READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED.
PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH
INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions
should always be followed to reduce the risk of fire,
electric shock and injury to person, including the following:
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK AND
INJURY TO PERSON, OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you
have questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service panel
and lock the service disconnecting means to prevent power from
being switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as
a tag, to the service panel.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK AND
INJURY TO PERSON, OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified
person(s) in accordance with all applicable codes and standards,
including fire-related construction.
b) Sufficient air is needed for proper combustion and exhausting
of gases through the flue (chimney) of fuel burning equipment
to prevent back drafting. Follow the heating equipment manufacturer’s
guideline and safety standards such as those published by the National
Fire Protection Association (NFPA) and the American Society for
Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE), and
the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
d) Ducted fans must always be vented to the outdoors.
e) If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI (Ground
Fault Circuit Interrupter) - protected branch circuit.
f) This unit must be grounded.
g) To avoid motor bearing damage and noisy and/or unbalanced
impellers, keep drywall spray, construction dust, etc. off power unit.
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, DO
NOT USE THIS FAN WITH ANY SOLID-STATE SPEED CONTROL DEVICE.
CAUTION: FOR GENERAL VENTILATING USE ONLY. DO NOT USE
TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS.
WARNING: DO NOT USE IN KITCHENS.
h) Read all instructions before installing or using exhaust fan.
WARNING: THE DUCTING FROM THIS FAN TO THE OUTSIDE OF
THE BUILDING HAS A STRONG EFFECT ON THE AIR FLOW, NOISE AND
ENERGY USE OF THE FAN. USE THE SHORTEST, STRAIGHTEST DUCT
ROUTING POSSIBLE FOR BEST PERFORMANCE, AND AVOID INSTALLING
THE FAN WITH SMALLER DUCTS THAN RECOMMENDED. INSULATION
AROUND THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD
GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY NOT ACHIEVE
THEIR RATED AIRFLOW.
SAVE THESE INSTRUCTIONS
A210952014 Rev. G 6-151 of 12
www.airkinglimited.com
INSTALLATION INSTRUCTIONS
CAUTION:
STARTING INSTALLATION.
MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
2. Choose the location for your fan. To ensure the best air and sound performance, it
is recommended that the length of ducting and the number of elbows be kept to a
minimum, and that insulated hard ducting be used Larger duct sizes will reduce noise
and airflow restrictions. This fan will require at least
8" of clearance in the ceiling or wall, and will mount
through drywall up to 3/4" thick. The fan mounts
between 16" or 24" on center joists using the 4
provided mounting rails.
3. Select the most convenient electrical knockout and
remove using a straight-blade screw driver (Figure 1).
4. No additional vibration deadening materials are needed
for this fan.
SECTION 2
New Construction
1. Install the rails on the housing and position the housing next to the joist. Line up housing
so that it will be flush with the finished ceiling. Secure the ends of the rails with screws
or nails (not included) to the joists and slide the housing into the final position (Figure 2).
Figure 1
SECTION 4
Ducting
NOTE: 4" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL
BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible
for best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed
with existing ducts may not achieve their rated air flow.
1. Connect the ducting to the fan’s duct collar (Figure 4). Secure in place using tape
or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is
recommended that low restriction termination fittings be used.
Ducting
Duct
Collar
Figure 4
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar
material to create an air-tight path to minimize building heat loss or gain and to reduce
the potential for condensation. Place/wrap insulation around duct and/or fan in order to
minimize possible condensation buildup within the duct, as well as building heat loss or
gain (Figure 5).
Roof Cap*
Insulation*
(place around and
over Fan Housing
(with built-in
damper)
Housing
Joist
Figure 2
Mounting Rails
SECTION 3
Existing Construction
1. Set housing in position between the joist and trace an outline onto the ceiling material
(Figure 3). Set housing aside and cut opening, being careful not to cut or damage any
electrical or other hidden utilities. Install the rails on the housing and position the housing
in the previously cut hole so that it is flush with the finished ceiling. Secure the ends of
the rails to the joists (Figure 2).
Joist
Figure 3
Power Cable*
Seal gaps
Fan Housing
or
Keep duct
runs short
around Housing
Round
Duct*
Round
Elbows*
Wall Cap*
*Purchase separately
Figure 5
Seal duct joints
with tape
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE
STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE IN ACCORDANCE
WITH LOCAL CODES, ORDINANCES, OR NATIONAL ELECTRICAL CODE. IF YOU ARE
UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL WIRING, SECURE THE
SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of
the fan’s blower assembly. If you choose to wire the unit from the inside, you will need to
remove the blower assembly and internal wiring compartment. Both methods are equally
effective.
1a. External Wire Compartment: Remove the wire compartment cover screw and place
cover in a secure place (Figure 6).
A210952014 Rev. G 6-152 of 12
www.airkinglimited.com
Screw
Wire
Compartment
Cover
3. Intermittent Ventilation: For two speed fans wired for intermittent ventilation with the
recommended AKS4 switch (not included). Properly ground the switches. Run a wire from the
Blue wire in the fan to the Common terminal of one of the switches. Connect the Black wire
from the power source to the top terminal of the switch. This will turn the fan on and off. Run
a wire from the Black wire in the fan to the bottom terminal of the same switch. This is the fan
speed control and closing the switch will change from normal to high speed. On the second
switch run a Black (Hot) wire from the supply to the common terminal of the switch. On the
same switch run a wire from the Yellow wire in the fan to the top terminal of the switch. This
is the light control. Run a wire from the Purple wire in the fan to the bottom terminal of the
switch you just connected the yellow wire to. This is the night light control (Figure 10).
Figure 6
1b. Internal Wire Compartment: Remove the screw holding the blower assembly in place
and lift assembly out of housing (Figure 7). Remove the wire compartment cover screw
and place the cover in a secure place (Figure 8).
Plug
Screw
Venturi
Figure 7
NOTE: If the fan motor plug is connected to the fan housing receptacle, unplug so the
blower assembly can be completely removed.
Wire Compartment
Cover
Screw
Figure 8
2. Continuous Ventilation: For two speed fans wired for continuous ventilation with the
recommended AKS3 switch (not included). Properly ground the switch. Connect the Black
(Hot) wire from the supply to both the Blue wire of the fan and a black wire run to the
common terminal of the wall switch. Run 3 wires from the wall switch (not included) to the
fan. Connect the Yellow wire from the fan to the top terminal of the AKS3 switch. This is
the light control. Connect the Purple wire from the fan to the middle terminal of the AKS3
switch. This is the night light control. Connect the black wire from the fan to the bottom
terminal of the AKS3 switch. This is the fan control and closing the switch will change
from normal to high speed (Figure 9).
Supply from
house
Hot (Black)
Ground
Neutral (White)
(Green or
Bare)
Yellow
Purple
Black
Switch
Switch
Blue
Figure 10
NOTE: The fan’s receptacle wires might need to be pulled outside compartment for connection.
Only pull the three loose wires outside of compartment. Additional wires will be present.
4. Carefully tuck wires back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
Black
SECTION 6
Completing the Installation
1. Use a sealant appropriate for contact with the building materials present and for the
temperature requirements of the installation to prevent air leakage from unconditioned
spaces is recommended. If gaps between unit housing and ceiling are great, additional
material (backing rod, ceiling material) may be required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan
be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.
2. If the fan’s blower assembly was removed during the wiring process, reinstall the blower
by reversing the directions in Step 1b in Section 5Wiring.
3. Plug the fan’s 5 pin quick connect motor cord into the receptacle on the side of the
wiring compartment cover and the light’s 4 pin quick connect into the receptacle on
the top of the wiring compartment cover. These cords will only fit one way into the
receptacles (Figure 11).
Supply from
house
Hot (Black)
Ground
Neutral (White)
(Green or
Bare)
Blue
Black
Figure 11
Yellow
4. Install the included 26 watt fluorescent lamp into the lamp holder by lining up the pins on
Purple
Figure 9
A210952014 Rev. G 6-153 of 12
Black
Switch
www.airkinglimited.com
the lamp base to the socket of the lamp holder and turning the lamp body clockwise until
the lamp snaps into place and is firmly seated in the lamp holder. Install a 4 watt maximum
type C7 (candelabra base) night light (not included) into the side lamp holder (Figure 12).
Night Light
Socket
Pin
Lamp
Lamp Holder
Figure 12
5. Install the reflector onto the grill by placing the slots on the side of the reflector over the
lens clips near the center of the grill. While squeezing the middle of the reflector, slide it so
that the plastic notches rest under the lens clips and the reflector feels secure (Figure 13).
Slot
Clip
Figure 13
6. Install the grill (with reflector) by squeezing the two ends of the springs together and installing
them up into the slots on the fan’s housing. Push the grill up into position (Figure 14).
Figure 14
7. Restore power and test your installation.
SECTION 7
Use and Care
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE PANEL BEFORE
STARTING INSTALLATION.
1. Cleaning the Grill: Remove grill and use a mild detergent, such as dishwashing liquid,
and dry with a soft cloth. NEVER USE ANY ABRASIVE PADS OR SCOURING POWDERS.
Completely dry grill before reinstalling. Refer to instructions in Section 6Finishing the Installation, to reinstall grill.
2. Cleaning the Fan Assembly: Wipe all parts with a dry cloth or gently vacuum the fan.
NEVER IMMERSE ELECTRICAL PARTS IN WATER.
CAUTION: ALLOW BULBS TO COOL BEFORE REPLACING.
3. Changing the Lamp: Disconnect power to the unit. Remove grill by pulling downward
on grill and squeezing grill springs together to release from housing (Figure 13). Remove
Reflector from grill by sliding the reflector notches from beneath the lens clips on grill.
(Figure 12).
Fluorescent Bulb: Remove lamp by gently twisting the lamp base counterclockwise while
applying outward pressure. Installation is the reverse of removal. Replace with Air King
model 26SBL or a compatible GU24 26 watt self ballasted lamp.
Night Light: Unscrew night light bulb from socket and replace with a 4 watt maximum type
C7 (candelabra base) night light bulb.
A210952014 Rev. G 6-154 of 12
www.airkinglimited.com
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.