe bad gaseous and smokes.
1.4 Control
The microprocessor indoor controller, and an infrared remote control, supplied as standard, provide complete operating function and programming.
Remote control RC 8
Compact and economically design, it offers excellent user comfort. Combining modern design
with high technology, the RC8 remote control offers powerful functions of real considering of user
comfort and energy saving of air-conditioner .
For detail of functions, please refer to Appendix 1
INTRODUCTION
SM HGFHHF 1-A.1 GB 1-3
1.5 Outdoor Unit
The outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2. It includes :
Compressor mounted in a soundproofed compartment :
Axial fan.
Outdoor coil with hydrophilic louver fins for RC units.
Outlet air fan grill.
Interconnecting wiring terminal block.
1.6 Tubing Connections
Flare type interconnecting tubing to be produced on site. For further details please refer to the Installation Manual.
1.7 Inbox Documentation
Each unit is supplied with its own installation, operation and remote control manuals.
INTRODUCTION
1.8 Matching Table
INDOOR UNITS
AWSI-HGF009-H11 AWSI-HGF012-H11 AWSI-HGF018-H11 AWSI-HGF024-H11
OUTDOOR
UNITS
AWSI-HHF009-H11 AWSI-HHF012-H11 AWSI-HHF018-H11 AWSI-HHF024-H11
AWAU-YGF009-H11
AWAU-YGF012-H11
AWAU-YGF018-H11
AWAU-YGF022-H11
1-4 SM HGFHHF 1-A.1 GB
PRODUCT DATASHEET
2. PRODUCT DATA SHEET SHEET
2.1 HGF009 / HHF009 // YGF009 2.1 HGF009 / HHF009 // YGF009
Model Indoor Unit Model Indoor Unit
HGF009/HHF009 HGF009/HHF009
Model Outdoor Unit
YGF009
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) kW 2.64 2.81 Power input (4) kW 0.82 0.78 EER (Cooling) or COP(Heating) (4) W/W 3.21 3.61 Energy efficiency class A A
V 220-240
Ph 1
Power supply
Hz 50
Rated current A 3.8 3.6 Power factor 0.92 0.92 Prated (IDU+ODU) W 1120 Circuit breaker rating A 10A
Fan type & quantity Crossflow x 1
Cooling SH/H/M/L RPM 1390/1280/1180/1080
Fan speeds
Heating SH/H/M/L RPM 1350/1250/1140/1040 Air flow (1) SH/H/M/L M3/hr 400/370/340/310 External static pressure Min Pa 0 Sound power level (2) SH/H/M/L dB(A) 50/47/45/42 Sound pressure level(3) SH/H/M/L dB(A) 40/37/35/32 Moisture removal l/hr 1.0 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 730x255x174 Net Weight kg 8 Package dimensions WxHxD mm 790x325x245
INDOOR
Packaged weight kg 10.5 Refrigerant control Capillary Compressor type, model Rotary, Panasonic-5PS102EAA22 Fan type & quantity Propeller(direct) x 1 Fan speeds H RPM 830 Air flow H M3/hr 1500 Sound power level H dB(A) 60 Sound pressure level(3) H dB(A) 50 Dimensions WxHxD mm 785x540x320 Net Weight kg 31 Package dimensions WxHxD mm 820x580x355 Packaged weight kg 34 Refrigerant type R410A Standard charge kg(4m) 0.76 Additional charge g/m 30g/m(4m<L<15m)
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 3/8"(9.53)
Max.tubing length m. Max. 15
OUTDOOR
Connections
between units
Max.height difference m. Max. 10
Operation control type Remote control
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
SM HGFHHF 1-A.1 GB 2-1
PRODUCT DATASHEET
2-2 SM HGFHHF 1-A.1 GB
2.2 HGF012 / HHF012 // YGF012
Model Indoor Unit
HGF012/HHF012
Model Outdoor Unit
YGF012
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) kW 3.22 3.52 Power input (4) kW 1.00 0.97 EER (Cooling) or COP(Heating) (4) W/W 3.21 3.61 Energy efficiency class A A
V 220-240
Ph 1
Power supply
Hz 50
Rated current A 4.7 4.6 Power factor 0.92 0.92 Prated (IDU+ODU) W 1450 Circuit breaker rating A 16A
Fan type & quantity Crossflow x 1
Cooling SH/H/M/L RPM 1350/1250/1100/950
Fan speeds
Heating SH/H/M/L RPM 1350/1250/1100/950 Air flow (1) SH/H/M/L m3/hr 550/500/420/350 External static pressure Min Pa 0 Sound power level (2) SH/H/M/L dB(A) 50/48/45/42 Sound pressure level(3) SH/H/M/L dB(A) 40/38/35/32 Moisture removal l/hr 1.0 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 790x265x177 Net Weight kg 9 Package dimensions WxHxD mm 870x355x248
INDOOR
Packaged weight kg 12 Refrigerant control Capillary
Compressor type, model Rotary, LANDA- QXA-B120C150 Fan type & quantity Propeller(direct) x 1
Fan speeds H RPM 850 Air flow H m3/hr 1800 Sound power level H dB(A) 62 Sound pressure level(3) H dB(A) 52 Dimensions WxHxD mm 798x540x320 Net Weight kg 35 Package dimensions WxHxD mm 825x580x355 Packaged weight kg 40 Refrigerant type R410A Standard charge kg(4m) 0.76 Additional charge g/m 30g/m(4m<L<20m)
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 1/2"(12.7)
Max.tubing length m. Max. 20
OUTDOOR
Connections
between units
Max.height difference m. Max. 10
Operation control type Remote control
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
PRODUCT DATASHEET
SM HGFHHF 1-A.1 GB 2-3
2.3 HGF018 / HHF018 // YGF018
Model Indoor Unit
HGF018/HHF018
Model Outdoor Unit
YGF018
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) kW 5.30 5.70 Power input (4) kW 1.64 1.67 EER (Cooling) or COP(Heating) (4) W/W 3.23 3.41 Energy efficiency class A B
V 220-240
Ph 1
Power supply
Hz 50
Rated current A 7.8 7.9 Power factor 0.92 0.92 Prated (IDU+ODU) W 2550 Circuit breaker rating A 25A
Fan type & quantity Crossflow x 1
Cooling SH/H/M/L RPM 1350/1200/1050/900
Fan speeds
Heating SH/H/M/L RPM 1350/1200/1050/900 Air flow (1) SH/H/M/L m3/hr 850/780/650/550 External static pressure Min Pa 0 Sound power level (2) SH/H/M/L dB(A) 58/55/52/48 Sound pressure level(3) SH/H/M/L dB(A) 48/45/42/38 Moisture removal l/hr 3.0 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 940x298x200 Net Weight kg 13 Package dimensions WxHxD mm 1010x380x285
INDOOR
Packaged weight kg 17 Refrigerant control Capillary Compressor type, model Rotary, HITACHI - ASH210SV-C8LU Fan type & quantity Propeller(direct) x 1 Fan speeds H RPM 860 Air flow H m3/hr 2790 Sound power level H dB(A) 64 Sound pressure level(3) H dB(A) 54 Dimensions WxHxD mm 913x680x378 Net Weight kg 46 Package dimensions WxHxD mm 994x725x428 Packaged weight kg 50 Refrigerant type R410A Standard charge kg(4m) 1.5 Additional charge g/m 30g/m(4m<L<25m)
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 1/2"(12.7)
Max.tubing length m. Max. 25
OUTDOOR
Connections
between units
Max.height difference m. Max. 10
Operation control type Remote control
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
PRODUCT DATASHEET
2-4 SM HGFHHF 1-A.1 GB
2.4 HGF024/ HHF024 // YGF024
Model Indoor Unit
HGF024/HHF024
Model Outdoor Unit
YGF024
Installation Method of Pipe Flared
Characteristics Units Cooling Heating
Capacity (4) kW 6.16 6.50 Power input (4) kW 1.90 1.90 EER (Cooling) or COP(Heating) (4) W/W 3.24 3.42 Energy efficiency class A B
V 220-240
Ph 1
Power supply
Hz 50
Rated current A 8.9 8.9 Power factor 0.92 0.92 Prated (IDU+ODU) W 2700 Circuit breaker rating A 25A
Fan type & quantity Crossflow x 1
Cooling SH/H/M/L RPM 1350/1200/1050/900
Fan speeds
Heating SH/H/M/L RPM 1350/1200/1050/900 Air flow (1) SH/H/M/L m3/hr 850/780/650/550 External static pressure Min Pa 0 Sound power level (2) SH/H/M/L dB(A) 57/54/51/48 Sound pressure level(3) SH/H/M/L dB(A) 47/44/41/38 Moisture removal l/hr 3.0 Condensate drain tube I.D mm 16 Dimensions WxHxD mm 940x298x200 Net Weight kg 13 Package dimensions WxHxD mm 1010x380x285
INDOOR
Packaged weight kg 17 Refrigerant control Capillary
Compressor type, model Rotary, HITACHI - ASH232SV-C8LU Fan type & quantity Propeller(direct) x 1
Fan speeds H RPM 780 Air flow H m3/hr 2790 Sound power level H dB(A) 64 Sound pressure level(3) H dB(A) 54 Dimensions WxHxD mm 913x680x378 Net Weight kg 46 Package dimensions WxHxD mm 994x725x428 Packaged weight kg 50 Refrigerant type R410A Standard charge kg(4m) 1.45 Additional charge g/m 30g/m(4m<L<15m)
Liquid line In.(mm) 1/4"(6.35)
Suction line In.(mm) 1/2"(12.7)
Max.tubing length m. Max. 25
OUTDOOR
Connections
between units
Max.height difference m. Max. 10
Operation control type Remote control
(1)Airflow in ducted units; at nominal external static pressure. (2)Sound power in ducted units is measured at air discharge. (3)Sound pressure level measured at 1-meter distance from unit. (4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
RATING CONDITIONS
3. RATING CONDITIONS TING CONDITIONS
Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units).
Cooling: Cooling:
Indoor: 27
o
C DB 19oC WB Indoor: 27oC DB 19oC WB
Outdoor: 35
o
C DB Outdoor: 35 oC DB
Heating: Heating:
Indoor: 20
o
C DB Indoor: 20oC DB
Outdoor: 7
o
C DB 6oC WB Outdoor: 7oC DB 6oC WB
3.1 Operating Limits 3.1 Operating Limits
R410AR410A
Indoor Outdoor
Upper limit 32oC DB 23oC WB 46oC DB
Cooling
Lower limit 21oC DB 15oC WB 21oC DB
Upper limit 27oC DB 24oC DB 18oC WB
Heating
Lower limit 10oC DB -9oC DB 80%RH
Voltage
1-PH 50Hz 198 – 264 V
SM HGFHHF 1-A.1 GB 3-1
OUTLINE DIMENSION
4. OUTLINE DIMENSION NE DIMENSION
4.1 Indoor: HGF/HHF009-012-018-024 4.1 Indoor: HGF/HHF009-012-018-024
Unit: mm
Model W H D Q R S
09K 730 255 174 27 562 141
12K 790 265 177 35 605 150
18-24K 940 298 200 52 694 194
SM HGFHHF 1-A.1 GB 4-1
OUTLINE DIMENSION
4.2 Outdoor: YGF009-012-018-024
Model 09/12
Model 18/24
4-2 SM HGFHHF 1-A.1 GB
OUTLINE DIMENSION
SM HGFHHF 1-A.1 GB 4-3
Unit: mm
Model W H D W1 W2 D1
09-12K 776 549 320 714 510 286
18-24K 913 680 378 847 549 342
PERFORMANCE DATA & PRESSURE CURVES
5. PERFORMANCE DATA RFORMANCE DATA
5.1 HGF009 / HHF009 // YGF009 5.1 HGF009 / HHF009 // YGF009
5.1.1 Cooling Capacity (kW) 5.1.1 Cooling Capacity (kW)
Entering Air WB/DB ID Coil(oC) Entering Air WB/DB ID Coil(oC)
Entering Air DB
OD Coil(
o
C)
Data
15/21 17/24 19/27 21/29 23/32
TC
2.69 2.84 2.92 2.99 3.06
20 SC
1.77 1.87 1.95 2.00 2.04
PI
0.63 0.63 0.64 0.64 0.64
TC
2.55 2.75 2.89 2.98 3.05
25 SC
1.73 1.83 1.93 1.99 2.02
PI
0.68 0.69 0.69 0.70 0.70
TC
2.38 2.59 2.80 2.90 2.99
30 SC
1.67 1.78 1.89 1.95 1.98
PI
0.74 0.75 0.75 0.76 0.77
TC
2.20 2.39
2.64
2.77 2.90
35 SC
1.59 1.70
1.85
1.90 1.94
PI
0.79 0.81
0.82
0.83 0.83
TC
2.00 2.18 2.38 2.60 2.74
40 SC
1.50 1.61 1.75 1.80 1.84
PI
0.86 0.87 0.89 0.90 0.90
TC
1.74 1.90 2.09 2.31 2.49
46 SC
1.38 1.48 1.59 1.65 1.69
PI
0.94 0.95 0.97 0.99 1.00
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
SM HGFHHF 1-A.1 GB 5-1
PERFORMANCE DATA & PRESSURE CURVES
5.1.3 Heating Capacity (kW)
ENTERING AIR DB ID COIL(OC)
15 20 25
ENTERING WB
OD COIL(
o
C)
TH Pl TH Pl TH Pl
-10 1.48 0.62 1.42 0.66 1.36 0.70
-7 1.59 0.64 1.53 0.67 1.48 0.71
-2 1.69 0.65 1.63 0.69 1.58 0.72
2 2.05 0.68 1.97 0.72 1.89 0.76
6 2.90 0.73
2.81 0.78
2.72 0.83
10 3.15 0.77 3.07 0.82 2.98 0.88
15 3.40 0.80 3.32 0.86 3.24 0.92
20 3.59 0.83 3.50 0.90 3.40 0.97
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.1.4 Curves
5.1.4.1 Cooling
Suction Pressure VS.Outdoor Temp
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5-2 SM HGFHHF 1-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
5.1.4.2 Heating
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5.2 HGF012 / HHF012 // YGF012
5.2.1 Cooling Capacity (kW)
Entering Air WB/DB ID Coil(oC)
Entering Air DB
OD Coil(
o
C)
Data
15/21 17/24 19/27 21/29 23/32
TC
3.29 3.46 3.57 3.66 3.74
SC
2.17 2.28 2.38 2.45 2.49
20
PI
0.77 0.78 0.78 0.78 0.78
TC
3.11 3.36 3.53 3.64 3.73
SC
2.11 2.24 2.36 2.43 2.47
25
PI
0.84 0.84 0.85 0.85 0.86
TC
2.91 3.17 3.42 3.54 3.65
SC
2.04 2.17 2.31 2.38 2.42
30
PI
0.90 0.91 0.92 0.93 0.94
TC
2.69 2.92
3.22
3.38 3.54
SC
1.94 2.08
2.26
2.32 2.37
35
PI
0.97 0.99
1.00
1.01 1.02
TC
2.45 2.67 2.91 3.18 3.34
SC
1.83 1.97 2.13 2.20 2.25
40
PI
1.05 1.06 1.08 1.10 1.11
TC
2.12 2.32 2.55 2.82 3.04
SC
1.69 1.81 1.95 2.01 2.06
46
PI
1.15 1.16 1.19 1.21 1.22
SM HGFHHF 1-A.1 GB 5-3
PERFORMANCE DATA & PRESSURE CURVES
5-4 SM HGFHHF 1-A.1 GB
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.2.2 Heating Capacity (kW)
ENTERING AIR DB ID COIL(OC)
15 20 25
ENTERING WB
OD COIL(
o
C)
TH Pl TH Pl TH Pl
-10 1.85 0.78 1.78 0.83 1.71 0.87
-7 1.99 0.80 1.92 0.84 1.85 0.89
-2 2.11 0.81 2.04 0.86 1.97 0.90
2 2.57 0.85 2.46 0.90 2.36 0.95
6 3.62 0.91
3.52 0.97
3.39 1.03
10 3.94 0.96 3.83 1.03 3.73 1.10
15 4.25 1.00 4.15 1.08 4.04 1.15
20 4.48 1.03 4.38 1.12 4.25 1.21
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
PERFORMANCE DATA & PRESSURE CURVES
5.1.5 Curves
5.1.5.1 Cooling
Suction Pressure VS.Outdoor Temp
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5.1.5.2 Heating
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
SM HGFHHF 1-A.1 GB
5-5
PERFORMANCE DATA & PRESSURE CURVES
5-6 SM HGFHHF 1-A.1 GB
5.3 HGF018 / HHF018 // YGF018
5.3.1 Cooling Capacity (kW)
Entering Air WB/DB ID Coil(oC)
Entering Air
DB OD Coil(oC)
Data
15/21 17/24 19/27 21/29 23/32
TC
5.40 5.70 5.88 6.02 6.14
20 SC
3.56 3.75 3.91 4.02 4.10
PI
1.26 1.27 1.27 1.28 1.28
TC
5.11 5.52 5.81 5.98 6.13
25 SC
3.47 3.68 3.88 3.99 4.07
PI
1.36 1.37 1.38 1.39 1.40
TC
4.78 5.21 5.63 5.83 6.00
30 SC
3.36 3.57 3.80 3.91 3.98
PI
1.47 1.49 1.51 1.52 1.53
TC
4.43 4.80
5.30
5.57 5.83
35 SC
3.20 3.43
3.71
3.82 3.89
PI
1.59 1.61
1.64
1.65 1.66
TC
4.03 4.38 4.78 5.23 5.50
40 SC
3.01 3.24 3.51 3.62 3.70
PI
1.71 1.74 1.77 1.79 1.81
TC
3.49 3.82 4.20 4.64 5.00
46 SC
2.77 2.97 3.20 3.31 3.39
PI
1.87 1.90 1.94 1.97 1.99
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
PERFORMANCE DATA & PRESSURE CURVES
5.1.3 Heating Capacity (kW)
ENTERING AIR DB ID COIL(OC)
15 20 25
ENTERING WB
OD COIL(oC)
TH Pl TH Pl TH Pl
-10 2.99 1.34 2.88 1.42 2.76 1.49
-7 3.22 1.37 3.11 1.44 2.99 1.52
-2 3.42 1.39 3.31 1.47 3.19 1.55
2 4.16 1.45 3.99 1.54 3.82 1.64
6 5.87 1.56
5.70 1.67
5.50 1.77
10 6.38 1.65 6.21 1.76 6.04 1.88
15 6.90 1.72 6.73 1.85 6.56 1.97
20 7.27 1.77 7.10 1.92 6.90 2.07
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.1.6 Curves
5.1.6.1 Cooling
Suction Pressure VS.Outdoor Temp
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
SM HGFHHF 1-A.1 GB 5-7
PERFORMANCE DATA & PRESSURE CURVES
5.1.6.2 Heating
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
40
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5.4 HGF024 / HHF024 // YGF024
5.4.1 Cooling Capacity (kW)
Entering Air WB/DB ID Coil(oC)
Entering Air
DB OD Coil(oC)
Data
15/21 17/24 19/27 21/29 23/32
TC
6.28 6.62 6.82 6.99 7.14
20 SC
4.14 4.36 4.54 4.67 4.76
PI
1.46 1.47 1.47 1.48 1.48
TC
5.94 6.41 6.74 6.95 7.11
25 SC
4.03 4.28 4.51 4.64 4.72
PI
1.58 1.59 1.60 1.61 1.62
TC
5.55 6.05 6.53 6.77 6.97
30 SC
3.90 4.15 4.41 4.54 4.63
PI
1.70 1.73 1.74 1.76 1.77
TC
5.14 5.58
6.16
6.46 6.77
35 SC
3.71 3.98
4.31
4.43 4.52
PI
1.84 1.87
1.90
1.91 1.93
TC
4.68 5.09 5.55 6.07 6.39
40 SC
3.50 3.76 4.08 4.21 4.29
PI
1.98 2.01 2.05 2.07 2.09
TC
4.06 4.44 4.88 5.39 5.81
46 SC
3.22 3.45 3.72 3.85 3.93
PI
2.17 2.20 2.25 2.28 2.31
5-8 SM HGFHHF 1-A.1 GB
PERFORMANCE DATA & PRESSURE CURVES
SM HGFHHF 1-A.1 GB 5-9
LEGEND
TC – Total Cooling Capacity, kW SC – Sensible Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C) DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
5.4.2 Heating Capacity (kW)
ENTERING AIR DB ID COIL(OC)
15 20 25
ENTERING WB
OD COIL(oC)
TH Pl TH Pl TH Pl
-10 3.41 1.52 3.28 1.62 3.15 1.70
-7 3.67 1.56 3.54 1.64 3.41 1.73
-2 3.90 1.58 3.77 1.67 3.64 1.77
2 4.75 1.65 4.55 1.76 4.36 1.86
6 6.70 1.78
6.50 1.90
6.27 2.02
10 7.28 1.88 7.09 2.00 6.89 2.14
15 7.87 1.96 7.67 2.11 7.48 2.24
20 8.29 2.01 8.09 2.19 7.87 2.36
LEGEND
TH – Total Heating Capacity, kW PI – Power Input, kW WB – Wet Bulb Temp., (
o
C)
DB – Dry Bulb Temp., (
o
C) ID Indoor OU – Outdoor
PERFORMANCE DATA & PRESSURE CURVES
5.1.7 Curves
5.1.7.1 Cooling
Suction Pressure VS.Outdoor Temp
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15 20 25 30 35 40 46
Outdoor Temp.(DB oC )
Suction Pressure (Bar[g])
15/21(WB/DB ºC) 17/24(WB/DB ºC) 19/27(WB/DB ºC) 21/29(WB/DB ºC) 23/32(WB/DB ºC)
5.1.7.2 Heating
Discharge Pressure VS.Outdoor Temp
16
18
20
22
24
26
28
30
32
34
36
38
40
-10-5 0 5 101520
Outdoor Temp.( WB oC )
Discharge Pressure(Bar[g])
25 DB (ºC) 20 DB (ºC) 15 DB (ºC)
5-10 SM HGFHHF 1-A.1 GB
SOUND LEVEL CHARACTERISTICS
6. SOUND LEVEL CHARACTERISTICS CHARACTERISTICS
6.1 Sound Pressure Level - Indoor 6.1 Sound Pressure Level - Indoor
6.2 Sound Pressure Level Spectrum - Indoor (Measured as Figure 1)
HGF007 / HHF007 / HGF009 / HHF009
Cooling
HGF007 / HHF007 / HGF009 / HHF009
Heating
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Ban d Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Sound Pre ssure Level [dB re 20 mPa ]
SM HGFHHF 1-A.1 GB 6-1
SOUND LEVEL CHARACTERISTICS
HGF012 / HHF012
Cooling
HGF012 / HHF012
Heating
Noise spe ctrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Ce nte r Fre quencies [Hz]
Octave Band Soun d Pressur e Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencie s [Hz]
Octave Band Sound P ressure Level [dB re 20 mPa]
HGF018 / HHF018
Cooling
HGF018 / HHF018
Heating
Noise spe ctrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Ce nte r Frequen cies [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octav e Band Sound P ressure Leve l [dB re 20 mPa]
6-2 SM HGFHHF 1-A.1 GB
SOUND LEVEL CHARACTERISTICS
HGF024 / HHF024
Cooling
HGF024 / HHF024
Heating
Noise spectrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Sound P ress ure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Ce nter Freque ncie s [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
SM HGFHHF 1-A.1 GB
6-3
SOUND LEVEL CHARACTERISTICS
6.3 Sound Pressure Level - Outdoor
6.4 Sound Pressure Level Spectrum - Outdoor (Measured as Figure
1)
YGF007 Cooling
YGF007 Heating
Noise spe ctrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Ce nter Freq uencie s [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Ce nter Freque ncie s [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
6-4 SM HGFHHF 1-A.1 GB
SOUND LEVEL CHARACTERISTICS
YGF009 Cooling
YGF009 Heating
Noise spectrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Cente r Frequencies [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
YGF012 Cooling
YGF012 Heating
Noise spectrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencie s [Hz]
Octav e Band Sound P ressure Leve l [dB re 20 mPa]
SM HGFHHF 1-A.1 GB
6-5
SOUND LEVEL CHARACTERISTICS
YGF018 Cooling
YGF018 Heating
Noise spe ctrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Freque ncies [Hz]
Octave Band Sound P ress ure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Freque ncies [Hz]
Octave Band Sound Pressure Leve l [dB re 20 mPa]
YGF024 Cooling
YGF024 Heating
Noise spe ctrum & NC Curv es
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Cente r Frequencies [Hz]
Octave Band Sound P ress ure Level [dB re 20 mPa]
Noise spectrum & NC Curves
NC15
NC20
NC25
NC30
NC35
NC40
NC45
NC50
NC55
NC60
NC65
0
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequencies [Hz]
Octave Band Sound Pressure Level [dB re 20 mPa]
6-6 SM HGFHHF 1-A.1 GB
ELECTRICAL DATA
7. ELECTRICAL DATA
MODEL YGF009 YGF012 YGF018 YGF024
To indoor
Power Supply
1PH-220-240V-50Hz
Max Current, A 5.1A 6.3A 11.1A 11.7
Circuit Breaker, A 10A 16A 25A 25A
Power Supply No. X Cross Section mm
2
3x1.0 3x2.5
Interconnecting Cable No. X Cross Section mm
2
3X1.0+2X0.75 5x2.5
NOTE
Power wiring cord should comply with local laws and electrical regulations requirements.
SM HGFHHF 1-A.1 GB
7-1
WIRING DIAGRAM
8. WIRING DIAGRAM
8.1 HGF009 / HHF009 // YGF009
SM HGFHHF 1-A.1 GB
8-1
WIRING DIAGRAM
8.2 HGF012 / HGF012 // YGF012
8-2 SM HGFHHF 1-A.1 GB
WIRING DIAGRAM
8.3 HGF018 / HHF018 // YGF018
SM HGFHHF 1-A.1 GB 8-3
WIRING DIAGRAM
8.4 HGF024 / HHF024 // YGF024
8-4 SM HGFHHF 1-A.1 GB
REFRIGERATION DIAGRAMS
9. REFRIGERATION DIAGRAMS
SM HGFHHF 1-A.1 GB
9-1
TUBING CONNECTIONS
10. TUBING CONNECTIONS
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. In case the indoor unit is installed above the outdoor, no
trap is required.
SM HGFHHF 1-A.1 GB 10-1
CONTROL SYSTEM
11. CONTROL SYSTEM
11.1 Electronic Control
11.1.1 Abbreviations
AC -Alternate Current A/C - Air-Conditioner ANY - ON or OFF status COMP - Compressor CPU - Central Processing Unit E2PROM, EEP - Erase Enable Programmable Read Only Memory H/W - Hardware ICT - Indoor Coil Temperature sensor IF, IFAN - Indoor Fan IR - Infra Red Max - Maximum Min - Minimum min - Minute (time) NA - Not Applicable OCT - Outdoor Coil Temperature sensor OF, OFAN - Outdoor Fan OPER - Operate Para. - Paragraph RAT - Return Air Temperature (RT1) sensor RC - Reverse Cycle (Heat Pump) R/C - Remote Control RCT - Remote Control Temperature RH - Resistance Heater RV - Reversing Valve SB, STBY - Stand-By Sec - Second (time) Sect - Section SH - Supplementary Heater SPT - Set Point Temperature ST - Standard (a Model with Cooling Only) S/W - Software TEMP - Temperature W/O - Without
SM HGFHHF 1-A.1 GB 11-1
CONTROL SYSTEM
11-2 SM HGFHHF 1-A.1 GB
11.1.2 System Operation Concept
11.1.3 Compressor operation
For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting except during outdoor deicing.
Whenever COMP starts, it will not stop in 6 min even the RAT is changed.
* For the units with memory function, the 1
st
time of Power ON, there will be no 3 min delay if the
previous stage of unit is OFF.
11.1.4 Indoor Fan Control
8 Indoor fan speeds are determined for each model. 4 speeds for COOL modes and 4 speeds for HEAT mode.
Unit Model Mode Turbo(Super high) High Medium Low
Cooling 1390 1280 1180 1080
09
Heating 1350 1250 1140 1040 Cooling 1350 1250 1100 950
12
Heating 1350 1250 1100 950 Cooling 1350 1200 1050 900 18 Heating 1350 1200 1050 900 Cooling 1350 1200 1050 900 24 Heating 1420 1250 1150 900
In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed.
In AutoFan user setting, fan speed will be adjusted automatically according to the difference between actual room temperature(RAT) and user set point temperature(SPT).
Indoor Fan speed High Medium Low
Cooling >=2 (0,2) <=0
RAT-SPT
Heating <=1 (1,3) >=3
During Auto Fan operating, one speed should keep at least 210sec operating before switching to other speeds. In DRY mode, the automatic fan speed is forced to be low.
11.1.4.1 Turbo Speed
In COOL and HEAT mode (not available in AUTO, DRY, FAN mode), press the Turbo button, the super high fan speed is selected on Remote control and the indoor fan rotates at super high speed.
11.1.5 Outdoor Fan Control
CONTROL SYSTEM
SM HGFHHF 1-A.1 GB 11-3
11.1.5.1 OFAN Speed Type
The OFAN motor is a one speed AC motor and controlled by the relay on outdoor controller.
11.1.5.2 General rules
1. The OFAN is ON when COMP ON during Cool, Dry and Heat Mode.
2. When the unit is off by remote control, in safety stops and stop after reaching to the temperature point, the outdoor fan stops.
3. Outdoor fan OFF will compressor when COMP is OFF during cooling and heating mode.
11.1.6 Refrigerant control
Capillary is used in each mode.
11.1.7 Reversing Valve (RV) Control
Reversing valve is on in heat mode. Switching of RV state is done only after COMP is off for over 2 minutes.
11.2 Fan Mode
In this mode, the IFAN may run at high,medium,low and automatic speed. The COMP, OFAN and RV will be OFF. In this mode, the range of setting temperature is 16~30C
11.3 Cool Mode
If RATSPT+1, the unit starts cooling operation. In this case, the COMP and OFAN will operate and the IFAN will run at the setting speed. If RATSPT-1, the COMP and OFAN will stop operating, while the IFAN will run at the setting speed. If SPT-1<RATSPT+1, the unit will maintain the previous status.
In AutoFan user setting, fan speed will be adjusted automatically according to the SPT and RAT, refer to 11.1.4
11.4 Heat Mode
If RATSPT+2, the unit will operate in heating mode. The COMP, OFAN and RV will operate and the IFAN will delay 3min to start at the latest If SPT+2≤RAT≤SPT+4,the unit will maintain the previous status. If RATSPT+4, the COMP and OFAN will stop and the IFAN will blow for 60s at setting speed. During this period, the fan speed cannot be switched.
11.4.1 Indoor Fan Control in Heat Mode
CONTROL SYSTEM
IFAN speed depends on the indoor coil temperature
Anti-cold air function
When starting the heating mode, anti-cold air function will be activated and IFAN can run at low speed or stop running. This function will terminate after the unit runs for 2min or the ICT reaches 40 degree.
Residual heat blowing function
During heating, when the stopping condition for the COMP is reached, the COMP and OFAN stop running while the louver moves to position L. The IFAN will stop after running for 60s at setting speed.
11.5 Auto Cool/Heat Mode
In AUTO mode, the system selects the running mode (COOL/HEAT/FAN) automatically according to the room temperature. The display shows the actual running mode and setting temperature. There will be 30s delay for mode conversion.
1. When RAT≥25 degree, the cooling mode is selected.
2. When RAT20 degree, the unit runs in heating mode
3. When 20 degree <RAT< 25 degree, upon initial startup, the unit will enter auto mode and run in automatic fan mode. If the other mode changes into auto mode, the previous running mode will remain.
11.6 Dry Mode
If RATSPT+2, the unit starts cooling operation. In this case, the COMP and OFAN will operate and the IFAN will run at the low speed. If RATSPT-2, the COMP and OFAN will stop. While IFAN will run at low speed. If SPT-2<RAT≤SPT+2, While IFAN will run at low speed. COMP and OFAN will operation in 6 min ON and 4 min OFF in cycling. In this mode, the RV will be OFF and the temperature setting range is 16~30.
11-4 SM HGFHHF 1-A.1 GB
11.7 Louver Control
After power on, the up and down swing louver will automatically open and then close completely. In heating mode, if the swing function is not set, the up and down louver will rotate to maximum in clockwise direction. Then it will rotate to position D. Under other states, the upper and lower air deflector will rotate to level L. If the swing function is set when starting the unit, the louver will swing between Position L and D. there are 7 states for louver: in position L, A, B, C, D, and swing between L and D, stop in any place between Position L and position D. When the unit is turned
CONTROL SYSTEM
SM HGFHHF 1-A.1 GB 11-5
off, the air deflector will stay in position 0.
The swing is available only when the swing function is set and the indoor fan is running. The louver swing can also be set between L and B, between A and C, between B and D.
11.8 Protections
11.8.1 Indoor Coil Defrost Protection
During Cool Mode/Dry Mode, this protection prevents freezing of the indoor heat exchanger. When ICT <= 0 C for continuous 3 mins, COMP and OFAN will stop and IFAN will run at its setting speeds. The system will resume its previous status if the protection is cleared and COMP OFF time is 3 min. (COMP OFF time will be 4 min during the 6 min ON and 4 min OFF cycling during Dry Mode)
11.8.2 Indoor Coil over Heating Protection
During Heat Mode, this protection prevents abnormal high pressure. When ICT reaches 58C, OFAN will stop operating and resume operating if the ICT go to normal.
11.8.3 Over Current Protection
Detect an input current by the CT during the COMP is running. If the current is high than 22A for continuous 3 sec, COMP and OFAN will stop, IFAN will run at setting speed. The system will resume its previous status if the protection is cleared and COMP stops for 3 min.
If the unit stops as such protection for 6 times,(the counter will be cleared after the compressor has run for 6min), it cannot resume running automatically and display malfunction, it can resume by pressing ON/OFF.
11.8.4 Outdoor Coil Deicing Protection
This protection is for Heat Pump Only This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more than its setting values when finishing the deicing protection. In the deicing protection, IFAN is forced OFF.
11.8.4.1 Deicing Starting Conditions
The starting conditions must be made with the room air temperature (RAT) and indoor coil temperature (ICT) and the trend of changing. Under the conditions that the system is in heating operation, after the time for defrosting is judged to be satisfied, the deicing operation will start.
CONTROL SYSTEM
The minimum operating time of heating mode before deicing: a) 40 min after 1
st
time of power on
b) 5 min after system is STBY by RC or temperature condition.
11.8.4.2 Deicing Protection Procedure
1 Start to defrost: COMP stops and starts up 55S later 2 Start to defrost: Outdoor fan will stop after COMP stops for 50S. 3 Defrosting finish: COMP stops and starts up 55S later. 4 Defrosting finish: Outdoor fan will start up when the COMP is stopping.
11.8.4.3 Exiting Deicing
The deicing operation depends:
1. RAT & ICT and the trend of changing
2. The continuous running time of deicing reaches to 12min.
11.9 Indoor Unit Controllers and Indicators
The following shows the indicators of the indoor unit (Layout of display in HGF/HHF has some difference.)
STBY/RUN INDICATOR
Lights up in RED in when the Air Conditioner is connected to power and the mode is STBY.
Lights up in GREEN when the when the unit is turned on.
COOL INDICATOR
FAN INDICATOR
DRY INDICATOR
HEAT INDICATOR
Lights up during specified operation mode (COOL/DRY/HEAT).
2* 7 segments display
1. In normal situation, the setting temperature is displayed.
2. Shows room temperature when receiving the
corresponding demand from controller. When received effective RC command, setting temperature will be shown for 5 sec, and then go back to room temperature display.
3. Shows the fault code when there is a fault(Refer to 12.1.3)
11-6 SM HGFHHF 1-A.1 GB
CONTROL SYSTEM
11.10 Characteristics of sensor
11.10.1
RAT/OAT
RAT/OAT R-T chart
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
-20-15-10-5 0 5 10152025303540455055606570
Temperature(C)
Resistance(Kohm)
11.10.2 ICT/OCT
ICT/OCT R-T Chart
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
-20-15-10-5 0 5 10152025303540455055606570
Temperature(C)
Resistance(Kohm)
SM HGFHHF 1-A.1 GB
11-7
CONTROL SYSTEM
11.10.3 CTT
CTT R-T Chart
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
Temperature(C)
Resistance(Kohm)
11-8 SM HGFHHF 1-A.1 GB
TROUBLESHOOTING
12. TROUBLESHOOTING
12.1 ELECTRICAL & CONTROL TROUBLESHOOTING
12.1.1
Precautions before Performing Inspection or Repair
Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop from high attitude.
* Static maintenance is the maintenance during de-energization of the air conditioner. For static maintenance, make sure that the unit is de-energized and the plug is disconnected.
*Dynamic maintenance is the maintenance during energization of the unit. Before dynamic maintenance, check the electricity and ensure that there is ground wire on the site. Check if there is electricity on the housing and connection copper pipe of the air conditioner with voltage tester. After ensure insulation place and the safety, the maintenance can be performed.
Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power. At time such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position. Normally, diagnose troubles according to the trouble diagnosis procedure as described below.(Refer to the checkpoints in servicing written on the wiring diagrams attached to the indoor/outdoor units.)
12.1.2 Confirmation
12.1.2.1 Confirmation of Power Supply Confirm that the power breaker operates(ON) normally;
12.1.2.2 Confirmation of Power Voltage Confirm that power voltage is AC220~240V +/­10%. If power voltage is not in this range, the unit may not operate normally.
SM HGFHHF 1-A.1 GB
12-1
TROUBLESHOOTING
12-2 SM HGFHHF 1-A.1 GB
12.1.3 Judgment by Indoor/Outdoor Unit Diagnostics
If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be
directly displayed though indoor display. In other situations, error code can be displayed by pressing
LIGHT button 6 times within 4s.
LEDs blinking
(0.5s ON and 0.5s OFF)
Fault description
2* 7
segments
RUN COOL HEAT
Possible Reason
No feedback of indoor motor H6 11
1. IFAN motor damaged
2. IFAN motor blocked
3. IDU PCB problem
Malfunction protection of jumper cap
C5 15
Poor connection of the jumper on indoor PCB.
Zero-crossing protection (IDU)
U8 17
1. IFAN motor damaged
2. Zero-crossing circuit damaged on IDU PCB
RAT failure F1 1
ICT failure F2 2
1. Sensor connection is not good
2. Senor was broken or damaged (Refer to Sect 14 to check the sensor value)
3. PCB temperature detection circuit has problem
12.2 Simple procedures for checking the Main Parts
12.2.1 Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range, abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and look for broken or loosed cable lugs or wiring mistake(s).
12.2.2 Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again.
12.2.3 Checking the Outdoor Fan Motor.
Run the unit in Cool/Heat/Dry mode (where the OFAN speed is high) Check the voltage between two terminals( N and 5 ), normal voltage is 220-240VAC.
12.2.4 Checking the Compressor.
The compressor is rotary compressor with single-phase power input. It includes two windings of main and auxiliary. Check the resistance of terminal R and C and resistance of terminal S and C. If the windings is open or short, compressor should be replaced.
Pay attention, for the wiring connections, please refer to the wiring diagram and have double confirmation before checking the compressor.
12.2.5 Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two terminals( N and 4 ), normal voltage is 220-240VAC.
EXPLODED VIEW & SPARE PART LIST
13. EXPLODED VIEW & SPARE PART LIST
13.1 Exploded view of indoor unit: HGF009/HHF009
SM HGFHHF 1-A.1 GB
13-1
EXPLODED VIEW & SPARE PART LIST
13-2 SM HGFHHF 1-A.1 GB
13.2 Spare part list of indoor Unit: HGF009
NO. Part Code Part Description qty 1 22202135 Rear Case assy 1 2 26112201 Motor Press Plate 1 3 26152022 Bearing cushion rubber base 1 4 10352034 Cross Flow Fan 1 5 26112202 Helicoid tongue 1 6 10542704 Axile Bush 1 7 10582070 Crank 1 8 1521210801 Motor MP24AA 1 9 0523001408 Drainage hose 1 10 10512113 Air Louver 1 1 11 10512114 Swing Louver 1 12 76712012 Water Tray Glue Plug 1 13 76512051 O-Gasket sub-assy of Bearing 1 14 15012115 Motor 1 15 26112199 Pipe Clamp 1 16 10512162 Guide Louver 1 17 10542008 Axile Bush (guide louver) 1 18 0100257702 Evaporator Assy 1 19 2020227302 Electric Box Assy 1 20 30135353 Main Board 1 21 390000453 Ambient Temperature Sensor 1 22 390000591 Tube Sensor (20K black) 1 23 None Relay 0 24 None Relay 0 25 None Relay 0 26 46010055 Fuse 1 27 30565127 Display Board 1 28 4202300114 Jumper 1 29 20112091 Electric Box 1 30 42010262 Terminal Board 1 31 20122114 Electric Box Cover 1 32 01592080 Shield box (electric box) 1 33 20122075 Electric Box Cover2 1 34 11122095 Filter Sub-Assy 2 35 24252016 Screw Cover 3 36 20012833 Front Panel Assy 1 37 None Decorate Piece 0 38 01252231 Wall Mounting Frame 1 39 400220113 Power cord Sub-Assy 1 40 40020540 Connecting Cable 1 41 40020536 Connecting Cable 1 42 30510065 Remote controller YX1F 1 43 20012396 Front Case 1
111220071 Photocatalysis Filter 1 11012025 Air Cleaner 1
EXPLODED VIEW & SPARE PART LIST
SM HGFHHF 1-A.1 GB 13-3
13.3 Spare part list of indoor Unit: HHF009
NO. Part Code Part Description qty 1 2220213501 Rear Case assy 1 2 26112201 Motor Press Plate 1 3 26152022 Bearing cushion rubber base 1 4 10352034 Cross Flow Fan 1 5 26112202 Helicoid tongue 1 6 10542704 Axile Bush 1 7 10582070 Crank 1 8 1521210801 Motor MP24AA 1 9 0523001408 Drainage hose 1 10 10512113 Air Louver 1 1 11 10512114 Swing Louver 1 12 76712012 Water Tray Glue Plug 1 13 76512051 O-Gasket sub-assy of Bearing 1 14 15012115 Motor 1 15 26112199 Pipe Clamp 1 16 10512162 Guide Louver 1 17 10542008 Axile Bush (guide louver) 1 18 0100257702 Evaporator Assy 1 19 20202933 Electric Box Assy 1 20 30135353 Main Board 1 21 390000453 Ambient Temperature Sensor 1 22 390000591 Tube Sensor (20K black) 1 23 None Relay 0 24 None Relay 0 25 None Relay 0 26 46010055 Fuse 1 27 30565156 Display Board 1 28 4202300114 Jumper 1 29 20112091 Electric Box 1 30 42010262 Terminal Board 1 31 20122114 Electric Box Cover 1 32 01592080 Shield box (electric box) 1 33 20122075 Electric Box Cover2 1 34 11122095 Filter Sub-Assy 2 35 24252016 Screw Cover 3 36 20012879 Front Panel Assy 1 37 None Decorative Strip 0 38 01252231 Wall Mounting Frame 1 39 400220113 Power cord Sub-Assy 1 40 40020540 Connecting Cable 1 41 40020536 Connecting Cable 1 42 30510065 Remote controller YX1F 1 43 2001239601 Front Case 1
11012025 Air Cleaner 1 111220071 Photocatalysis Filter 1
EXPLODED VIEW & SPARE PART LIST
13.4 Exploded view of indoor unit: HGF012/HHF012
13-4 SM HGFHHF 1-A.1 GB
EXPLODED VIEW & SPARE PART LIST
SM HGFHHF 1-A.1 GB 13-5
13.5 Spare part list of indoor Unit: HGF012
NO. Part Code Part Description qty 1 01252015 Wall-Mounting Frame 1 2 2220210101 Rear Case assy 1 3 10542704 Axile Bush 1 4 10582070 Crank 1 5 10352018 Cross Flow Fan 1 6 76512051 O-Gasket sub-assy of Bearing 1 7 76512203 O-Gasket of Cross Fan Bearing 1 8 26152022 Bearing cushion rubber base 1 9 26112162 Helicoid tongue 1 10 10512114 Swing Louver 1 11 10512113 Air Louver 1 1 12 0100255213 Evaporator Assy 1 13 24212090 Evaporator Support 1 14 0523001406 Drainage hose 1 15 10512111 Guide Louver1 1 16 10542008 Axile Bush (guide louver) 1 17 20012179 Front Case 1 18 24252016 Screw Cover 1 19 11122081 Filter Sub-Assy 2 20 20012834 Front Panel Assy 1 21 none Receiver Window 0 22 30565127 Display Board 1 23 30510065 Remote controller YX1F 1 24 20122075 Electric Box Cover2 1 25 26112160 Motor Clamp 1 26 15012115 Motor 1 27 42010262 Terminal Board 1 28 20122103 Electric Box Cover1 1 29 0159207301 Shield cover of Electric Box sub-assy 1 30 2020238803 Electric Box Assy 1 31 20112082 Electric Box 1 32 30135283 Main Board 1 33 43110236 Transformer 41X26.5G 1 34 4202300128 Jumping Connector 1 35 76712012 Water Tray Glue Plug 1 36 1521210801 Motor MP24AA 1 37 26112164 Pipe Clamp 1 38 4002046413 Power Cord 1 39 40020540 Connecting Cable 1
40020536 Connecting Cable 1 390000591 Tube Sensor (20K black) 1 42020063 Sensor Insert 1 390000453 Ambient Temperature Sensor 1 11012025 Air Cleaner 1 111220071 Photocatalysis Filter 1
EXPLODED VIEW & SPARE PART LIST
13-6 SM HGFHHF 1-A.1 GB
13.6 Spare part list of indoor Unit: HHF012
NO. Part Code Part Description qty 1 01252015 Wall-Mounting Frame 1 2 2220210101 Rear Case assy 1 3 10542704 Axile Bush 1 4 10582070 Crank 1 5 10352018 Cross Flow Fan 1 6 76512051 O-Gasket sub-assy of Bearing 1 7 76512203 O-Gasket of Cross Fan Bearing 1 8 26152022 Bearing cushion rubber base 1 9 26112162 Helicoid tongue 1 10 10512114 Swing Louver 1 11 10512113 Air Louver 1 1 12 0100255213 Evaporator Assy 1 13 24212090 Evaporator Support 1 14 0523001406 Drainage hose 1 15 10512111 Guide Louver1 1 16 10542008 Axile Bush (guide louver) 1 17 20012120 Front Case 1 18 24252016 Screw Cover 1 19 11122081 Filter Sub-Assy 2 20 20012880 Front Panel Assy 1 21 none Receiver Window 0 22 30565156 Display Board 1 23 30510065 Remote controller YX1F 1 24 20122075 Electric Box Cover2 1 25 26112160 Motor Clamp 1 26 15012115 Motor 1 27 42010262 Terminal Board 1 28 20122103 Electric Box Cover1 1 29 0159207301 Shield cover of Electric Box sub-assy 1 30 2020226601 Electric Box Assy 1 31 20112082 Electric Box 1 32 30135283 Main Board 1 33 43110236 Transformer 41X26.5G 1 34 4202300128 Jumping Connector 1 35 76712012 Water Tray Glue Plug 1 36 1521210801 Motor MP24AA 1 37 26112164 Pipe Clamp 1 38 4002046413 Power Cord 1 39 40020536 Connecting Cable 0
40020540 Connecting Cable 1 390000591 Tube Sensor (20K black) 1 42020063 Sensor Insert 1 390000453 Ambient Temperature Sensor 1
EXPLODED VIEW & SPARE PART LIST
13.7 Exploded view of indoor unit: HGF018
SM HGFHHF 1-A.1 GB
13-7
EXPLODED VIEW & SPARE PART LIST
13-8 SM HGFHHF 1-A.1 GB
13.8 Spare part list of indoor Unit: HGF018
NO. Part Code Part Description qty
1 2001246601_K46462 Front Panel Assy 1
2 1112208901 Filter Sub-assy 2
3 20012766 Front Case Sub-Assy 1
4 24252016 Screw Cover 3
5 30565127 Display Board 1
6 76712012 Water Tray Glue Plug 1
7 01002590 Evaporator Assy 1
8 10352019 Cross Flow Fan 1
9 26152022 Bearing cushion rubber base 1
10 12312214 Rear Case assy 1
11 01252218 Wall Mounting Frame 1
12 26112238 Helicoid tongue 1
13 10512116 Air Louver 1 1
14 10542008 Axile Bush (guide louver) 1
15 10512037 Left Axile Bush 1
16 10512115 Guide Louver 1
17 10582070 Crank 1
18 15012086 Step Motor 1
19 10512117 Air Louver 2 1
20 05230014 Drain Pipe 1
21 26112164 Pipe Clamp 1
22 15012116 Motor 1
23 26112178 Motor Press Plate 1
24 20202703 Electric Box Assy 1
25 30135228 Mian board 1
26 43110237 Transformer 57X25C 1
27 42010268 Terminal board 1
28 20122128 Electric Box Cover1 1
29 01592092 Shield cover of Electric Box 1
30 20112081 Electric Box cover 2 1
31 390000591 Tube Sensor (20K black) 1
32 390000451 Ambient Temperature Sensor 1
33 30510065 Remote controller YX1F 1
34 400205402 Connecting Cable 0
35 4002053603 Connecting Cable 0
36 none Power Cord 0
11012025 Air Cleaner 1 4202300109 Jumper 1 20122122 Display Cover 1 24212100 Evaporator Support 1 76512051 O-Gasket sub-assy of Bearing 1 111220071 Photocatalysis Filter 1
EXPLODED VIEW & SPARE PART LIST
13.9 Exploded view of indoor unit: HHF018, HHF024
SM HGFHHF 1-A.1 GB
13-9
EXPLODED VIEW & SPARE PART LIST
13-10 SM HGFHHF 1-A.1 GB
13.10 Spare part list of indoor Unit: HHF018
NO. Part Code Part Description qty 1 2001228601 Front Panel Assy 1 2 1112208901 Filter Sub-assy 2 3 20012288 Front Case Sub-Assy 1 4 24252016 Screw Cover 3 5 30565156 Display Board 1 6 76712012 Water Tray Glue Plug 1 7 20112081 Electric Box cover 2 1 8 10352019 Cross Flow Fan 1 9 26152022 Bearing cushion rubber base 1 10 12312214 Rear Case assy 1 11 01252218 Wall Mounting Frame 1 12 26112238 Helicoid tongue 1 13 10512116 Air Louver 1 1 14 10542008 Axile Bush (guide louver) 1 15 10512037 Left Axile Bush 1 16 10512115 Guide Louver 1 17 10582070 Crank 1 18 15012086 Step Motor 1 19 10512117 Air Louver 2 1 20 05230014 Drain Pipe 1 21 26112164 Pipe Clamp 1 22 15012116 Motor 1 23 26112178 Motor Press Plate 1 24 20112108 Electric Box 1 25 30135228 Mian board 1 26 43110237 Transformer 57X25C 1 27 42010268 Terminal board 1 28 20202914 Electric Box Assy 1 29 01592092 Shield cover of Electric Box 1 30 20122128 Electric Box Cover1 1 31 390000591 Tube Sensor (20K black) 1 32 390000451 Ambient Temperature Sensor 1 33 30510065 Remote controller YX1F 1 34 400205402 Connecting Cable 0 35 4002053603 Connecting Cable 0 36 4002048716 Power Cord 1
76512203 O-Gasket of Cross Fan Bearing 1 4202300109 Jumper 1 01002590 Evaporator Assy 1 24212100 Evaporator Support 1 76512051 O-Gasket sub-assy of Bearing 1 26112228 Baffle Plate 1 49010104 Magnetic Ring 1 42020063 Sensor Insert 1
EXPLODED VIEW & SPARE PART LIST
SM HGFHHF 1-A.1 GB 13-11
13.11 Spare part list of indoor Unit: HHF024
NO. Part Code Part Description qty 1 2001228601 Front Panel Assy 1 2 1112208901 Filter Sub-assy 2 3 20012288 Front Case Sub-Assy 1 4 24252016 Screw Cover 3 5 30565156 Display Board 1 6 76712012 Water Tray Glue Plug 1 7 20112081 Electric Box cover 2 1 8 10352019 Cross Flow Fan 1 9 26152022 Bearing cushion rubber base 1 10 12312214 Rear Case assy 1 11 01252218 Wall Mounting Frame 1 12 26112238 Helicoid tongue 1 13 10512116 Air Louver 1 1 14 10542008 Axile Bush (guide louver) 1 15 10512037 Left Axile Bush 1 16 10512115 Guide Louver 1 17 10582070 Crank 1 18 15012086 Step Motor 1 19 10512117 Air Louver 2 1 20 05230014 Drain Pipe 1 21 26112164 Pipe Clamp 1 22 15012116 Motor 1 23 26112178 Motor Press Plate 1 24 20112108 Electric Box 1 25 30135295 Main Board 1 26 43110237 Transformer 57X25C 1 27 4201026201 Terminal Board 1 28 20202909 Electric Box Assy 1 29 01592092 Shield cover of Electric Box 1 30 20122128 Electric Box Cover1 1 31 390000591 Tube Sensor (20K black) 1 32 390000451 Ambient Temperature Sensor 1 33 30510065 Remote controller YX1F 1 34 400205382 Connecting Cable 0 35 4002053603 Connecting Cable 1 36 400203253 Power Wire 1
4202300109 Jumper 1 76512203 O-Gasket of Cross Fan Bearing 1 42020063 Sensor Insert 1 76512051 O-Gasket sub-assy of Bearing 1 49010104 Magnetic Ring 1 11012025 Air Cleaner 1 01002590 Evaporator Assy 1 24212100 Evaporator Support 1 26112228 Baffle Plate 1
EXPLODED VIEW & SPARE PART LIST
13.12 Exploded view of indoor unit: HGF024
13-12 SM HGFHHF 1-A.1 GB
EXPLODED VIEW & SPARE PART LIST
SM HGFHHF 1-A.1 GB 13-13
13.13 Spare part list of indoor Unit: HGF024
NO. Part Code Part Description
qty
1 2001246601_K46462 Front Panel Assy 1 2 1112208901 Filter Sub-assy 2 3 12312214 Rear Case assy 1 4 24252016 Screw Cover 3 5 30565127 Display Board 1 6 01002590 Evaporator Assy 1 7 10352019 Cross Flow Fan 1 8 26152022 Bearing cushion rubber base 1 9 20012766 Front Case Sub-Assy 1 10 01252218 Wall Mounting Frame 1 11 26112238 Helicoid tongue 1 12 10512116 Air Louver 1 1 13 10542008 Axile Bush (guide louver) 1 14 10512037 Left Axile Bush 1 15 10512115 Guide Louver 1 16 10582070 Crank 1 17 15012086 Step Motor 1 18 10512117 Air Louver 2 1 19 05230014 Drain Pipe 1 20 26112164 Pipe Clamp 1 21 15012116 Motor 1 22 26112178 Motor Press Plate 1 23 20202720 Electric Box Assy 1 24 30135295 Main Board 1 25 43110237 Transformer 57X25C 1 26 4201026201 Terminal Board 1 27 20122128 Electric Box Cover1 1 28 01592092 Shield cover of Electric Box 1 29 20112081 Electric Box cover 2 1 30 390000591 Tube Sensor (20K black) 1 31 390000451 Ambient Temperature Sensor 1 32 30510065 Remote controller YX1F 1 33 4002053603 Connecting Cable 1 34 400203253 Power Wire 1 35 76712012 Water Tray Glue Plug 1 36 400205382 Connecting Cable 1
20122122 Display Cover 1 24212100 Evaporator Support 1 76512051 O-Gasket sub-assy of Bearing 1 20012767 Front Case 1 76512203 O-Gasket of Cross Fan Bearing 1 49010252 Radiator 1 33010043 Capacitor 1 22202158 Rear Case 1 26112228 Baffle Plate 1 111220071 Photocatalysis Filter 1 11012025 Air Cleaner 1 4202300109 Jumper 1 76512210 Fan Bearing 1
EXPLODED VIEW & SPARE PART LIST
13.14 Exploded view of outdoor unit: YGF009YGF012
13-14 SM HGFHHF 1-A.1 GB
EXPLODED VIEW & SPARE PART LIST
SM HGFHHF 1-A.1 GB 13-15
13.15 Spare part list of outdoor Unit: YGF009
NO. Part Code Part Description qty
1 22413007 Grille 1
2 01533029P Front panel 1
3 26233100 Small Handle 1
4 01203799P Chassis Sub-assy 1
5 01233066 Isolation Sheet 1
6 10333427 Axial Flow Fan 1
7 150130671 Fan Motor 1
8 0111347201 Condenser Assy 1
9 01703052 Motor Support Assy 1
10 01253031 Top Cover Sub-Assy 1
11 1112320501 Grill 1
12 0306301701 Capillary Sub-Assy 1
13 02603240 Electric Box Assy 1
14 42010265 Terminal Board 1
15 33010026 Capacitor CBB61 2.5uF/450V 1
16 01303183 Right Side Plate Sub-Assy 1
17 26233433 Big Handle 1
18 0170308901P Valve Support 1
19 07100003 Cut-off Valve (1/4) 1
20 07100005 Cut-off Valve (3/8) 1
21 40040007_GY1 Terminal Board 1
22 33000018 Capacitor 1
23 00103203 Compressor and fittings 1
24 0312328601 4-way Valve Assy 1
0130304802 Right Side Plate 1 430004022 4-Way Valve 1 430004002 4-way Valve Accessary 1 06123401 Drainage Connecter 1 00183012 Overload Protector 1 76710217 Compressor Gasket AD7070837 3
EXPLODED VIEW & SPARE PART LIST
13-16 SM HGFHHF 1-A.1 GB
13.16 Spare part list of outdoor Unit: YGF012
NO. Part Code Part Description qty
1 22413007 Grille 1
2 01533029P Front panel 1
3 26233100 Small Handle 1
4 01203767P Chassis Sub-assy 1
5 01233066 Isolation Sheet 1
6 10333427 Axial Flow Fan 1
7 150130676 Fan Motor 1
8 01113449 Condenser Assy 1
9 01703052 Motor Support Assy 1
10 01253031 Top Cover Sub-Assy 1
11 1112320501 Grill 1
12 03103997 Capillary Sub-Assy 1
13 01403947 Electric Plate 1
14 42010265 Terminal Board 1
15 33010743 Capacitor CBB65 1
16 01303183 Right Side Plate Sub-Assy 1
17 26233433 Big Handle 1
18 0170308901P Valve Support 1
19 07100006 Cut-off Valve 1
20 07100003 Cut-off Valve (1/4) 1
21 42011147 Terminal Board 1
22 33010026 Capacitor CBB61 2.5uF/450V 1
23 00103281 Compressor and fittings 1
24 03123592 03123592 1
430004002 4-way Valve Accessary 1 0130304802 Right Side Plate 1 06123401 Drainage Connecter 1 430004032 4-way Valve 1
EXPLODED VIEW & SPARE PART LIST
13.17 Exploded view of outdoor unit: YGF018
SM HGFHHF 1-A.1 GB
13-17
EXPLODED VIEW & SPARE PART LIST
13-18 SM HGFHHF 1-A.1 GB
13.18 Spare part list of outdoor Unit: YGF018
NO. Part Code Part Description qty
1 26235401 Small Handle 1
2 10335257 Axial-flow Fan 1
3 15015057 Fan Motor 1
4 0170510702 Motor Support Sub-Assy 1
5 01113238 Condenser Assy 1
6 07130213 Gas Valve Assy 1
7 01255001 Top Cover 1
8 01475004 Rear grill 1
9 06813401 Choke Plug 3
10 33000039 Capacitor 1
11 02603068 Electric Box Assy 1
12 33010026 Capacitor CBB61 2.5uF/450V 1
13 42011147 Terminal Board 1
14 42010265 Terminal Board 1
15 03023870 4-way Valve Assy 1
16 430004002 4-way Valve Accessary 1
17 03103780 Capillary Sub-Assy 1
18 01305013 Right Side Plate 1
19 26235254 Handle 1
20 07100003 Cut-off Valve (1/4) 1
21 01713075 Valve Support Sub-Assy 1
22 00103007 Compressor and Fittings 1
23 01233035 Clapboard Sub-Assy 1
24 06123401 Drainage Connecter 1
25 0120362602P Chassis 1
26 01305015 Front Side Plate 1
27 22415001 Front Grill 1
76710202 Compressor Gasket 4CYC00008 3 430004032 4-way Valve 1 07210022 Filter 1 01705003 Motor Support 1 07245007 Silencer Mounting 1 00180252 Overload Protector 1
EXPLODED VIEW & SPARE PART LIST
13.19 Exploded view of outdoor unit: YGF024
SM HGFHHF 1-A.1 GB
13-19
EXPLODED VIEW & SPARE PART LIST
13-20 SM HGFHHF 1-A.1 GB
13.20 Spare part list of outdoor Unit: YGF024
NO. Part Code Part Description qty
1 26235401 Small Handle 1
2 10335257 Axial-flow Fan 1
3 15015057 Fan Motor 1
4 0170305901 Motor Support Sub-Assy 1
5 01113396 Condenser Assy 1
6 01255001 Top Cover 1
7 0147500401 Rear Grill 1
8 02603219 Electric Box Assy 1
9 33000039 Capacitor 1
10 33010027 Capacitor CBB611A(3uF/450V) 1
11 42011147 Terminal Board 1
12 420101941 Terminal Board 1
13 03123248 4-way Valve Assy 1
14 00180157 Overload Protector 1
15 03103946 Capillary Sub-Assy 1
16 01305013 Right Side Plate 1
17 26235254 Handle 1
18 07130213 Gas Valve Assy 1
19 06813401 Choke Plug 3
20 01713075 Valve Support Sub-Assy 1
21 430004002 4-way Valve Accessary 1
22 00103702 Compressor and Fittings 1
23 01233035 Clapboard Sub-Assy 1
24 06123401 Drainage Connecter 1
25 0120362602P Chassis 1
26 01305015 Front Side Plate 1
27 22415001 Front Grill 1
02141375 Capacitor Clamp 1 07245007 Silencer Mounting 1 44010245 AC Contactor CJX9B-25S/D 1 430004032 4-way Valve 1 76710202 Compressor Gasket 4CYC00008 3 07100003 Cut-off Valve (1/4) 1
APPENDIX
SM HGFHHF 1-A.1 GB 14-1
14. APPEDDIX
APPENDIX