Aico EI428 User Manual

Model: Ei428
RadioLINK
RELAY BASE
Instruction Manual
Contains vital information on the product’s operation and installation. Read and retain carefully. If you are just installing this product the manual MUST be given to the householder.
1. Introduction
The Ei428 RadioLINK Relay Module is a device that switches a relay upon receipt of an alarm signal from a suitable Ei smoke/ heat alarm. The electrically isolated contacts can be used for many applications such as signalling, turning on lights, etc. The Ei428 is designed to operate with Ei RadioLINK devices.
The Ei428 RadioLINK Relay Module is powered by the 230VAC mains and has rechargeable back-up cells. As supplied the relay operates continuously (i.e. it switches when one of the smoke / heat alarms detects fire and switches back when the smoke clears).
2. Installation
WARNING: Mains powered Ei428 RadioLINK Relay modules
should be installed by a qualified electrician in accordance with the Regulations for Electrical Installations published by the Institution of Electrical Engineers (UK) (i.e. BS7671) Failure to install the unit correctly may expose the user to shock or fire hazards. This unit is not waterproof and must not be exposed to dripping or splashing.
1. Choose a suitable mounting position near the mains supply and the device to be connected to the relay. Keep it away from metal surfaces or large metal objects (e.g. water cylinder, fuse boards) which can reduce the RF signal range.
2. Disconnect the AC mains supply from the circuit that is going to be used.
3. Where the incoming wiring is on the surface of the wall/ ceiling, the appropriately sized trunking / conduit must be chosen to mate with the unit. Use a sharp knife to remove the material from the knockout, making sure that there is no gap when mated with trunking/conduit. There is one suitable surface cabling knockout (the other two surface entries are not recommended as the wiring will reduce the antenna signal). There is one rear entry knockout. See figure 1b.
4. Screw the Ei428 module to the wall after first removing the required knockout and bringing the house wires through it (see figure 1b).
1
MODEL: Ei428
WARNING: DISCONNECT MAINS BEFORE REMOVAL
RadioLINK RELAY
for Smoke Alarms
HOUSE CODE SWITCH
INDICATOR LIGHT
GREEN - MAINS RED - LOW BATTERY RED - HOUSE CODING
COVER ATTACHMENT
SCREWS
Figure 1a
5. Connect the house wires (L-Live to wires coloured brown, red or marked L, N-Neutral to wires coloured blue, black or marked N) to the terminal block as shown in figure 1b.
NB: The unit must not be earthed so do not connect a green / yellow or copper earth wire to any terminal.
6. Connect the wires to the required relay contacts for controlling the auxiliary device. (The contacts are isolated and are rated at 250VAC, 5 amps resistive).
P - PULSE RELAY CHANGES FOR 5 SECONDS
REAR ENTRY
KNOCKOUT
INDICATOR
LIGHT
ANTENNA
(KEEP CABLES
AWAY)
CONNECT RELAY WIRES TO THE TERMINAL BLOCK NO - NORMALLY OPEN NC - NORMALLY CLOSED C - COMMON
(DOUBLE INSULATE ALL WIRES)
Figure 1b
NO
MOUNTING
NC
C
SCREW
HOLES
If momentary relay operation is required, carefully and gently slide the yellow switch to the “P” position with a small screwdriver (see figure 1b). This is commonly used with warden call systems where only momentary short circuit signalling
1 2
1 2
ON
SURFACE CONDUIT CABLE ENTRY
C - CONTINUOUS RELAY
ON
OFF
N IC L L IC N
RECHARGEABLE
SLIDE SWITCH
CONNECT MAINS TO TERMINAL BLOCK L - LIVE N - NEUTRAL
CELLS
ON/OFF
HOUSE CODE
SWITCH
is required. This must be done before the mains power is connected or the rechargeable cells are activated.
7. Connect the rechargeable cells by carefully and gently sliding the switch to the “ON” position (see figure 1b). This switch must be in the ‘on’ position to ensure correct operation.
2
8. Fit and screw the cover to the module pillars using the two screws supplied.
9. Connect the mains power to the Ei428 module. Check the green light is on. If the green light changes to red every 10 seconds then switch off the mains power, remove the cover and check that the battery slide switch is in the “ON” position (see figure 1b). Replace the cover and turn the mains power back on. If there is still a problem the rechargeable cells may be depleted, leave the unit on mains power for 2 hours to charge and test again.
10. Press and hold the House Code switch through the hole in the cover using a small screwdriver, see figure 1a, until the green light changes to red. Release the switch and the light will flash red quickly, a few times. The red light will then flash every 5 seconds. Similarly, put all the other RadioLINK units in the property into House Code Mode (see relevant user instructions) within 30 minutes.
11. Check that all the RadioLINK Relay communicates with each other by counting the number of times the RF light flashes on each unit in turn. For example, 3 units in the system should have 3 flashes every 5 seconds, 4 units should have 4 flashes and so on (if there is a problem see section 3).
12. All the units will automatically exit the house code mode after 30 minutes.
13. Check the RadioLINK communication by pressing the test/hush button for up to 60 seconds on each alarm. Ensure that the device connected to the relay contacts operates. After 60 seconds release the test button – check the device switches off. (If the continuous/pulse slide switch is in the pulse position, check the relay just switches on for 5 seconds and then switches off).
3. Troubleshooting RadioLINK
If, when checking the radio link interconnection, some of the Ei428 RadioLINK Relays do not respond to the button test, then:
(i) Ensure you have held the smoke/heat alarm test button down until the RF light comes on (this could take up to 40 seconds).
(ii) Re-locate/rotate the units. There are a number of reasons why the radio link signals may not reach all the RadioLink Relays in your system (see section on “Limitations of Radio Frequency Signals”). Try rotating the unit or re-locating the units (e.g. move them away from metal surfaces or wiring) as this can significantly improve signal reception.
Rotating and/or relocating the units may move them out of the range of existing units even though they may have already been house coded correctly in the system. It is important therefore to check that all detectors/relays are communicating in their final installed positions. If units are rotated and/ or resited, we recommend that all units are returned to the factory settings (press and hold the house code switch on for about 6 seconds until the relevant light comes on and then flashes slowly). Then house code all units again in their final
3
Loading...
+ 5 hidden pages