Read carefully all security information before use or install the air conditioner.
Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
This unit must be installed by qualified personnel with a capacity certificate for handling
refrigerant fluids. Refer to regulation and laws in use on installation place.
The installation must be carried out in compliance with regulations in force in the place
of installation and the installation instructions of the manufacturer.
This unit is part of a set constituting an air conditioner. It must not be installed alone or
with non-authorized by the manufacturer.
Always use a separate power supply line protected by a circuit breaker operating on all
wires with a distance between contact of 3 mm for this unit.
The unit must be correctly earthed (grounded) and the supply line must be equipped
with a differential breaker in order to protect the persons.
The units are not explosion proof and therefore should not be installed in explosive
atmosphere.
Never touch electrical components immediately after the power supply has been turned
off. Electric shock may occur. After turning off the power, always wait 5 minutes before
touching electrical components.
This unit contains no user-serviceable parts. Always consult authorized service personnel to repairs.
When moving, consult authorized service personnel for disconnection and installation
of the unit.
This mark indicates procedures which, if improperly performed,
might possibly result in personal harm to the user, or damage
to property.
2. ABOUT THIS PRODUCT
2.1. Precautions for using R410A refrigerant
WARNING
Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle. If air enters the refrigeration cycle, the pressure in the refrigeration cycle will
become abnormally high and cause the piping to rupture.
If there is a refrigerant leak, make sure that it does not exceed the concentration limit.
If a refrigerant leak exceeds the concentration limit, it can lead to accidents such as
oxygen starvation.
Do not touch refrigerant that has leaked from the refrigerant pipe connections or other
area. Touching the refrigerant directly can cause frostbite.
If a refrigerant leak occurs during operation, immediately vacate the premises and thoroughly ventilate the area. If the refrigerant comes in contact with a flame, it produces a
toxic gas.
2.2. Special tools for R410A
1. SAFETY PRECAUTIONS
• Be sure to read this Manual thoroughly before installation.
• The warnings and precautions indicated in this Manual contain important information
pertaining to your safety. Be sure to observe them.
• Hand this Manual, together with the Operating Manual, to the customer. Request the
customer to keep them on hand for future use, such as for relocating or repairing the
unit.
WARNING
Request your dealer or a professional installer to install the indoor unit in accordance
with this Installation Manual. An improperly installed unit can cause serious accidents
such as water leakage, electric shock, or fire. If the indoor unit is installed in disregard of
the instructions in the Installation Manual, it will void the manufacturer’s warranty.
Do not turn ON the power until all work has been completed. Turning ON the power
before the work is completed can cause serious accidents such as electric shock or fire.
If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant
comes in contact with a flame, it produces a toxic gas.
Installation work must be performed in accordance with national wiring standards by
authorized personnel only.
Except for EMERGENCY, never turn off main as well as sub breaker of the indoor units
during operation. It will cause compressor failure as well as water leakage.
First, stop the indoor unit by operating the controller, converter or external input device
and then cut the breaker.
Make sure to operate through the controller, converter or external input device.
When the breaker is designed, locate it at a place where the users cannot start and stop
in the daily work.
This mark indicates procedures which, if improperly performed,
might lead to the death or serious injury of the user.
WARNING
To install a unit that uses R410A refrigerant, use dedicated tools and piping materials that have been manufactured specifically for R410A use. Because the pressure
of R410A refrigerant is approximately 1.6 times higher than the R22, failure to use
dedicated piping material or improper installation can cause rupture or injury.
Furthermore, it can cause serious accidents such as water leakage, electric shock, or
fire.
Tool nameContents of change for R22 tool
Pressure is huge and cannot be measured with a conventional gauge. To prevent erroneous mixing of other refriger-
Gauge manifold
Charging hose
Vacuum pump
Gas leakage detectorSpecial gas leakage detector for HFC refrigerant R410A.
ants, the diameter of each port has been changed.
It is recommended to use a gauge manifold with a high
pressure display range -0.1 to 5.3 MPa and a low pressure
display range -0.1 to 3.8 MPa.
To increase pressure resistance, the hose material and base
size were changed.
A conventional vacuum pump can be used by installing a
vacuum pump adapter.
• A conventional vacuum pump can be used by installing a
vacuum pump adapter.
• Be sure that the pump oil does not back flow into the
system. Use one capable for vacuum suction of -100.7kPa
(5 Ton, -755mmHg).
En-1
2.3. Accessories
WARNING
For installation purposes, be sure to use the parts supplied by the manufacturer or other
prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit falling,
water leakage, electric shock, or fire.
• The following installation parts are furnished. Use them as required.
• Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and ShapeQ’tyApplication
Operating
Manual
Installation
Manual
Operating
Manual
(CD-ROM)
Wall hook bracket
Tapping screw (M4 × 25 mm)(004/007/
Drain hose Insulation
Cloth tape
Cable tie
Air cleaning filter
Air cleaning filter frame
1
1
1
1
009
model)
5
(030/034
model)
8
(030/034
model)
1
1
(030/034
model)
2
(030/034
model)
2
(030/034
model)
2
(This book)
For indoor unit installation.
For wall hook bracket installation.
For installing drain hose
For indoor unit installation.
For transmission and remote controller
cable binding.
For installation, refer to the “CLEANING
AND CARE” in the operating manual.
2.4. Optional parts
Descrip-
tion
External
connect kit
ModelApplication
UTY-XWZXZC For output function (Output terminal / CNB01)
UTY-XWZXZB
UTY-XWZXZD For control input function (Dry contact terminal / CNA02)
UTY-XWZXZ7
UTY-XWZXZE
For control input function (Apply voltage terminal /
CNA01)
For forced thermostat off function (Apply voltage terminal
/ CNA03)
For forced thermostat off function (Dry contact terminal
/ CNA04)
3. INSTALLATION WORK
Correct initial installation location is important because it is difficult to move unit after it is
installed.
3.1. Selecting an installation location
Decide the mounting position together with the customer as follows.
WARNING
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
CAUTION
Do not install the indoor unit in the following areas:
• Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the parts to fail or the unit to leak water.
• Area filled with mineral oil or containing a large amount of splashed oil or steam, such
as a kitchen. It will deteriorate plastic parts, causing the parts to fail or the unit to leak
water.
• Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
• Area that can cause combustible gas to leak, contains suspended carbon fibers or
flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas leaks
and settles around the unit, it can cause a fire.
• Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects.
It can degrade the quality of the preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, power supply cable, transmission cable, and remote controller
cable at least 1 m away from a television or radio receivers. The purpose of this is to
prevent TV reception interference or radio noise. (Even if they are installed more than 1
m apart, you could still receive noise under some signal conditions.)
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Take precautions to prevent the unit from falling.
(1) Install the indoor unit on a place having a sufficient strength so that it withstands
against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where connection to the outdoor unit (or RB unit) is easy.
(5) Install the unit where the connection pipe can be easily installed.
(6) Install the unit where the drain pipe can be easily installed.
(7) Install the unit where noise and vibrations are not amplified.
(8) Take servicing, etc., into consideration and leave the spaces. Also install the unit
where the filter can be removed.
(9) Do not install the unit where it will be exposed to direct sunlight.
Detection range of the human sensor (030/034 model only)
CAUTION
Do not hit or push the human sensor. This may lead to damage or malfunction.
Do not touch the human sensor. Any scratches or dirt may lead to incorrect detection.
Do not place large objects near the human sensor. Also keep heating units outside the
sensor’s detection area.
*1: The distance between the wall hook bracket and the ceiling.
*2: The distance between the wall hook bracket and the side wall.
80 mm or
more (*1)
1800 mm or
more
Wall hook bracket
Wall cap
Right side 200
mm or more (*2)
3.3. Installing the unit
WARNING
Install the air conditioner in a location which can withstand a load of at least 5 times the
weight of the main unit and which will not amplify sound or vibration. If the installation
location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
3.3.1 Determining the piping direction
The piping can be connected
according to the figure and table.
When the piping is connected
in direction (B), (C), (D) or (E),
cut along the piping groove in
the side of the front panel with a
hacksaw.
Model
004/007/009
030/034GoodGoodGoodGoodGoodGoodGood
(A)
Rear
outlet
(B)
Right
outlet
GoodGoodGoodGoodGood―Good
(B)
(C)
Bottom
outlet
(C)
(D)
Left
bottom
outlet
(A)
(E)
Left
outlet
(F)
(F)
Center
outlet
3.3.2 Installing the wall hook bracket
• Refer to figure below for the installation hole dimensions of the wall hook bracket.
• Before fastening the wall hook bracket to the wall with the screws, level it by tapping the
hook at the center of bracket to the wall with the handle of a screwdriver.
(1) Fasten the wall hook bracket to the wall with 5 or more screws and anchor bolts
through the holes near the outer edge of the bracket.
(Do not install the wall hook bracket at only 1 place or at an angle.)
(2) For a concrete wall, embed anchor bolts (10 mm dia.) into the wall at the wall hook
bracket holes.
(Allow the anchor bolts to stick out at least 18 mm from the wall. Use 2 bolts for flat
concrete wall and 4 bolts for blister concrete wall.)
(3) Install the nuts to the anchor bolts through the wall hook bracket.
(4) Finally tighten the bolts and wood screws after confirming, using the level indicator,
that the clamp is horizontal.
WARNING
Install the wall hook bracket level, both horizontally and vertically. If the wall hook
bracket is tilted, wa ter will drip to the floor.
As the weight of the indoor unit is 15 to 18 kg, it should be installed after properly examining the place where it is in tended to be in stalled. If the place is not strong enough, a
plank or girder should be used to make the place sufficiently strong so that the wall can
support the weight.
(D)
(G)
Left rear
outlet
(E)
(G)
Wall hook bracket
Tapping screw
(accessory, 8 pcs)
3.3.3 Cutting the hole in the wall for the connecting piping
(1) Cut a hole in the wall at the position shown in the following.
(2) Cut the hole so that the outside end is lower (5 to 10 mm) than the inside end.
(3) Always align the center of the wall hole. If misaligned, water leakage will occur.
(4) Cut the wall pipe to match the wall thickness, stick it into the wall cap, fasten the cap
with vinyl tape, and stick the pipe through the hole.
(5) For left piping and right piping, cut the hole a little lower so that drain water will flow
freely.
004/007/009 model
Wall hook bracket
Center markCenter mark
65 mm dia. hole65 mm dia. hole
030/034 model
Wall hook bracket
10 mm
or more
Attach the wall pipe
WARNING
If the wall pipe is not used, the
cable interconnecting the indoor
and outdoor units may touch
metal and cause electric leakage.
Fasten with vinyl
tape
Wall cap*
Center mark
80 mm dia. hole80 mm dia. hole
Wall pipe*
(Inside)Wall(Outside)
10 mm
or more
5 to 10 mm
low
* Locally
LowerLower
purchased
3.3.4 Attach the drain hose insulation (030/034 model only)
• Wrap the insulation around the
drain hose, making sure that
there are no gaps.
• Attach the Insulation (Drain
hose) to the drain hose.
Insulation (Drain hose)
Drain hose
(Accessories)
En-3
3.3.5 Forming the drain hose and pipe
CAUTION
Insert drain hose and drain cap securely. Drain should slope down to avoid water leakage.
When inserting the drain hose, no other material than water should be applied. Application of other material than water will cause deterioration of the hose, and may cause
water leakage.
After you remove a drain hose, be sure to attach the drain cap.
When you secure the piping and drain hose with tape, arrange the drain hose so that it
is at the bottom of the piping.
For drain hose piping in low temperature environment, you need to apply freeze protec-
tion to prevent a frozen drain hose.
After cooling operation is performed in low temperature environment, (when outdoor
temperature under 0 °C,) water in the drain hose could be frozen. Frozen drain water
will block the water flow in the hose, and may cause water leakage at the indoor unit.
[For (A) Rear piping, (B) Right piping and (C) Bottom piping]
(1) Install the indoor unit piping in
the direction of the wall hole
and bind the drain hose and
pipe together with vinyl tape.
(2) Install the piping so that the
drain hose is at the bottom.
(3) Wrap the pipe of the indoor unit
that visible from the outside
with decorative tape.
(4) For right or bottom outlet
piping, cut off the piping outlet
cutting groove with a hacksaw.
Bottom piping
Indoor unit drain hose
(bottom)
Bind with vinyl tape
Pipe (top)
Rear piping
[For (D) Left bottom piping, (E) Left piping and (F) Center piping, (G) Left rear
piping]
CAUTION
Insert the drain hose and drain cap into the drain port, making sure that it comes in contact with the back of the drain port, and then mount it. If the drain hose is not connected
properly, leaking will occur.
(1) Interchange the drain cap and the drain hose.
• For left outlet piping, cut off
the piping outlet cutting groove
with a hacksaw.
• Remove the drain cap by pulling at the projection at the end
of the cap with pliers, etc.
Right side
Drain cap
Left side
Drain hose
Drain hose removal and installation method of the 004/007/009 model
RemovalInstallation
Screw
Drain fixture
Remove the screw at the left
of drain hose and pull out drain
hose.
Drain hose
Screw hole
Vertically insert the drain hose toward the inside, so that
the drain fixture can accurately align with the screw hole
around the drain cock. After inserting and before replacing, reinstall and fix the removed screws.
Drain cock
Drain fixture
Drain hose
Screw
Installing the drain cap
No gap
Hexagonal
wrench
(2) Align the marks on the wall hook bracket and shape the connection pipe.
For left piping and left rear piping, align the marks on the wall hook bracket and
shape the connection pipe.
Wall hook
bracket
Drain cock
Drain cap
Use a hexagonal wrench 4 mm at opposite side to
insert the drain cap, till the drain cap contacts the
tip of drain cock.
Alignment marks
004/007/009 model
(3) Bend the connection piping at the bend radius of 70 mm or more and install no more
than 35 mm from the wall.
030/034 model
(4) Bend the connection piping at the bend radius of 100 mm or more and install no
more than 35 mm from the wall.
3.3.6 Installing the indoor unit
(1) After passing the indoor piping and drain hose through the wall hole, hang the indoor
unit on the hooks at the top and bottom of the wall hook bracket.
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the
2 bottom hooks while lowering the unit and pushing it against the wall.
004/007/009 model
Indoor
unit
030/034 model
Indoor
unit
(2) Insert the spacer, etc. between the
indoor unit and the wall hook bracket
and separate the bottom of the indoor
unit from the wall.
(Fitting)
Top hooks
Bottom hooks
Top hooks
Bottom hooks
Indoor unit
Spacer
Wall hook bracket
Wall hook
bracket
Wall hook
bracket
4. PIPE INSTALLATION
CAUTION
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with
refrigerant R410A models. Also, when storing the piping, securely seal the openings by
pinching, taping, etc.
While welding the pipes, be sure to blow dry nitrogen gas through them.
4.1. Selecting the pipe material
CAUTION
Do not use existing pipes from another refrigeration system or refrigerant.
Use pipes that have clean external and internal sides without any contamination which
may cause trouble during use, such as sulfur, oxide, dust, cutting waste, oil, or water.
It is necessary to use seamless copper pipes.
Material : Phosphor deoxidized seamless copper pipes
It is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes that have a collapsed, deformed, or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may
become blocked with contaminants.
Improper pipe selection will degrade performance. As an air conditioner using R410A
incurs pressure higher than when using conventional (R22) refrigerant, it is necessary to
choose adequate materials.
• Thicknesses of copper pipes used with R410A are as shown in the table.
• Never use copper pipes thinner than those indicated in the table even if they are available on the market.
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter [mm (in)]Thickness [mm]
6.35 (1/4)0.80
9.52 (3/8)0.80
12.70 (1/2)0.80
15.88 (5/8)1.00
19.05 (3/4)1.20
Connection
piping
Connection pipe
(Liquid pipe)
Connection pipe (Gas pipe)
En-4
4.2. Pipe requirement
CAUTION
Refer to the installation manual for the outdoor unit for description of allowable pipe
length and height difference.
Use pipe with water-resistant heat insulation.
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause
water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is
expected to exceed 70 %, install heat insulation around the refrigerant piping.
If the expected humidity level is 70 to 80 %, use heat insulation that is 15 mm or thicker
and if the expected humidity exceeds 80 %, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the
surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less
(at 20 °C).
4.3. Flare connection (pipe connection)
WARNING
Tighten the flare nuts with a torque wrench using the specified tightening method. Otherwise, the flare nuts could break after a prolonged period, causing refrigerant to leak
and generate hazardous gas if the refrigerant comes into contact with a flame.
4.3.1 Flaring
Use special flare tool exclusive for R410A.
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor and outdoor units
(or RB unit) respectively) onto the pipe and perform the flare processing with a flare
tool. Use the special R410A flare tool. Leakage of refrigerant may result if other flare
nuts are used.
(4) Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from
entering the pipes.
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
L
Pipe outside diameter
[mm (in)]
6.35 (1/4)
9.52 (3/8)13.2
12.70 (1/2)16.6
15.88 (5/8)19.7
19.05 (3/4)24.0
When using conventional (R22) flare tools to flare R410A pipes, the dimension A should
be approximately 0.5 mm more than indicated in the table (for flaring with R410A flare
tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
It is recommended that a R410A flaring tool is used.
Width across flats
Pipe outside diameter [mm (in)]
Dimension A [mm]
Flare tool for R410A,
clutch type
0 to 0.5
6.35 (1/4)17
9.52 (3/8)22
12.70 (1/2)26
15.88 (5/8)29
19.05 (3/4)36
A
Pipe
Dimension B
Width across flats of Flare nut [mm]
4.3.2 Bending pipes
• The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
• When pipes are repeatedly bend or stretched, the material will harden, making it difficult
to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
If the pipe is bent repeatedly at the same place, it will break.
9.1
0
[mm]
-0.4
4.3.3 Pipe connection
When the flare nut is tightened properly by your hand, hold the body side coupling with a
separate spanner, then tighten with a torque wrench.
CAUTION
Be sure to install the pipe against the port on the indoor unit and the outdoor unit correctly. If the centering is improper, the flare nut cannot tightened smoothly. If the flare
nut is forced to turn, the threads will be damaged.
Do not remove the flare nut from the indoor unit pipe until immediately before connecting the connection pipe.
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to
tighten the flare nut correctly.
Flare nut
[mm (in)]
6.35 (1/4) dia.16 to 18 (160 to 180)
9.52 (3/8) dia.32 to 42 (320 to 420)
12.70 (1/2) dia.49 to 61 (490 to 610)
15.88 (5/8) dia.63 to 75 (630 to 750)
19.05 (3/4) dia.90 to 110 (900 to 1,100)
Tightening torque
[N·m (kgf·cm)]
Tighten with 2 wrenches.
Torque
wrench
Indoor unit pipe
(Body side)
Holding
wrench
Flare
nut
Connection pipe
5. ELECTRICAL WIRING
WARNING
Electrical work must be performed in accordance with this Manual by a person certified
under the national or regional regulations. Be sure to use a dedicated circuit for the unit.
An insufficient power supply circuit or improperly performed electrical work can cause
serious accidents such as electric shock or fire.
Before starting work, check that power is not being supplied to the all units.
Use the included connection cables and power cables or ones specified by the
manufacturer. Improper connections, insufficient insulation, or exceeding the allowable
current can cause electric shock or fire.
For wiring, use the prescribed type of cables, connect them securely, making sure that
there are no external forces of the cables applied to the terminal connections. Improperly connected or secured cables can cause serious accidents such as overheating the
terminals, electric shock, or fire.
Do not modify the power cables, use extension cables, or use any branches in the wiring. Improper connections, insufficient insulation, or exceeding the allowable current can
cause electric shock or fire.
Match the terminal board numbers and connection cable colors with those of the outdoor unit (or RB unit). Erroneous wiring may cause burning of the electric parts.
Securely connect the connection cables to the terminal board. In addition, secure the
cables with wiring holders. Improper connections, either in the wiring or at the ends of
the wiring, can cause a malfunction, electric shock, or fire.
Always fasten the outside covering of the connection cable with the cable clamp. (If the
insulator is chafed, electric discharge may occur.)
Securely install the electrical box cover on the unit. An improperly installed electrical box
cover can cause serious accidents such as electric shock or fire through exposure to
dust or water.
Install sleeves into any holes made in the walls for wiring. Otherwise, a short circuit
could result.
Install an earth leakage breaker. In addition, install the earth leakage breaker so that the
entire AC main power supply is cut off at the same time. Otherwise, electric shock or fire
could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable firmly to the terminal board. Imperfect installation may
cause a fire.
If the supply cable is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualified persons in order to avoid a hazard.
En-5
CAUTION
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cable to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 50 mm or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of the
PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor units for more than 10 seconds to discharge static
electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.
5.1. Electrical requirement
Voltage rating
Operating range
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Specifications for local wiring power cord and branch wiring are in compliance with local
code.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Breaker should be installed at every refrigerant system. Do not use a breaker in a different
refrigerant system.
Refer to the table for the breaker specifications of each installation condition. Perform
the power crossover wiring within the range of the same refrigerant system. When the
crossover wiring is done, make a connection for indoor units to satisfy conditions A and B
below.
A. Current breaker requirements
ModelMCAMFA
AS*A004GTAH 0.16 A
AS*A007GTAH 0.23 A
AS*A009GTAH 0.38 A
AS*E004GTAH 0.16 A
AS*E007GTAH 0.23 A
AS*E009GTAH 0.38 A
AS*A030GTAH 0.66 A
AS*A034GTAH 0.87 A
• MCA: Minimum Circuit Ampacity
• MFA: Maximum Fuse Ampacity
When the power crossover wiring is done, make it
so that the total of the MCA of the connected RB
units and indoor units does not exceed the 15 A.
For RB unit MCA, refer to the RB unit installation
manual.
20 A
If the capacity of connected RB units and indoor
units exceeds the upper limit, either add breakers
or use a breaker with a greater capacity.
B. Earth leakage breaker requirements
Maximum connect-
Breaker capacity
30 mA, 0.1 sec or less44 or less *2
100 mA, 0.1 sec or less45 to 148
able “indoor units”
or “indoor units +
RB units” *1
5.1.1 Cable specifi cations
Recommended
cable size (mm²)
Power supply cable2.5
Transmission cable0.33
Remote controller
cable (2-wire type)
*1: Use shielded cable in accordance with local rules for remote controller cable.
0.33 to 1.25
Cable typeRemark
Type245 IEC57
or equivalent
LONWORKS
compatible
cable
Sheathed PVC
cable *1
230 V
198 to 264 V (50 Hz)
198 to 253 V (60 Hz)
*1: Heat pump type: indoor units,
Heat recovery type: indoor units
and RB units.
*2: If the total number of units con-
nected to the breaker exceeds 44,
either add a 30mA breaker, or use
breakers with a greater capacity.
2 Cable + earth (ground)
22 AWG LEVEL 4 (NEMA)
non-polar
2 core, twisted pair
solid core diameter 0.65 mm
Non-polar 2 core, twisted
pair
5.2. Wiring method
Example
Outdoor unit or RB unit *1
Transmission
Indoor unit
Transmission
Power supply
Breaker
Power supply
*1: When connecting to the Heat Recovery System, refer to the installation manual of the
RB unit.
*2: Earth (Ground) the remote controller if it has an earth (ground) cable.
*3: The 3-wire type remote controller is not used.
(Crossover wiring of power supply)
Pull box
*2*2
Remote controller
Indoor unit
Power supplyPower supplyPower supply
Breaker
Power supply
Remote
control
Breaker
*3*3*3
(Master)
Pull box
Indoor unitIndoor unit
*2
Breaker
Remote controller
(Slave)
Indoor unitIndoor unit
Remote controller
5.3. Unit wiring
• Before attaching the cable to terminal block.
5.3.1 Power supply cable
20 mm
Earth
(ground) cable
A. For solid core wiring
(1) To connect the electrical terminal, follow the below diagram and connect after looping
it around the end of the cable.
(2) Use the specified cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(3) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
(4) Do not tighten the terminal screws too much, otherwise, the screws may break.
(5) See the table for the terminal screw tightening torques.
(6) Please do not fix 2 power supply cables with 1 screw.
Strip 25 mm
Cable
L
Screw with
special washer
Cable end (Loop)
Terminal block
L (mm)
004/007/009
model
4065
Screw with
special washer
Cable end (Loop)
Cable
Loop
030/034
model
WARNING
When using solid core cables, do not use the attached ring terminal. If you use the solid
core cables with the ring terminal, the ring terminal's pressure bonding may malfunction
and cause the cables to abnormally heat up.
En-6
B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the figure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fix 2 power supply cables with 1 screw.
Strip 10 mm
Ring terminal
5.4. Wiring
(1) Open the intake grille. Refer to “8. FRONT PANEL REMOVAL AND INSTALLATION”.
(2) Remove the wire cover and remove the cable clamp.
004/007/009 model030/034 model
Screw
Wire cover
Screw
Cable
clamp
Cable
clamp
Screw
Sleeve
Screw with
Cable
special washer
Ring terminal
Terminal block
Screw with
special washer
Ring terminal
Cable
WARNING
Use ring terminals and tighten the terminal screws to the specified torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
Terminal numberTightening torque
M4 screw (Power supply/L, N, GND)1.2 to 1.8 N·m (12 to 18 kgf·cm)
5.3.2 Transmission and Remote controller cable
Transmission cableRemote controller cable
GOOD
20 mm
35 mm
PROHIBITED
Shield
cable
(no film)
• Connect remote controller and transmission cables as shown in figure below.
20 mm
Wire cover
(3) Connect the end of the connection cable fully into the terminal block.
004/007/009 model
Symbol Connection cable
A
LPower supply cable
B
N
C
D
E
F
G
H
Earth (ground) for
power supply cable
Earth (ground) for
transmission cable,
wired remote controller cable (if necessary) and EV kit cable
(EEV external model
Tighten the terminal screws to the specified torques, otherwise, abnormal overheating
may be occurred and possibly cause serious damage inside the unit.
To peel the sheath from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the wire by overtightening the
screw. On the other hand, an under tightened screw can cause faulty contact, which will
lead to a communication failure.
Connect
After connecting the EV kit cable, slide the tube (included with
the EV kit) over the connector to protect it.
TubeConnectCable tie (Small)
When you attach the cable clamp, make sure that the cables are not jutting out from the
clamp or being pinched by the clamp.
030/034 model
Symbol Connection cable
A
LPower supply cable
B
I
H
G
F
E
D
C
Cable tie
(accessories)
X1Y1 Y2 Y3X2
LN
Cable
clamp
A
B
N
C
D
E
F
G
H
I
Earth (ground) for
power supply cable
X1 Transmission cable
X2
Earth (ground) for
transmission cable
and wired remote
controller cable (if
necessary)
Y1 Wired remote control-
ler cable (nonpolar)
Y2
Y3 Do not use
En-7
6. FIELD SETTING
There are 3 methods for address setting by FIELD SETTING as follows.
Please set by either of the methods.
Each setting method is described in below (1) to (3).
(1)
IU AD, REF AD SW settings:
(2) Remote controller settings: Refer to the wired or wireless remote controller manual
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
6.1. Setting the address
Manual address setting method
The indoor unit address and the refrigerant circuit address can also be set up through the
wireless remote controller
Be sure to turn OFF the power before performing the field setting.
• Position and detail of the switches
In the 004/007/009 models, you need to
remove the front panel. Refer to “8. FRONT
PANEL REMOVAL AND INSTALLATION”.
004/007/009 model030/034 model
This section (7.1. Setting the address)
for detailed setting information. (Set IU AD, REF AD
SW to 0)
information. (Set IU AD, REF AD SW to 0)
CAUTION
• If working in an environment where the wireless remote controller can be used, the addresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to “00”.
(For information on setting using the wireless remote controller.)
t set the indoor unit address (IU AD SW) at 64 to 99. It may result in failure
Do no
.
6.2. Custom code setting
• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor unit
Code change
A B C D
004/007/009 model030/034 model
For refrigerant
circuit address
IU ADREF ADRC AD
SET3SET4
For refrigerant
circuit address
For indoor unit
address
×10 IU AD ×1×10 REF AD ×1
For indoor
unit address
SET4
SET3
×10 ×1×10 ×1
• Please set it according to the following procedures when setting manually.
CAUTION
Use an insulated screwdriver to set the dip switches.
Be careful not to make mistakes for switch settings.
6.1.1 Indoor unit address
• Rotary switch (IU AD × 1)....Factory setting “0”
• Rotary switch (IU AD × 10)....Factory setting “0”
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A
6.1.2 Refrigerant circuit address
• Rotary switch (REF AD × 1)....Factory setting “0”
• Rotary switch (REF AD × 10)....Factory setting “0”
In the case of multiple refrigerant systems, set REF AD SW as shown in the Table A for
each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
SettingSetting rangeType of switch
Remote
controller
A B C D
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
004/007/009 model030/034 model
SET4
DIP switch
“SET3”
×10 IU AD ×1×10 REF AD ×1
ON
OFF
SET3
DIP switch “SET3”
SW1SW2SW3SW
DIP switch
SET3
SW1OFFONOFFON
SW2OFFOFFONON
4
IU ADREF ADRC AD
×10 ×1×10 ×1
SET3SET4
DIP switch “SET3”
Custom code
A (Factory
setting)
BCD
Indoor unit
address
Refrigerant
circuit address
0 to 63
0 to 99
Setting
example 2
Setting
example 63
IU AD × 10IU AD × 1
REF AD × 10REF AD × 1
En-8
6.3. Function setting
WARNING
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “6.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Filter
indicator
interval
Filter
indicator
action
(Forbidden)2300
Horizontal
swing
airflow
direction
Cool air
temperature trigger
Heat air
temperature trigger
Auto restart40
Cool Air
Prevention
Function
number
11
13
24
30
31
43
Setting number DefaultDetails
00 Standard
01 Longer
02 Shorter
00 Enable
01 Disable
Display only
on central
02
remote
controller
00 Standard
01 Left half
02 Right half
00 Standard
01 Adjust (1)
02 Adjust (2)
00 Standard
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
00 Enable
01 Disable
00 Super low
Follow the
setting on
01
the remote
controller
Adjust the filter cleaning interval
○
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
○
Enable or disable the filter indicator. Setting 02 is for use with a
central remote controller.
Adjust the cool air trigger temperature. To lower the trigger temperature, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic system
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor
unit by this function in normal
operation.
Be sure to operate by the control
unit, converter or external input
device.
○
Restrain the cold airflow with making the airflow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
○
00 All
Error report
target
Fan setting
when
cooling
thermostat
OFF
(Forbidden)6000
(Forbidden)6100
(Forbidden)6200
Auto mode
type
Deadband
value
47
49
68
69
Display only
on central
01
remote
controller
Follow the
setting on
00
the remote
controller
01 Stop
Single setpoint auto
00
mode
(traditional)
Dual setpoint auto
01
mode
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
04 2.0°C
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
6.3.1 Indoor unit indicator lamps
004/007/009 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
030/034 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
○
Change the target for reporting errors. Errors can either be reported
in all locations, or only on the
central remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
○
operation. Connection of the wired
remote controller (2-wire type
or 3-wire type) and switching its
thermistor are necessary.
○
○
○
○
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master indoor
unit (by wired remote controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
External
control
En-9
46
00 Start/Stop
Emergency
01
stop
02 Forced Stop
Allow an external controller to start
or stop the system, or to perform
○
an emergency stop.
If an
emerge
from an external controller, all refrigerant systems will be disabled.
If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
ncy stop is performed
6.3.2 Checking the function settings
Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
For use with a remote controller, set all rotary switches to 0, and refer to “6.1. Setting the
address” for details.
All switches are set to 0 at the factory.
ON
OFF
ON
OFF
ON
OFF
01Indoor unit address00 to 63
02Refrigeration address00 to 99
6.4. External input and external output (Optional parts)
In this setting, you need to remove the front panel. Refer to “8. FRONT PANEL REMOVAL
AND INSTALLATION”.
004/007/009 model
Dry contact
terminal
DIP switch
(SET 2)
ON OFF
SW4
SW3
SW2
SW1
Apply voltage terminal
(CNA02)
(CNA01)
030/034 model
Controller PCB
DIP switch
(SET 2)
ON OFF
SW4
SW3
SW2
SW1
Apply voltage terminal
(CNA04)
6.4.1 External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• “Operation/Stop” mode, “Emergency stop” mode or “Forced stop” mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Input
Input
Load
resistance
*a
device 1
Load
resistance
*a
device 2
(CNA04)
(CNA03)
(CNA02)
Controller
PCB
Output
terminal
(CNB01)
Output
terminal
(CNB01)
Dry contact
terminal
(CNA03)
(CNA01)
*1
P.C . B
CNA01
*b
Load
Input
*1:
Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a: The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
resistance
*a
device 3
Connected unit
CNA03
En-10
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
Input
Input
DC power supply
Load
resistance
device 1
Load
resistance
device 2
Connected unit
12 to 24V
P.C . B
CNA01
P.C . B
CNA01
P.C . B
CNA01
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
P.C . B
*c
*c
Ch 1
Ch 2
*c
Ch 3
Connected unit
*c: Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*d: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
K1
K4
K2
K5
Power supply for relay
K3
Input device 1
Input device 2
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
K6
GND
P.C . B
P.C . B
P.C . B
K1 - K6: Relay
(Device for DC Current)
CNA02
*d
CNA04
CNA02
CNA02
CNA02
Indoor unit
Indoor unit
Indoor unit
Operation behavior
● Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [SET2 SW2]Input signal type
OFF (Factory setting)Edge
ONPulse
● When function setting is “Operation/Stop” mode.
[In the case of “Edge” input]
ConnectorInput signalCommand
Ch1 of CNA01 or CNA02
OFF → ONOperation
ON → OFFStop
Edge
Pulse
The width of pulse must be
longer than 200 msec.
[In the case of “Pulse” input]
ConnectorInput signalCommand
CNA01 or CNA02
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
Indoor unit
● When function setting is “Emergency stop” mode.
[In the case of “Edge” input]
ConnectorInput signalCommand
Ch1 of CNA01 or CNA02
Indoor unit
[In the case of “Pulse” input]
ConnectorInput signalCommand
CNA01 or CNA02
Indoor unit
* All indoor units of same refrigerant system stops when Emergency stop operates.
Ch1
Ch2
Ch1OFF → ONEmergency stop
Ch2OFF → ONNormal
OFF → ON
OFF → ON
OFF → ONEmergency stop
ON → OFFNormal
Operation
Stop
● When function setting is “Forced stop” mode.
[In the case of “Edge” input]
ConnectorInput signalCommand
Ch1 of CNA01 or CNA02OFF → ONForced stop
ON → OFFNormal
[In the case of “Pulse” input]
ConnectorInput signalCommand
CNA01 or CNA02
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
“Operation/Stop” mode or “Emergency stop” mode, “Forced stop” mode can be selected
with function setting of indoor unit.
Ch1OFF → ONForced stop
Ch2OFF → ONNormal
● Forced thermostat off function
[“Edge” input only]
ConnectorInput signalCommand
Ch3 of CNA03 or CNA04
OFF → ONThermostat off
ON → OFFNormal
6.4.2 External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When indicator etc. are connected directly
Operation
indicator
Error
indicator
Indoor unit Fan
status indicator
connected unit
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
connected unitRelay (Locally purchased)
P.C . B
P.C . B
CNB
01
CNB
01
En-11
Operation behavior
ConnectorOutput voltageStatus
0VStop
DC 12 VOperation
0VNormal
DC 12 VError
0VIndoor unit fan stop
DC 12 VIndoor unit fan operation
CNB01
External output 1
Pins 1-2
External output 2
Pins 1-3
External output 3
Pins 1-4
6.4.3 Connection methods
Wire modification
(1) Remove insulation from wire attached to wire kit connector.
(2) Remove insulation from field supplied cable. Use crimp type insulated butt connector
to join field cable and wire kit wire.
(3) Connect the wire with connecting wire with solder.
IMPORTANT:
Be sure to insulate the connection between the wires.
Option parts:
Locally purchased
Solder and insulate the connected parts.
Connection terminals and wiring arrangement
In following figure, all the possible connectors are connected for description.
In actual installation, you cannot connect all the connectors at once.
004/007/009 model
CNA02
CNA01CNA03
Controller
PCB
External input /output wire
CNA04
CNB01
7. FINISHING
CAUTION
After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform
this section.
Install heat insulation around both the large (gas) and small (liquid) pipes. Failure to do
so may cause water leaks.
7.1. Connection pipe, cable and drain hose
Insulate the drain hose, if necessary, to prevent it from freezing.
(1) Insulate between pipes.
• For (A) Rear, (B) Right and (C) Bottom piping, overlap the connection pipe heat insula-
tion and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no
gap.
• For (D) Left bottom piping, (E) Left piping, (F) Center piping and (G) Left rear piping, butt
the connection pipe heat insulation and indoor unit pipe heat insulation together and bind
them with vinyl tape so that there is no gap.
((A) Rear, (B) Right and (C) Bottom piping)
Connection pipe
(heat insulation)
Bind the pipes together so
that there is no gap.
(For (D) Left bottom piping, (E) Left piping, (F) Center piping and (G) Left rear piping)
• Wrap the area which accommodates the rear piping housing section with cloth tape.
• Bind the connection cable with vinyl tape.
• Bundle the piping and drain hose together by wrapping them with cloth tape over the
range within which they fit into the rear piping housing section.
Connection pipe
Cloth tape
(Accessories)
Wrap with cloth tape.
Overlap the insulation.
Indoor unit pipe
(heat insulation)
Vinyl tape
Indoor unit pipe
030/034 model
Controller PCB
Connecting
cables
CNB01
CNA04
CNA03
CNA02
CNA02
CNA01
Connecting
cables
Connection cable (Power supply cable)
Vinyl tape
Connection cable (Transmission and Remote controller cable)
Pipe
Drain hose
(2) Temporarily fasten the connection cable along the connection pipe with vinyl tape.
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Pipe
Wrap with cloth tape
Cloth tape
Saddle*
GOOD
Pipe
Outside wall cap*
Wall
(Outdoors)
*Locally purchased
PROHIBITED
Sealer putty*
Drain
hose
Saddle
Lifted upWaveEnd in water
En-12
8. FRONT PANEL REMOVAL AND INSTALLATION
8.1. Intake grill removal and installation
Intake grill removalIntake grill installation
Open the intake
grille. While gently
pressing the left and
right mounting shafts
of the intake grille
outward “a”, remove
the intake grille in
direction of the arrow “b”.
Press 4 places on the intake grille to close it completely.
b
004/007/009
model
8.2. Front panel removal
004/007/009 model
(1) Remove wire cover and remove 3
screws.
NOTES:
When replacing the front panel, do not
scratch or damage the louver.
(2) The front panel is pulled to the front,
raising the upper surface, then the front
panel is removed.
030/034 model
(1) Remove 4 caps, remove
wire cover and remove
10 screws.
NOTES:
When replacing the front
panel, do not scratch or damage the louver.
(2) The front panel is pulled
to the front, raising the
upper surface, then the
front panel is removed.
While holding the
grille horizontal, set
the left and right
mounting shafts into
a
the pillow blocks
at the top of the
panel “c”. To latch
each shaft properly,
insert the shaft until
it snaps.
030/034
model
Screws (Wire cover)Wire cover
Screws (3 position)
Screws (Wire cover)
Screws
(10 position)
Caps (4 position)
c
Wire cover
Front panel
8.3. Front panel installation
004/007/009 model
(1) Firstly, fit the lower part of the front panel, and insert top and bottom hooks. ( 3 top
sides, 6 bottom sides)
Top holes
Bottom holes
(2) Three screws is attached.
(3) The wire cover is attached.
Indoor unit
Top hooks
Front panel
Bottom hooks
030/034 model
(1) First, fit the lower part of the front panel, and insert top and middle hooks. (3 top
sides, 5 middles)
Top hooks
Top holes (3 position)
Indoor unit
(2) Attach the 10 screws.
(3) Attach the wire cover.
(4) Attach the 4 caps.
Middle hooks
(5 position)
Front panel
(3 position)
Middle hooks
(5 position)
9. TEST RUN
9.1. Test run using Outdoor unit (PCB)
Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to be
used for the test run.
9.2. Test run using remote controller
• Refer to the Installation Manual for the remote controller to perform the test run using the
remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamp
flash slowly at the same time.
10. CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After
installation is complete, be sure to check the following check items again.
Check itemsIf not performed correctly
Has the indoor unit been installed
correctly?
Has there been a check for gas leaks
(refrigerant pipes)?
Has heat insulation work been
completed?
Does water drain easily from the
indoor units?
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
Are the wires and pipes all connected
completely?
Is the indoor unit earthed (grounded)? Short circuit
Is the connection cable the specified
thickness?
Are the inlets and outlets free of any
obstacles?
Does start and stop air conditioner
operation by remote controller or
external device?
After installation is completed, has the
proper operation and handling been
explained to the user?
Vibration, noise, indoor unit may drop
No cooling, No heating
Water leakage
Water leakage
No operation, heat or burn damage
No operation, heat or burn damage
No operation, heat or burn damage
No cooling, No heating
No operation
Check
box
En-13
11. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote controller
display. If you use a wireless remote controller, the lamp on the photodetector unit will
output error codes by way of blinking patterns. See the lamp blinking patterns and error
codes in the table below.
OPERATION
lamp (green)
(1) (2)
(1) (4)
(1) (6)
(2) (6)
(2) (9)
(3) (1)
(5) (1)
(3) (10)
(4) (1)
Error indications
TIMER lamp
(orange)
FILTER lamp
(red)
Wired Remote
Controller Error
code
Error contents
Remote controller communication error
Network communication error
Peripheral unit communication error
Indoor unit address
setting error
Connection unit
number error in wired
remote controller
system
Indoor unit power supply abnormal
Indoor unit main PCB
error
Indoor unit communication circuit (wired
remote controller) error
Indoor unit room temp.
thermistor error
Wired Remote Controller Display
UTY-RNR*Z2 (2-wire type)
Error icon
Touch the [Status].Touch the [Error Information].
2-digit numbers are corresponding to
the error code in the preceding table.
For more information, refer to the installation manual of the remote controller.
Touch the [Next Page] (or [previous page])
to switch to other indoor unit information.
UTY-RLR* (2-wire type)
Error icon
Error code
For more information, refer to the installation manual of the remote controller.
(4) (2)
(4) (4)
(5) (1)
(5) (2)
(5) (3)
(9) (15)
(10) (8)
(13) (1)
Display mode
: 0.5 s ON / 0.5 s OFF
: 0.1 s ON / 0.1 s OFF
( ) : Number of flashing
Indoor unit heat ex.
temp. thermistor error
Human sensor error
Indoor unit fan motor
1 error
Indoor unit coil (expansion valve) error
Indoor unit water drain
abnormal
Outdoor unit miscellaneous error
Poor refrigerant circulation
RB unit error
En-14
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.