Airease L85UFC87V14, L85BR, L85UF, L885UFC67V14, L85UFC104V20 Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
L85UF, L85BF, L85BR
Variable Speed Oil-Fired Furnaces
Save these instructions for future reference
WARNING
Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage.
Refer to this manual. For assistance or additional information, consult a qualied installer or service agency.
WARNING
Do not store combustible materials, including gasoline
and other ammable vapors and liquids, near the furnace,
vent pipe, or warm air ducts. The homeowner should be cautioned that the furnace area must not be used as a broom closet or for any other storage purposes. Such uses may result in actions that could cause property damage, personal injury, or death.
CAUTION
Never burn garbage or paper in the heating system
and never leave rags, paper, or any ammable items
around the unit.
WARNING
This furnace is not approved for installation in a mobile home. Do not install this furnace in a mobile home. Installation in a mobile home could result in actions that could cause property damage, personal injury, or death.
TABLE OF CONTENTS
START-UP CHECKLIST ........................................2
INSTALLATION .....................................................3
Location ....................................................3
Clearances ...............................................3
Venting ......................................................4
Filters ........................................................7
Variable Speed Features ..........................8
START-UP ...........................................................10
MAINTENANCE AND SERVICE .........................13
WIRING DIAGRAM .............................................14
Manufactured By
Allied Air Enterprises LLC
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
*p507148-01*
(P) 507148-01
The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association Standard for the Installation of Oil Burning Equipment, NFPA No. 31; the National Electrical Code, ANSI/NFPA No. 70 (in the USA); the Installation Code for Oil Burning Equipment, CSA Standard CAN/CSA B139 (in Canada); the Canadian Electrical Code Part 1, CSA 22.1; the Recommendations of the National Environmental Systems Contractors Association; and any state or provincial laws or local ordinances. Local authorities having jurisdiction should be consulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual.
507148-01 Page 1 of 14Issue 1406
CAUTION
OIL FURNACE START-UP CHECKLIST
(Complete this page and keep for future reference)
Customer Name ________________________________________________________________________________
Address ______________________________________________________________________________________
City __________________________________________State ________________ Zip Code __________________
Furnace Model # ____________________________________________________ Serial # ___________________
Input Rate __________________________________________________________ Nozzle Used _______________
New Construction ___________________________________________________ Replacement ______________
Date of Installation _____________________________
Installaon Data
Furnace Location:
A. Basement – Open _________ Enclosed* _________ B. Utility room – Open ________ Enclosed* _________ C. Closet – Open ____________ Enclosed* _________ D. Crawl space – Open ________ Enclosed* _________ * Provisions must be made for adequate air for combustion.
See Combuson and Venlaon Air on page 6.
Chimney Data:
A. Inside __________ Outside _________ B. Brick or Masonry _________ C. Lined __________ Size: ___________ D. Type: Class A all-purpose ____________ Type L ________ E. Condition ________________________
Flue Pipe:
A. Distance to chimney _____________ Pitch __________ B. Diameter ______________________ C. Barometric damper installed __________
D. Drill 5/16” hole in ue pipe 12” upstream of barometric
damper __________ E. Obtain drafting reading; adjust barometric _____________
Oil Tank Data: A. Installed in basement ______________ B. Outside ____________ C. Buried/Depth: _________________ D. Size: ___________ gallons E. Age: ________________________ F. Date of last cleaning: ___________________
Oil Lines:
A. Size: 3/8” _________1/2” _______ Other ________ B. Single pipe _________ Two pipe _________ C. Distance from tank __________ Lift _________ D. Filter type _____________ Inspect ______Change _____ E. Pressure test ___________
F. Recheck all ttings for tightness ____________
Thermostat
A. Type: Heating _________ Cooling ________ B. Anticipator set ________ C. Wires: New ___________ Old ___________
Air Filter
A. Type: Permanent ______ Disposable ______ B. Installed _____________ C. Size: ________________
Start-Up Procedure
A. Close disconnect switch ___________ B. Set thermostat to call for heat ___________ C. Bleed air from lines and pump; run for 20 seconds after bubble disappears __________ D. Install vacuum gauge; check pump vacuum ___________ E. Install pressure gauge; adjust pressure to 145 or 150 psig ___________________________________________ Always verify proper pump pressure to corresponding tables with instructions supplied with unit.
F. After 10 minutes of operation, obtain ue temperature
reading: 1st _________ 2nd _________ 3rd ________ G. Obtain smoke reading: 1st _________ 2nd _________ 3rd ________ H. Measure CO2: 1st _________ 2nd ________ 3rd _______ I. Check draft overre __________ Breech _________ J. Air shutter setting _____________ Locked _________ K. Measure static pressure in duct system Static pressure on supply side ___________ Static pressure on return side ___________ Static pressure drop __________ L. Temperature rise after steady state conditions have been achieved: Supply side _______ Return side ______ M. Block off return air (limit control checkout); burner should shut down in 2 or 3 minutes ____________
Owner Record
Installed By: _______________________________________
Dealer ________________________________________
Address ________________________________________
________________________________________
________________________________________
Telephone # _______________________________________
License # _________________________________________
Manufactured By
Allied Air Enterprises Inc.
A Lennox International Inc. Company
215 Metropolitan Drive
West Columbia, SC 29170
These checks or tests are required for all oil units.
507148-01Page 2 of 14 Issue 1406
INSTALLATION
Read all instructions before starting work so installation will conform to Underwriters’ Laboratories or Canadian Standards Association requirements. The furnace must be
level when placed on its foundation (upow, counterow, and
basement models) or in its suspended position (horizontal models). Using a carpenter’s level, check the furnace in at least two directions. The weight must be distributed evenly before the duct work is attached.
These instructions must be placed on or near the furnace in a conspicuous place.
Inspection of Shipment
This furnace is shipped in one package, completely assembled and wired. The thermostat is shipped in a
separate carton when ordered.
Upon receipt of equipment, carefully inspect it for possible shipping damage. If damage is found, it should be noted on
the carrier’s freight bill. Damage claims should be led with the carrier immediately. Claims of shortages should be led
with the seller within 5 days.
Location
Locate the furnace as centrally as possible so that all warm pipes to the various rooms are nearly the same length. This allows each room to receive an equal and proper amount of heat. This may vary with each particular installation.
Position the furnace so the pipe connection to the chimney
will be of minimum distance and have a minimum of ttings.
In utility rooms or similar installations, the door or access opening should be large enough to permit replacement of the furnace, or another appliance such as a water heater, without disturbing any other equipment.
WARNING
In any installation where damage from oil may occur, a drain pan must be installed. The drain pan must be large enough size to completely prevent any potential oil damage. The drain pan piping must be sized to drain the oil pump capacity and the piping must be routed to drain the oil back to the oil tank.
For attic installations, a booster oil pump may be required to supply oil to the oil burner. Check state and local codes
for specic requirements.
Clearances
A minimum of 24” is recommended in front of the furnace for servicing the burner on all models.
See Table 1 for a complete listing of the minimum clearances
required for basement type and upow installations.
Minimum Clearances to Combustibles – Upow Installations
Basement Type Units Hi - Boy (Upow)
LBF & LBR LUF
67/87 104/118 67/87 104/118
Top of Plenum and Duct Work 2” 2” 2” 2”
Plenum Sides 3” 3” 3” 3”
Furnace Sides 6”* 6”** 0” 0”
Furnace Rear 24” 24” 0” 0”
From Front Door 4” 4” 4” 4”
Flue Pipe Clearance to Combustibles** 9” 9” 6” 6”
Type of Floor Comb. Comb. Comb. Comb.
Combustion Air Openings (2 req’d) 10” x 20” 11” x 22” 10” x 20” 11” x 22”
* A passage, suitable for a large person, shall be provided between the furnace and chimney for inspection or replacement of the ue connector
when necessary. A clearance of 24” shall be allowed at the rear and on one side of the furnace for service and cleaning of the blower.
** The minimum clearance shown to the ue pipe may be reduced by using special protection permitted by local building codes and National
Fire Protection Association Standards and CSA 139.
Table 1
507148-01 Page 3 of 14Issue 1406
Combustion and Ventilation Air
Adequate provisions for combustion air, ventilation of furnace, and dilution of the gases must be made.
If the furnace is installed in a conned space and combustion
air is taken from the heated space, the supply air and ventilating air must be through two permanent openings of
equal area. A conned space is “a space whose volume
is less than 50 cubic feet per 1000 BTU per hour of the combined input rating of all appliances installed in that space.” One opening must be within 12” of the ceiling and
the other within 12” of the oor. Each opening must have a
minimum free area of at least 1 square inch per 1000 BTU per hour of total input rating of all appliances within the space but not less than 100 square inches.
WARNING
Combustion air openings in the front of the furnace must be kept free of obstructions. Any obstruction will cause improper burner operation and may result in a
re hazard or injury.
WARNING
The barometric control shall be in the same atmospheric pressure zone as the combustion air inlet to the furnace. Deviation from this practice will cause improper burner
operation and may result in a re hazard or injury.
If the furnace is installed in a space within a building of tight construction, air must be supplied from outdoors. In this case, one opening shall be within 12” of the ceiling and the
other within 12” of the oor. If vertical combustion ducts are
run, each opening must have a free area of at least 1 square inch per 4000 BTU per hour. If horizontal combustion ducts are run, 1 square inch per 2000 BTU per hour of the total input of all appliances is required.
As supplied, the furnace is designed to use air inside the dwelling for combustion. If additional combustion air is required, installing fresh air kit ABOOT571 allows air from outside the dwelling to be brought in to the oil burner. This kit brings air into the burner through air inlet ductwork run through the furnace cabinet side panel and terminated outside the dwelling (see Figure 5). The kit includes a vacuum relief valve to guard against combustion problems associated with directly connecting oil burners to the outside.
Fresh Air Kit ABOOT571 Installation
Intake
Air
Hood
Field Supplied
4Piping
Mounts Through Furnace Cabinet
IMPORTANT: No more than 10’ of vertical piping allowed without weight support.
To Vent System
Flue
Furnace Cabinet
NX Beckett Burner
Furnace Boot™
WARNING
The barometric control must be removed from the vent pipe when using a combustion air adapter. Deviation from this practice will cause improper burner operation
and may allow ue products into the living space which
may result in personal injury or death..
Circulating Air Supply
A return air duct system is recommended. Where there is no complete return air duct system, a return connection should
be run full size to a location outside the conned space and completely sealed so that no air from the conned space
can be circulated through the heating duct system.
Outdoor Make Up Air
A minimum mixed return air temperature of 60 – 65°F must be maintained for outdoor make up air to prevent condensation and corrosion.
Venting
Chimney
Before installing the furnace, a thorough inspection of the chimney should be made to determine whether repairs are necessary and that the chimney is of the proper size and constructed in accordance with the requirements of the National Board of Fire Underwriters or Canadian Standards Association. The smallest dimension of the chimney should
be at least equal to the diameter of the ue pipe of the
furnace. Be sure the chimney will produce a steady draft
sufcient to remove all the products of combustion from the furnace. A fabricated vent system the same size as the ue
outlet of the furnace may also be used. If a manufactured
vent is used, it must be listed for use with oil-red equipment.
WARNING
Figure 5
This furnace is certied for use with Type “L” vent, Type “A”, and “factory-built” chimneys. “B” vent must not be
used with oil furnaces.
507148-01Page 4 of 14 Issue 1406
Vertical Venting
Thimble
Flue Pipe
CombustibleWall
Barometric Control (in either location)*
Factory-Built Chimney
Drain for Condensate
Factory-Built Chimney
Barometric Control (in either location)*
Drain for Condensate
1. Local building codes may have more stringent installation requirements and should be consulted before installation of the unit.
2. The ue pipe should be as short as possible to do the job.
3. The ue pipe should not be smaller than the outlet diameter of the ue outlet of the furnace.
4. Single wall ue pipe should not run outside or through
any unconditioned space.
5. The chimney should terminate 2’ above the highest peak
of a peaked roof, and 3’ higher than a at roof.
Factory-Built Chimney
6. The ue pipe must not pass through a oor or ceiling. Clearances to single wall ue pipe should be no less than specied in the Clearances section beginning on page 3.
7. The ue pipe may pass through a wall where provisions
have been made for a thimble as specified in the Standards of the National Board of Fire Underwriters (see Figure 6).
8. The ue pipe should slope upward toward the chimney
on a horizontal run of at least 1/4” per foot and should be supported by something other than the furnace (see Figure 7 on this page and Figure 8 on page 8).
Wall Thimble
Figure 6
Front Flue
Rear Flue
* Barometric control may be installed in either the vertical or
horizontal section of the ue pipe within 18” of the ue outlet of
the furnace.
Figure 7
12. The ue pipe shall not be connected to a chimney
ue serving a solid fuel appliance or any mechanical
draft system.
13. All unused chimney openings should be closed.
9. Extend the ue pipe into the chimney so that it is ush with the inside of the ue liner. Seal the joint between
the pipe and the liner.
10. The furnace shall be connected to a factory-built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
11. When two or more appliances vent into a common ue,
the area of the common ue should not be less than the area of the largest ue or vent connection plus 50% of the areas of the additional vents or ue connections. The chimney must be able to sufciently vent all appliances
operating at the same time.
507148-01 Page 5 of 14Issue 1406
14. All vent pipe run through unconditioned areas or outside shall be constructed of factory-built chimney sections (see Figure 7).
15. Where condensation of ue gases is apparent, the vent
shall be constructed to prevent the condensation from
entering the ue transition box opening. Provisions shall
be made to drain off the condensate (see Figure 7).
16. Vent connectors serving this appliance shall not be connected into any portion of a mechanical draft system operating under positive pressure.
17. Keep the area around the vent terminal free of snow, ice, and debris.
Masonry Chimney
Cleanout
Liner
Cleanout
Cleanout
Liner
Cleanout
Barometric Control (in either location)*
Masonry Chimney
Masonry Chimney
Barometric Control (in either location)*
Barometric
Control*
Control for Horizontal
Venting
Barometric
Control*
Control for Horizontal
Venting
Horizontal Venting
* Barometric control may be installed in either the vertical or
horizontal section of the ue pipe within 18” of the ue outlet of
the furnace.
Horizontal Venting
The design of this furnace has been approved for horizontal venting with the following mechanical vent systems:
Tjernlund (sideshot)
Refer to the manufacturer’s installation instructions for proper installation procedures and service parts information.
Vent systems are available through the local distributor.
Barometric draft control must be used in the horizontal venting (sidewall) system. It must be located within 18” of
the furnace ue outlet (see Figure 9).
Manufacturer
Field Control
Front Flue
Rear Flue
Figure 8
Model
SS1, SSC, SS2
SWGII-5-SS
with CK61 Control Kit
Front Flue
Rear Flue
* Barometric control must be installed in the horizontal venting
system and located within 18” of the ue outlet of the furnace.
Figure 9
Do not common vent with any other appliance when using the sidewall system.
Maximum permissible vent length is 100 equivalent feet, and minimum permissible length is 15 equivalent feet. Calculate the equivalent vent pipe footage from the furnace to the mechanical vent system by adding the straight vent pipe length and equivalent elbow lengths together. Each 90° elbow is equivalent to 10’ of straight pipe; each 45° elbow is equal to 5’ of straight pipe.
Removal of Unit from Common Venting System
When an existing furnace is removed from a common venting system serving other appliances, the venting system is likely to be too large to properly vent the remaining attached appliances. The following test should be conducted with each appliance while the other appliances connected to the common venting system are not in operation.
1. Seal any unused openings in the common venting system.
507148-01Page 6 of 14 Issue 1406
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion, or other deciencies
which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located and other spaces in the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer
exhaust fan. Close replace dampers.
4. Following the lighting instructions, place the unit being inspected in operation. Adjust the thermostat so the appliance will operate continuously.
5. Test for spillage at the draft control relief opening after
5 minutes of main burner operation. Use the ame of
a match or candle.
Filters
Optional lter rack kit for Upow units:
R37398C001 - Sized for 24 X 16 X 1/2 lter
Basement
Permanent lters are supplied with these units.To clean the lters, shake to remove any excess dirt and/or use a
vacuum cleaner. Wash with soapy detergent water and dry.
The lters should be cleaned at least once a month, or more
frequently in unusually dusty environments.
Never leave the access panels to the blower compartment off or partially open.
Oil Supply and Oil Filter Connection
Continuous lengths of heavy wall copper tubing or steel pipe
are recommended and should be installed under the oor
or near walls to protect from damage. Do not run lines on
oor joists or other reverberating surfaces. Always use are ttings located in accessible places.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other fuel burning appliance to their previous condition of use.
7. If improper venting is observed during any of the above tests, the common venting system must be corrected.
See National Fuel Gas Code, ANSI Z223.1 (latest edition) or CAN/CGA B149.1 & .2 Installation Codes
to correct improper operation of common venting
system.
Supply and Return Air Plenum
Secure return air plenum to unit using sheet metal screws.
Follow these procedures when installing supply air plenum:
1. Use sealing strips of berglass.
2. Attach the plenum to the furnace or evaporator cabinet with sheet metal screws.
3. Both supply and return air plenums shall be square and at least 18” long. They should be the same dimension as the furnace opening.
4. Install supply and return air ducts as desired.
Install a generous capacity oil lter inside building between the fuel shutoff valve and burner. Locate lter and valve
close to burner for easy servicing. An oil lter is required
for all models. A 10-micron lter is recommended.
Combustion Chamber
The combustion chamber is installed in the furnace at the factory. Read the instruction plate on the front of the unit concerning proper care of the chamber.
This combustion chamber is made of preformed ceramic ber
material. Use extreme care when installing the oil burner so that the chamber is not damaged around the burner tube.
Electrical Wiring
All wiring must conform to the National Electrical Code, the Canadian Electrical Code, and any local codes. Connect the 115-volt, single phase service to the unit at the junction box. Use a separate fused branch electrical circuit containing a properly sized fuse or circuit breaker. Run this circuit directly from the main switch box to an electrical disconnect that is readily accessible and located near the furnace. Follow carefully the wiring diagram adhered to the inside of the blower compartment door.
The electrical supply to the mechanical vent system must be supplied from the appliance. All wiring must be appropriate Class I wiring. Wiring must be installed in rigid metal conduit, intermediate metal, or be otherwise suitably protected from physical damage. Refer to the wiring diagrams supplied with the venter kit for proper electrical connections.
507148-01 Page 7 of 14Issue 1406
Thermostat
Locate the thermostat on an inside wall in a room usually occupied during the day, such as a living room or dining
room, at a height of 4-1/2’ from the oor. Avoid direct sunlight
or supply air from a register. Make sure the location is not adjacent to appliances such as ovens or lights. Wire the thermostat with minimum of #18 AWG thermostat wire.
Continuous Blower Operation
The comfort level of the living space can be enhanced when using this feature by allowing continuous circulation of air between calls for cooling or heating. The circulation
of air occurs at half the full cooling airow rate. This can
produce more even temperatures throughout the home and/ or continuous operation of IAQ accessories.
To enable the continuous blower operation, place the fan switch on the thermostat into the ON position. A call for fan from the thermostat closes R to G on the blower interface board. The control waits for a 1-second thermostat debounce delay before responding to the call for fan by
ramping the circulating blower up to 50% of the cooling speed. When the call for continuous fan is satised, the
control immediately ramps down the circulating blower.
Humidier
Terminals are provided on the control board which provides a
120-volt output to operate a humidier. The “HUM” terminal is
energized whenever the thermostat calls for heat. Refer to
furnace wiring diagram for specic connection information.
Electronic Air Cleaner
Terminals are provided on the control board for connection
of a 120-volt electronic air cleaner. The “EAC” terminal is
energized whenever the thermostat calls for heat, cooling, or continuous blower. Refer to the furnace wiring diagram
for specic connection information.
Variable Speed Features
This furnace is equipped with a variable speed circulation
air blower motor that will deliver a constant airow within a
wide range of external static pressures. Other features of this variable speed motor include:
For situations where humidity control is a problem, a
dehumidication feature has been built into the variable
speed motor. At the start of each cooling cycle, the variable
speed motor will run at 82% of the rated airow for 7.5
minutes. After 7.5 minutes has elapsed, the motor will
increase to 100% of the rated airow.
To achieve additional dehumidification, remove the dehumidify jumper located at the bottom right of the blower interface board (see Figure 11) and connect a humidity control that opens on humidity rise to the HUM and R terminals. The HUM terminal on the blower interface board must be connected to the normally closed contact of the humidity control so that the board senses an open circuit on high humidity. In this setup, the variable speed
motor will operate at 82% of the normal cooling airow rate whenever there is a call for dehumidication. When the
relative humidity has been brought down to an acceptable
level, the cooling blower speed will return to 100% of design.
Circulating Airow Adjustments
Cooling Mode
The units are factory set for the nominal airow for each model. Adjustments can be made to the cooling airow by
changing the position (A, B, C, or D) of the jumper plug on the tap marked COOL (on the blower interface board) based on the information provided in Figure 10. To determine what CFM the motor is delivering at any time, count the number of times
the LED labeled CFM on the blower interface board ashes. Each ash signies 100 CFM; count the ashes and multiply
by 100 to determine the actual CFM delivered (for example:
10 ashes x 100 = 1000 CFM).
Moving the jumper plug on the tap marked ADJUST from the NORM position to the (+) or (–) position will increase or
decrease the cooling airow (Y or O call) by 15%. Changing
the position of the ADJUST jumper plug does not affect
heating airow except if a heat pump is used in conjuction
with the oil furnace. If a heat pump is used, moving the ADJUST jumper plug to the (+) or (–) position will increase
or decrease the airow by 15% when operating in all heat pump modes, but will not affect heating airow when the oil
furnace is used for heating.
Blower Ramp Up
The variable speed motor will slowly ramp up to normal operating speed. This minimizes sound and increases comfort by eliminating the initial blasts of air encountered with standard blower motors.
Blower Ramp Down
At the end of a cooling or heating cycle, the variable speed motor will slowly ramp down. If continuous blower operation has been selected, the variable speed motor will slowly ramp
down to 50% of the selected cooling CFM.
Passive and Active Dehumidication
For single stage cooling, jumper Y1 and Y2 to obtain rated cooling CFM. In two stage cooling conguration, Y1 will produce 70% of rated cooling CFM and Y2 will produce 100%.
Heating Mode
The unit as shipped is factory set to run at the middle of the heating rise range as shown on the unit rating plate. The jumper plug on the tap marked HEAT should remain in the position (A, B, C, or D) listed in the HEAT Setting column found in Figure 10.
507148-01Page 8 of 14 Issue 1406
Adjusting Airow
DEHUMIDIFY
CUT TO ENABLE
COOLHEATADJUST
NORM A
B C D
A
B C D
(+) (–)
TEST
D1
ADJUST*, HEAT, and COOL Taps
(on Blower Interface Board)
* Placing ADJUST jumper plug in the TEST position energizes the motor to a default factory setting. This
can be used to determine if the motor is operating properly. Test pin function is enabled during any mode of thermostat call. If no thermostat call is present, test function is disabled. The ADJUST jumper plug must be returned to original position after testing procedure is completed. Failure to do so will result
in improper air ow.
Heating CFM @ .50 Static Cooling CFM @ .50 Static
Model
Motor
HP
Heat
Set-
ting
Heat-
ing
CFM
Heat
Set-
ting
A
Heat
Set-
ting
B
Heat
Set­ting
C
Heat
Set-
ting
D
Cool
Setting
A
Cool
Set-
ting
B
Cool
Set-
ting
C
Cool
Set-
ting
D
L885UFC67V14 1/2 D 1200 1500 1400 1300 1200 1400 1200 1000 800
L85UFC87V14 1/2 A 1500 1500 1400 1300 1200 1400 1200 1000 800
L85UFC104V20 3/4 C 1550 1850 1730 1550 1400 2000 1800 1600 1200
L85UFC118V20 3/4 A 1850 1850 1730 1550 1400 2000 1800 1600 1200
L85BFC67V14 1/2 D 1200 1550 1450 1400 1200 1400 1200 1000 800
L85BFC87V14 1/2 B 1450 1550 1450 1400 1200 1400 1200 1000 800
L85BFC104V20 1 C 1550 2000 1730 1550 1450 2000 1800 1600 1200
LBF85C118V20 1 B 1730 2000 1730 1550 1450 2000 1800 1600 1200
L85BRC67V14 1/2 D 1200 1550 1450 1400 1200 1400 1200 1000 800
L85BRC87V14 1/2 A 1550 1550 1450 1400 1200 1400 1200 1000 800
L85BRC104V20 1 D 1450 2000 1730 1550 1450 2000 1800 1600 1200
L85BRC118V20 1 B 1730 2000 1730 1550 1450 2000 1800 1600 1200
Figure 10
507148-01 Page 9 of 14Issue 1406
START-UP
Burner Adjustment
Oil Burner
Burner Specication: Factory Settings
1. Burner type: NX
2. Air tube combination: NX70LHHS
WARNING
Do not attempt to start the burner when excess oil has accumulated in the chamber, when the furnace is full of vapor, or when the combustion chamber is very hot. Such actions could result in property damage, personal injury, or death.
CAUTION
Do not start burner unless blower access door is secured in place.
Burner Start-Up
1. Set the operating control to call for heat.
2. Open all shutoff valves in the oil supply line to burner.
3. While the ignition is on, press and release the reset button (hold 1/2 second or less). If the control has not locked out since its most recent complete heat cycle, the lockout time will be extended to 4 minutes, and the ignition will remain on for the entire heat cycle.
4. Bleed the pump until all froth and bubbles are purged. The bleed port is located on the bottom of the fuel pump. To bleed, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all the air is purged. NOTE:
Bleeding might not be necessary with a two-pipe system.
5. If prime is not established within the extended lockout time, the control will lock out. Press the reset button to reset control (see Step 3). NOTE: The reset button can be
held for 15 seconds for the Beckett 7505B primary control, at any time to reset the control’s lockout counter to zero and send the control to standby.
6. Repeat Steps 3 and 4, if necessary, until pump is fully primed and oil is free of bubbles. Then terminate the call for heat, and the control will resume normal operation.
All adjustment to this furnace and its components must
be done by a qualied service technician.
Refer to Table 2 for nozzle and pump pressure information. The proper way to adjust an oil burner is with a CO2 analyzer
Burner Information
Fur-
nace
Model
67* 6-SLOT .50 GPH/60 DELAVAN A 150 PSI
87* 6-SLOT .65 GPH/60 DELAVAN A 150 PSI
104 6-SLOT .75 GPH/60 DELAVAN A 145 PSI
118 6-SLOT .85 GPH/60 DELAVAN A 145 PSI
Burner
Head
Nozzle/Angle
Spray
Pattern
Pump
Pres-
sure
*Denotes low re bafe installed. See oil burner specications included with instructions
Table 2
and a smoke gun. A properly adjusted burner will result in
a quiet, clean re which will prevent sooting and minimize
cleaning. Using the following procedure will provide a margin of reserve air to accommodate variable conditions.
To adjust the burner:
1. Punch a 5/16” diameter service hole in the ue outlet. This sampling hole should be at least two ue diameters
above the breech, or elbow at the breech, but ahead of the barometric damper.
2. Operate burner for approximately 5 to 10 minutes.
3. Take a draft reading at the service hole in the ue outlet.
Adjust barometric draft control in the stack to achieve
an overre draft of –.01” to –.02” and a breach of –.02”
to –.04”.
4. Pull and record a smoke reading at the service hole using an industry standard smoke tester.
5. If the burner is producing more than #1 smoke, adjust the intake air using the zero setting locking nut and adjustment screw. Loosen the locking nut approximately one turn. Turn the adjustment screw clockwise to increase air or counterclockwise to decrease air.
6. Once the desired smoke level is achieved, use a suitable test instrument for CO2 to take and record a CO2 reading at the service hole in the ue outlet.
7. Adjust the air shutter (and air band, if necessary) to reduce CO2 to the desired percentage.
8. Recheck smoke level.
507148-01Page 10 of 14 Issue 1406
Set the NX
tip position by aligning the electrode top with the mark shown in Figure 12.
Figure 11
9. Recheck draft and CO2 reading at the service hole in
the ue outlet.
10. Using a suitable thermometer, obtain and record the ue gas temperature at the service hole in the ue outlet.
11. Use the CO2 reading and the ue gas temperature
reading to determine unit efciency.
Set the electrode tip gap spacing (5/32”) by adjusting the tips to meet the two out side marks shown in Figure
13. Make sure the tips are centered about the nozzle centerline.
Figure 12
To check nozzle alignment:
1. Insert the small end of the “T” gauge into the end of the
cone and measure the nozzle and electrode alignment against the center lines marked on the gauge.
2. If nozzle is not centered, but found to be too far left or right, a new nozzle will need to be ordered. Do not attempt to
adjust by bending the 90° elbow in oil line.
12. When the proper combustion and smoke readings have been achieved, tighten the air shutter screw(s) and air band screws that were loosened in Step 5.
Nozzle and Electrode Alignment
Proper nozzle and electrode depth and alignment are essential for proper burner operation.
To check and adjust the nozzle depth:
1. Insert the small end of the “T” gauge into the end of the cone and measure from the at of the end cone to the
tip of the nozzle. The proper measurement should be
1.13”. When the depth is correct, the tip of the nozzle
should just touch the base of the “T” gauge.
2. Nozzle adjustments are made by sliding the entire nozzle assembly forward or backward within the blast tube.
OPERATION
Sequence of Operation
Heating (see Figure 13 on page 12)
The thermostat calls for heat, activating the burner motor. After a 15-second pre-purge period, power is sent to the burner and ignition is established. When the burner pump reaches full speed, the solenoid valve is energized. After the thermostat
is satised, the thermostat circuit opens. The solenoid valve
is de-energized before the pump rotation stops. Power to the burner is interrupted, shutting down the burner.
Cooling
Unit is set up at the factory for single stage cooling. For two
stage cooling operation, the jumper wire running from Y1 to Y2 on the blower interface board must be clipped and
removed. See Figure 17 on page 14 for two stage cooling wiring.
If the active dehumidification feature is enabled, the
circulating blower runs at 82% of the selected cooling speed
507148-01 Page 11 of 14Issue 1406
Heating
W
w
100%
82%
3.5 min
CALL OFF
W - Heat Demand Present
- Heat Demand Satisfied
w
13%
50%
1
min
1
min
7.5 minutes
Y
y
82%
100%
82%
1
min
CALL OFF
Y - Cool Demand Present
- Cool Demand Satisfied
y
G
g
50%
CALL OFF
G - Fan Switch ON
- Fan Switch OFF
g
Y1
y1
57%
100%
CALL OFF
7.5
minutes
70%
Y1 - 1 Stage Cool Demand Present
st
- Demand Satisfied1 Stage Cool
st
y1
Y2 - 2 Stage Cool Demand Present
nd
- 2 Demand Satisfied
nd
Stage Cool
y2
1
min
70%
Y1
y2
/
Y1
/
Y2
y1
57%
1
min
57%
Figure 13
IMPORTANT
The system must not be in either the passive or active
dehumidication mode when charging a cooling system.
as long as there is a call for dehumidication.
Single Stage Cooling (see Figure 14)
A call for cooling from the thermostat closes the R to Y
circuit on the blower interface board. The control waits for a 1-second delay before energizing the circulating
blower to 82% of the selected cooling CFM (passive dehumidication mode). After 7.5 minutes, the circulating blower automatically ramps up to 100% of the selected cooling airow. When the call for cooling is satised, the
Single Stage Cooling
blower motor runs at 70% of the selected cooling air ow
until 1st stage cooling demand is satised. A call for 2nd stage cooling from the thermostat closes the
R to Y2 circuit on the blower interface board. The blower motor ramps up to 100% of the selected cooling air ow.
Two Stage Cooling
Figure 15
When the demand for cooling is met, the blower ramps
down to Y1 until satised, then ramps down to 57% for 1
minute, then turns off.
Heat Pump
For heat pump operation, clip the jumper wire between R and O. In heat pump mode, a call for heat pump operation follows the same sequence as a call for cooling with the exception that there is a 30-second blower ramp up to blower CFM.
Continuous Fan (see Figure 16)
When the thermostat is set for continuous fan operation and there is no demand for heating or cooling, a call for fan closes
the R to G circuit and the circulating blower motor runs at 50%
of the selected cooling CFM until switched off.
Figure 14
circulating blower ramps back down to 82% of the selected cooling airow for 1 minute, then shuts off.
Two Stage Cooling (see Figure 15)
A call for 1st stage cooling from the thermostat closes the
R to Y1 circuit on the blower interface board. The control
waits for a 1-second delay before energizing the circulating
blower. The blower motor runs at 57% of the selected air ow for the rst 7.5 minutes of the 1st stage cooling demand
(passive dehumidication mode). After 7.5 minutes, the
Continuous Fan
Figure 16
507148-01Page 12 of 14 Issue 1406
MAINTENANCE AND SERVICE
Oil Burner
It is recommended that the nozzle and oil lter be checked
before each heating season. Also recheck the conditions shown on the OIL FURNACE START-UP CHECKLIST found on page 2.
Close the oil line shutoff valve if the burner is shut down
for an extended period of time.
Heat exchanger cleanout kit #ABRSH380-3 is available for purchase.
Emergency Replacement Motor Operation
If the variable speed motor in this furnace needs to be
replaced in an emergency situation (such as “no heat”) and
an exact replacement motor is not immediately available, a standard PSC motor of equivalent frame size, voltage, rotation, and horsepower can be temporarily installed until the correct replacement motor can be obtained.
Flue Pipe
Have the ue pipe inspected annually by a qualied service technician. If any soot or ash has formed inside the ue pipe, remove and clean. If the ue pipe has any holes or is rusted out, replace with a new ue pipe of the same size. Inspect the ue draft control device and replace if defective.
Blower
Blower motor is pre-lubricated and sealed for extended operation. No further lubrication is required. The blower assembly may be removed from the cabinet for cleaning and servicing of the blower. Disconnect power to the unit before servicing.
Heat Exchanger
To clean the heat exchanger:
1. Remove the vent pipe from the furnace.
2. Remove the locking screws and the caps from the two
cleanout tubes; remove the ue access elbow.
3. Using a long spiral wire brush, sweep down the outer drum of the heat exchanger. Using a shop vacuum hose attachment, vacuum out all loose debris.
4. Remove the locking screw and cap from the inspection tube and with the spiral wire brush reach upward toward the rear of the heat exchanger to clean out the crossover tube; replace the locking screw and cap on the inspection tube.
5. Do not attempt to clean the combustion chamber, as it can be easily damaged.
6. Replace the three previously removed cleanout caps
and ue access elbow, making sure to re-install the
locking screws.
Connect the desired speed taps to the HEAT and COOL terminals and the neutral tap to the neutral terminal on the control board (refer to the furnace wiring diagram).
Verify that the unit is operating at the desired speed and within the rise range as shown on the unit rating plate. The
correct replacement motor must be installed as soon as possible to ensure continued satisfactory operation of the furnace.
Emergency Fuel Pump Replacement
If replacement of the A2EA6520 fuel pump becomes necessary, replace it with another Beckett CleanCut fuel pump. In an emergency situation where the correct replacement parts are not available, an A2VA7116 fuel pump could be used. This option can produce a smoky start-up and shutdown that could result in fouling of a heat exchanger. This is only a short-term option and should
be used only until the correct parts can be obtained and installed.
Complete National Fuel Gas Codes are available from:
1. American Gas Association 1515 Wilson Boulevard Arlington, VA 22209
2. National Fire Protection Association, Inc. 1 Battery March Park Quincy, MA 02269
3. American National Standards Institute, Inc. Publications Sales Department 11 West 42nd Street
New York, NY 10036
7. Brush out and vacuum the vent outlet area of the outer drum and reattach the vent pipe.
8. Clean up around burner, blower deck, and vestibule area.
507148-01 Page 13 of 14Issue 1406
Wiring Diagram
P/N 48252-001
Figure 17
507148-01Page 14 of 14 Issue 1406
Loading...