Air King AILT4 User Manual

IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
Models: AIDB4Y, AILT4
Dryer Booster Fan
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT
WARNING: DO NOT CONNECT POWER SUPPLY UNTIL FAN
IS COMPLETELY INSTALLED. MAKE SURE ELECTRICAL SERVICE TO THE FAN IS LOCKED IN OFF POSITION.
WARNING: MODEL AIDB4Y DRYER BOOSTER FAN IS NOT
EXPLOSION PROOF. DO NOT USE IF A POTENTIALLY EXPLOSIVE SITUATION MAY EXIST.
1. Read all instructions before installing or using fan.
2. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE TO COMPLY WITH
INSTRUCTIONS COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions
should always be followed to reduce the risk of fire,
CAUTION: FOR GENERAL VENTILATING USE ONLY. DO
NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE MATERIALS AND VAPORS.
6. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.
7. Ducted fans must always be vented to the outdoors.
8. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off power unit.
3. Before servicing or cleaning the unit, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
4. Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes and standards, including fire-related construction.
5. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those published by the National Fire Protection Association (NFPA) and the American Society for Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE), and the local code authorities.
SAVE THESE INSTRUCTIONS
AIDB4YEF New 3-07
www.airkinglimited.com
9. This unit has rotating parts and safety precautions should be exercised during installation, operation and maintenance.
10. Guards must be installed when fan is within reach of personnel or within seven (7) feet of working level or when deemed advisable for safety.
11. DO NOT insert or allow fingers or foreign objects to enter the motor.
12. DO NOT use with heated air in excess of 140°F (60°C).
1 of 8
INSTALLATION INSTRUCTIONS CAUTION:
PANEL BEFORE STARTING INSTALLATION.
MAKE SURE POWER IS SWITCHED OFF AT SERVICE
SECTION 1
Preparing for Installation
1. Fan and Switch Mounting: The recommended location of the booster fan is a minimum of 15 linear (not equivalent) feet of duct from the dryer outlet. If the fan is mounted closer than the recommended 15 feet, it may develop enough pressure to lift wet lint into the fan impeller resulting in excessive lint loading in the fan. The best location for the fan to be mounted is as close as possible to the termination of the duct work. (Exception: If a secondary lint filter is installed between the dryer and the booster fan, the booster fan may be mounted within the minimum distance otherwise recommended (Figure 1). A mounting bracket attached to a rafter or joist should be used to stabilize the fan. Although not recommended, a vertical rigid duct may support the fan if the duct is securely stabilized. (Consult local codes prior to supporting the fan in the duct alone.) Duct work should be attached to the inlet and outlet of the fan by means of vibration isolation clamps (not included) or ducting tape. The duct connection should be properly sealed to prevent leakage and loss of fan performance. Flex duct connections between the dryer duct connection and exhaust duct should be stretched as smooth as possible.
Recommended
Fan Location
Alternative Fan
Location
Secondary Lint
Trap
2. The electricity to the booster fan is connected in series through a normally open terminal on the switch. A pressure tap is connected to a fitting on the side of the switch. When the dryer begins operation, positive pressure in the duct causes the switch diaphragm to expand, closing the circuit to the booster fan. An integral delay­on-break timer in the switch will cycle the fan on for intervals of 10 minutes. This will continue until the dryer has stopped and the timer delay period has lapsed. Drying cycles, the booster fan, the delay timer and the pressure switch are not adversely affected by the starting/stopping intervals.
SECTION 3
Installation
1. Selecting Fan Location: Fan must be mounted a minimum of 15 feet from the dryer outlet. If the fan is mounted closer than the recommended 15 feet, it may develop enough pressure to lift wet lint into the fan impeller resulting in excessive lint loading in the fan. (Exception: If a secondary lint filter is installed between the dryer and the booster fan, the booster fan may be mounted within the minimum distance otherwise recommended (Figure 1). The best location for the fan to be mounted, in any application, is as close as possible to the termination of the duct work. In order to perform recommended maintenance, fan location should allow sufficient access for service. Refer to dimensional drawings shown above.
2. Mounting the Bracket: Using the wood screws provided, attach the mounting bracket to a support beam at the selected location. Bracket is provided with grommets in order to isolate any vibration and prevent the transmission of sound through the structure. Be careful not to overtighten. Fan mounting can be in any angle (Figure 2), however, vertical mounting is recommended to reduce condensation buildup in the fan. If a horizontal installation is necessary and condensation buildup may pose a problem, wrap insulation around the fan to minimize buildup.
Vertical Mounting
Horizontal Mounting
Bracket
Bracket
or
Stud
Joist
Figure 1
2. Calculating Duct Run: To calculate the length of your planned duct run, measure from the dryer to external venting point in roof or wall. For each bend or elbow add 5-7 feet to your total duct run calculations. This booster fan can be used on runs up to 108 feet.
Figure 2
3. Mounting the Fan: For proper operation, the switch diaphragm must be positioned vertically (Figure 3). Wiring box should be positioned for easy access. Attach fan to the mounting bracket with the self tapping screws provided. Care should be taken not to strip the plastic housing. Although screw pilot holes are not required, 3|32" (or smaller) pilot holes are recommended (Figure 4).
SECTION 2
Understanding the Pressure Sensor Switch
1. This unit is equipped with a pressure switch. This is a positive pressure sensing switch which recognizes dryer operation and activates the booster fan from an independent electrical circuit. This eliminates connections through the dryer circuit which may void the manufacturers’ warranty as well as manual systems which require the attention of the operator or costly current/temperature sensing systems.
AIDB4YEF New 3-07 2 of 8
www.airkinglimited.com
Correct Positions
Incorrect Positions
Figure 3
2. Bring incoming electrical service through the romex connector and the fan knockout. Be sure to place the connector nut over the wiring coming into the terminal box. There are three open ports on the terminal strip. Using a small regular screwdriver, tighten the Neutral (white) wire of the incoming supply under the open terminal labeled "N". Tighten the Line (black) wire of the incoming supply under the open terminal labeled "L". Tighten the Ground (green) wire of the incoming supply under the open terminal labeled
(Figure 6). For reference, a wiring diagram is included on the
" " inside of the terminal box lid.
Supply from house
Ground
Green
Fan
Stud
Figure 4
NOTE: Steps 2 and 3 may be reversed.
Bracket
Screws
SECTION 4
Electrical Connections
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE
PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: The fan motor, capacitor and pressure switch connections are
pre-wired from the factory.
1. Remove the screws securing the terminal box cover plate located on the side of the fan. All fan motor connections are prewired to an electrical terminal strip. A 3|8" romex type cable restraint connector will be needed to secure the wiring through the knockout provided on the side of the terminal box (Figure 5).
Black
Black
White
Capacitor
L
N
Black
White
Blue
Brown
Red
Figure 6
3. Secure the incoming supply with the romex connector and replace the fan terminal box cover.
4. Restore power to the unit and test the installation.
SECTION 5
Finishing the Installation
1. Included with the unit is an identifying label that must be placed above the dryer. This label serves as a reminder that there is a booster fan installed and that periodic cleaning must take place.
SECTION 6
Use and Care
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE
PANEL BEFORE SERVICING THE UNIT.
1.
Fan impeller may accumulate lint. Periodic inspection, based upon dryer usage, should be performed to ensure that the fan impeller is not obstructed or loaded with lint. Under normal conditions, fan should be inspected a minimum of every Six (6) Months.To inspect and clean the impeller:
a. Disconnect the incoming power supply at the source. b. Remove the duct from the fan inlet and remove any lint buildup
on the impeller.
c. Reconnect the duct to the fan. Turn power supply on.
NOTE: Excessive booster fan noise or vibration may be an indication of lint buildup on the impeller.
Screws
Figure 5
AIDB4YEF New 3-07 3 of 8
Terminal Box
www.airkinglimited.com
2. The fan’s bearings are sealed and provided with an internal lubricating material, no additional lubrication is necessary.
Loading...
+ 5 hidden pages