Airwell AWSI-CFV009-N11, AWSI-CFV024-N11, AWSI-CFV016-N11, AWSI-CFV018-N11, AWSI-CFV028-N11 Operation & Installation Manual

...
Indoor Unit Operation & Installation Manual
AWSI-CFV007-N11
AWSI-CFV009-N11
AWSI-CFV012-N11
AWSI-CFV016-N11
AWSI-CFV018-N11
AWSI-CFV024-N11
AWSI-CFV028-N11
AWSI-CFV030-N11
AWSI-CFV038-N11
AWSI-CFV048-N11
AWSI-CFV060-N11
No. 0150524399
• Please read this manual carefully before using.
• Keep this operation manual for future reference.
User Manual
The multiple air conditioning systems adopt the consistent running mode, by which, all indoor units can only be heating or refrigerating operation at the same time.
To protect the compressor, the air conditioning unit should be powered on for over 12 hours before using it. All indoor units of the same refrigerating system should use the unied power switch to ensure that all indoor units are in the state of being powered on at the same time during the operation of air conditioner.
Product Features:
1. Hanging-style installation to save space;
2. Automatic display of faults;
3. Function of central control (optional from our company).
4. The air conditioner is provided with the function of compensation for power supply. During operation, when the power supply fails emergently and resumes again, the air conditioner returns to the working condition before power failure, if provided with compensation function.
5. The operating methods and functions are same although the shapes of indoor units are different.
6. Now this indoor unit only has wired controller function,the indoor unit that has remote controller function need to set in factory especially.
Contents
Parts and Functions....................................................... 1
Safety ............................................................................ 2
Maintenance .................................................................. 4
Fault Checkup ............................................................... 6
Installation Procedures .................................................. 7
Electrical Wiring ........................................................... 14
Test Run & Fault Code ................................................ 19
Whole model Brief model
AWSI-CFV007-N11 CFV007 AWSI-CFV009-N11 CFV009 AWSI-CFV012-N11 CFV012 AWSI-CFV016-N11 CFV016 AWSI-CFV018-N11 CFV018 AWSI-CFV024-N11 CFV024 AWSI-CFV028-N11 CFV028 AWSI-CFV030-N11 CFV030 AWSI-CFV038-N11 CFV038 AWSI-CFV048-N11 CFV048 AWSI-CFV060-N11 CFV060
The brief model is used in this manual for above models.
Operating Range of Air Conditioner
Cooling
Indoor
dry
Outdoor
Indoor
Heating
Outdoor
Max. DB:32°C WB:23°C
Min. DB:18°C WB:14°C
Max. DB:43°C WB:26°C
Min. DB:-5°C
Max. DB:27°C
Min. DB:15°C
Max. DB:21°C WB:15.5°C
Min. DB:-15°C
Warning
• If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualied persons in order to avoid a hazard.
• This appliance is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the appliance.
• This appliance can be used by children aged from 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
• The appliances are not intended to be operated by means of an external timer or
separate remote-control system.
• Keep the appliance and its cord out of reach of children less than 8 years.

Parts and Functions

Indoor unit
Outlet guide plate (air direction can be adjusted by using direction adjustment key on the remote controller)
Air-inlet grille
Air lter (inside air-inlet grille)
1

Safety

• If the air conditioner is transferred to a new user, this manual shall be transferred to the user, together with the conditioner.
• Before installation, be sure to read Safety Considerations in this manual for proper installation.
• The safety considerations stated below is divided into " caused from wrong installation, which is likely to lead to death or serious injury, are listed in " Warning". However, the matters listed in " Attention" are also likely cause the severe accidents. In general, both of them are the important items related to the security, which should be strictly abided by.
• After the installation, perform test run to make sure everything is in normal conditions, and then operate and maintain the air conditioner in accordance with the User Manual. The User Manual should be delivered to the user for proper keeping.
Warning" and " Attention". The matters on severe accidents
WARNING
• Please ask the special maintenance station for installation and repair. Water leakage, electric shocks or re accidents might be caused from improper installation if you conduct the installation by your own.
• The installation should be conducted properly according to this manual. Water leakage, electric shocks or re accidents might be caused from improper installation.
• Please make sure to install the air conditioner on the place where can bear the weight of the air conditioner. The air conditioner can't be installed on the grids such as the non-special metal burglar-proof net. The place with insufcient support strength might cause the dropdown of the machine, which may lead to personal injuries.
• The installation should be ensured against typhoons and earthquakes, etc. The installation unconformable to the requirements will lead to accidents due to the turnover of the machine.
• Specic cables should be used for reliable connections of the wirings. Please x the terminal connections reliably to avoid the outside force applied on the cables from being impressed on the cables. Improper connections and xings might lead to such accidents as heating or re accidents.
• Correct shapes of wirings should be kept while the embossed shape is not allowed. The wirings should be reliably connected to avoid the cover and the plate of the electrical cabinet lipping the wiring. Improper installation might cause such accidents as heating or re accidents.
• While placing or reinstalling the air conditioner, except the specic refrigerant (R410A), don't let the air go into the refrigeration cycle system. The air in the refrigeration cycle system might lead to the cracking or personal injuries due to abnormal high pressure of the refrigeration cycle system.
• During installation, please use the accompanied spare parts or specic parts. If not, water leakage, electric shocks, re accidents or refrigerant leakage might be caused.
• Don't drain the water from the drainpipe to the waterspout where may exist harmful gases such as sulfureted gas to avoid the harmful gases entering into the room.
• During installation, if refrigerant leakage occurs, ventilation measures should be taken, for the refrigerant gas might generate harmful gases upon contacting the ame.
• After installation, check if any refrigerant leakage exists. If the refrigerant gas leaks in the room, such things as air blowing heaters and stoves, etc. may generate harmful gases.
• Don't install the air conditioner at the places where the ammable gases may leak. In case the gas leakage occurs around the machine, such accidents as re disasters may be caused.
• The drainpipe should be properly mounted according to this manual as to ensure the smooth drainage. In addition, heat preservation should be taken to avoid condensation. Improper drainpipe mounting might cause water leakage, which will get the articles at home wet.
• The refrigerant gas pipe and liquid pipe should be heat insulated to preserve heat. For inappropriate heat insulation, the water caused from the condensation will drop to get the article at home wet.
2
Safety
CAUTION
• The air conditioner should be effectively grounded. Electric shocks may occur if the air conditioner is ungrounded or inappropriately grounded. The wire for earthing shouldn't be connected to the connections on the gas pipe, water pipe, lightning rod or telephone.
• The breaker for electricity leakage should be mounted. If not, accidents such as electric shocks may happen.
• The installed air conditioner should be checked for electricity leakage by being powered.
• If the ambient humidity bigger than 80%, when the water discharge hole be blocked or the lter becomes dirty, or airow speed change, there maybe leads to condensing water drop down, and at the same time there maybe some drops of water spit out.
Attention
• It is not allowed to put any heating apparatus under the indoor units, for the heat may cause distortion of the units.
• Pay attention to the aeration condition to avoid anoxic symptom.
• Flammable apparatus should not be placed in the place where the air conditioner wind could reach directly, or incomplete burning of the apparatus may be caused.
• Check the mount table of the air conditioner for damage for a long period of operation. If placed on the damaged table, the unit may drop down causing damage.
• Plants and animals should not be put to the place where wind of the air conditioner blows directly, otherwise damage to them may be caused.
• It cannot be used for the preservation of food, living creature, precise instrument and artworks, etc,
Notices during Operation
otherwise damage may occur.
• Use the fuse with proper capacity. Metal wires and copper wires, etc., may cause re or other faults.
• Do not use water heater or like next to the indoor unit and the wired controller. Water/power leakage or short circuit may happen if the steam generating apparatus is working next to machine.
• Defrosting during heating To improve the heating effect, the outdoor unit will perform defrosting automatically when frost appears on the outdoor unit during heating (approximately 2-10 min). During defrosting, the fan of the indoor unit runs at a low speed or stops while that of the outdoor unit stops running.
• Do not touch the switch with the wet hand to avoid power shock.
• Power should be cut off when the air conditioner is left unused for a long period. Power will be consumed if the air conditioner is not powered off. The power switch of the outdoor unit switch should be powered on 12 hours in advance before operation to protect the unit after a long period of storage.
• 3-minute protection To protect the unit, compressor can be actuated with at least 3-minute delay after stopping.
• Close the window to avoid outdoor air getting in. Curtains or window shutters can be put down to avoid the sunshine.
• Stop running and switch off the manual power switch when cleaning the unit.
• During the operation of the control unit, don't switch off the manual power switch and the controller can be used. Please do not press the liquid crystal zone of controller to prevent damage.
• Cleaning the unit with water may cause electric shock.
• Do not put ammable spray close to the air conditioner. Don't inject ammable spray towards the air conditioner, which may cause re.
• Stopping fan rotation The unit which stops operating will actuate the fan for a 2-8 min swing every 30-60 minutes for protecting the unit while other indoor unit are in the operating state.
• This appliance is not intended for use by persons (including children) with reducedphysical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
3

Maintenance

Attention
• Repair can only be performed by professional personnel.
• Before touching the connection line, all power supplies should be switched off. Only after switching off the power supply can the operator clean the air conditioner as to avoid electric shock or injury.
• When cleaning the air cleaner, make sure to use a stable platform; don't ush the air conditioner with water, or the electric shock might be caused.
Daily Maintenance:
Clean the air cleaner & air inlet grid.
• Don't dismantle the air cleaner if not cleaning, or faults might be caused.
• When the air conditioner operates in the environment with too much dust, clean the air conditioner more times (generally once every two weeks).
1. Remove the air inlet grid as shown in the gure: press down the two locks on the grid (as shown in Fig. 1) to move it
close to the nearby grid, gently lift it 45 degree (as shown in Fig. 2), and then remove the air inlet grid.
2. Dismantle the gauze: press the outer frame of the air inlet grid by the thumb, and draw the base angle of gauze by the
forenger and pull it out as to make the gauze disengage the locks, and dismantle the gauze (as shown in Fig. 3).
press down the locks
lock device
lock port
bottom of gauze
locks
remove air inlet grid
frame of air inlet grid
Fig. 1 Fig. 2 Fig. 3
lock device
Cleaning Air Cleaner
• Cleaning Clean the air cleaner with the dust collector or water to remove dusts. For too much dust, use the fan or directly spray the special cookware detergent on the air inlet grid, and then clean it with water after 10 minutes. (A) remove dust with dust collector.
(B) for too much dust, use soft-hair brush and mild detergent to clean. (C) throw off water and then dry it at cool places.
Attention
• Don't clean it with hot water of over 50°C to avoid fading or distortion.
• Don't dry it on the re, or the cleaner might cause re.
4
Maintenance
Installing air cleaner and air inlet grid:
1. Mounting the gauze: opposite to the ways of dismantling the gauze
(as shown in Fig. 3 above).
2. Mounting the air inlet grid: as shown in the right gure, nip the
locks on the grid as directed by arrows, put the side with the lock device into the lock port, and then put the side with locks into the panel frame. Release the locks to position the grid after determining that the grid is abutting upon the bottom of the panel frame.
Cleaning the air outlet port and the shell:
Attention
• Don't use gasoline, benzene, diluents, polishing powder or liquid insecticide to clean them.
• Do not clean them with hot water of above 50°C to avoid fading or distorting.
• Wipe them with soft dry cloth.
• Water or neutral dry cleanser is recommended if the dust cannot be removed.
• The Wind Deector can be dismantled to clean (as below).
lock device
lock port
locks
insert air inlet grid
Cleaning Wind Deector:
• Do not wipe the wind deector with water forcibly to avoid the oss falling off.
Maintenance before and after Operating Season
Before Operating Season:
1. Please make the following checkup:
• There is no blockage in inlet port and outlet port of outdoor and indoor units.
• The ground line and the wiring are in the proper state. If abnormal condition occurs, consult the after-service personnel.
2. Clean the air cleaner and the shell.
• After cleaning, the air cleaner must be mounted.
3. Switch it on to the power.
• After cleaning, the air cleaner must be mounted.
After Operating Season:
1. In sunny days, blowing operation can be performed for half a day to make the inside of machine dry.
2. Switch it off.
• Electrical power should be cut down to economize electricity, or the machine will still consume power.
3. Clean the air cleaner and the shell.
• Air cleaner and shell must be mounted after cleaning. For cleaning details, refer to Maintenance.
5

Fault Checkup

Please check the following when consigning repair service:
Symptoms Reasons
Water ow sound can be heard when starting operation, during operation or
Water ow sound
Cracking sound
Terrible smell in outlet air
Flashing operating indicator
Awaiting indication
All these are not problems
Sound in shutdown indoor unit or white steam or cold air
Clicking sound when switching the air condition on
Start or stop working automatically Check if it is in the state of Timer-ON and Timer-OFF.
Failure to work
Bad cooling & heating effects
Please make another check.
immediately after stopping operation. When it starts to work for 2-3 minutes, the sound may become louder, which is the owing sound of refrigerant or the draining sound of condensed water.
During operation, the air conditioner may make the cracking sound, which is caused from the temperature changes or the slight dilation of heat exchanger.
The terrible smell, caused from walls, carpet, furniture, clothing, cigarette and cosmetics, attaches on the conditioner.
When switching it on again after power failure, turn on the manual power switch and the operating indicator ashes.
It displays the awaiting indication as it fails to perform refrigerating operation while other indoor units are in heating operation. When the operator set it to the refrigerating or heating mode and the operation is opposite to the setting, it displays the awaiting indication.
To prevent oil and refrigerant from blocking the shutdown indoor units, refrigerant ows in the short time and make the sounds of refrigerant owing. Otherwise, when other indoor units performs heating operation, white steam may occur; during refrigerating operation, cold air may appear.
When the conditioner is powered on, the sound is made due to the resetting of the expansion valve.
Check if there is a power failure. Check if the manual power switch is turned off. Check if the supply fuse and breaker are disconnected. Check if the protective unit is working. Check if refrigerating and heating functions are selected simultaneously with the awaiting indication on line control.
Check if air intake port and air outlet port of outdoor units are blocked. Check if the door and windows are open. Check if the ltering screen of air cleaner is blocked with sludge or dust. Check if the setting of wind quantity is at low wind. Check if the setting of operation is at the Fan Operation state. Check if the temperature setting is proper.
Under the following circumstances, immediately stop the operation, disconnect the manual supply switch and contact the after-service personnel.
• When buttons are inexible actuated;
• When fuse and breaker have been burnt over and over;
• When there are foreign objects and water in the refrigerator;
• When it cannot still be operated after removing the operation of protective unit;
• When other abnormal conditions occur.
6

Installation Procedures

The standard attached accessories of the units of this series refer to the packing list; prepare other accessories according to the requirements of the local installation point of our company. Indoor units should be installed in places with the environment of even circulation of cool and warm blows. The following places should be avoided.
• places with high salinity (beach), high sulfureted gas(such as the thermal spring regions where copper tubes and soft soldering are easy to be eroded), much oil(including mechanical oil) and steam; places where organic substance solvent is used; where special spray is frequently used;
• places where machines generate the high frequency electromagnetic wave (abnormal condition will appear in the control system);
• places where there is high humidity exists near the door or windows (dew is easily formed).
Warning: protect the machine from gales or earthquake, make the installation according to the regulations. Improper installation will cause accidents due to the overturn of the air conditioner.
1. Select the following places to install indoor units.
(1) where there is enough room for the machine above the ceiling; (2) where the drainpipes can be well arranged; (3) where the distance between the air outlet port of the machine and the oor is not more than 2.7m; (4) where air inlet & outlet of the indoor units are not blocked; (5) where it is hard enough to bear the weight of the unit; (6) where there are no television, piano and other valuables under the indoor units as to avoid condensate dropping down,
causing damage.
(7) Where it is over 1m away from the television and radio as to avoid the disturbance from television and radio.
Installation Space
Ensure the required space for installation and maintenance (refer to the following drawings). The installation height should be kept within 2.7m. When the height of the ceiling exceeds 2.7m, the warm air is hard to blow to the ground.
≥1500
≥1500
Outlet Outlet
≥1000
More than 2500
above the ground
Space required for installation (unit: mm)
Model H
CFV007~018 206 CFV024~028 227 CFV030~038 269
CFV048~CFV060 311
Suction inlet
H
≥1500
≥1500
≥1500
≥1500
7
Installation Procedures
2. Location Relationship among Ceiling Hole, Unit and Hoisting Studs
765(spacing of hanging screw)
850(indoor unit)
890(ceiling opening)
950(trim panel)
Ceiling
Overlap between ceiling and trim panel≥30
Trim panel
Distance between indoor unit and ceiling≤20
850(indoor unit)
765(spacing of hanging screw)
Hanger bracket
950(trim panel)
890(ceiling opening)
H
130
Distance between indoor unit and ceiling≤20
Overlap between ceiling and trim panel≥30
Model H
CFV007~018 236 CFV024~028 257 CFV030~038 299
CFV048~CFV060 341
Note: Before suspending the indoor unit, select the installation location according to the piping and wiring in the ceiling, and determine the lead direction of the piping. Prepare all pipes (refrigerator and drainage) and wiring (connection line for remote control and connection line of indoor units and outdoor units) connected to indoor units before suspending the indoor unit so as to make the connections right after the installation.
• In the situation with the ceiling, before suspending the unit, set refrigerant pipe, drainpipe, connection line in the room, lead wire of line control to the locations of piping and wiring.
• Conrm the size of the indoor unit and x it according to the requirements in the manual.
3. Ceiling Hole & Reinforcement
(1) Cut and withdraw the foundation of ceiling according to the size of indoor unit. (2) After cutting an appropriate hole, reinforce the cutting area on the foundation of indoor unit, and append the rim to the
ceiling to secure its foundation. In order to prevent the ceiling from vibrating, it is vital to reinforce the ceiling foundation and ensure the original levelness of the ceiling.
8
Installation Procedures
4. Hoisting Stud Installation
• To support the weight of the unit, use barb bolts in the situation with the ceiling. In the situation with the new ceiling, use inlaid bolts, embedded bolts or other parts provided on site. Before proceeding the installation, adjust the gap between the bolts and the ceiling.
• Use four M10 hoisting studs (provided on site) (when the height of the hoisting stud exceeds 0.9m, M10 studs should be used.). The gaps should be kept according to the overall drawing of the air conditioner. Make the installation according to regulations for various building structures as to ensure the safety. Use the level meter to perform the parallel installation.
Ceiling Suspending
Situation with New Ceiling
(1) Install the indoor unit temporarily:
attach the hoisting foot to hoisting stud. Make sure that nuts and washers should be used at two ends of the foot to secure the foot.
(2) For the size of the ceiling hole, please refer to the schematic drawing at the previous page.
<After nishing the installation of the ceiling> (3) Adjust the unit to the proper installation location. (4) Check if the unit is in the horizontal level:
The indoor unit is equipped with a built-in drainage pump and a oater switch.
Check if the 4 angles of the unit are in the horizontal level with the water level
or the polythene tube with water, as shown in the gure,taking only one indoor
unit as an example. If the unit inclines opposite to the direction of condensate
ow, the oater switch might have faults, causing water dropping. (5) Tighten the nut on the washer.
Situation with Original Ceiling
(1) Install the indoor unit temporarily: attach the hoisting foot to
hoisting stud. Make sure that nuts and washers (provided on site) should be used at two ends
of the foot to secure the foot. (2) Adjust the height and location of the unit. (3) Perform Step 4 and 5 in Situation with New Ceiling.
[secure hoisting foot] [secure washer foot]
tightening (dual nuts)
water level
nut (provided on site)
washer
hoisting foot
polythene tube
washer
Preparation of Decorated Board
• Don't put the decorated board downward to the oor. Putting it against the wall or on the extrusive objects is not allowed.
• Don't touch the wind deector or apply force on it, or the wind deector will have faults.
9
Installation Procedures
Installation
(1) Conrming the position of unit hanger Please conrm the installation position of the hanger for indoor unit is about 130mm above the ceiling. For details, please refer to the Instructions for Installation and Maintenance of indoor unit.
(2) Removing the air-inlet grille Open the air-inlet grille to make it at an angle of 45° to the trim panel. As shown in the following gure, please remove the air-inlet grille as per the operation requirements.
Angle trim cover
Step 3: Gently push the air-inlet grille in the direction of arrow.
Step 1: Open the two snaps in the direction of arrow.
(3) Installing the panel
1) Please remove the four (4) angle trim panels. Removal method: Flip the jack catches of the angle trim panel in the order of ipping direction is indicated by the arrows. Then the angle trim panel can be removed.
①②③④
Jack catch
, as shown in the following gure. The
1
Panel
Jack catch
3
4
Step 2: Open the air-inlet grille to make it at 45°to the panel. Air-inlet grille
2
Jack catch
Refrigerant pipe
Indoor unit
Drain pipe
2 x U-shaped hooks
Trim panel
5) When tightening the four (4) bolts, please make sure there is no clearance between the panel xing seat on the side of the indoor unit and the panel xing seat on the side of the panel. That is to say: the bolts shall be fully tightened (see * in the gure). If there is a clearance, air leakage or water leakage is likely to occur.
Panel xing seat
(Indoor unit side)
Ceiling
Trim panel
Caution:
• Improper tightening of bolts would lead to the faults shown in the following gure.
Air leakage
4x Bolts (M5*25)
(including gaskets)
Housing
Panel
xing seat
(Panel side)
Jack catch
2) Pull out the two (2) U-shaped hooks on the indoor unit from below.
3)Adjust the panel direction to make the angle side engraved with"Pipe side" consistent with the refrigerant pipe of the indoor unit, and make the angle side engraved with "Drain side" consistent with the drain side of the indoor unit. Then hang the 2 hooks in the inner side of the panel on the 2 U-shaped hooks of the indoor unit.
4) Finally x the panel on the indoor unit with the bolts (M5*25) and gaskets delivered with the unit. Caution: Gaskets must be used for xing, or else the panel would be easy to fall off.
Ceiling pollution
• After tightening the bolts, if there is a clearance between the ceiling and the trim panel, please readjust the height of the indoor unit.
Clearance is not allowed
10
Water condensate, water dripping
Installation Procedures
If the elevation level of the indoor unit and drain pipe are not affected, you can adjust the height of the indoor unit through the corner pore on the trim panel. Please keep the unit horizontal in the process of adjustment, or else water leakage is easy to occur.
• Please do not swing the louver blade by hand, or else the blade mechanism would be damaged.
6) Connection of trim panel. Connect the black lead-out
terminal of the panel to the black lead-out terminal of the indoor unit housing.
Indoor unit
Connecting terminal Connecting to the panel side
8) Installing the air-inlet grille. Install the air-inlet grille with the steps opposite to that for removing. For reference The method for removing angle trim panels when the installation of trim panel is complete: a.Insert a straight screwdriver in the notch①. Gently turn the screwdriver downward, and slowly insert it in, and then move it up and down to make the angle fall off. b.Make the angle ② and ③ fall off in the same way. c.Take off the angle trim panel by hand.
Straight screwdriver
Angle trim panel
Connecting terminal
Trim panel
7) When the installation of panel is complete, please x the
four (4) angle trim panels.
• Hang and tighten the strap of the angle trim panel on the shackle of the trim panel, as shown in the gure.
• Fix the angle trim panel on the trim panel.
Connecting to the indoor unit side
Requirements:
• The drainpipe of the indoor unit should be heat-insulated.
• Heat insulation should be treated for the connection with the indoor unit. Improper heat insulation may cause condensing.
• The drainpipe with the down gradient of over 1/100 can't be in the S shape, or abnormal sound can be caused.
• The horizon length of the drainpipe should be kept with 20m. Under the condition of long pipes, supports can be provided every 1.5~2m as to avoid unevenness.
• The central piping should be connected according the following drawing.
• Take care not to apply external force on the connection of the drainpipes.
1.5m~2m
heat insulating material
as big as possible (about 10 CM)
down gradient over 1/100
support bracket
s-shape elbow
11
down gradient over 1/100
VP30
Installation Procedures
Piping Materials & Heat Insulating Materials
As to prevent condensation, heat insulating treatment should be performed. The heat insulating treatment for piping should be done respectively.
Piping Material
Heat Insulating Material
Hose
The attached hoses can be used to adjust the eccentricity and angle of the hard PVC tube.
• Stretch the hose directly to make connections as to avoid distortion. The soft end of the hose should be positioned with a clamp.
• The hose should be used in the horizon direction.
Hard PVC tube VP31.5mm (inner bore) Vesicant polythene thickness: over 7mm
eccentricity adjustment (max.20mm)
20
Heat Insulating Treatment:
• Wrap the connection between the clamp and the root segment of the indoor unit without any gap with heat insulating
materials as shown in the drawing
45°bending (max.)
hose
45°
indoor unit
hose hose clamp
hose clamp
hose
Lifting Drainpipe
The drainpipe can be lifted 360mm. When the down gradient of the drainpipe can't be ensured, after upright lifting, the drainpipe is in the down slope.
attached heat insulating material
heat insulating material
horniness pvc pipe
Conrming Drainage
The drainage should be conrmed during the test run to make sure that there is leakage at the connection. The conrmation of drainage should be also performed during the installation in the winter season. Fill water from the outlet or the specied position and conrm the drainage. Fill 600cc water with a hose from the outlet or the specied location on the machine. Add the water slowly. Don't add water to the motor of the drainage pump.
• After mounting the electrical system, do cooling operation and meanwhile add
water and check.
• If the electrical installation hasn't been completed, pull out the terminal(2P)
of the oater switch on the electrical cabinet. After conrming the drainage, connect the terminal of the oater switch and run the drainage pump for 5 minutes until it stops automatically.
• Conrm the sound of the motor:
Conrm the sound of the motor of the drainage pump and meanwhile check the drainage.
12
lifting
360mm below
100mm below
under the ceiling
joint of drainpipe
lifting 600mm below
Installation Procedures
Tubing Permissible Length & Height Difference
Please refer to the attached manual of outdoor units.
Tubing Materials & Specications
Please refer to the attached manual of outdoor units.
Model CFV007~009 CFV012~018 CFV024~060
Tubing Size (mm)
Tubing Material Phosphor deoxybronze seamless pipe (TP2) for air conditioner
Refrigerant Filling Amount
Add the refrigerant according to the installation instruction of outdoor unit. The addition of R410A refrigerant must be performed with a measure gage to ensure the specied amount while compressor failure can be caused by lling too much or little refrigerant.
Connecting Procedures of Refrigerant Tubing
Proceed the are tube connecting operation to connect all the refrigerant tubes.
• Dual wrenches must be used in the connection of indoor unit tubing.
• Mounting torque refers to the right table
wrench
Gas pipe Ø9.52 Ø12.7 Ø15.88
Liquid pipe Ø6.35 Ø6.35 Ø9.52
Outer Diameter of Tubing
(mm)
Ø6.35 11.8(1.2kgf-m) 13.7(1.4kgf-m) Ø9.52 24.5(2.5kgf-m) 29.4(3.0kgf-m) Ø12.7 49.0(5.0kgf-m) 53.9(5.5kgf-m)
Ø15.88 78.4(8.0kgf-m) 98.0(10.0kgf-m)
Mounting Torque
(N-m)
Increase mounting Torque
(N-m)
Cutting and Enlarging Connecting
Cutting or enlarging pipes should be proceeded by installation personnel according to the operating criterion if the tube is too long or are opening is broken.
Vacuumizing
Vacuumize from the stop valve of outdoor units with vacuum pump. Refrigerant sealed in indoor machine is not allowed to use for vacuumization.
Open All Valves
Open all the valves of outdoor units. [NB: oil balancing stop valve must be shut up completely when connected one main unit.]
Checkup for Air Leakage
Check if there is any leakage at the connecting part and bonnet with hydrophone or soapsuds.
1. Connecting circular terminals: The connecting method of circular terminal is shown in the Fig. Take off the screw, connect it to the terminal tier after heading it through the ring at the end of the lead and then tighten it.
2.Connecting straight terminals: The connection methods for the circular terminals are shown as follows: loosen the screw before putting the line terminal into the terminal tier, tighten the screw and conrm it has been clamped by pulling the line gently.
3.Pressing connecting line After connecting line is completed, press the connecting line with clips which should press on the protective sleeve of the connecting line.
correct
pressing
Connecting circular terminals:
terminal tier
pressing clip
wrong
pressing
13

Electrical Wiring

WARNING
• Electrical construction should be made with specic mains circuit by the qualied personnel according to the installation
instruction. Electric shock and re may be caused if the capacity of power supply is not sufcient.
• During arranging the wiring layout, specied cables should be used as the mains line, which accords with the local
regulations on wiring. Connecting and fastening should be performed reliably to avoid the external force of cables from transmitting to the terminals. Improper connection or fastness may lead to burning or re accidents.
• There must be the ground connection according to the criterion. Unreliable grounding may cause electrical shocks. Do
not connect the grounding line to the gas pipe, water pipe, lightening rod and telephone line.
Attention
• Only copper wire can be used. Breaker for electric leakage should be provided, or electric shock may occur.
• The wiring of the mains line is of Y type. The power plug L should be connected to the live wire and plug N connected
to null wire while should be connected to the ground wire. For the type with auxiliary electrically heating function, the live wire and the null wire should not be misconnected, or the surface of electrical heating body will be electried. If the power line is damaged, replace it by the professional personnel of the manufacturer or service center.
• The power line of indoor units should be arranged according to the installation instruction of indoor units.
• The electrical wiring should be out of contact with the high-temperature sections of tubing as to avoid melting the
insulating layer of cables, which may cause accidents.
• After connected to the terminal tier, the tubing should be curved into be a U-type elbow and fastened with the pressing
clip.
• Controller wiring and refrigerant tubing can be arranged and xed together.
• The machine can't be powered on before electrical operation. Maintenance should be done while the power is shut
down.
• Seal the thread hole with heat insulating materials to avoid condensation.
• Signal line and power line are separately independent, which can't share one line. [Note: the power line, signal line are
provided by users. Parameters for power lines are shown as below: 3×(1.0-1.5)mm parameters for signal line: 2×(0.75-1.25)mm2 ( shielded line)]
• 5 butt lines (1.5mm) are equipped in the machine before delivery, which are used in connection between the valve box
and the electrical system of the machine. The detailed connection is displayed in the circuit diagram.
2
;
Supply Wiring Drawing
Outdoor 1 Outdoor 2 Outdoor 3
Ground Fault Interruptor Ground Fault Interruptor Ground Fault Interruptor Circuit Breaker Circuit Breaker Circuit Breaker
Supply: 3N~,380-400V,50/60Hz
Indoor 1 Indoor 2 Indoor 3
Supply: 1PH,220-230V~,50/60Hz Supply: 1PH,220-230V~,50/60Hz Supply: 1PH,220-230V~,50/60Hz
• Indoor units and outdoor units should be connected to the power source separately. Indoor units must share one single
electrical source, but its capacity and specications should be calculated. Indoor & outdoor units should be equipped with the power leakage breaker and the overow breaker.
Supply: 3N~,380-400V,50/60Hz Supply: 3N~,380-400V,50/60Hz
Ground Fault InterruptorGround Fault Interruptor Circuit BreakerCircuit Breaker
Ground Fault Interruptor Circuit Breaker
14
Electrical Wiring
Signal Wiring Drawing
AP Q B C
(AC machine) (AC machine) (DC machine)
AP Q B C AP Q B C AP Q B C AP Q B C AP Q B C
AP Q B C AP Q B C AP Q B C AP Q B C AP Q B C
(This machine)
AP Q B CAP Q B CAP Q B CAP Q B CAP Q B C
AP Q B CAP Q B CAP Q B CAP Q B CAP Q B C
Outdoor units are of parallel connection via three lines with polarity. The main unit, central control and all indoor units are of parallel connection via two lines without polarity. There are three connecting ways between line control and indoor units: A. One line control controls multiple units, i.e. 2-16 indoor units, as shown in the above gure, (1-5 indoor units). The
indoor unit 5 is the line-controlled main unit and others are the ine-controlled sub units. The remoter control and the main unit (directly connected to the indoor unit of line control) are connected via three lines with polarity. Other indoor units and the main unit are connected via two lines with polarity.SW01 on the main unit of line control is set to 0 while SW01 on other sub units of line control are set to 1, 2, 3 and so on in turn. (Please refer to the code setting at page 17)
B. One line control controls one indoor unit, as shown in the above gure(indoor unit 6-19). The indoor unit and the line
control are connected via three lines with polarity.
C. Two line controls control one indoor unit, as shown in the gure (indoor unit 20). Either of the line controls can be set to
be the master line control while the other is set to be the auxiliary line control. The master line control and indoor units, and the master and auxiliary line controls are connected via three lines with polarity. When the indoor units are controlled by the remote control, switch over the modes by Switching Mode of Line­Controlled Main Unit/ Line-Controlled Sub Units/ Remote-Controlled Types. The signal terminals needn't to be equipped with wires and connected to the line control.
15
Electrical Wiring
The wiring for the power line of indoor unit, the wiring between indoor and outdoor units as well as the wiring between indoor units:
Items
Total Current of Indoor Units(A)
Cross
Section
(mm2)
Length
(m)
Rated
Current of
Overow
Breaker(A)
Rated current of residual
Circuit Breaker(A)
Ground Fault
Interruptor(mA)
Response time(S)
Outdoor -indoor
Cross Sectional
Area of Signal Line
Indoor -indoor
(mm
2
)
(mm2)
<10 2 20 20 20 A,30 mA,0.1S or below ≥10 and <15 3.5 25 30 30 A,30 mA,0.1S or below ≥15 and <22 5.5 30 40 40 A,30 mA,0.1S or below
2 cores×0.75-2.0mm
shielded lin
2
≥22 and <27 10 40 50 50 A,30 mA,0.1S or below
• The electrical power line and signal lines must be fastened tightly.
• Every indoor unit must have the ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of signal lines of outdoor units grounded at one point.
• It is not permissible if the whole length of signal line exceeds 1000m.
Signal Wiring of Wired controller
Length of Signal Line (m) Wiring Dimensions
<100 0.3mm
≥100 and <200 0.5mm
≥200and <300 0.75mm
≥300 and <400 1.25mm
2
× core shielding lin
2
× core shielding lin
2
× core shielding lin
2
× core shielding lin
≥400 and <600 2 mm2× core shielding lin
• The shielding lay of the signal line must be grounded at one end.
• The total length of the signal line shall not be more than 600m.
16
Electrical Wiring
Dipswitch Setting
Indoor Units PCB
In the following table, 1 represents ON and 0 represents OFF. Denition principles of code switches: SWO1 is used to set capabilities of master and slave indoor units as well as indoor unit; SW03 is used to set indoor unit address (combine original communication address and address of centralized controller).
(A) Denition and description of SW01
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
0 0 0 0 0# (wire controlled master unit) (default) 0 0 0 1 1# (wire controlled slave unit)
SW01_1 SW01_2 SW01_3 SW01_4
SW01_5 SW01_6 SW01_7 SW01_8
Address of wire
controlled indoor unit
Capability of indoor unit
0 0 1 0 2# (wire controlled slave unit) 0 0 1 1 3# (wire controlled slave unit) 0 1 0 0 4# (wire controlled slave unit) 0 1 0 1 5# (wire controlled slave unit)
∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙
1 1 1 1 15# (wire controlled slave unit)
[5] [6] [7] [8] Capability of indoor unit
0 0 0 1 0.8HP (CFV007) 0 0 1 0 1.0HP (CFV009) 0 0 1 1 1.2HP (CFV012) 0 1 0 1 1.7HP (CFV016) 0 1 1 0 2.0HP (CFV018) 0 1 1 1 2.5HP (CFV024) 1 0 0 0 3.0HP (CFV028) 1 0 0 1 3.2HP (CFV030) 1 0 1 0 4.0HP (CFV038) 1 0 1 1 5.0HP (CFV048) 1 1 0 0 6.0HP (CFV060)
17
Electrical Wiring
(B) Denition and description of SW03
SW03_1
SW03_2
~
SW03_8
Note *:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller=communication address+0 or+64. SW03_ 2=OFF, address of centralized controller=communication address+0=communication address SW03_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller is used and there are more than 64 indoor units)
• To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1=0N and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are address codes which are set according to actual address.
• Address setting function of wired controller for ultrathin card machine is disnabled.
Address setting
mode
Code-set indoor
unit address
and centralized
controller address
(Note *)
[1] Address setting mode
0 Automatic setting (default) 1 Code-set address
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit
0 0 0 0 0 0 0 0# (Default) 0# (Default) 0 0 0 0 0 0 1 1# 1# 0 0 0 0 0 1 0 2# 2#
0 1 1 1 1 1 1 63# 63# 1 0 0 0 0 0 0 0# 64# 1 0 0 0 0 0 1 1# 65# 1 0 0 0 0 1 0 2# 66#
1 1 1 1 1 1 1 63# 127#
Address of centralized
controller
18

Test Run & Fault Code

Before Test Run
• Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm meter and check if the resistance is above 1MΩ. It can't be operated if it is below 1MΩ.
• Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To protect the compressor at startup, power it on 12 hours prior to the operation.
Check if the arrangements of the drainpipe and connection line are correct.
The drainpipe shall be placed at the lower part while the connection line placed at the upper part. Heat preservation measures should be taken such as winding the drainpipe esp. in the indoor units with heating insulating materials. The drain pipe should be made a slope type to avoid protruding at the upper part and concaving at the lower part on the way.
Checkup of Installation
check if the mains voltage is matching check if there is air leakage at the piping joints check if the connections of mains power and indoor & outdoor
units are correct
check if the serial numbers of terminals are matching
Ways of Test Run
Do ask the installation personnel to make a test run. Take the testing procedures according to the manual and check if the temperature regulator works properly. When the machine fails to start due to the room temperature, the following procedures can be taken to do the compulsive running. The function is not provided for the type with remote control.
• Set the wired controller to cooling/heating mode, press "ON/OFF" button for 5 seconds to enter into the compulsive cooling/heating mode. Repress "ON/OFF" button to quit the compulsive running and stop the operation of the air conditioner.
check if the installation place meets the requirement check if there is too much noise check if the connecting line is fastened check if the connectors for tubing are heat insulated check if the water is drained to the outside check if the indoor units are positioned
Fault Remedies
When any fault appears, consult the fault code of line control or the ashing times for LED5 of computer panel of indoor units/health lamp of receiving window of remote control and nd out the faults as shown in the following table to remove all faults. Indoor Unit Faults
Failure code at
wired controller
01 1 02 2 03 3 04 4 05 5 06 6 07 7 08 8
09 9 0A 10 0C 12 Fault of zero cross sing 0E 14 Fault of DC fan
Outdoor Unit
Code
PCB LED5(Indoor Units)/
Receiver Timer Lamp(Remote
Controller)
20
Fault Descriptions
Fault of indoor unit ambient temp. transducer TA
Fault of indoor unit pipe temp. transducer TC1
Fault of indoor unit pipe temp. transducer TC2
Fault of indoor unit dual heat source temp. transducer
Fault of indoor unit EEPROM
Fault of communication between indoor & outdoor units
Fault of communication between indoor unit and wired control
Fault of indoor unit water drainage
Fault of duplicate indoor unit address
Fault of communication between indoor unit and Display Board
Corresponding faults of outdoor units
19