AirStage ARXB24LATH, ARXB45LATH, ARXB07LALH, ARXB09LALH, ARXB12LALH Service Manual

...
Small VRF system
for light commercial and home use
CONTENTS
1. TEST RUN
1-3 TEST RUN CONTROL................................................................................................
1-2-1 Check Items Before Power ON............................................................................
1-2-2 Check Items After Power ON...............................................................................
1-2 TEST RUN METHOD..................................................................................................
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS.............................
1-2-4 Automatic address setting procedure for indoor units..........................................
01-01 01-03 01-03 01-04
01-07
1-2-3 Automatic address setting procedure for Signal amplifiers.................................. 01-06
01-10
1-4 Field Setting And Monitor Mode List....................................................................... 01-11
2-1 INPUT / OUTPUT LIST..............................................................................................
2. OUTDOOR UNIT OPERATION CONTROL
2-2 COMPRESSOR OPERATION....................................................................................
02-01 02-02
02-02 02-03
2-2-3 Speed Range of Start,Stop,and Operation..........................................................
2-2-2 Capacity Control.................................................................................................
02-02
2-2-1 Operation / Stop Condition.................................................................................
2-5 SPECIAL OPERATION..............................................................................................
02-09 02-09 02-10
2-5-2 Pre-Heat Operation............................................................................................
2-5-1 Oil Recovery Operation......................................................................................
2-6 PROTECTIVE FUNCTION........................................................................................
02-11 02-11
2-6-1 Protective Function List......................................................................................
2-5-3 Defrost Operation Control..................................................................................
02-10
2-3 FAN CONTROL..........................................................................................................
02-05
2-4 EXPANSION VALVE CONTROL...............................................................................
02-08
02-05
02-07
2-3-3 Low noise mode..................................................................................................
02-08
2-3-4 Other Control.......................................................................................................
2-3-1 Cooling Operation...............................................................................................
02-06
2-3-2 Heating Operation...............................................................................................
1-2-5 Indoor unit connection check procedure ............................................................. 01-08
1-2-6 Test run from the outdoor unit ............................................................................ 01-09
1-2-7 Test run from the Remote controller .................................................................... 01-09
CONTENTS
3-2 MASTER CONTROL..................................................................................................
3-1-2 "AUTO" Position...................................................................................................
3-1-1 Fan Speed Setting...............................................................................................
3-1 FAN CONTROL..........................................................................................................
3. INDOOR UNIT OPERATION
3-2-1 Operation Mode Control.......................................................................................
3-2-2 Auto Changeover.................................................................................................
03-01 03-01
03-01 03-02 03-02 03-04
3-3 LOUVER CONTROL..................................................................................................
3-2-3 "COOL" Position..................................................................................................
03-05
3-2-4 "HEAT" Position..................................................................................................
03-05 03-06
3-5 DRAIN PUMP OPERATION.......................................................................................
3-4 ELECTRONIC EXPANSION VALVE CONTROL......................................................
3-6 FUNCTION..................................................................................................................
03-09 03-09 03-10
3-6-1 Auto Restart.........................................................................................................
03-10
4-1-2 Outdoor Unit Display...........................................................................................
4-1-1 Indoor Unit Display..............................................................................................
4-1 NORMAL OPERATION..............................................................................................
4. TROUBLE SHOOTING
4-2 ABNORMAL OPERATION.........................................................................................
4-2-1 Indoor Unit Display..............................................................................................
04-01 04-01
04-02
04-03 04-03
4-2-4 Remote Controller Display...................................................................................
4-2-3 Error Code List for Outdoor Unit..........................................................................
4-2-2 Outdoor Unit Display...........................................................................................
4-3 TROUBLE SHOOTING..............................................................................................
04-04 04-05
4-2-5 Error Code List for Simple and Wired Remote Controller...................................
04-07
4-2-6 Error Code List for Group Remote Controller......................................................
04-07
4-2-7 Error Code List for External Switch Controller.....................................................
04-07
+1
4-2-8 Error Code List for Signal Amplifier.....................................................................
04-07
+1
4-2-9 Error Code List for Network Convertor................................................................
04-07
+1
4-2-10 Trouble Level of System.....................................................................................
04-08
04-06
04-11
4-3-3 Trouble Shooting for Optional Parts....................................................................
4-3-2 Trouble Shooting With Error Code (OUTDOOR UNIT).......................................
4-3-1 Trouble Shooting With Error Code (INDOOR UNIT)...........................................
04-11 04-22 04-63
4-4 SERVICE PARTS INFORMATION............................................................................ 04-84
3-6-2 Icing Protection Control.......................................................................................
03-10
3-6-3 Oil Recovery Operation.......................................................................................
03-10
3-7 TIMER CONTROL......................................................................................................
03-11
3-7-1 Wireless Remote Controller................................................................................
03-11
3-7-2 Group Remote Controller..................................................................................... 03-13
3-7-3 Wired Remote Controller..................................................................................... 03-15
4-2-11 Error History Mode..............................................................................................
04-10
CONTENTS
5-2-1 Indoor Unit............................................................................................................
5-2 WIRING DIAGRAM....................................................................................................
5-1 REFRIGERANT CIRCUIT..........................................................................................
5. APPENDING DATA
5-3-1 Pressure sensor..................................................................................................
05-01
05-02
05-02
5-2-2 Outdoor Unit.........................................................................................................
05-15
5-3 CHARACTERISTICS OF SENSORS........................................................................
05-16
05-16
5-3-2 Thermistor resistance..........................................................................................
05-17
5-3-3 Saturation temperature and saturation pressure tables (R410A)........................
05-18
5-3-4 Temperature and pressure of refrigerant (Graph)...............................................
05-19
6. DISASSEMBLY PROCESS
1. TEST RUN
Before execution
Execution 1/2
Location decision
Execution procedure and precautions Reason
01-01
1-1 EXECUTION PROCEDURE AND EXECUTION PRECAUTIONS
1. TEST RUN
Sleeve and insert work
Indoor unit installation
Refrigerant piping work
Drain piping work
Duct work
Heat insulation work
Electrical work
Outdoor unit foundation work
Outdoor unit installation
Refrigerant piping connection work
Air tightness test
Vacuum drying
Use new refrigerant piping of the thickness specified by the D&T manual. Since R410A dedicated tools are necessary, prepare them in advance. Absolutely avoid use of existing piping. If use of existing piping is unavoidable, the piping must be cleaned.
Use pipe that is not dirty inside. Confirm the design for the piping ( Diameter, Thickness ) When the pipe is left standing, protect it. Confirm the angle of separation tube and header correctry. Finish flaring exactly. Confirm the width across flats dimension and shape of flare nuts. Always blow nitrogen while brazing. Perform flushing before connecting the equipment.
Always make the downward slope of the drain pipe 1/100 or greater and make the horizontal length within 20m. Use hard polyvinylchloride pipe as the drain pipe. Support the drain pipe between 1.5 to 2.0m. Use pipe of 1 rank up (VP30 or greater) as central piping.
Prevention of water leakage
Foreign matter, water, etc. in the piping will cause faulty cooling and compressor trouble. Incorrect pipe diameter will cause faulty cooling Incorrect angle of separation tube or header will be cause poor cooling or refrigerant noise problem Refrigerant leakage will cause low performance and abnormal stopping
Prevention of water leakage
Prevention of water leakage
Refrigerant leakage will cause low performance and abnormal stopping.
Refrigerant leakage will cause low performance and abnormal stopping.
Mixing in of vacuum pump oil by reverse flow will cause equipment trouble.
Always use a level and keep the indoor unit level. If the equipment is tilted toward the drain port, install it so that the tilt is within 10mm. Excessive tilt will cause water leakage.
Select the size of the heat insulating material according to the ambient temperature and relative humidity of the refrigerant. Use a heat insulating material having a heat conductivity of 0.043W/ (m.k) or less.
When making flare connections always use a torque wrench and tighten the flare nut positively to the specified torque.
Pressurize the product with nitrogen gas up to the design pressure and conduct a 24Hr air tightness test.
Install a vacuum pump with reverse flow check mechanism or a reverse flow check adaptor to a conventional vacuum pump and use. Pump down sufficiently. Approximately 1 hour or longer after -0.10MPa reached. Allow to stand for approximately 1 hour after stopping the vacuum pump and confirm that the needle does not return. Air purging using refrigerant is strictly prohibited.
1
1
1
2
3
2 3 4 5 6
1
2 3 4
2
3
Vaccuming mode
This function is used for vacuuming the indoor unit and the connection piping.
Note: For starting Vaccuming mode, the refrigerant address setting has to be finished.
When the [vacuuming mode] is set, <Push switch setting, F3:21> EEV of connected all indoor units opens. So, the vacuuming indoor unit and piping becomes easier.
When the vacuuming ends, please turn off the power supply for all of the indoor units and the outdoor unit, [vacuuming mode] is released.
*
recommend the vacuuming mode
Do not install the units in the place not recommended in the installation manual.
The performance may drop significantly due to the protection controlling
Use of a refrigerant other than the specified refrigerant will invite equipment trouble
Confirmation of Refrigerant used
Preparation of execution drawings
Confirmation of installation site
Preparation before execution
Check the characteristics of the refrigerant used and grasp the special features of the refrigerant. If refrigerant must be charged, always charge the refrigerant specified for the product.
*Confirm the product design pressure. < R410A 4.20MPa >
Prepare the design for the system
Secure the necessary pressure resistance.
When performing piping work, observe the following items so that the inside of the piping is clean and air tight.
7 8
01-02
[Note] Perform in the power OFF state.
Execution 2/2
Set according to the length of the connection piping. Set to "Standard (40 to 65m)" at the factory. Set using the push button SW on the outdoor unit main PCB. < Refer to the Page 01-16 Setting mode F2-00 > Set the pipe length to be the nearest indoor unit from the outdoor unit
Set the refrigerant circuit address and indoor unit address. Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch PCB) or from a remote controller or from a push button SW on the outdoor unit Main PCB < Automatic address setting, Refer to the Page 01-07 Setting mode F3-11>
Initial setting
Gas leak test
Use an R410A dedicated leak tester to check for gas leaks.
1
2
3
Confirm the additional refrigerant amount with the installation manual, etc. Always take the R410A refrigerant from the cylinder liquid phase and charge it using the gas phase. (Do not lay a cylinder with siphon pipe on its side.) Use an R410A dedicated gauge manifold and charging hose. Charge refrigerant using the liquid pipe. When the defined amount of refrigerant cannot charge using the liquid pipe, charge refrigerant using the gas pipe while opearing the cooling test run. Charge refrigerant bit by bit with cautious operation of valve for the liquid refrigerant back prevention.
If taken from the air phase, since the composition of the refrigerant which is charged will change, low performance and abnormal stop will occur easily. Prevent erroneous sealing in of refrigerant.
A leak tester for other than R410A cannot detect leaks.
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
4
Turnover & explanation of operation
Address setting for Indoor unit
Test run & adjustment
Piping length setting
Addition refrigerant charging
5
Indoor unit connection check
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state after all indoor units have stopped operation.
When setting the address of Signal amplifier, please refer to the installation manual of the signal amplifier. The address setting can be set by automatically from 1 outdoor unit on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Address setting for Signal Amp
- When using signal Amps -
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
[Note] Perform in the power ON state after all indoor units have stopped operation
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Dual address setting No. is not allowed in one network.
When the setting is not same as the real piping length, the system may not work correctly.
Dual address setting No. is not allowed in one network.
Dual address setting No. is not allowed in one network.
Normal operation will not be possible without performing the indoor unit connection check.
Before starting the system, check on the number of indoor units and the total capacity. < Refer to the Page 01-08 Setting mode F3-12 >
Execution procedure and precautions Reason
1
2
Confirm the DIP SW setting SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF, SET 4: Factory setting
If the DIP SW setting is wrong, the sys­ tem may not work correctly
3
Confirm the Terminal resister setting SET 5-4 OFF: Disable, ON: Enable
If the Terminal resister setting is wrong, the system may detect transmission error
If the pipe length is set as the farthest indoor unit, the nearest operating indoor unit may be stopped the operation by the icing up protection as by over cooling.
Outdoor unit: 32A ( AJ*A36,45,54LALH )
Indoor unit: 20A
Leakage current: 30mA 0.1sec or less
Install a breaker (Included with Earth Leakage Circuit Breaker) in accordance
with the related laws and regulations.
Outdoor unit: 6mm
2
2 wires + Ground 4mm
2
Indoor unit: 2.5mm2 2 wires + Ground
Outdoor unit side: AC 230V (220-240V)
Indoor unit side: AC 230V (220-240V)
Use crimp-type terminals with insulating sleeves for stranded conductor cable
Power
source
Shall be no scratches, deformation, etc. (Be careful of deformation of the front panel)
Shall be checked and entered in the check sheet.
Shall be checked and entered in the check sheet.
Connection points check & loose terminal block screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
DIP SW SET1, SET4 : Factory setting, SET2,SET3, SET5-1,2,3: ALL OFF Terminal resistor setting SET5 - 4 OFF: Disable, ON: Enable Check the resistance value for each network segment
Refer to the installation manual 7.7
Refrigerant circuit address setting (SET : REF AD x10 and REF AD x1)
Comparison of calculated value and value written on electrics box. Entered in check sheet.
Refer to the installation manual 8.3.2
Gas pipe: fully open
Liquid pipe: fully open
There shall be no scratches, deformation, tilting, etc.
Shall be checked and entered in the check sheet.
Shall be installed positively.
Connection points check & loose terminal panel screws check
0.33mm2, shielded wire used (22AWG)
Connection points check & loose terminal panel screws check
0.33mm
2
Connection points check & loose terminal panel screws check
Check whether or not the heat insulation material is installed without a gap.
Refrigerant circuit address (REF AD)
Indoor unit address (IU AD)
At automatic address setting, IU AD/REF AD shall be [0].
Remote controller address (RC AD)
Function setting (Remote controller custom code/ external input switching/
auxiliary heater ON-OFF)
Indoor
unit
Outdoor
unit
Judgement standard
Check
Check contentsProcedure
1-2 TEST RUN METHOD
1-2-1 Check Items Before Power ON
01-03
[Note] If operated with the 3-way valve closed, the oil discharged from the compressor will not be returned and will lead to trouble.
Circuit breaker capacity
Type of power source wiring
Supply power source
Appearance
Serial No.
Drain cap installation
Power source wiring connection
Type of communication line
Communication line connection
Type of remote controller wiring
Remote controller wiring connection
Connection piping
Rotary SW setting
DIP-SW setting
Appearance
Serial No.
Outside air temperature
Power source wiring connection
Type of communication line
Communication line connection
Connection piping
DIP-SW setting
Rotary SW setting
Additional refrigerant amount
3-way valve
Wiring on terminal blocks
Addresses shall be assigned to all indoor units / Signal amps. Check for unset or duplicated addresses. < For the setting, Refer to the page 01-06, 07 >
All the indoor units in the same refrigerant
circuit
shall enter the coolingtest run
state.
The outdoor units corresponding to the operation capacity of the indoor
units shall operate. < Test operation procedure, Refer to the page 01-09,10 >
Cooling
test run
All of the
indoor units
operation
(after 30 mins)
Automatic address setting
Address read
Outdoor unit circuit breaker ON
Indoor unit circuit breaker ON
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Address
setting/
check
There shall be no Error information on the 7-segment display on the Main PCB.
Between L - N AC230V (220-240V)
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
HPS: 2.7 MPa
LPS: 0.9 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV Excel)
Outdoor unit push button
SW operation
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
Heat exchange inlet temperature (indoor unit)
Heat exchange outlet temperature (indoor unit)
Compressor operation
Data output
1-2-2 Check Items After Power ON
01-04
Function setting
Are the necessary functions set ? < For the setting, Refer to the page 01-15 18 >
Outdoor unit Main
PCB push button SW setting/check
[Note] Cooling test run for each refrigerant circuit. If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Judgement standard
Check
Check contentsProcedure
Power ON
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
[Note] Turn on all indoor units power in the same refrigerant circuit address. When the system operates with the indoor units remaining no power, it is cause of malfunction.
Indoor unit connection check
Are the number of connecting indoor units correct ? Is the total capacity of indoor units correct ? < For the checking, Refer to the page 01-08 >
Indoor unit
connection check
Address record
Address hold check
All the indoor units and outdoor units of the same refrigerant circuit can be checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool after indoor/outdoor circuit breakers were turned OFF to ON.
[Note] Before connecting service tool, the address setting has to be completed.
Fan operation
Louver operation (except duct)
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Indoor unit
individual
operation
Shall be switched to all fan speeds in the cooling mode.
Louver shall be switched to all positions. Shall also swing.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-05
Judgement standard
Check
Check contentsProcedure
These are representative figures of AJYA54LALH at the standard condition. ( Indoor : 27
°C, Outdoor : 35°C ) If conditions are different from those above mentioned, the figures will be changed slightly. It depends on following conditions.
Outdoor unit capacity Indoor and outdoor temperature Indoor unit capacity Pipe length etc
<Indoor unit service tool + actual measurement>
1. Error occured
- Check on the Error code on the Remote controller or Indoor unit or Outdoor unit or Service tool and check the description of the Error code. < Refer to the Trouble shooting in the Service manual.> < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1>
2. No good performance without error code
- Check if the protection controlling is operating or not Evaporator Icing up protection, High discharge temperature protection,etc. < Refer to the part of protection controlling in the Service manual >
- Check on the refrigerant circuit Refrigerant amount, Pipe blockage, Wrong position of separation pipes etc. < Refer to the Execution of precautions 1-1 and Check item Before power ON 1-2-1> < Refer to the regulation of installation in the Installation manual>
Trouble shooting on Test run operation
01-06
1-2-3 Automatic address setting for signal amplifiers When using signal amplifiers
When setting the address of the signal amplifier, please use the factory setting. (See the installation manual of the signal amplifier)
When the system is normal, nothing will be displayed on the 7 segment display.
When ERROR is displayed, inspect the units. Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB to conÞ gure settings according to the procedures below.
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the "SELECT" button until [ F3 ] is displayed)
MODE/EXIT
SELECT
SELECT
ENTER
SELECT
ENTER
Automatic address setting for
signal ampliÞ ers
Press the “SELECT” button until "10" is displayed
Press the “ENTER” button for more than 3 seconds
* Setting is complete when the number of unit is displayed
End
ENTER
MODE/EXIT
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
*
01-07
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
Check that the rotary switch IU AD on the indoor unit Main PCB is set to “00”.If it is not set to “00”, it means the address of that device is not set. (Factory default is “00”).
Turn on the power of the indoor and outdoor units.
When the system is normal, nothing will be displayed on the 7 segment display. When ERROR is displayed, inspect the units.
Use the “MODE/EXIT”, “SELECT”, and “ENTER” buttons on the outdoor unit Main PCB
to configure settings according to the procedures below .
1: FUNCTION Setting
First 2 digits Last 2 digits
(the display when the main power is turned on)
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
MODE/EXIT
SELECT
SELECT
ENTER
1-2-4 Automatic address setting for Indoor units
It may take about 10 minutes for completing the processing.
End
First 2 digits
Last 2 digits
Press the “SELECT” button until “11” is displayed.
Press the “ENTER” button for more than 3 seconds.
Automatic address setting for indoor units
The number of indoor units with normal set­tings will be displayed at the first 2 digits of
the 7 segment display. The number of indoor units with error will be displayed at the last 2 digits.
NOTE) After the “ENTER” button is pressed, the
end processing will occur for about 30 seconds.
During this period, the 7 segment will blink.
ENTER
SELECT
ENTER
Error
Found
01-08
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
1-2-5 Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
MODE/EXIT
SELECT
SELECT
SELECT
ENTER
LED105
LED104
ENTER
Set to Function mode [F3].
(When [F4] to [F9] are displayed, continue to press the “SELECT” button until [F3] is displayed.)
Press the “SELECT” button until “12” is displayed.
When indoor unit connection check can not be performed
Turn on the power • of indoor unit and outdoor unit.
Press the
“ENTER”
button for
more than 3 seconds.
This will be displayed when the • Indoor unit connection check starts.
MODE/EXIT
SELECT
ENTER
ENTER
ENTER
(*1)
(*2)
(*1) The number of connected
indoor units
(*2) Volume ratio of the indoor
units connection
Ex.) When 8 units are connected
Ex.) When the ratio is 120%
Please refer to the following “Error code” for details
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
When it finishes normally, nothing will be displayed on 7 segment display.
When error occurs
Confirm the number of connected indoor • units and the volume ratio of the indoor units connection.
Exit indoor unit connection check • mode.
01-09
1-2-6 Test Run From Outdoor Main PCB
All the indoor units connected to the outdoor unit can be test-operated by push button setting.
LED105 LED104LED105 LED104 LED105 LED104LED105 LED104
L
ED
1
0
5
L
ED
1
0
4
LED105 LED104
LED105 LED104
[ Cooling test run ]
[ Heating test run ]
[ Test run stop ]
LED105 LED104
LED105 LED104
LED105 LED104
LED105 LED104
Press the ENTER button for at least 3 seconds.
Press the "ENTER" button or Time out ( 5 seconds)
MODE / EXIT
< Pursuance completion >
< Monitoring condition >
< Mode select condition >
< Return to mode select condition >
< Fuction select condition >
[ Function mode ]
SWITCH POSITION
SW107 SW108 SW109
MODE
/EXIT
SELECT ENTER
LED101
(GREEN)
POWER
MODE
LED105 LED104
LED102
(RED)
ERROR
Push button switch
7 Segment LED Lamp
Outdoor unit printed circuit board
TEST RUN SETTING
[ Monitoring mode ] [ Setting mode ]
[ Error history mode ]
For a detailed description of push button operation, refer to the [D&T manual Chapter 6. SYSTEM DESIGN]
LED105 LED104
< Return to monitoring condition >
example, Normal indicate : [ Cooling mode ]
[ Central control setting Forced reset ]
There are the following 2 methods of resetting test operation.
Automatic reset when 60 minutes has elapsed.(1)
Reset when operation stop was performed.(2)
Note
SELECT
SELECT
SELECT
SELECT
SELECT
SELECT
ENTER
ENTER
ENTER
MODE / EXIT
1-2-7 Test Run From Remote Controller
Press the TEST RUN button on the remote controller, while the air conditioner is running. To end test run operation, press the remote controller START / STOP button.
When the air conditioner is being test run, the OPERATION and TIMER lamps of indoor unit flash slowly at the same time.
START / STOP button
TEST RUN button
2. Standard wireless remote controller
Stop the indoor unit. Push the button and button simultaneously for more than two seconds. The air conditioner will start to conduct a test run and " " will display on the remote controller display. However, the , setting button does not have function, but all other buttons, displays, and protection functions will operate.
To stop test run, push the START / STOP button of the standard wired remote controller. For the operation method, refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
Perform the test operation for 60 minutes.
1. Standard wired remote controller
UTY - LNH
UTY - RNK
button
button and
Stop the indoor and outdoor units. Push the remote controller simultaneously for more than three seconds. The air conditioner will start to conduct a test run and " " will display on the temperature display.
SET
However the setting button does not have function but all other buttons, displays and protection functions will operate.
To stop test running press the button of the simple remote controller. For the operation method refer to the operating manual and perform operation check. Check that there are no abnormal sounds or vibration sounds during test run operation.
3. Simple remote controller
UTY - RSK
01-10
TIMER MODE
CLOCK ADJUST
TEST RUN
RESET
TIMER
SLEEP
FILTER RESET
SWING
SET
SET
ECONOMY
FANMODE
START
STOP
SET
TEMP.
TIMER MODE
DAY
SET BACK
CLOCK ADJUST
DAY OFF
TIMER DELETE TIMER SET
FAN MODE
SET TEMP.
START / STOP
6)
or
[ Select All (F2) ]: All of R.C.Group (Indoor units) [ Identify Unit (F3) ] : Specific R.C.Group (Indoor unit)
Setup Menu
Indoor unit Special Setting
Test Operation
Central Controller Setting
Indoor unit Special setting
Indoor Unit Set Temp. Range
Filter Sign
R.C. Prohibition
Group
Select All
Identify Unit
Clear Unit
On
Select All
Details
Off
Operation
Help
Setup Menu
Monitor Group
1
2
Monitor - All
UTY-DCG
On
Coll
25.0
05/31 03:59
05/31 03:59
05/31 03:59
Test Operation
05/31 03:59
RCG_05
Test run operating procedure
<Monitor screen (icon)>
<Monitor screen (list)>
(1)
(1)
(2)
( * )
(1)
(1)
(2)
( * )
01-12
5. Touch panel controller
UTY - DTG
(1) Select the objective you want to test run. Select the objective icon or list at the monitor screen. (Multiple selections is possible) Select all the devices registered as objectives by pressing "Select All" on the monitor screen.
(2) After objective selection at (1), switch to the <Setting screen> by pressing "Operation".
On
C
1
On
On
On
On
On
On
On
On
Office B
Conference
A
Conference B
Meeting 1
Meeting
2
Parking lot
Meeting
3
Entrance
Restrant
Room
101
Office A
PC Room
Top Up
Down
List
Heat
Auto
Cool
26.0 C
24.0
C
Auto
22.0
C
Auto
24.0 C
21.5 C
Heat
21.5 C
21.5 C
Cool
Off
Off
Off
All
21.0
C
Heat
All
Lange Group
Lange Group
Top Up
Down
List
Office A
PC Room
Room 101
Restrant
Entrance
Meeting 1
Off
Off
Off
Mixed
Heat
Auto
Cool
24.0 C
26.0 C
Low
Auto
21.5 C
High
Office B
Mixed Mixed Mixed
Mixed
Name
Expand
Status Mode
Set Temp
Fan
R/C Prohibit
On
On
On
Status: On
Status: On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Monitor Mode
Monitor Mode
Heat
21.0
C
Off
On
Operation
Clear All
Select All
Schedule
Setting
Off
On
Operation
Clear All
Select All
Setting
Schedule
Group Error
Schedule Filter Sign Op. Controlled Op. Restricted
RC Prohibition All On/Off On
Mode Temp. Timer
Filter
Mode Set Temp.
Group Error
Schedule Filter Sign
Op.Controlled Op.Restricted
<Setting screen>
(3) Switch to the <Details setting screen> by pressing "Optional Setting" on the setting screen.
<Details setting screen>
(4) Send (start) test run by pressing "Start" and then pressing "OK" on the details setting screen. Test run continues for 60 minutes. During sending, the slave screen shown below is displayed. When sending is completed, the sending slave screen and details setting screen are closed.
To interrupt test run, select the device being test run and execute an operation stop command.
(*) At the monitor screen, test run is reset by stopping operation of the objective devices by pressing "OFF". (*) Or test operation is reset by stopping operation of the objective devices by pressing "Off" of Operation and then pressing "OK" on the setting screen.
01-13
(3)
(4)
(5)
( * )
Cancel
Off
On
OK
Transferring data. Please wait.
On
On
Reset
Cancel
Stand by (Defrost) Stand by (Oil Recovery) Test Operation
Start
Air Flow Direction
Economy
Anti Freeze
Filter Sign
Operation
Test
Up
Down
Swing
Swing
Left Right
Off
Off
Special State
Status: On
1
2
3
4
5
1
2
3
4
SettingOptional
Cancel
OK
On
Off
Auto
Auto
Cool
Dry
Fan
Heat
Operation Controlled
High
Med
Low
Quiet
Meeting Room
24.0 C
operation
R/C Prohibition
Mode Set Temp. Fan
Optional
Setting
All
On/Off
Filter
Timer
Temp.
Mode
On
10/11.2008.Mar. 02:20 PM
10/11.2008.Mar. 02:20 PM
Air Flow Direction Economy Anti Freeze Filter Sign Test Operation
Control Unit :
Operation Setting
Operation Setting
OK
Status: On
1-3 TEST RUN CONTROL
01-14
1. When the test run signal is transmitted from standard wired, wireless remote controller, simple remote controller, transmitted network, and outdoor unit.
(1) The test run operation starts and the electric expansion valve is controlled to a maximum flow, regardless of the temperature condition.
(2) Frost prevention operation has priority over item(1). (3) Whether state of the indoor unit operates or stops, All units in the same refrigerant circuit will start to conduct a test run in accordance with the operation mode set by push switch of outdoor unit ( see 1 - 2 - 3 ). (4) After 60 minutes passes, the test run stops. (5) Test running initialization is shown below.
Fan speed Hi Hi
Room Temperature Indication 18 30
Hi Hi
18 30
Vertical Air Direction Panel
Swing
Operating Mode
Cooling Heating Cooling Heating
OFF OFF
Position
1
Position
4
EXCEPT FOR THE DUCT MODEL DUCT TYPE
CEILING TYPE
COMPACT CASSETTE TYPE
COMPACT WALL MOUNTED TYPE
4
3
2
1
1
2
3
4
*EXAMPLE
1
2
3
4
4
3
2
1
Push switch onoutdoor unit PCB
00 Connected number of indoor unit The number of the communicating unit is displayed
01
Software version :
[ ] [ ] [ ] [ ] [ ] displays by five items
It skips when there is no suffix
02 Software version of INV PCB
03 Software version of communication PCB
Operation of each part
10 Rotational speed of outdoor unit fan motor The rotational speed of the outdoor unit fan motor is displayed
[ rpm ]
11 Rotational speed of INV compressor The rotational speed of the compressor is displayed
[ rps ]
12 Current value of INV compressor Current value of INV compressor is displayed
[ A ]
14 Pulse of EEV1 Pulse of EEV1 is displayed
[ pls ]
15
Pulse of EEV2 Pulse of EEV2 is displayed
[ pls ]
Time guard 20 Accumulated current time Accumulated current time is displayed
[ 10 hour ]
21 INV compressor accumulated time
[ Cooling ]
Accumulated time is displayed in the cooling operation of the INV compressor [ 10 hour ]
22 INV compressor accumulated time
[ Heating ]
Accumulated time is displayed in the heating operation of the INV compressor [ 10 hour ]
Refrigerant cycle data 1
30 Information on Thermistor 1
( INV compressor discharge temperature )
The value of the Thermistor 1 is displayed
32
Information on Thermistor 3
( Outdoor temperature )
The value of the Thermistor 3 is displayed
33 Information on Thermistor 4
( Suction temperature )
The value of the Thermistor 4 is displayed
34
Information on Thermistor 5
( Heat-exchanger temperature )
The value of the Thermistor 5 is displayed
36
Information on Thermistor 7
( Liquid temperature 2 )
The value of the Thermistor 7 is displayed
37
Information on Thermistor 8
( Sub-cool heat-exchanger inlet temperature )
The value of the Thermistor 8 is displayed
38 Information on Thermistor 9
( Sub-cool heat-exchanger outlet temperature )
The value of the Thermistor 9 is displayed
39 Information on Thermistor 10
( INV compressor temperature )
The value of the Thermistor 10 is displayed
50
Information on pressure sensor 1
( High pressure sensor )
The value of the pressure sensor 1 is displayed [ MPa ] or [ psi ]
51
Information on pressure sensor 2
( Low pressure sensor )
The value of the pressure sensor 2 is displayed
[ F1 ]
Monitor mode
Setting Mode
ITEM CODE No.
Information contents
Refrigerant cycle data 2
Device and system
Software version of outdoor unit
Classification
01-15
1-4 Field Setting And Monitor Mode List for Outdoor unit
[ MPa ] or [ psi ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
[°C ] or [°F ]
Setting Mode
ITEM CODE No.
Setting Function
Default
Install 00 Pipe length setting 00 40-65m
Setting mode
01 0-40m 02 65-90m 03 90-120m 04
Correction 10
Sequential start shift
00 01 02 03
11
Cooling capacity shift 00 Normal mode
01 Save energy mode 1 (+2°C) 02 High power mode 1 (-2°C) 03 High power mode 2 (-4°C)
12
Heating capacity shift
00 Normal mode 01 Save energy mode (-2°C) 02 High power mode 1 (+2°C) 03 High power mode 2 (+4°C)
13 Defrost setting shift 00 End temperature:Normal
01 End temperature:Higher
01 Emergency stop
21 Operation mode selecting method 00 Priority given to the first command
01 Priority given to the external input of outdoor unit 02 Priority given to the master indoor unit
22
Snow falling protection fan mode
00 Normal operation 01
23
Interval setting for snow falling
00 Standard 01 02 03
24
High static pressure mode
00 Standard 01 02
28 Change of unit (Temperature) 00 Celsius(°C)
01 Fahrenheit ( F)
29 Change of unit (Pressure) 00 MPa
01 psi
Change of
Change of function 3
30 Energy saving level setting 00 Level 1 (stop)
01 Level 2 (operated at 40% capacity) 02 Level 3 (operated at 60% capacity) 03 Level 4 (operated at 80% capacity) 04 Level 5 (operated at 100% capacity)
Low noise 40 Capacity priority setting 00 Off (quiet priority)
01 On (capacity priority)
41 Low noise mode setting
00 Off (Normal)
60
Back up operation
00 Standard 01
01 On (Low noise mode operation is always done)
42
Low noise mode operation level
00 Standard (47dB) 01
[ F2 ]
ITEM CODE No.
Standard
20 Switching between forced stop or 00 Forced stop
Change of
function 1
emergency stop
protection fan mode
setting 1
(in low noise mode)
function 2
Classification
01-16
Push switch on outdoor unit PCB
Setting is forbidden
Setting is forbidden
Setting is forbidden
Setting is forbidden
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No of the electricity meter connected to CN135.)
*3
00~99 Setting number x00~x99
00
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the electricity meter connected to CN135.)
*3
00~02 Setting number 0xx~2xx 00
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of the electricity meter pulse setting connected to CN135.)
*4
00~99 Setting number xx00~xx99 00
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit of the electricity meter pulse setting connected to CN135.)
*4
00~99 Setting number 00xx~99xx 00
Change of function 4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective. Available setting number is "001" to "200" *4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective. Available setting number is "0001" to "9999"
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
( Refer to Design & Technical Manual for details.)
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
14 Pressure equalization time shift
before defrosting start
00 No time shift
01 Shift 1 ( 30 sec.) 02 Shift 2 ( 60 sec.) 03 04
Shift 3 ( 90 sec.)
Shift 3 ( 120 sec.)
Only for solution :
Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
compressor operating time in heating will be shorter.
Only for solution
04 High power mode 3 (-5°C)
03
Oil recovery
00
02
Setting is forbidden
01
25
Oil recovery Abnormal low pressure protection control
00
01
26
27 Error code Notification
00 01
Enable Disable
31
Heating Starting prosess
00 01
Standard
Standard
Standard
Setting is forbidden
Setting is forbidden
Setting is forbidden
Setting is forbidden
Setting is forbidden
Push switch on outdoor unit PCB
Forced operation 00 Cooling test run
Forced thermostat-ON in Cooling.
Function mode
01 Heating test run Forced thermostat-ON in Heating.
02 Test run stop Test run is stopped.
Install and maintenance 1
10 Signal amplifier automatic address Automatic address setting operates for signal amplifier.
11 Indoor unit automatic address
21 Vacuuming mode Vacuuming mode operatesRefer to page 01-01 for the function.
Clear 30 Error history clear All the abnormal code histories are cleared.
32 Current time clear Accumulated current time becomes [ 0 ]
33 INV compressor accumulated time clear Accumulated time of the INV compressor becomes [ 0 ]
35 Field setting all clear Return to default the all set items.
Reset 40 Abnormal reset It was displayed when abnormality occurs, and abnormal
code is reset.
This is a function that uses to clear abnormal display after the repair is completed.
Please operate the switch after power off or power on the outdoor unit.
Specialtyfunction 91 Foreced Central control function release
Maximum memorized indoor unit number is reset.
Setting Mode
ITEM CODE No.
Setting Function
Install and maintenance 2
*
Automatic address setting operates for indoor unit of same refrigerant circuit.
[ F3 ]
01-17
Compressor Motor Loss of Synchronization Compressor 1 Temperature Abnormal Inverter Compressor Start Up Error Discharge Temperature 1 Abnormal Low Pressure Abnormal Current Sensor 1 Error Trip Detection Rush Current Limiting Resistor Temp Rise Protection Outdoor Unit FAN motor 1 Lock Error Outdoor Unit FAN motor 2 Lock Error
< Reset Error Item List By Abnormal Reset Setting >
*
Push switch on outdoor unit PCB
1 time ago (Newest)
Error History Mode
2 times ago
5 times ago
Meaning of Error History Number
ITEM CODE No.
Information contents
[ F9 ]
00
01
02
03
04
05
06
07
08
09
Error history
10 times ago (Oldest)
4 times ago
3 times ago
6 times ago
7 times ago
8 times ago
9 times ago
When the centralized control device failure, and the centralized control setting cannot be released, this function is used.
All the limitations set with the centralized control device are released.
Maximum memorized indoor unit number reset
41
"E14.5:Indoor unit number shortage" error is cleared.
When the error occurred, the error code is memorized up to 10 on Main PCB.
If the memorized error code becomes over 10, the oldest one will be erased.
Refer to Chapter 4.TROUBLE SHOOTING
4-2-3 Error Code List of Outdoor unit
12
The number of indoor units and the total capacity of indoor units of same refrigerant circuit.
Indoor unit connection check
36
Clear memorized information of "F3 - 12 " ( Indoor unit connection check )
The information of the number of indoor units and the total capacity of indoor units are cleared.
34 Constant Speed compressor accumulated
time clear
Not in Use on J-Series
90
Foreced Normal operation release Normal operation foreced release
01-18
1-5 Field Setting / Function Setting for Indoor unit
Setting Mode
ITEM CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by remote controller
01 Indoor unit address 00~63 00~63 00 02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable 02 Display only on central remote control
Airflow 20 Ceiling airflow 00 Default
(Cassette type only) 01 High ceiling
23 Vertical airflow direction 00 Default
01 Raise
24 Horizontal swing airflow direction 00 Default
01 Left half
02 Right half
Correction
30
Cool air temperature trigger
00 Default (0°C)
01 Temperature overshoot setting (+2
°C)
02 Temperature undershoot setting (-2
°C)
31 Heat air temperature trigger 00 Default (0°C)
01 Temperature undershoot setting (-6
°C)
02 Temperature slightly undershoot setting (-4
°C)
03 Temperature overshoot setting (+4
°C)
Change of 40 Auto restart 00 Enable
01 Disable
43 Cool air prevention 00 Enable
01 Disable (Ventilation mode)
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target 00 All
01 Display only for central remote control
ITEM CODE No.
Function 1
Classification
26
32
Model name Range of static pressure
AR XD 07L ATH
0 to 90 Pa
AR XD 09 LATH AR XD 12LATH AR XD 14LATH AR XD 18L ATH AR XD 24L ATH 0 to 50 Pa
00 01 02 03 04 05 06 07 08 09 31
0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa 60 Pa 70 Pa 80 Pa 90 Pa 25 Pa
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is different from one model to other.
Temperature correction in Auto
00 01
Disable Enable (Nonfunctional on J2 Series)
2. OUTDOOR UNIT OPERATION CONTROL
2-1 INPUT / OUTPUT LIST
2. OUTDOOR UNIT
02-01
Input / output or kind of detail Control range
Discharge pressure sensor <HIGH> Pressure sensor Measure range 0.0 to 5.0MPa Suction pressure sensor <LOW> Pressure sensor Measure range 0.0 to 1.7MPa Discharge temperature sensor <TH1> Themistor <Blue>
Measure range 10 to 130
Heat exchanger temperature sensor <TH5> Themistor <Pink>
Measure range -35 to 70
Sub-cool heat exchanger (inlet) sensor <TH8> Themistor <White>
Measure range -35 to 70
Sub-cool heat exchanger (outlet) sensor<TH9> Themistor <Brown>
Measure range -35 to 70
Liquid temperature sensor <TH7> Themistor <Green>
Measure range -35 to 70
Suction temperature sensor <TH4> Themistor <Red>
Measure range -35 to 70
Outdoor temperature sensor <TH3> Themistor < - >
Measure range -25 to 58
Operation current sensor
Current transformer
Rotary SW & DIP-SW & Push SW
Electronic expansion valve 1 (Main) EEV coil Operating voltage DC12V Electronic expansion valve 2 (SC-Hex) EEV coil Operating voltage DC12V
4-way valve 4-way valve coil AC220-240V, 50/60Hz 6/5 W Solenoid valve Comp pressure equalizing valve AC220-240V, 50Hz, 6W Crank case heater For Inverter Compressor AC240V, 25W Base heater Field supply AC220-240V, 35W
LON WORKS Inverter communication
External input 1 (CN131) (Low noise mode operation) External input 2 (CN132) (Cooling / Heating priority) External input 3 (CN133) (Outdoor unit operation peak control) External input 4 (CN134) (Emergency stop operation)
Dry contact input
Single LED 101 Single LED 102
LED display
Address and function setting
Display the information on operation, error and setting with single LED and 7 segment LED.
Control output: DC 0/12-24V, Max.30mA Control output: DC 0/12-24V, Max.30mA
External output 1 (CN136) (Error display) External output 2 (CN137) (Operation display)
ON (Error) / OFF (Normal) ON (Operation) / OFF (Stop)
Communication Input / Output
External Input / Output
I N P U
T
O U T P U T
Compressor temperature sensor <TH10> Themistor < - > Measure range 10 to 130
Pressure switch
Pressure switch
Open 4.2MPa Short 3.2MPa
Fan motor 1 (Upper) DC Brushless motor
7 Segment LED
Compressor
Magnetic relay
Operation coil AC220-240V, 50Hz
Indoor unit Outdoor unit
Fan motor 2 (Lower) DC Brushless motor
2-2-1 Operation / Stop Condition
When cooling requirement capacity or heating requirement capacity from either of the indoor units in the same refrigerant circuit is input, the compressor operates. When all the indoor units in no "cooling requirement capacity" or "heating requirement capacity",
the compressor is stopped. But in the following case, the compressor operates in accordance with operation of each mode.
During 3 minute restart prevention operation Icing protection Failure (Refer to chapter 4, TROUBLE SHOOTING )
Under expansion valve initialization At protective operation
Emergency stop Defrost operation
02-02
2-2 COMPRESSOR OPERATION
2-2-2 Capacity Control
(1) Capacity of compressor operation
By the operation of DC inverter rotary compressor, the amount of required refrigerant circulation acceding to cooling and heating load can be supplied from compressor efficiently.
DC inverter rotary compressor is able to control the amount of required refrigerant circulation in details.
Cooling/Heating load
Capacity of
compressor operation
Total capacity
Peak cut stop operation
Oil recovery
Inverter Compressor
(2) Target low-pressure and high-pressure control
In order to make the evaporation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be controlled by low-pressure sensor of the outdoor unit.
In order to make the condensation pressure of the indoor unit at the proper pressure on a variety of operations, capacity of the compressor will be controlled by high-pressure sensor of the outdoor unit.
Target low-pressure and high pressure temperature depends on system capacity, capacity of compressor operation, pipe length, and capacity shift switch settings.
<Cooling>
<Heating>
02-03
2-2-3 Speed Range of Start, Stop, And Operation
On stop mode : 0 rps
On operating mode : 20 - 100 rps
(1) Cooling starting process For cooling operation only, the upper limit speed at starting is made 50rps and is raised in +10rps increments every 60 seconds.
Speed
Time
0
50rps
60sec
Target speed
60sec
60sec
60rps
70rps
80rps
60sec
120sec 180sec 240sec
90rps
10rps
10rps
The compressor operates at the upper limit speed if the target speed is higher than the upper limit speed.
The compressor operates at the target speed if the target speed is lower than the upper limit speed.
60sec
10rps
02-04
Cancel conditions
Normal control
32rps fixed
(3) Limits the upper limit speed of the INV compressor according to the present high-pressure value.
(2) Heating starting process
At the start of heating, the compressor is started by the following process. Compressor start-up to change the 4 way valve. Capacity control returns to normal control after the end of the starting process. (target high-pressure control)
Starting process Starting process
Starting process
Starting process
3 minutes elapsed from start of process or High-pressure 2.63MPa
20 minutes elapsed from start of process or High-pressure 2.63MPa or Discharge SH 10 and Discharge temperature 10
[ a ] = 1.25 Low pressure value 2.125
High Pressure
3.60MPa
3.30MPa
(Maximum) 3.00MPa
Maximum speed = 80rps
Maximum speed = 90rps
Maximum speed = 95rps
Maximum speed = 100rps
[ a ]
< Starting process >
Compressor operates based on the required capacity at the start up, after that the target high-pressure control begins.
*However, when the following condition (A) or (B) are satisfied, starting process is not performed.
< Conditions under which starting process is not performed >
(A) The compressor temperature 32 , when the room temperature reached to the setting temperature ( Thermostat - OFF controlling )
(B) The compressor temperature 32 , when the system keeps heating mode with stop condition
< Operation >
Compressor operation speed
4rps/Min
Switching conditions of step
2-3 FAN CONTROL
2-3-1 Cooling Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
780 700 660 660 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
AJ A36LALH AJ A45LALH AJ A54LALH
Fan speed (rpm)
02-05
(Conditions which lower the fan speed) High-pressure saturation low limit of target high-pressure
saturation range and heat sink temperature 75°C
(Conditions which raise the fan speed) High-pressure saturation upper limit of target high-pressure saturation or heat sink temperature 80°C
Fan step
7
5
2
0
Outside air temperature sensor detected value
TAOUT 30°C
30°C TAOUT 20°C
20°C TAOUT 10°C
10°C TAOUT
The initial speed of the outdoor unit is detected by out door temperature sensor.
35 52
40.4
46.6
54
High-pressure saturation temperature
Outdoor temperature
Upper limit of target high-pressure saturation temp.
Low limit of target high-pressure saturation temp.
Target high-pressure saturation temp.
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
The fan is controlled to keep high puressure saturation temperature within the target range as follows
780 700 660 660 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
780 700 700 700 670 590 540 540 450 410 340 340 270 250 390 0 340 0 290 0 250 0 0 0
Step
Upper FAN Lower FAN
02-06
2-3-2 Heating Operation
Fan step
11
10
9
8
7
6
5
4
3
2
1
0
800 700 660 660 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
AJ A36LALH AJ A45LALH AJ A54LALH
Fan speed (rpm)
Switching conditions of step
Fan step
11
8
5
5
Outside air temperature sensor detected value
TAOUT 10°C
10°C TAOUT 15°C
15°C TAOUT 20°C
20°C TAOUT
Thereafter, the high-pressure is monitoring at a set time interval and the fan speed is changed by the following conditions.
(Condition which lowers the fan speed)
High-pressure 3.30MPa and heat sink temperature 80°C
(Condition which raises the fan speed) High-pressure saturation 3.20MPa or heat sink temperature 85°C
The initial speed of the first boot outdoor unit is detected by outdoor air temperature sensor value (TAOUT).
800 700 660 660 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
800 700 700 700 670 590 540 540 450 410 340 340 270 250 0 0 0 0 0 0 0 0 0 0
02-07
Capacity priority setting
Operation mode
Low noise level setting
ON
OFF
4HP
AJ*A36LALH
450
7
5HP
AJ*A45LALH
ON
ON
COOL
HEAT
«
Low noise mode and operation contents
»
( PUSH SW ) ( PUSH SW )
Normal operation
Low capacity
Not switched for 30 minutes after being once switched.
* Automatic switching
«
Settings and corresponding operations
»
LOW NOISE MODE
* Automatic switching
* Low capacity Compressor capacity is low or High-pressure is high (high-pressure saturation 58°C) at cooling or Low-pressure is low (low-pressure saturation 0°C) at heating
Operation in low noise mode
When the low noise mode setting ON from PUSH SW or EXTERNAL INPUT, the outdoor unit operates in the low noise mode as follows.
LOW NOISE MODE
The operating sound lowers from about 3 to 5 dB more than the rated value
Capacity does not become low even when switched to low noise mode
The operating noise is reduced by limiting the rotational speed of the compressor and fan motor
2-3-3
Low noise mode
410
40
450
7
410
45
450
7
410
52
450
7
410
60
450
7
410
60
450
7
410
60
6HP
AJ*A54LALH
Max FAN Step
Max FAN Step
Max Compressor Speed
Max Compressor Speed
Upper FAN Lower FAN
Upper FAN Lower FAN
Low Noise Mode
To accurately detect the outside air temperature, the fan is operated while the outdoor unit is stopped.
2-3-4 Other Control
02-08
EEV 1
EEV 2
EEV is controlled so that the system reaches closer to the target discharge temperature that is calculated from high and low pressure.
< Cooling mode >
< Heating mode >
500 pulses basically.
Initialization conditions
Control range
operation stop
500 pulses
55 - 500 pulses 0 pulses
0 pulses
2-4 EXPANSION VALVE CONTROL
Cooling
Heating
Operation mode
40 - 500 pulses
Cooling
Heating
When power turned on When operation stopped
2-5 SPECIAL OPERATION
2-5-1 Oil Recovery Operation
Purpose of the operation
The amount of refrigerant lubricant oil which has been transported to the indoor units and the connection pipe with the refrigerant will become large as the operation time of compressor increases. It is necessary to recover the oil back into the outdoor unit for a certain time interval in order to prevent compressors from damaging due to lack of lubrication oil.
During the oil recovery operation, appears on the display of wired and central remote controller, and appears on the simple remote controller. The operation indicators (LED) of the indoor units flash slowly.
Others
02-09
< Start condition >
Compressor accumulated operation time since last cooling oil recovery operation exceeds 3 hours (first time : 1hour)
< End condition > 30 seconds have elapsed since the start and "suction temperature - low pressure saturation temperature 5deg" or 6 minutes
have elapsed since the start.
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit): Controlled pulse (as normal operation mode). FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode).
2. Oil Recovery in Heating operation
1. Oil Recovery in Cooling operation
< Start condition >
Compressor accumulated operation time since the last heating oil recovery exceeds 8 hours (first time : 1hour)
< End condition > After 4 minutes have elapsed
< Operation >
COMPRESSOR: The rotation speed varies depending on the operation state. EEV Opening (Indoor/Outdoor unit) : Controlled pulse (as normal operation mode) FAN speed (Indoor/Outdoor unit) : Controlled fan speed (as normal operation mode)
02-10
2-5-3 Defrost Operation Control
Accumulated heating operation time is 40 minutes or longer [Accumulated heating operation time is reset at the end of cooling operation or defrosting operation.] and an outdoor unit satisfies condition or below
Condition : "Heat exchange temperature -2°C" accumulated operating time is 180 minutes or longer
Condition : After the following all condition satisfied, "heat exchange temperature defrosting start judgment temperature and during heat exchange liquid temperature drop" accumulated time:10minutes
(a) accumulated heating operation time 30 minutes (b) 10 minutes have elapsed after outdoor unit starting (c) 5 minutes have elapsed since oil recovery
* Defrosting start and end judgment temperature are determined by the outdoor temperature.
Defrosting start judgment temperature = 0.8 x outdoor temperature - 11.6 (However, -27.6°C to - 6°C)
At all outdoor units, heat exchange liquid temperature end judgment temperature or when 10 minutes have elapsed from the start (When the indoor unit connection capacity is 90% or less, after 15 minutes have elapsed.)
Defrosting end judgment temperature = 0.39 x outdoor temperature + 12.7 (However, 5 to 12°C range)
If the calculated result is lower than -27.6 , the judgment temperature is defined as -27.6 If the calculated result is higher than -6 , the judgment temperature is defined as -6
2-5-2 Pre-heat Operation
This pre-heat operation protects the start up failure by preventing the refrigerant from soaking into the oil in compressor.
Crankcase heater ON: 30 minutes elapsed since installed compressors stopped
(However, ON when power turned on)
*It doesn't control according to the temperature.
If the calculated result is lower than 5 , the judgment temperature is defined as 5 If the calculated result is higher than 12 , the judgment temperature is defined as 12
OFF: Compressor starts
Outdoor temperature <2 and Compressor stop count exceed 20 times at less than 10 minutes of accumulated heating operation time
Defrost Operation Start Condition 1
Defrost Operation Start Condition 2
Defrost Operation End Condition
2-6 PROTECTIVE FUNCTION
02-11
2-6-1 Protective Function List
Protective Function
Detect Parts
Operating Condition
Operation
Discharge Temp Protection 1
Discharge Temp Thermistor
Discharge Temp Protection 2
Discharge Temp Thermistor
High Pressure Protection 1
High Pressure Sensor
High Pressure Protection 4
High Pressure Sensor
COOL HEAT
<Starting conditions> 3 minutes have elapsed since the start of operation and (discharge temperature 100°C or suction SH 10°C accumulated time 30 minutes)
<Reset conditions> Discharge temperature 95°C and suctionSH 7°C
EEV of operating indoor unit gradually opened
<Starting conditions> Cooling: Discharge temperature 95°C Heating: Discharge temperature 102°C
<Reset conditions> Discharge temperature 90°C Discharge temperature 97°C
EEV2 + 30pls/30 secs
Discharge Temp Protection 4
Discharge Temp Thermistor
< starting condition> Discharge temperature 105°C
<Pattern reset condition> Discharge temperature 100°C
Compressor speed -6rps every 30 secs Speed rise prohibited, when discharge temperature becomes lower than 105 , prohibit the rotational speed rise of the compressor.
Discharge Temp Protection 5
Discharge Temp Thermistor
<Starting conditions> Discharge temperature 95°C and EEV1=500pls
<Reset conditions> 2 minutes have elapsed and (discharge temperature 90°C or EEV1 400pls)
Expansion valve of stopped indoor unit gradually opened (upper limit 200pls)
Discharge Temp Protection Stop
Discharge Temp Thermistor
<Pattern starting condition> Discharge temperature fixed value (115°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 80°C
Compressor stopped
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on again
Compressor stopped (permanent stop) Error display
<Starting conditions> COMP < 25 rps ---- HP 3.3 MPa 25 rps COMP < 30 rps ---- HP 3.5 MPa 30 rps COMP
<Reset conditions> Fixed time has elapsed and Fixed time when SV2: ON 30 secs COMP < 25 rps ---- HP 3.0 MPa 25 rps COMP < 30 rps ---- HP 3.2 MPa 30 rps COMP
SV2 ON
High Pressure Protection 2
High Pressure Sensor
<Starting conditions> COMP 25 rps ---- HP 3.5 MPa COMP < 25 rps ---- HP 3.3 MPa
<Reset conditions> 3 minutes have elapsed and high-pressure 2.80MPa
SV2 ON
High Pressure Protection 3
High Pressure Sensor
<Starting conditions> Fixed time has elapsed and high-pressure 3.50MPa (* Fixed time at start of operation: 10 secs, after operation execution: 20 secs)
<Reset conditions> Operation (fan speed 1 step increase) complete
Fan speed 1 step increase
<Pattern starting condition> High-pressure 3.30MPa
<Pattern starting condition> High-pressure 3.50MPa
<Pattern reset condition> High-pressure 3.2MPa
<Pattern reset condition> High-pressure 3.5MPa
Fan speed lowered/every 30 secs
Fan lowest speed Upper 270 rpm Lower 250 rpm
DISPLAY
P1
EA11
High Pressure Protection 5
High Pressure Sensor
Abnormal High Pressure Protection Control
High Pressure Sensor
<Starting conditions> High-pressure 3.20MPa
Compressor capacity lowered/every 15 secs
<Pattern starting condition> COMP < 30 rps ---- HP 3.18 MPa COMP 30 rps ---- HP 3.68 MPa
<Pattern reset condition> After 25 seconds have elapsed and, COMP < 30 rps ---- HP 3.1 MPa COMP 30 rps ---- HP 3.6 MPa
Compressor capacity rise prohibited
<Reset conditions> High-pressure 3.20MPa
<Pattern starting condition> COMP 30 rps ---- HP 3.3 MPa COMP 30 rps ---- HP 3.8 MPa
<Pattern reset condition> After 25 seconds have elapsed and, COMP 30 rps ---- HP 3.18 MPa COMP 30 rps ---- HP 3.68 MPa
Compressor capacity lowered every 30 secs
---- HP 3.8 MPa
---- HP 3.5 MPa
02-12
Protective Function
Detect Parts
Operating Condition
Operation
Low Pressure Protection 4
Low Pressure Sensor
COOL HEAT
High Pressure Protection Stop 1
High Pressure Sensor
<Pattern starting condition> High-pressure 4.00MPa
<Pattern reset condition> 5 minutes have elapsed and high-pressure 3.50MPa
Compressor stopped
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition> Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition> 5 minutes have elapsed and pressure SW operation reset (Reset by high-pressure 3.2MPa)
Compressor stopped
High Pressure Protection Stop 2
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and pressure SW operation reset (Reset by high-pressure 3.2MPa)
Compressor stopped Error display
<Starting conditions> Low-pressure 0.20MPa
<Reset conditions> 5 minutes have elapsed and low-pressure 0.30MPa
SV2 ON
Low Pressure Protection 1
Low Pressure Sensor
<Starting conditions> Low-pressure 0.10MPa
<Reset conditions> 3 minutes have elapsed and low-pressure 0.17MPa
SV2 ON
<Starting conditions> 3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions> 3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly (450pls)
Abnormal Low Pressure Protection Control
Low Pressure Sensor
<starting condition> Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure Protection Stop
Low Pressure Sensor
<Pattern starting condition> Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition> 3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition> Pattern generated 5 times within 180 minutes.
<Pattern reset condition> Error reset (push button SW) executed after power turned on again.
Compressor stopped (permanent stop) Error display
Low Pressure Sensor
Low Pressure Protection 2
<reset condition>
3 minutes have elapsed and low-pressure 0.18MPa
Compressor stopped
DISPLAY
Compressor Temp Protection Stop
Compressor Temp Thermistor
<Pattern starting condition> Compressor temperature fixed value (110°C)
<Pattern reset condition> 3 minutes have elapsed and discharge temperature 80°C
Compressor stopped
Compressor stopped (permanent stop) Error display
<Pattern starting condition> Pattern generated 2 times within 40 minutes
<Pattern reset condition> Error reset (push button SW) executed after power turned on again
P2
EA41
EA31
EA42
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
P2
Compressor stopped
02-13
Protective Function
Detect Parts
Operating Condition
Operation
Overcurrent Break Stop (Compressor)
Overcurrent Protection Circuit
COOL HEAT
Compressor stopped
Heatsink Temp Thermistor
<Pattern starting condition> Heat sink temperature 100°C
<Pattern reset condition> 3 minutes have elapsed and heat sink temperature 85°C
Compressor stopped
Heatsink Temp Protection Stop
<Pattern starting condition> Pattern generated 3 times within 60 minutes.
<Pattern reset condition> 10 minutes have elapsed and heat sink temperature 85°C
Compressor stopped Error display
<Pattern starting condition> Current value Cooling: 22.5A / Heating: 23.5A
<Pattern reset condition> Current value Cooling: 22.5A / Heating: 23.5A
Frequency Maximum Setting Protection (Compressor)
<Pattern starting condition> Current value Cooling: 23.0A / Heating: 24.0A
<Pattern reset condition> Current value Cooling: 23.0A / Heating: 24.0A
Current Detector Circuit
Compressor is stopped when the over currernt protectioncircuit in the inverter PCBoad detects an abnormal current duringthe operation. If it repeated 5 times, the compressor becomes permanentstop.
Compressor is stopped when the over current protection circuit in the inverter PC Board detects an abnormal current at the time of start up. Compressor becomes permanent stop if it repeated over the number of set time.
<Reset condition> Error reset (push button SW) executed after power turned on again.
Compressor speed lowered
Compressor speed rise prohibited
• Pattern and start current value changed by outside temperature
DISPLAY
E941
E931
(permanent stop)
(permanent stop)
EAC4
3. INDOOR UNIT OPERATION
3-1 FAN CONTROL
03-01
3-1-1 Fan Speed Setting
3. INDOOR UNIT OPERATION
AUTO
HIGH MED LOW
Press the FAN CONTROL button to set the fan speed.
Fan speed setting
3-1-2 "AUTO" Position
Fan speed zone
Hi zone
Med zone
Low zone
When the room temperature decreases
When the room temperature increases
3. DRY OPERATION
1. COOLING OPERATION
2. HEAT OPERATION
• Expansion
valve
• Indoor fan motor
ON OFF
OPEN CLOSE
ON
ON
ON
ON ON ON
ON
ON
30s
30s
5s
3min
5s
2min30s
The indoor fan always rotates at "Lo" speed.
TIME -->
2
TR-TS
1
2
TR-TS
1
TR-TS
2
TR-TS
2
3
TR-TS
3
TR-TS
(1) When the TS is changed. (2) When the operation mode is changed from other mode to "COOL". (3) When the fan control is changed from other position to "AUTO".
The fan speed is determined automatically in accordance with the condition "(TR(corrected room temperature) - TS (corrected set temperature)" as shown on the right. However, the fan speed zone is determined in the manner as the room temperature increases for the following cases.
Same as Cooling operation, fan speed is decided by the difference between the room temperature and the set temperature.
(1) The indoor fan starts operation 5 seconds after the electric expansion valve opens. However, when the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is not stopped, the fan will rotate immediately without a delay time of 5 seconds. (2) The indoor fan will stop in 30 seconds when the refrigerant circulation stops. (3) The indoor fan will stop immediately when the indoor unit is stopped by pushing the stop button or by a setting of ON timer. (4) When the refrigerant circulation is stopped due to a lower room temperature for more then 3 minutes, the fan will rotate 2 minutes at intervals of 3 minutes. (5) When the indoor unit just starts its operation or the operation mode is changed from other to "DRY" and the refrigerant circulation is stopped, the fan will rotate for 1 minute and then it will operate according to the statement (4).
2min
Fan speed zone
Low zone
Med zone
Hi zone
When the room temperature decreases
When the room temperature increases
-2
TR-TS
-2
-3
TR-TS
-3
TR-TS
-2
TR-TS
-1
-2
TR-TS
-1
TR-TS
3-2 MASTER CONTROL
03-02
3-2-1 Operation Mode Control
(2) Cool, Dry and Heat Mode
Indoor fan motor
Operates according to
the AIR FLOW-MODE
setting.
See the fan control
page.
Cool Dry
Drain pump
Turns ON-OFF by the drain pump control function
Electrical expansion valve
Pulse controlled by
the temperature differ-
ence calculation and
frost prevent fuction
Each operation mode is controlled as below. (1) Stop mode
Indoor fan motor : OFF Electric expansion valve Drain pump
: Stop pulse : Turns ON-OFF by the drain pump control function
Operates according to
the AIR FLOW-MODE
setting, and besides
cold air prevention
operation
Pulse controlled by
the temperature dif-
ference calculation
and frost prevent
function
Heat
Pulse controlled by
the temperature dif-
ference.
(3) Priority mode
The purpose of the priority mode is to restrict operation commands (heating, cooling, dry) from the connected indoor units. There are 3 priority modes of Neutral, Cooling Priority, and Heating Priority. The operation modes restricted by each of these modes are as follows:
Priority mode
Neutral
Cooling priority
Heating priority
Restricted operation mode
No restrictions
Heating
Cooling, dry
Neutral
Cooling priority
Heating priority
Cooling priority
Heating priority
1. Priority mode decision methods Method 1. (Default value) The initial priority mode is made Neutral and is shifted to Cooling Priority when cooling and to Heating Priority when heating depending on which operation mode (cooling, heating) was input first. After shifting to Cooling Priority or Heating Priority, the priority mode shifts to Neutral only when there was a Stop input from all the indoor units.
Method 2. (Management by outdoor unit) Operation mode management is made "Management by outdoor unit" by outdoor unit PUSH-SW (field setting). The priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the outdoor unit regardless of the current mode.
03-03
Cooling priority
Heating priority
Method 3. (Management by indoor unit) Operation mode management is made "Management by indoor unit" by outdoor unit PUSH-SW (field setting). Then the master indoor unit is set by wired remote controller. Thereupon the priority mode shifts to Cooling Priority or Heating Priority in accordance with input from the master indoor unit regardless of the current priority mode. The priority mode is fixed at either cooling or heating even if the master indoor unit stops Cooling/heating switching can be performed by the master indoor unit only.
(4) Opposite operation mode When the operation mode commanded from an indoor unit (remote controller) and the operation mode allowed by the system (cooling and dry operation for cooling only type and operation mode allowed by priority mode for heat pump type) do not match, it is indicated by blinking of an LED.
Timer lamp: 3 secs ON/1 sec OFF repeated
03-04
3-2-2 Auto Changeover
Operation flow chart
START
Room temp.
Room temp.
Ts+2°C ?
COOLING OPERATION
HEATING OPERATION
YES
YES
NO
NO
NO
NO
YES
YES
AUTO CHANGEOVER operation
TS : Setting temperature
Ts- 2°C ?
[Method]
1. Switch operation mode management to "Management by indoor unit" by outdoor unit DIP-SW.
2. Set the master indoor unit by wired remote controller.
3. Judge cooling/heating by the difference between the master indoor unit's setting temperature and the room temperature.
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
NO
NO
Thermostat remains
in OFF state for 6 minutes or
longer?
System stops
or operation command other than
auto changeover operation?
YES
YES
03-05
3-2-3 "COOL" Position
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
When using the cooling mode, set the temperature to a value lower than the current room temperature, otherwise
the indoor unit will not start the cooling operation and only the fan will rotate.
• Indoor fan
Ts
• Opening of EEV
100% 0%
• Refrigerant flow
ON OFF
ON OFF
• Temperature
Ts + 0.5 C
TR
3Min.
Ts : Corrected setting temperature
TR : Corrected room temperature
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts - 0.5 C
Ts + 0.5 C
Ts - 0.5 C
Ts + 0.5 C Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts + 0.5 C Ts - 0.5 C
3-2-4 "HEAT" Position
(1) When using the heating mode, set the temperature to a value higher than the current room temperature, otherwise
the indoor unit will not start the heating operation.
(3)
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation will be temporarily interrupted.
• Indoor fan
Ts
• Opening of EEV
100% 0%
• Refrigerant flow
ON OFF
ON OFF
• Temperature
TR
4Min.
1Min.
4Min.
1Min.
4Min.
1Min.
Ts : Corrected setting temperature TR : Corrected room temperature
: Duration of cold air prevention
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to blow out warm air.
3-3 LOUVER CONTROL
03-06
Instructions relating to heating ( ) are applicable only to heat pump type outdoor unit.
Begin air conditioner operation before performing this procedure.
Vertical Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Press the VERTICAL AIR FLOW DIRECTION SET button.
LARGE CEILING TYPE
UNIVERSAL FLOOR/CEILING TYPE
Example : When set to vertical air direction.
DANGER!
(1) ADJUSTING THE DIRECTION OF AIR CIRCULATION
WALL MOUNTED TYPE
1
2
3
4
1
2
3
4
1
2
3
4
3
4
2
1
Never place fingers or foreign objects inside the outlet ports, since the internal fan opertes at high speed and could cause personal injury.
Always use the remote control umit's AIR FLOW DIRECTION button to adjust the UP/DOWN air direction flaps or RIGHT/LEFT air direction louvers. At­tempting to move them manually could result in improper operation; in this case, stop operation and restart. The louvers should begin to operate properly again. When used in a room with infants, chil­dren, elderly or sick persons, the air direction and room temperature should be considered carefully when making settings.
COMPACT WALL MOUNTED TYPE
CASSETTE TYPE
1
3
4
2
1
2
3
4
Press the VERTICAL AIRFLOW DIRECTION button. The temperature display will change to the vertical airflow direction setting display.
Use the air direction adjustments within the ranges shown above.
The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
During Cooling mode : Horizontal flow During Heating mode : Downward flow
During AUTO mode operation, for the first minute after beginning operation, airflow will be horizontal , the air direction cannot be adjusted during this period.
1
4
1
Cooling & Dry : 1 , 2 , 3 , 4
Heating : 1 , 2 , 3 , 4
Press the VERTICAL AIRFLOW DIRECTION button to change the vertical louvre position. The position number will appear on the display.
Horizontal Air Direction Adjustment
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE" and "WALL MOUNTED TYPE".
Press the HORIZONTAL AIR FLOW DIRECTION SET button.
LARGE CEILING TYPE
UNIVERSAL FLOOR/CEILING TYPE
WALL MOUNTED TYPE
Example : When set to horizontal air direction.
(2) SWING OPERATION
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
Begin air conditioner operation before performing this procedure.
To select Vertical airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR/CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE" and "COMPACT WALL MOUNTED TYPE".
1
3
4
5
2
03-07
1
2
3
4
5
Press the VERTICAL SWING button for more than two seconds.
The remote controller's Vertical Swing Display will light up. In this mode, the UP/DOWN air direction flaps will swing automat­ically to direct the air flow both up and down.
Example : When set to vertical swing.
1
3
4
5
2
Press the HORIZONTAL AIRFLOW DIRECTION button. The temperature display will change to the horizontal airflow direction setting display.
Press the HORIZONTAL AIRFLOW DIRECTION button to change the horizontal louvre position. The position number will appear on the display.
Cooling & Dry : 1 , 2 , 3 , 4 , 5
Heating : 1 , 2 , 3 , 4 , 5
To Stop Vertical airflow SWING Operation
Press the VERTICAL SWING button for more than two seconds once and again.
The remote controller's Vertical Swing Display will go out. Airflow direction will return to the setting before swing was begun.
Instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "CASSETTE TYPE", "WALL MOUNTED TYPE", and "COMPACT WALL MOUNTED TYPE".
About Vertical Airflow SWING Operation
About Horizontal Airflow Swing Operation
Air flow direction set
Range of swing
Air swing range
To select Horizontal Airflow SWING Operation
This instructions are applicable to "LARGE CEILING TYPE", "UNIVERSAL FLOOR / CEILING TYPE", "WALL MOUNTED TYPE".
Press the HORIZONTAL SWING button for more than two seconds.
The remote controller's Horizontal Swing Display will light up. In this mode, the RIGHT/LEFT air direction louvers will swing automatically to direct the airflow both right and left.
To stop Horizontal airflow SWING Operation
Press the HORIZONTAL SWING button for more than two seconds once and again.
The remote controller's Horizontal Swing Display will go out. Airflow direction will return to the setting before swing was begun.
Example : When set to horizontal swing.
Range of swing
03-08
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
The SWING operation may stop temporarily when the air conditioner's fan is not operating, or when operating at very low speeds.
The swing operation is not available depending on the model. Please refer to the operating manual for the indoor unit.
Left and right swing range can be changed in 3 steps by field setting.
( Factory setting)
Function Number
Setting Value
24
00 01 02
Left and right swing range
1 to 5 (All range)
1 to 3 3 to 5
1 to 4 (All range)
1 2 3 4
3-4 ELECTRONIC EXPANSION VALVE CONTROL
03-09
3-5 DRAIN PUMP OPERATION
1. Initialization
2. Operation Control
When starting up
Automatic operatic control
Automatic PI control is performed based on the indoor unit heat exchanger outlet temp and inlet temp.
Room temperature control
The room temperature is controlled so that it reaches to the set-up temperature based on the difference between the room temperature and the set-up temperature, and the change of indoor unit temperature. if the room temperature becomes 0.5 C lower than the set-up temperature, EEV is fully closed.
3. Special Control
(1) When cooling and refrigerant circulation starts, the drain pump starts simultaneously. (2) The drain pump operates continuously for 3 minutes after the refrigerant circulation stopped. (3) When the refrigent circulation is stopped by a start of indoor heat exchanger frost prevention operation, the drain pump will turn off in 1 hour after the end of indoor heat exchanger frost prevention operation. (4) When the water level in the drain pan rises up and then the float switch functions:
Microcomputer stops the refrigerant circulation and indoor fan motor operation. Drain pump operates continuously for 3 minutes after the float switch is turned off.
(Almost condensing water may be drained) (5) When the float switch turns ON continuously for 3 minutes, 'FAILURE INDICATION' operates. (6) When the float switch turns OFF within 3 minutes, the unit starts cooling operation.
1 2
When the power is turned ON. When it has passed the limited time since the last initialization.
When indoor unit stopping
Oil recovery operation : Controlled pulse. Test run operation : Controlled pulse. Icing protection control : Fully closed. Pump down operation : Fully open. Defrost operation : Controlled pulse
Outdoor unit Condition
EEV Condition
Cooling
Heating
Fully closed
Slightly open
(Cooling) Move to the cooling control base pulse in steps. (Heating) Move to the heating control base pulse in steps.
OFF
Fully closed
3-6 FUNCTION
03-10
3-6-1 Auto Restart
The air conditioner restarts with the previous setting operation.
3-6-2 Icing Protection Control
3-6-3 Oil Recovery Operation
[Oil recovery operation] : It periodically returns the residual refrigerant ion oil in the indoor unit and the connection piping back to the outdoor unit , and prevents the compressor oil level from decreasing.
6 sec ON 2 sec OFF Blinking
Indoor unit LED : Operation LED
Indoor fan : Same operation before oil recovery operation.
Indoor EEV : Control pulse
During the above operation, a refrigerant noise may be from the indoor unit.
The icing of the indoor heat exchanger is prevented during the cooling and dry mode operation.
(1) Starting Condition Compressor is operation more than 3 minutes. When "Heat exchanger inlet temperature TA" continues *4 minutes or more. Compressor is operation more than 3 minutes. When "Heat exchanger outlet temperature TA" continues 4 minutes or more.
(2) Operation EEV is closed. Fan is at the setting amount.
(3) Completing Condition Heat exchanger inlet and middle temperature TB After more than 5 minutes
*
Drain pump turns off at 60 minutes past the completion of the icing protection operation.
TA
TB
1°C
7°C
3-7 TIMER CONTROL
03-11
3-7-1 Wireless Remote Controller
There are following 4 kinds of timer modes are available.
ON Timer OFF Timer PROGRAM Timer SLEEP Timer
1. ON / OFF TIMER
3. SLEEP TIMER
2. PROGRAM TIMER
To set the PROGRAM timer
1
2
3
4 5
Select "OFF TIMER" Adjust the OFF time. Select "ON TIMER"
Adjust the ON time.
(About 5 seconds later, the entire display. will reappear.)
Select "PROGRAM TIMER"
(Either OFF ON or OFF ON will display.) (If the ON timer has been se­ lected to operate first, the unit will stop operating at this point.)
Select "CANCEL".
The air conditioner will return to normal op­eration.
To cancel the TIMER
*To change operating conditions
If you wish to change the operating conditions (ON/OFF,Mode, Fan Speed, Temperature Setting), after making the time set­ting, wait until the entire display reappears, then press the ap­propriate buttons to change to the desired operating condition.
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
The timer functions cannot be used when this controller is used together with the remote controller (Wired type). A beeping sound is made when a signal is received.
To set the ON / OFF timer
1
2
Adjust the OFF or ON time.
(About 5 seconds later, the entire display will reappear.)
Press the TIMER MODE button to select "OFF TIMER" or "ON TIMER"
CANCEL OFF TIMER ON TIMER
PROGRAM TIMER (OFF ON, OFF ON)
Press the START/ STOP button to start the air conditioner, and then proceed as follows.
To set the SLEEP timer
(Both the indoor unit's OPERATION indi­ cator lamp (green) and the TIMER indi­ cator lamp (orange) will light.)
Select "CANCEL".
The air conditioner will re­turn to normal operation.
Adjust the OFF time.
(About 5 seconds later,the entire display will reappear.)
1
2
To change the timer settings
1 2
*To cancel the TIMER
Press the SLEEP button once again.
Set the time using the TIMER SET buttons.
Unlike other timer functions, the SLEEP timer is designed to set the duration of time in which the unit does not operate. The SLEEP timer can be set regardless of whether the indoor unit is operating or stopped.
* Even ON/OFF and Sleep timer are valid.
* Even ON/OFF and Program timer are valid.
UTY - LNH
*To stop air conditioner operation during timer operating
03-12
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sieeping.
Cooling operation / dry operation Heating operation
When the sleep timer is set, the set temperature automatically rises 1°C every hour.The set temperature can rise up to a maximum of 2°C
Timer setting
60min.
1°C
2°C
When the sleep timer is set, the set temperature sutomatically drops 1°C every 30 minutes. The set temperature can drop to a maximum of 4°C
1 C
2 C
3 C
4 C
30min.
60min.
90min.
Timer setting
03-13
2
1
3
4
3-7-2 Group Remote Controller
UTY - CGG
WEEKLY TIMER
Different schedules can be set for each day of the week. Four timers can be set for each day. Operation on/off time, operation mode, and temperature can be specified for each timer.
1. WEEKLY TIMER
The timer function is not available depending on the initial setting.
Note: When a time is not set, the weekly timer cannot be started.
Different schedules can be set for each day of the week.
Four timers can be set for each day
Press the ALL TIMER button to start or cancel the WEEKLY timers for all indoor units.
If any of the indoor units are in the timer mode, pressing this button cancels the timers for all indoor units. If none of the indoor units are in the timer mode, pressing this button starts the timers for all indoor units.
Press the Select button to select the indoor unit.
Press the PROGRAM (CLOCK AD­JUST) button.
* Do not press this button for two sec­ onds or more, otherwise you will en­ ter the time setting mode.
Press the Select button to select the indoor unit.
* If all indoor units are selected, the times for all of the registered indoor unit timers are set at once.

Day of the week setting

S M T W T F S
ALL
All indoor units
SUN MON TUE WED THU FRI SAT
Press the Timer Mode (DELETE) button to start or cancel the WEEKLY timers.
The timer does not start if the time is not set.
Press the DAY button to select the day of the week.
* For ALL, all of the days can be set together when a appears around each day.
To start / cancel the WEEKLY timer operation
To set the WEEKLY timer
Press the Set Time buttons to set the time in 10-minute increments. * Hold down a Set Time button to adjust the time quickly.
* The time already set at another timer is skipped at the relevant indoor unit.
Decrement Increment
Timer setting
03-14
7
8
NOTES
To delete the operating time
5
6
Operating setting
Raise
Lower
Press the Start/Stop button or the Mode button or the Set Temperature button to set the operation.
* For the operations that can be set, refer to "Operation mode setting", "Room tem­ perature setting", and "To start /stop operation" , in "OPERATION". * Only the current operation settings are displayed.
ex.TIMER-1 will start operation at 8:00 on COOL.
Setting the next timer for the same day:
TIMER-1 TIMER-2 TIMER-3 TIMER-4
Then press the ENTER button to proceed to the time setting, and repeat steps from to .
4 5
Repeat steps to to set the timer for another day of the week.
3 5
Be careful for pressing the ENTER button without any operation setting because the time that is set will be cancelled.
When the operating time is set, the mark appears.
ex. TIMER-1 will start operation at 8:00 on COOL with a set­ ting of 20 C
1. Press the ENTER button to confirm the set timer.
2. Press again the PROGRAM (CLOCK ADJUST) button to complete the weekly timer setting.
* flashes for two seconds.

Setting the timer for the other indoor units:
Before setting the timer for other indoor units, press the ENTER button to confirm the settings. * The display switches to the next timer.
Repeat steps to to set the timer for other indoor units.
2 6
1. If the Timer Mode (DELETE) button is pressed during steps to , the operat­ ing time for the selected day will be deleted. * If all the days are selected, the operating times for all of the days of the se­ lected timer will be deleted.
2. Press the ENTER button to confirm the deletion.
3 7
AM
(1) The WEEKLY timer does not operate when the HEAT timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the cooling mode. In addition, the WEEKLY timer does not operate when the COOL or DRY timer is set if a HEAT PUMP MODEL in the air conditioning system is operating in the heating mode. (2) Even if the timer operation is set, the timer lamp of the indoor unit does not light up. (The timer lamp is used for wireless remote controller only.) (3) If the same time is set in Timer-1 to Timer-4 of an indoor unit, the timer setting of the smallest number will be effective.
03-15
3-7-3 Wired Remote Controller
UTY - RNK
ON / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER
1. ON / OFF TIMER
The timer function is not available depending on the model.
To set the ON/OFF timer
Press the timer mode button to se­lect the ON timer or OFF timer.
It is switched every time as shown in the below diagram when the button is pressed.
2
Press the DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the timer mode button.
1
NON STOP
OFF TIMER
ON TIMER
WEEKLY TIMER
No display
Press the set time buttons to set the time. After the time is set, the timer will start automatically. The amount of time until the OFF timer operates that is displayed on the timer display decreases as time passes.
From 1 to 24 hours
ex. OFF timer set for 6 hours
To cancel
SUMOTUWETH FR
SA
03-16
2. WEEKLY TIMER
The timer function is not available depending on the model.
Press the timer mode button to select the weekly timer.
2
Press the SET button for 2 sec­onds or more.
1
3
SUMOTUWETH FR
SA
369
12 15 18 21
Day of the week setting
Press the DAY button to select the day of the week, and then press the TIMER SET button to confirm the setting.
For ALL, all of the days can be set together when a each day.
appears around
ALL SU MO TU WE TH FR SA
SUMOTUWETH FR
SA
369
12 15 18 21
1
2
Weekly timer setting
4
Time setting (ON / OFF timer)
Press the SET TIME buttons to set the ON time in 30-minute increments, then press the TIMER SET button to proceed to the OFF time setting. Set the OFF time in the same way. If necessary, set the second weekly timer settings in the same way.
When the operating time is set, the
mark appears.
6
Press the TIMER SET button for 2 seconds or more to complete the weekly timer settings.
To delete the operating time
If the TIMER DELETE button is pressed during steps or , the operating time for the selected day will be deleted. If all the days are selected, the operating times for all of the days will be deleted.
3
4
ex. The timer is set for 7:00-18:00.
5
Repeat steps and to set the weekly timer for another day of the week.
3 4
ON-1 OFF-1 ON-2 OFF-2
Time setting (Independent OFF timer)
1
2
1
Press the TIMER MODE button to change to the independent OFF timer setting. * The time setting process is the same as the ON/OFF timer. Press the TIMER MODE button to return to the ON/OFF timer setting.
Switching from ON/OFF timer to independent OFF timer
The independent timer will flash on the display.
ON-2 OFF-2 OFF-2 OFF-3
03-17
SUMOTUWETH FR
SA
369
12 15 18 21
SUMOTUWETH FR
SA
369
12 15 18 21
To start
When the weekly timer is selected, the timer starts automatically.
To cancel
Press the TIMER DELETE button to cancel the timer mode. The timer mode can also be canceled by changing the timer mode using the TIMER MODE button.
1
During the weekly timer, press the TIMER SET button for 2 seconds or more to set the day.
Select the day to set the DAY OFF.
Press the DAY (DAY OFF) button for 2 seconds or more to set the DAY OFF.
Press the TIMER SET button for 2 seconds or more to complete the DAY OFF setting.
2 3 4
To cancel
Follow the same procedures as those for setup.
ex. The DAY OFF is set for Monday.
NOTES
The DAY OFF setting is only available for days for which weekly settings already exist. If the operating time carries over to the next day (during a next day setting), the effective DAY OFF range will be set as shown below.
Normal Next day setting
Setting dayPreceding day Next day Setting dayPreceding day Next day
The DAY OFF setting can only be set one time. The DAY OFF setting is cancelled automatically after the set day has passed.
Flashing mark: indicates the DAY OFF.
ON OFF ON OFF
DAY OFF
WEEKLY WEEKLY
WEEKLY
WEEKLY
ON
OFF
ON
OFF
DAY OFF
To start /cancel the WEEKLY timer operation
To set the DAY OFF (for a holiday)
369
12 15 18 21
The operating time for the current day is displayed.
ex.Operating time 7:00-18:00 Indpnd. OFF time 21:00
The independent timer will flash on the display.
NOTES
(1) PRECAUTIONS DURING WEEKLY TIMER SETUP Setup is not possible in the following cases, so amend the time. Be sure to set the ON time first, then the OFF time. If either the ON time or the OFF time is not set cor rectly, the timer will not operate properly. The WEEKLY 2 settings cannot be set earlier than the WEEKLY 1 settings. The WEEKLY 1 and WEEKLY 2 time spans cannot overlap.
(2) The earliest OFF time you can set is 30 minutes after the ON time. (3) The OFF time can be carried over to the next day. (4) The earliest independent OFF time you can set is 30 min­ utes after the last OFF time. (5) An independent OFF time can be set up to 0:00 hours of the next day. (6) Even if the timer operation is set, the timer indicator lamp of the indoor unit does not light up. (The timer indicator lamp is used for wireless remote controllers only.)
03-18
3. TEMPERATURE SET BACK TIMER
The timer function is not available depending on the model.
Press the SET BACK button to change to the SET BACK con­firmation display. The SET BACK operating time and the set temperature will be displayed.
2
Press the SET button for 2 seconds or more.
1
3
Day setting Operating time setting
Follow step and in "To set the WEEKLY timer". The DELETE button is also used as described in the procedures for the weekly timer.
4
NOTES
The SET BACK timer only changes the set temperature, it cannot be used to start or stop air conditioner operation. The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used. The SET BACK timer can be used together with the ON, OFF, and weekly timer functions. The SET BACK operating time is displayed only in the SET BACK confirmation display. (Refer to step 1 for the SET BACK confirmation display. )
During the COOL/DRY mode, the air conditioner will operate at a minimum of 18°C even if the SET BACK temperature is set to 17°C or lower. Room temperatures as low as 10, 12, and 14°C cannot be set depending on the model.
SET BACK
SUMOTUWETH FR
SA
369
12 15 18 21
SUMOTUWETH FR
SA
369
12 15 18 21
ex. When setting all days together
Temperature setting
Press the set temperature buttons to set the temperature. (The temperature setting range is the same as the range for the operation mode.)
ex. Operating time 15:00 - 22:00
5
Repeat steps and . Press the SET button for 2 sec­onds or more to complete the temperature SET BACK timer settings.
3 4
ON OFF
24°C
24°C
28°C
SET BACK temperature
Normal temperature
To start
SET BACK
Press the SET BACK button. The SET BACK confirmation display appears for 5 seconds, and then the timer starts automatically.
ex. Display during SET BACK timer operation (The operating time will not be displayed.)
To cancel
Press the SET BACK button, and then press the DELETE button while the SET BACK confirmation display is dis­played. Even if the SET BACK button is pressed again, the SET BACK timer will be cancelled.
SUMOTUWETH FR
SA
369
12 15 18 21
If there is no existing SET BACK tempera­ture setting, " - - " will be displayed for the temperature.
SUMOTUWETH FR
SA
1
3
2
4
1
2
Temperature SET BACK timer setting
To start /cancel the temperature SET BACK timer operation
3 4
4. TROUBLE SHOOTING
Continuous lighting(lowered light)Anti Freeze
Operation LEDTest Operation
Operation LED
Power Failure
Oil Recovery
Operation LED
Defrosting
Timer LED
Timer LED
Timer LED
Continuous lighting(lowered light)Timer LEDTimer
Continuous lighting
Operation LED
Operation
Flashing PatternIndication LampIndication type
04-01
Opposite Operation Mode
4-1 NORMAL OPERATION
4. TROUBLESHOOTING
4-1-1 Indoor Unit Display
Filter Filter LED Continuous lighting
ON
OFF
ON
OFF
1 sec
1 sec
6 sec 2 sec
ON
OFF
ON
OFF
Operation LED
Timer LED
Filter LED
Maintenance Mode
1 sec 1 sec
1 sec
1 sec
3 sec 1 sec
ON
OFF
1 sec 1 sec
ON
OFF
LED101
Inverter Compressor Operation Indication
Low Noise Mode
System stopped with compressor Temperature Protection
System stopped with Low Pressure Protection
System stopped with High Pressure Protection
System stooped with Discharge Temp. Protection
Defrost Operation
Oil Recovery Operation
Heating Mode
Cooling Mode
Idling(stop)
Indication type 7 Segment LED Pattern
4-1-2 OUTDOOR UNIT DISPLAY
LED104
LED105
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
Blank
"C" OO "L"
"H" EA "T"
"O" IL "R" ECOVERY
"D" E "F" ROST
"P" ROTECT "1"
"P" ROTECT "2"
"P" ROTECT "3"
"P" eak "C" ut
"L" OW "N" OISE
Blinking
Description
POWER LED101
ERROR LED102
ON
ON
OFF
OFF
"P" ROTECT "4"
ON
OFF
1 sec 1 sec
Peak Cut Mode
<Starting condition> Discharge temp fixed value: 115°C <Release condition> 3 minutes have elapsed and discharge temperature 80°C
<Starting condition> Compressor temp fixed value :110°C <Release condition> 3 minutes have elapsed and discharge temperature 80°C
<Starting condition> Low pressure 0.05MPa or low pressure 0.10MPa continues for 10 minutes <Release condition> 3 minutes have elapsed and low pressure 0.17MPa
<Starting condition> High pressure 4.00MPa <Release condition> 5 minutes have elapsed and high pressure 3.50MPa
Refer to 02-10 page for operation.
Refer to 02-11 page for operation.
Refer to 02-08 page for operation.
04-02
Water Drain Abnormal
Outdoor Unit Error
Indoor Unit Fan Motor Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Indoor Unit Parallel Communication Error
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Network Communication Error
Remote Controller Communication Error
Error Contents
12 ~ 48
7
Continuous flash
8
Continuous flash
9 times flash
5,6
Continuous flash1 times flash
5 times flash
Continuous flash2 times flash
5 times flash
4
Continuous flash1 times flash
4 times flash
1,3
Continuous flash
6 times flash
4 times flash
2
3 times flash
1 times flash
Continuous flash 2 times flash3 times flash
10
Continuous flash1 times flash3 times flash
Continuous flash
4 times flash
1 times flash
11
Continuous flash2 times flash1 times flash
9
Trouble shooting
Filter LEDTimer LEDOperation LED
Depending on contents of Outdoor unit, it may not indicate. (Refer to "TROUBLE LEVEL OF SYSTEM")
Error Indication Flashing Pattern
Please refer the flashing pattern as follows.
04-03
4-2 ABNORMAL OPERATION
4-2-1 Indoor Unit Display
0.1s / 0.1s
4.0s
1.0s
0.5s 0.5s
0.5s 0.5s 0.5s 0.5s
1.0s
0.5s 0.5s
0.5s 0.5s
3.0s
1.0s
4.0s
1 cycle
ON
ON
ON
OFF
OFF
OFF
Operation LED
Timer LED
Filter LED
Example : Indoor Unit Main PCB Error (Operation LED : 3 times, Timer LED : 2 times)
15 times flash
4-2-2 Outdoor Unit Display
LED101
POWER LED101
ERROR LED102
MODE
EXIT
SELECT
ENTER
SW107
SW108 SW109
POWER
MODE
ERROR
(GREEN)
LED102
(RED)
0.1sec 0.1sec
ON
ON
OFF
OFF
POWER MODE LED : on ERROR LED : blink
ERROR transition
"Err." and quantity are alternately shown.
When there is more than one error, display is changed by "SELECT" short press.
When more than one indoor unit is abnormal, display is changed by "SELECT" short press.
"ENTER" short press"ENTER" short press
"ENTER" short press"ENTER" long press
*
Short press : less than 3 seconds Long press : more than 3 seconds
Annunciation
Type of errors
Address
"SELECT" short press display change
"SELECT" short press display change
If some error is newly occured or resolved during transition, it is reflected after going back to "Annunciation".
* Only in the case of "indoor unit abnormal (E.5U.1)", indoor unit address is shown by ENTER long press.
LED display
Operation button
ex : discharge thermistor 1 abnormal ex : indoor unit abnormal
04-04
Trouble
shooting
Error Contents
4-2-3 Error Code List for Outdoor Unit
Error
Code
Auto Address Setting Error
Indoor Unit Error
Initial Setting Error
Inverter PCB short intereuption detection
Inverter Error
Inverter Communication Error
Outdoor Unit EEPROM Access Error
EEPROM Data corrupted Error
Outdoor Unit transmission PCB Parallel Communication Error
20
19
18
16
15
17
Signal Amplifier Auto Address Setting Error
Trouble
shooting
Error Contents
High Pressure Switch Error
Suction Pressure Sensor Error
Current Sensor Error
SC HE. Liquid Outlet Temp Sensor Error < TH7 >
SC HE. Gas Outlet Temp. Sensor Error < TH9 >
SC HE. Gas Inlet Temp. Sensor Error < TH8 >
Discharge Pressure Sensor Error
Heat Sink Temp. Sensor Error < IPM built in >
Suction Gas Temp. Sensor Error < TH4 >
Outdoor Temp. Sensor Error < TH3 >
Heat Ex. Liquid pipe Temp. Sensor Error < TH5 >
33
32
31
30
29
28
27
26
25
24
23
21
- - - -
2 8 . 1
5 U . 1
6 2 . 8
6 2 . 3
6 2 . 6
6 3 . 1
6 7 . 2
6 9 . 1
2 8 . 4
7 2 . 1
7 3 . 3
7 4 . 1
7 5 . 1
7 7 . 1
8 2 . 1
8 2 . 2
8 3 . 2
8 4 . 1
8 6 . 1
8 6 . 3
8 6 . 4
7 1 . 1
Compressor Temp. Sensor Error < TH10 >
Discharge Temp. Sensor Error < TH1 >
22
Outdoor unit FAN motor under voltage (Lack of DC Voltage)
Outdoor Unit Fan Motor Lock Error (Start up Error)
Compressor Motor Loss of Synchronization
Trip Detection
Inverter Compressor Start Up Error
Outdoor Unit Fan Motor 1 Temperature Abnormal 39
38
37
36
35
34
Error
Code
9 3 . 1
9 4 . 1
9 5 . 5
9 7 . 1
9 7 . 4
9 7 . 5
A 1 . 1
A 3 . 1
A 4 . 1
A 4 . 2
A 5 . 1 Low Pressure Abnormal
High Pressure Protection 1
High Pressure Abnormal
Compressor Temperature Abnormal
Discharge Temperature Abnormal
45
44
43
42
41
12
1 - 11
04-05
46
47
48
1 4 . 5
The number of Indoor unit shortage
Outdoor Unit Fan Motor 2 Temperature Abnormal 39
379 8 . 1
9 8 . 5
Coil ( Expansion Valve 1 ) Error 409 A . 1
Coil ( Expansion Valve 2 ) Error 409 A . 2
14
1 4 . 2
Outdoor unit Network communication abnormal 2
Outdoor Unit Fan Motor Lock Error (Start up Error)
4-2-4 Remote Controller Display
04-06
<< WIRED REMOTE CONTROLLER >>
If an error occurs, the following display will be shown. ( will appear in the set room temperature display.) If
is displayed, immediately contact authorized
service personnel.
Unit number (usually 0) Error code
Ex. Error code display
ERROR CODE DISPLAY
<< SIMPLE REMOTE CONTROLLER >>
Error code
Ex. Error code display
Faulty unit No. (Remote controller address)
ERROR CODE DISPLAY
<< GROUP REMOTE CONTROLLER >>
The air conditioning system must be inspected if “ : “ (error code) appears on the timer and Clock Display, or the
operation lamp is flashing.
Model code
Error code
Ex. Error code display
ERROR CODE DISPLAY
Model code
: Outdoor unit : Indoor unit : Group remote controller : Convertor
*1 ;
*1
If an error occurs, the following display will be shown. ( will appear in the set room temperature display.) If
is displayed, immediately contact authorized
service personnel.
Trouble
shooting
Error Contents
4-2-5 Error Code List for Simple and Wired Remote Controller
Error
Code
Trouble
shooting
Error Contents
Error Code
1 2
1 4
1 5
1 6
- -
2 6
2 8
3 1
3 2
4 1
4 2
5 1
5 3
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Other Setting Error
Address Setting Error
Initial Setting Error
Indoor Unit Parallel Communication Error
Scan Error
Network Communication Error
Remote Controller Communication Error
Indoor Unit Fan Motor Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Water Drain Abnormal
6 2
6 3
6 7
6 9
Inverter PCB short interruption detection
Inverter Error
Outdoor Unit Main PCB Error
Outdoor Unit transmission PCB Error
8 2
8 3
8 4
8 6
9 3
9 4
9 5
9 7
Current Sensor Error
Liquid Pipe Temperature Sensor Error
Sub-cool Heat Ex. Gas Temperature Sensor Error
Pressure Sensor Error
Outdoor Unit Fan Motor 1 Error
Compressor Motor loss of Synchronization
Trip Detection
Compressor Start Up Error
A 1
A 3
A 4
A 5 Low Pressure Abnormal
High Pressure Abnormal
Compressor Temperature Abnormal
Discharge Temperature Abnormal
7 1
7 2
7 3
7 4
7 5
7 7 Heat Sink Temperature Sensor Error
Suction Gas Temperature Sensor Error
Outdoor Temperature Sensor Error
Heat Ex. liquid pipe Temperature Sensor Error
Compressor Temperature Sensor Error
Discharge Temperature Sensor Error
4-2-6 Error Code List for Group Remote Controller
Trouble
shooting
Error Contents
Error
Code
Trouble
shooting
Error Contents
Error Code
1 4
1 5
1 6
3 1
3 2
1 2
Remote Controller Communication Error
Indoor Unit Main PCB Error
Indoor Unit Power Frequency Abnormal
Indoor Unit Parallel Communication Error
Scan Error
Network Communication Error
4 1
4 2
5 1
5 3
9 U
Inddor Unit Fan Motor Error
Indoor Unit Heat Ex. Sensor Error
Room Temperature Sensor Error
Water Drain Abnormal
Outdoor Unit Error
9, 83
11
10
2
1, 3
5, 6
4
8
7
12 48
9,10,72,78
12
11,13,14,81
15 17
10
2
4
1, 3
5, 6
8
7
18
19
20
21
24
22
23
25
26
27,28
29
30
31 33
34
36
35
37 39
41
42
43, 44
45
04-07
84
C 4 PCB Error 77
C A Software Error 68, 75
C 1 PCB Error 1 66, 71
84
79
46, 47
9 8
Outdoor Unit Fan Motor 2 Error
37 39
9 A
Coil ( Expansion Valve ) Error
40
4-2-7 Error Code List for External Switch Controller (UTY-TEKX)
Trouble
shooting
Error Contents
Error Code
- -
- -
- -
- -
Power Supply Error
Switch Operation Error
Transmission Error
The abnormality in connection of remote controller cable
55
56
58
04-07
+1
57
4-2-8 Error Code List for Signal Amplifier (UTY-VSGX)
Trouble
shooting
Error Contents
Error Code
- -
2 6
C 1
- -
Power Supply Error
Parallel Communication Error
Address Setting Error
Communication Error
59
60
62
- -
Communication Error B
63
- -
Communication Error A
64
61
4-2-9 Error Code List for Network Convertor (UTY-VGGX)
Trouble
shooting
Error Contents
Error Code
C 1
1 2
C A
- -
Power Supply Error
Software Error
Communication Error with Group Remote Controller
PCB Error 1
65
66
68
2 6
Refrigerant circuit address setting error
69
67
Trouble
shooting
Error Contents
Error Code
C 1
1 2
1 6
- -
Power Supply Error
Communication Error with Indoor Unit
Communication Error with Standard Remote Controller
PCB Error 1
70
71
73
2 6
Communication Error with Indoor Unit
74
C A
Software Error
75
5 U
Indoor / Outdoor Unit Error
76
72
1. When connecting a group remote controller to a network convertor
2. When connecting a single split type indoor unit to a network convertor
4-2-10 TROUBLE LEVEL OF SYSTEM
<< System Condition when Outdoor Unit Error is occurred >>
(1) Not indicated on Indoor Unit. Not indicated on Peripheral Unit. Indicated on Service Tool.
(2) Indicated on Indoor Unit. Indicated on Peripheral. Indicated on Service Tool.
>Abnormal >LED indication >Outdoor unit does not stop
>Temporary blackout detection protection (Inverter compressor stop)
> Discharge temperature abnormal (Inverter compressor stops) > Compressor temperature abnormal (Inverter compressor stops) > High pressure switch error (Inverter compressor stops) > High pressure switch error (Constant speed compressor stops) > Discharge Temp sensor error (Inverter compressor stops) > Compressor Temp sensor error (Inverter compressor stop) > Heat sink Temp sensor error (Inverter compressor stop) > Current sensor error (Inverter compressor stop) > High pressure switch error (Inverter compressor stop) > Inverter error (Inverter compressor stop) > Heat sink temperature abnormal (Inverter compressor stop) > Inverter compressor start up error (Inverter compressor stop) > Trip detection (Inverter compressor stops) > Rush current limiting resister Temp rise protection (Inverter compressor stop) > Comp. motor loss of synchronization (Inverter compressor stop) > Inverter communication error (Inverter compressor stop) > Outdoor unit EEPROM access error > Outdoor unit EEPROM data corrupted
> Indoor unit number shortage
System Condition
Outdoor unit Condition
System is not stopped compulsorily
Trouble Level
1 2
(Not available)
04-08
This will not be displayed on indoor unit which Error Report Target(function setting 47 of indoor unit) is set "for administrator".
>Abnormal >LED indication >Outdoor unit does not stop
> Suction gas Temp sensor error > Outdoor Temp sensor error > Sub-cool heat Ex. gas inlet Temp sensor error > Sub-cool heat Ex. gas outlet Temp sensor error
(1) Not indicated on Indoor Unit. Not indicated on Peripheral Unit. Indicated on Service Tool.
(2) Indicated on Indoor Unit. Indicated on Peripheral. Indicated on Service Tool.
- Discharge temperature abnormal
- Compressor temperature abnormal
- Current sensor error
- Inverter compressor start up error
- Trip detection
- Rush current limiting resister Temp rise protection
- Comp. motor loss of synchronization
- Low pressure abnormal
- Fan motor 1 lock error
- Fan motor 2 lock error
System Condition
Outdoor unit Condition
System is compulsorily stopped.
Even if power is reset, the following Error cannot release.
<Important>
These errors can not be judged without operating the system, and the serviceman would not be able to check it if the system power is turned off before visiting the site for repair. In Error release, you need to operate push switch and apply "Error reset" (F3-40) after power restart.
Trouble Level
1 2
>Abnormal >LED indication >Outdoor unit stops >Need to repair >secondary accident is possible.
(Not available) >High pressure abnormal
>Low pressure abnormal >Fan motor 1 lock error >Fan motor 2 lock error >Fan motor 1 temp. abnormal >Fan motor 2 temp. abnormal >Heat Ex. liquid Temp sensor error >Discharge pressure sensor error >Suction pressure sensor error >Outdoor unit communication PCB parallel communication error >Outdoor unit network communication 2 error >Lack of DC Voltage >Indoor unit number shortage >SC HE. Liquid Outlet Temp Sensor Error
04-09
Trouble shooting 1 INDOOR UNIT Error Method:
Model Information Error (Indoor Unit Main PCB Error)
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
3 continuous failure of read test of EEPROM at Power ON, or Apparent Model information error from EEPROM. Also, Error on Model information upon model information test of EEPROM, or Model information of EEPROM not possible to recover.
Forecast of Cause : 1. Outside cause 2. Connection failure of electric components 3. Controller PCB defective
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 : Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
OK
Note : EEPROM
EEPROM(Electronically Erasable and Programmable Read Only Memory) is a non­volatile memory which keeps memorized information even if power is turned off. It can change the contents electronically. To change the contents, it uses higher voltage than normal, and it can not change a partial contents. (Rewriting shall be done upon erasing the all contents.) There is a limit in a number of rewriting.
4-3-1 Trouble shooting with error code (INDOOR UNIT)
4-3 TROUBLE SHOOTING
04-11
Trouble shooting 2 INDOOR UNIT Error Method:
Power Frequency Abnormal
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When 5 continuous failures occurred at Power frequency test.
Forecast of Cause : 1. Outside cause 2. Installation failure 3. Defective connection of electric components
4. Controller PCB defective
Check Point 2 : Check Installation condition
NO
Check Point 3 : Check connection of electric components
YES
Check Cable/Breaker Check loose or removed connection
>> If Installation defect is found, correct it by referring
to Installation Manual.
OK
Check power supply voltage (AC230V between Indoor unit terminal 1 and 2) Check connection of Connector (any lose connector or incorrect wiring) Check any shortage or corrosion on PCB.
OK
AC
Check Point 1-1 : Reset Power Supply
Does abnormal LED indication show again?
Check Point 1-2 : Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 4 : Replace Controller PCB
Change Controller PCB and set up the original address.
04-12
Wrong power supply installation ----- Check if the power supply frequency is stable or not.
Trouble shooting 3 INDOOR UNIT Error Method:
EEPROM Access Abnormal (Indoor Unit Main PCB Error)
Indicate or Display:
Indoor Unit : Operation LED 3 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 3 2
Detective Actuators:
Indoor Unit Controller PCB Circuit
Detective details:
When 3 continuous failure occurred on read test of EEPROM.
Forecast of Cause :
1. Outside cause 2. Defective connection of electric component 3. Controller PCB defective
Check Point 1-2 :­Check outside cause (Voltage drop or noise, etc.)
Instant drop ----- Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause harmonic wave). Check the complete insulation of grounding.
Check Point 3 : Replace Controller PCB
Change Controller PCB and set up the original address.
Check Point 1-1 : Reset Power Supply
Check Point 2 : Check Indoor Unit electric components
YES
NO
Does abnormal LED indication show again?
Check all connectors (loose connector or incorrect wiring) Check any shortage or corrosion on PCB.
OK
04-13
Trouble shooting 4 INDOOR UNIT Error Method:
Room Temperature Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Temperature Thermistor
Detective details:
When Indoor thermistor open or shortage is detected at power ON.
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.5
35
8.0
30
10.012.515.820.125.233.6Resistance Value ( )
2520151050
Temperature (°C)
3.54.35.3Resistance Value ( )
504540
Temperature (°C)
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
If the voltage does not appear, replace Controller PCB and set up the original address.
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Room Temp. Thermistor
(CN10 Wire:Black)
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
DC
Cassette Schematic Diagram (Connector connection)
Wall mount Schematic Diagram (Connector connection)
H/E Outlet Thermistor (CN9 Wire:Gray)
H/E Inlet Thermistor (CN9 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
H/E Outlet Thermistor (CN17Wire:Gray)
H/E Inlet Thermistor (CN17 Wire:Black)
Room Temp. Thermistor (CN16 Wire:Black)
04-14
Duct Schematic Diagram (Connector connection)
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Trouble shooting 5 INDOOR UNIT Error Method:
Heat Exchanger Inlet Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Inlet Thermistor
Detective details:
When open or shorted Heat Exchanger Inlet Thermistor is detected at Power ON.
Resistance Value ( )
Temperature (°C)
32.4
35
40.0
30
49.862.579.1100.9129.8168.6
2520151050
Resistance Value ( )
Temperature (°C)
17.821.226.3
504540
OK
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
If the voltage does not appear, replace Controller PCB and set up the original address.
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Room Temp. Thermistor
(CN10 Wire:Black)
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
04-15
DC
Cassette Schematic Diagram (Connector connection)
Wall mount Schematic Diagram (Connector connection)
H/E Outlet Thermistor (CN9 Wire:Gray)
H/E Inlet Thermistor (CN9 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
H/E Outlet Thermistor (CN17 Wire:Gray)
H/E Inlet Thermistor (CN17 Wire:Black)
Room Temp. Thermistor (CN16 Wire:Black)
Duct Schematic Diagram (Connector connection)
Trouble shooting 6 INDOOR UNIT Error Method:
Heat Exchanger Outlet Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 2
Detective Actuators:
Indoor Unit Controller PCB Circuit Heat Exchanger Outlet Thermistor
Detective details:
When open or shorted Heat Exchanger outlet Thermistor is detected at Power ON.
Forecast of Cause : 1. Connector defective connection 2.Thermistor defective 3.Controller PCB defective
Check Point 1 : Check connection of Connector
Check if connector is loose or removed Check erroneous connection Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 2 : Remove connector and check Thermistor resistance value
Resistance Value ( )
Temperature (°C)
32.4
35
40.0
30
49.862.579.1100.9129.8168.6
2520151050
Resistance Value ( )
Temperature (°C)
17.821.226.3
504540
04-16
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
If the voltage does not appear, replace Controller PCB and set up the original address
H/E Inlet Thermistor (CN20 Wire:Black)
H/E Outlet Thermistor (CN20 Wire:Gray)
Room Temp. Thermistor (CN19 Wire:Black)
Room Temp. Thermistor
(CN10 Wire:Black)
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
DC
Cassette Schematic Diagram (Connector connection)
Wall mount Schematic Diagram (Connector connection)
H/E Outlet Thermistor (CN9 Wire:Gray)
H/E Inlet Thermistor (CN9 Wire:Black)
Room Temp. Thermistor (CN8 Wire:Black)
H/E Outlet Thermistor (CN17 Wire:Gray)
H/E Inlet Thermistor (CN17 Wire:Black)
Room Temp. Thermistor (CN16 Wire:Black)
Duct Schematic Diagram (Connector connection)
Trouble shooting 7 INDOOR UNIT Error Method:
Water Drain Abnormal
Indicate or Display:
Indoor Unit : Operation LED 5 times Flash, Timer LED 3 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 5 3
Detective Actuators:
Indoor Unit Controller PCB Circuit Float Switch
Detective details:
When Float switch is ON for more than 3 minutes.
Check Point 1 : Check Float Switch
Check operation of float switch. (any blocking by dust, etc.) Remove Float switch and check ON/OFF switching operation
by using a meter.
>>If Float switch is defective, replace it.
ON OFF
OK
Forecast of Cause : 1. Float switch defective 2. Shorted connector/wire 3. Controller PCB defective 4. Drain pump defective
Check Point 2 : Check Connector (CN 1) / Wire
Check loose contact of CN1 /shorted wire (pinched wire).
>>Replace Float switch if the wire is abnormal
Check Point 3 : Check Controller PCB
If Check Point 1 & 2 do not improve the symptom, change
Controller PCB and set up the original address.
Attention!!
Small size wall mount type does not have a float switch. In this case, replace Controller PCB and set up the original address. Please refer to.
OK
04-17
Trouble shooting 8 INDOOR UNIT Error Method:
Indoor Unit Fan Motor Error
Indicate or Display:
Indoor Unit : Operation LED 5 times Flash, Timer LED 1 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 5 1
Detective Actuators:
Indoor Unit Controller PCB Circuit Indoor Fan Motor
Detective details:
When Indoor fan control is either phase control or DC control and rotation feed back control is ON, the feed back rotation value becomes 0 and lasts for more than 1 minute at motor operation condition. Or, the feed back rotation value continues at 1/3 of target value for more than 1 minute.
Check Point 2 : Check Motor winding
Check Indoor Fan motor
>>If Fan motor is abnormal, replace it.
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation..
Check Point 4 : Check Motor Capacitor
Check continuity of motor capacitor
>>If it is shorted, replace the capacitor.
Check Point 5 : Replace Controller PCB
OK
OK
OK
OK
Forecast of Cause : 1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temp. increase
4. Capacitor failure 5. Control PCB failure
Attention!!
In case of Duct type, replace Controller PCB and set up the original address, since it is a tapping control.
Change Controller PCB and set up the original address.
04-18
Trouble shooting 9 INDOOR UNIT Error Method:
Wired Remote Controller Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 2
Detective Actuators:
Indoor unit controller PCB circuit Wired Remote Control
Detective details:
Upon receiving the signal more than 1 time from Wired Remote or other Indoor unit, but the same signal has not been received more than 1 minute.
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of controller PCB Connector. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote If DC0V, Controller PCB failure (Remote is OK) >>> Replace Controller PCB
-In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
Trouble shooting 9 INDOOR UNIT Error Method:
Wired Remote Controller Token Error
Indicate or Display: Indoor Unit : Operation LED 1 times Flash, Timer LED 2 Times Flash, Filter LED Continuous Flash. Outdoor Unit : E.5 U.1, Error LED Continuous Flash. Remote Controller : 1 2
Detective Actuators:
Indoor unit Controller PCB circuit Wired Remote Control
Detective details:
More than 1 time of Token (Communication between wired remote controllers) is received, but it was not received more than 1 minute.
OK
DC
Forecast of Cause : 1. Terminal connection abnormal 2. Wired Remote Control failure 3. Controller PCB failure
Forecast of Cause : 1. Terminal connection abnormal 2. Mis-setting 3. Wired Remote Control failure 4. Controller PCB failure
Check Point 1 : Check the connection of terminal
After turning off the power, check & correct the followings.
Indoor Unit - Check the connection of terminal between remote control and Indoor unit, or between Indoor units, and
check if there is a disconnection or short of the cable.
OK
04-19
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
Check Point 2 : Check Remote and Controller PCB
Check terminal voltage of Controller PCB Connector. (Power supply for Remote)
If DC12V, Remote Control failure (Controller PCB is OK) >>> Replace Remote lIf DC0V, Controller PCB failure (Remote is OK) >>> Replace Conroller PCB
In case of re-installation is done due to removed connector or incorrect
wiring, turn on the power again.
DC
Cassette Type CN5 , AS*E 07,09,12,14LACH / AS*A 07,09,12,14LACH Type CN7 , Other CN17
Trouble shooting 10 INDOOR UNIT Error Method:
Indoor Unit Parallel Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 6 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 6
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When Parallel communication error (Communication reset occurs continuously more than specified times) is detected.
Check Point 3 : Replace Communication PCB
Replace Communication PCB (If the symptom does not change, replace Controller PCB and set up the original address.
Check Point 1-2 : Check outside cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which causes harmonic wave).
Check Point 1-1 : Reset the power
Check Point 2 : Check Connection
YES
NO
Does LED error indication reappear?
Check if Indoor Communication PCB is removed.
OK
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
04-20
Trouble shooting 11 INDOOR UNIT Error Method:
Network Communication Error
Indicate or Display:
Indoor Unit : Operation LED 1 times Flash, Timer LED 4 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 1 4
Detective Actuators:
Indoor unit Controller PCB circuit Indoor unit Communication PCB
Detective details:
When the cut-off of network communication is detected (more than 90 seconds passed since the last receipt of Outdoor unit signal).
Check Point 2 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----- Check if there is any electric equipment with a large load within the same circuit. Momentary power failure ----- Check contact failure or leak current in power supply circuit
>>Check Outdoor Unit as well.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light bulb or any electronic equipment which
causes harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
Check Point 1 : Check the connection
After turning off the power, check and correct followings.
Is Indoor Communication PCB loose? Check loose or removed connection of communication line between Indoor
and Outdoor unit.
When the signal amplifier is connected , is it failure of signal amplifier? (Refer to "TROUBLE SHOOTING FOR OPTIONAL PARTS")
Check Point 3 : Check Communication PCB and Controller PCB
If some of Indoor units have errors, replace Communication PCB of the Indoor units that have the error.
>>If the symptom does not change, replace Indoor unit Controller PCB.
If all the Indoor units have error, check if the Outdoor Unit Communication PCB has a loose connection.
>>If the symptom does not change, replace Outdoor unit Communication PCB (Replace Controller PCB if it does not change).
OK
OK
Forecast of Cause : 1. Connection failure 2. Outside cause 3. Communication PCB failure 4. Controller PCB failure
04-21
Initial Setting Error
Outdoor unit main PCB
Check Point 1 : Check the power supply
Main power ON/OFF state check Power cable connection, open check
OK
Check Point 2 : Check the outdoor unit address/number of connected slave units setting
Setting check of outdoor unit address of each outdoor unit
Outdoor unit address
SET 3-1 SET 3-2
Master
OFF OFF
OK
Check Point 3 : Replace Main PCB
Change Main PCB and set up the original address.
4-3-2 Trouble Shooring With Error Code (OUTDOOR UNIT)
1. Wrong DIP SW setting
2. Power supply defective
3. Main PCB defective
Indoor Unit : No Display
Outdoor Unit : - - - - ( Flashing 0.5 sec. ON and OFF )
Error Code : No Display
04-22
Trouble shooting 12
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
When the DIP SW setting was wrong, after turned on the power supply
Outdoor Unit Network Communication 1 Error
OK
Communication PCB connection check
Communication PCB check
OK
Communication line connection, open check
OK
OK
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
OK
Outdoor unit Main PCB Outdoor unit communication PCB
1. Noise, momentary open, voltage drop 2. Indoor unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
Check Point 3 : Check the communication line connection
No communication for 180 seconds or more from an indoor unit which received communication once and no outdoor network communication error 2.
Check Point 4 : Check the Terminal resistor setting
T
erminal resistor setting check
Check Point 6 : Replace Main PCB (outdoor unit / indoor unit)
Change Main PCB and set up the original address.
Indoor Unit : No display
Outdoor Unit : E. 14. 1
Error Code : 14
04-23
Trouble shooting 13
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
OUTDOOR UNIT Error Method ::
Outdoor Unit Network Communication 2 Error
OK
Communication PCB connection check
Communication PCB check
OK
Communication line connection, open check
OK
OK
OK
Outdoor unit Main PCB Outdoor unit communication PCB
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the indoor unit power supply
Main power ON check
Power cable connection and open check
Check Point 3 : Check the communication line connection
Detective Actuators:
Forecast of Cause :
No communication for 180 seconds or more from all indoor units that once received communication
Check Point 4 : Check the Terminal resistor setting
Terminal resistor setting check
Check Point 6 : Replace Main PCB (outdoor unit / in door unit)
Check Point 5 : Check the communication PCB (outdoor unit/indoor unit)
Change Main PCB and set up the original address.
Detective details:
1. Noise, momentary open, voltage drop 2. Indoor unit power off
3. Communication line connection defective 4. Terminal resistor setting mistake
5. Communication PCB mounting defective, Communication PCB defective 6. Main PCB defective
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 14. 2
Error Code : 14
04-24
Trouble shooting 14
Indicate or Display:
Outdoor Unit EEPROM Access Error
YES
NO
Check Point 1-2 : Noise, momentary open, voltage drop
Outdoor unit Main PCB
Access to EEPROM failed due to some cause after outdoor unit started.
1. Noise, momentary open, voltage drop 2. Main PCB defective
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the
power line.
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Check Point 1-1 : Turn the power on agaun.
Error displayed again?
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 62. 3
Error Code : 62
04-25
Trouble shooting 15
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Inverter Communication Error
YES
NO
OK
OK
Outdoor unit Main PCB Outdoor unit Inverter PCB
Check Point 2 : Check the main to Inverter PCB wiring
Connector connection state check
Cable open check
Check Point 3 : Check Main PCB
Chack Main PCB. (Refer to "Sarvise Parts Information )
1. Noise 2. Main to Inverter PCBs wiring connection defective
3. Main PCB defective 4. Inverter PCB defective
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
Check if ground is connection correctly or there are no related cables near the power line.
Check Point 1-1 : Turn the power on again.
Error displayed again?
Check Point 1-2 : Noise
Communication not received from Inverter PCB for 10 seconds or more
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 62. 6
Error Code : 62
04-26
Trouble shooting 16
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
EEPROM Data corrupted Error
*
YES NO
Outdoor unit Main PCB
1. Noise, momentary open, voltage drop 2. Main PCB defective
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Replace Main PCB
Change Main PCB and set up the original address.
Check Point 1-1 : Turn the power on again.
Error generated again after Field setting all clear (push button SW F3 (function mode) -35 execution) and the power was turned back on?
Set contents sum value memorized in EEPROM and sum value calculated based on the set contents read from EEPROM do not match Regarding the sum value, only the contents set in the push button SW setting mode (F2) shall be the objective.
Reset the setting of F2 (setting mode) by push button SW. * To clear the setting of F2 by Field setting all clear.
Check Point 1-2 : Noise, momentary open, voltage drop
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 62. 8
Error Code : 62
04-27
Trouble shooting 17
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Inverter Error
YES
NO
OK
Check Point 1-2 : Noise, momentary open, voltage drop
Inverter PCB
Error information received from Inverter PCB
1. Noise, momentary open, voltage drop. 2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open 3. Filter PCB ( INV) defective 4. Inverter PCB defective
Check if temporary voltage drop was not generated. Check if momentary open was not generated. Check if ground is connection correctly or there are no related cables near the
power line.
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check Cable open check
Check Filter PCB (INV) and Inverter PCB.
Check Point 1-1 : Turn the power on again.
Error displayed again?
Check Point 3 : Check Filter PCB (INV) and Inverter PCB
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 63. 1
Error Code : 63
04-28
Trouble shooting 18
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Filter PCB
Inverter PCB short interruption detection
OK
OK
OK
Inverter PCB
Check Point 1 : Noise, momentary power failure, voltage drop
Check if temporary voltage drop was not generated. Check if momentary power failure was not generated. Check if ground is connection correctly or there are no related cables near the power line.
Cable open check
Check Point 2 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check
Check Point 3 : Check Main PCB
Check Main PCB Power supply
Check Point 4 : Replace Inverter PCB
Replace Inverter PCB.
1. Noise, momentary power failure, voltage drop
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Main PCB defective 4. Inverter PCB defective
''Momentary power failure" received from Inverter PCB
Indoor Unit : No Display
Outdoor Unit : E. 67. 2
Error Code : 67
04-29
Trouble shooting 19
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
OUTDOOR UNIT Error Method: Outdoor Unit transmission PCB
Parallel Communication Error
YES
OK
OK
Check Point 1-2 : Noise
Detective details:
Forecast of Cause :
NO
Detective Actuators:
Outdoor unit Main PCB Communication PCB
Parallel communication (communication between main CPU and communication PCB ) failed 5 times.
1. Noise 2. Communication PCB connection defective
3. Communication PCB defective 4. Main PCB defective
Check if ground is connection correctly or there are no related cables near the power line.
Check Point 4 : Replace Main PCB
Change Main PCB and set up the original address.
Check Point 1-1 : Turn the power on again.
Error displayed again?
Check Point 2 : Check the communication PCB connection
Communication PCB connection check
Check Point 3 : Check the communication PCB
Communication PCB check
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 69. 1
Error Code : 69
04-30
Trouble shooting 20
Indicate or Display:
Discharge Temp Sensor Error
OK
OK
DC
CN141
THERMISTOR
(COMP SHELL )
< TH10 >
THERMISTOR
(DIS.TEMP )
< TH1 >
BLACK
BLACK
BLA
C
K
BLA
C
K
1 2 3 4 5 6
1 2 3 4 5 6
Discharge temperature thermistor 1
Discharge temperature thermistor 1 short detected Discharge thermistor 1 open detected after compressor 1 operated continuously for 5 minutes or more
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN141:1-2) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
If the voltage does not appear, replace Main PCB and set up orignal address.
Discharge temperature sensor 1 (CN141:1-2)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 71. 1
Error Code : 71
04-31
Trouble shooting 21
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Compressor Temp Sensor Error
DC
CN141
THERMISTOR
(COMP SHELL1)
<TH10>
THERMISTOR
(DIS.TEMP.1)
<TH1>
BLA
C
K
BLA
C
K
BLACK
BLACK
1 2 3 4 5 6
1 2 3 4 5 6
Compressor temperature thermistor 1
Compressor temperature thermistor 1 short detected Compressor thermistor 1 open detected after compressor 1 operated continuously for 5 minutes or more
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN141:5-6) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
Compressor temperature sensor 1 (CN141:5-6)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 72. 1
Error Code : 72
If the voltage does not appear, replace Main PCB and set up orignal address.
04-32
Trouble shooting 22
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
DC
CN143
THERMISTOR
THERMISTOR
(SUC. TEMP.)
< TH4 >
(HEX. EXIT.)
< TH5 >
BLACK
BLACK
1 2 3 4
1 2 3 4
BLACK
BLA
C
K
Heat exchanger liquid temperature thermistor
Heat exchanger liquid temperature thermistor short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN143:3-4) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
Heat exchanger liquid temperature sensor (CN143:3-4)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 73. 3
Error Code : 73
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
04-33
Outdoor Unit Heat Ex. Liquid Temp. Sensor Error
Trouble shooting 23
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Outdoor Temp Sensor Error
OK
DC
CN144
(OUT TEMP.)
< TH3 >
THERMISTOR
1 2 3
1 2 3
B
LA
CK
BLA
C
K
Outdoor temperature thermistor
Outdoor temperature thermistor short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
Check Point 2: Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information ".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN144:1-3) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
Outdoor temperature sensor (CN144:1-3)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 74. 1
Error Code : 74
If the voltage does not appear, replace Main PCB and set up orignal address.
If the voltage does not appear, replace Main PCB and set up orignal address.
04-34
Trouble shooting 24
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Suction Gas Temp Sensor Error
OK
DC
CN143
BLACK
BLA
C
K
1 2 3 4
1 2 3 4
BLACK
BLACK
Suction gas temperature thermistor
Suction gas temperature thermistor short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.) * For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN143:1-2) voltage value = 5V Remove the thermistor from Main PCB, check the voltage.
Suction gas temperature sensor (CN143:1-2)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 75. 1
Error Code : 75
If the voltage does not appear, replace Main PCB and set up orignal address.
04-35
THERMISTOR
(HEX. EXT)
< TH5 >
THERMISTOR
(SUC. TEMP)
< TH4 >
Trouble shooting 25
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Heat Sink Temp Sensor Error
Inverter PCB
Heat sink temperature thermistor ( Inside IPM ) open/short circuit detected
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash, Filter LED Continuous Flash.
Outdoor Unit : E. 77. 1
Error Code : 77
04-36
Trouble shooting 26
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
1. Inverter PCB failure
Forecast of Cause :
If this error is displayed, replace Inverter PCB
Loading...