Aico Ei261D, Ei261 User Instruction

The CO Alarm will automatically reset once the CO has cleared. Pressing the test/hush button resets the CO Alarm immediately. If CO is still present the red light and horn will turn on again after about 4 minutes.
The CO Alarm is no substitute for keeping chimneys and flues clear and in good condition, and all of your appliances serviced regularly according to the manufacturer s instructions.
Do not fit alarm until all building work is completed to avoid contamination.
2. CARBON MONOXIDE - THE SILENT KILLER
2.1 What is Carbon Monoxide ?
Congratulations on becoming the owner of an Ei Carbon Monoxide Alarm. This will help protect you and your household from the dangerous effects of Carbon Monoxide ­the silent killer. (CO is the chemical symbol).
Many are killed each year, and many more suffer ill health from Carbon Monoxide (CO) poisoning. CO is an invisible, odourless, tasteless and extremely toxic gas. It is produced
MAINS POWERED
CARBON MONOXIDE ALARMS
WITH RECHARGEABLE LITHIUM CELL BACK-UP
INSTRUCTION LEAFLET
Read and retain carefully for as long as the product is being used. It contains vital information on the operation and instal­lation. The leaflet should be regarded as part of the product.
If you are just installing the unit, the leaflet must be given to the householder. The leaflet is to be given to any subsequent user.
1. READ THIS FIRST
WARNINGS
(1) The Alarm should be permanently wired to the mains by a
qualified electrician in accordance with IEE wiring regulations.
(2) Do not locate the CO Alarm where it could be exposed to
dripping, splashing or condensation (e.g. bathroom, above an electric kettle etc).
Install the Carbon Monoxide Alarm (CO Alarm) in or near every room that contains a fuel burning appliance, particularly rooms where people spend a lot of time e.g. bedrooms, kitchens and sitting rooms.
Install preferably on the ceiling (300mm from walls) in rooms with an appliance. Install between 1.85m to 3m horizontally from appliance. In rooms remote from the appliance install about 1.5 to 2m above floor level, at
breath level.
Regularly check that the green power light is on, so standby rechargeable cells will fully charge. Important: The CO Alarm will not work if the mains supply is off and the rechargeable cells are depleted.
Test the unit weekly by pressing the test/hush button­the horn will sound.
Replace sensor module after 5 years operation (see page 16).
What to do when the alarm sounds:
(1) Open the doors and windows to ventilate.
(2) Turn off the appliance where possible and stop
using the appliance. (The alarm can be silenced immediately by pushing the test/hush button).
(3) Evacuate the property leaving the doors and windows open.
(4) Ring your gas or other fuel supplier on their emergency number; keep the number in a promi­nent place.
(5) Do not re-enter the property until the alarm has stopped. (If the alarm has been silenced by pressing the test/hush button, wait at least 5 min­utes so the alarm can check that the CO has cleared).
(6) Get medical help immediately for anyone suf­fering the effects of Carbon Monoxide poisoning (headache, nausea), and advise that Carbon Monoxide poisoning is suspected.
(7) Do not use the appliance again until it has been checked by an expert. In the case of gas appliances this must be a CORGI registered installer.
When the CO Alarm detects abnormal levels of CO (above 150ppm CO for 30 minutes) the horn sounds and the red light starts to flash. At higher levels of CO the alarm will turn on sooner (see table B). When it detects levels of CO above 50ppm the red light flashes every 5 seconds but the horn does not sound.
by appliances or vehicles burning fuels, such as coal, oil,
natural/bottled gas, paraffin, wood, petrol, diesel, charcoal etc. CO is absorbed by red blood cells in the lungs in preference to oxygen - this results in rapid damage to the heart and brain from oxygen starvation.
High levels of CO in a house can be caused by:
¥Incorrectly or poorly installed fuel-burning appliances.
¥Blocked or cracked chimneys/flues.
¥Blocked vents or draught-proofing which makes areas
¥with fuel burning appliances or fireplaces airtight.
¥Engines of cars, lawnmowers etc. left running in confined
¥spaces.
¥Portable paraffin or gas heaters in badly ventilated
¥rooms.
2.2 Symptoms of Carbon Monoxide Poisoning
Most people know that high levels of CO are harmful, howev­er the period of exposure is also important.
The following symptoms are related to Carbon Monoxide poi­soning and should be discussed with all members of the household.
Mild Exposure
: Slight headache, nausea, vomiting, fatigue
(often described as flu-like symptoms).
Medium Exposure
: Severe throbbing headache, drowsiness,
confusion, fast heart rate.
Extreme Exposure
: Unconsciousness, convulsions, car-
diorespiratory failure, death.
A high level of CO for a short period (e.g. 350 ppm CO for 30 minutes) will cause the same symptoms, a slight headache, as a lower level for a longer time (e.g. 150 ppm for 90 min­utes). Table Ashows how exposure to different concentrations of CO generally affects people. Many cases of reported Carbon Monoxide poisoning indicate that while victims are aware they are not well, they become so disorientated they are unable to save themselves by either leaving the building or calling for assistance. Young children and household pets may be the first affected.
Table A: Effects of Cumulative CO Exposure
35 The maximum allowable concentration for continuous exposure
in any 8 hour period according to OSHA *.
150 Slight headache after 1.5 hours.
200 Slight headache, fatigue, dizziness, nausea after 2-3 hours.
400 Frontal headaches within 1-2 hours, life threatening after 3 hours,
also maximum parts per million in flue gas (on an air free basis) according to US Environmental Protection Agency.
800 Dizziness, nausea and convulsions within 45 minutes.
Unconsciousness within 2 hours. Death within 2-3 hours.
1,600 Headache, dizziness and nausea within 20 minutes.
Death within 1 hour.
3,200 Headache, dizziness and nausea within 5-10 minutes.
Death within 25-30 minutes.
6,400 Headache, dizziness and nausea within 1-2 minutes.
Death within 10-15 minutes.
12,800 Death within 1-3 minutes.
ppm = parts per million
*OSHA Occupational Safety & Health Association
2.3 What happens when your CO Alarm detects Carbon Monoxide ?
When the Alarm detects dangerous levels of CO, it sounds a loud alarm and flashes the red alarm light. The digital display indicates the CO level in parts per million, ppm CO, (Model Ei261D only).
Table B: CO Alarm Response
*
Slight Headache
Table B shows how the built in microprocessor reacts to dif­ferent levels of CO gas and exposure time. At higher levels of CO the alarm turns on sooner. The rate of flashing of the red light indicates the level of CO.
If your CO Alarm sounds follow the instructions on page 2.
When ventilation is provided by leaving the window and doors open, the CO build up may have dissipated by the time help arrives and the alarm may have stopped sounding. Although your problem may appear temporarily solved it is crucial that the source of the CO is determined and appropriate repairs made.
NEVER IGNORE THE ALARM.
Pre-Alarm: When the alarm detects over 50ppm CO the red
light flashes every 5 seconds. This helps locate CO leaks as the unit gives an indication straight away. (Without this feature the CO level would need to be at 150ppm CO for 30 minutes for an indication to be given). Note the Pre-Alarm signal may be triggered by CO coming for example, from cooking with gas, from car engines or from nearby barbecues. This is usu­ally not a concern unless the Pre-Alarm signal persists for over an hour and the CO source is unknown.
NOTE: The CO Alarm may sound if cigarette smoke is blown into it, or aerosols are released nearby.
CO ALARM MEMORY.
When the test button is pressed the horn sounds and the indi­cator lights flash as follows:-
- Red Light is Off if no CO is detected since reset or power­up.
- Slow Flashing Red Light (every 2 seconds) if 150ppm CO has been detected since power-up.
- Fast Flashing Red Light (every 0.5 second) if 350ppm CO has been detected since power-up. This tells you if the unit has detected CO in your absence and helps to detect and locate leaks, monitor premises etc.
Reset Memory by holding down the test button for over 20
seconds until the red light stops flashing. cover the horn with a cloth to muffle the alarm.
Ei261-D Only
When the test button is held the display shows the previous peak reading. This tells you if the unit has detected CO in your absence and helps to detect and locate leaks, monitor premises etc. When the test button is held for 20 seconds the peak reading resets to zero. (Cover the horn with a cloth to muffle the loud alarm).
Please note the memory will also be reset when the unit is
removed from the mounting plate.
3. WHERE TO PLACE CO ALARMS
3.1 Suitable Locations
Ei Electronics recommends that the advice of the Health & Safety Executive (HSE) UK is followed as this is based on
research done at the BRE subsequent to the issuing of the BS 7860 : 1996 standard.
The Health & Safety Executive (HSE) UK give the following recommendations for rooms where CO alarms should be located — these are in order of priority:
- In rooms with flueless or open flued appliances.
- In rooms where the occupant spends most time
- In bedrooms
British Standard BS 7860:1996 give the following advice:
Ideally you should have a detector in or near every room that contains a fuel­burning appliance. However, if you have more than one appliance, but only one detector, you should take the following into consideration when deciding where best to put the detec­tor. (1) If there is an appliance in the room where you sleep, you should put the
detector in that room.
(2) If there is an appliance in a room that you use a lot, e.g. a sitting room, you
should put it in that room.
(3) If you live in a bedsit, put the detector as far away from the cooking appli-
ances as possible, but near to the place where you sleep.
(4) If the appliance is in a room not normally used (e.g. a boiler room), put the
detector just outside the room so that you will be able to hear the alarm more easily.
3.2 Unsuitable Locations
Do not place the CO Alarm in any of the following areas. (1) Within 1.85 metres (6 feet) of the appliance.
(2) Outside the building.
(3) In or below a cupboard.
(4) In a damp or humid area.
(5) Directly above a sink or cooker.
(6) Next to a door or window or anywhere that it would be
affected by draughts.
(7) Where it would be obstructed, e.g. by curtains
or furniture.
(8) In an area where the temperature could drop below
—5¡C or rise above 40¡C.
(9) Where dirt or dust could block the sensor and stop it
working.
(10) Where it could be easily knocked or damaged, or where
it could be accidentally turned off or removed.
(11) In a bathroom or where the CO alarm may be exposed
to water splashes or condensation (e.g. above an elec­tric kettle).
(12) Near paint, thinners, solvent fumes or air fresheners.
1
2
3
5
6
7
8
4
Model Ei 261 Model Ei 261D
WITH DIGITAL DISPLAY
DIGITAL DISPLAY Ei261D ONLY
' Ei ELECTRONICS 2001 P/N. B14332 R1
?
?
?
Figure 1
ppm
Concentration
of CO in Air
Inhalation Time (approx)
and Symptoms Developed
CO Level
ppm
Horn On
within
Red
Alarm Light
Time to first
Symptom*
0 ppm
50ppm 150 ppm 350 ppm
Off Off
30 min
6 min
-
-
90 min
30 min
Off
Flashes every 5 sec
Flashes every 2 sec
Flashes every 0.5 sec
* If they contain or are near a fuel-burning appliance
Figure 2
Kitchen *
Bedroom *
Sitting Room *
?
LOCATION FOR TAMPERPROOF SCREW
GAS ENTRY HOLES
SIDE VIEW
MOUNTING PLATE
TAMPERPROOF CATCH
WARNING: DISCONNECT MAINS BEFORE REMOVING ALARM FROM
CEILING OR WALL
PUSH SMALL
SCREWDRIVER
STRAIGHT IN TO RELEASE. PUSH COVER
BACK
3.3 Installation.
The HSE, UK gives more detailed recommendations as follows:
If locating the CO Alarm in a room with an appliance:
- the alarm should be located between 1.85m and 3m horizontally from the appliance.
- the alarm should be located preferably on the ceiling. Ceiling mounted detectors should be at least 300mm from any wall.
- if placed on a wall the CO Alarm should be as high as possible (higher than doors and windows) but not within 150mm of the ceiling.
If locating the CO Alarm in a room remote from the appliance:
- the alarm should be located at a level similar to the breathing zone of the occupant (typically in the living rooms at 1.5 to 2.0m above floor level and in bedrooms at the height of the bed).
The BS 7860 : 1996 standard recommends that the CO Alarm should be at least 1.5 metres (5ft) above floor level, and also the detector should be at least 1.85 metres (6ft) from the appliance.
INSTALLING CARBON MONOXIDE ALARMS
The Alarm is designed to be permanently mounted, using it s own built-in terminal block to connect it to the mains. The mounting plate can be screwed directly to the ceiling. Alternatively it can be screwed to a standard junction box (BS 4662 single gang accessory box). It requires a current of 60mA. The Alarm must not be exposed to dripping or splashing. There are important markings on the underside of the alarm.
IMPORTANT PRECAUTION: Do not install the actual alarm itself in new or renovated buildings until all work is completed (including floor coverings) and the building has been fully cleaned. The wiring can be installed when appropriate. (Excessive dust and debris from building work can contaminate the sensor and cause problems, it will also invalidate the guarantee). If it must be installed, cover it completely, particularly around the edges, with a dust cover, until all cleaning is finished.
The Alarm must not
be connected when the house wiring
insulation is being checked with high voltages i.e. don t use a
megger on the alarm.
WARNING: Do not use the CO Alarm on an intermittent basis, or as a portable detector for the spillage of combustion prod­ucts from fuel burning appliances or chimneys.
WARNING: Mains operated Alarms should be installed and interconnected by a qualified electrician in accordance with the Regulations for Electrical Installations published by the Institution of Electrical Engineers (UK). Failure to install this Alarm correctly may expose the user to shock or fire hazards.
WARNING: The Alarm must be continuously powered 24 hours a day so it is important that it is not on a circuit that can be turned off by a switch.
INSTALLATION
(1) Select a location complying with the above advice.
(2) Disconnect the AC mains supply from the circuit that is
going to be used.
(3) Remove the mounting plate from the CO Alarm by
releasing the tamper-proof catch with a small screwdriver as shown in Figure 1 and sliding the Alarm from the plate.
(4) The house wiring must be connected to the terminal block
on the mounting plate as follows:
L: Live - connect to the house wires coloured brown, red or marked L.
N: Neutral - connect to the house wires coloured blue, black or marked N.
IC: Interconnect - connect to the third core. (If you are not interconnecting units, do not connect anything to the IC terminal). See below for information on interconnecting).
Warning: Mixing Live & Neutral wires will damage interconnected alarms.
We recommend the use of 6243Y mains cable when interconnecting units. Use the third core for interconnection.
Do not use an earth wire for the interconnect line.
Lift off the wiring cover as shown in Figure 3. N.B. The Alarm does not need to be earthed. However the terminal marked is provided for the convenience of the installer so that any copper earth wire or cable coloured green or green & yellow, can be safely terminated.
To interconnect the Alarms connect all the IC terminals together as shown in Figure 5
(5) If the mains wires are recessed, bring the wires through the rear hole in the mounting plate as shown in Figure 4
If the mains wires are being brought along the surface, con­duit can be inserted into the top and/or bottom, for the cable.
(a) position the mounting plate so the cable conduit is as shown in Figure 4
(b) Carefully cut around the knockout on the outside wall so the conduit fits. (Note: to comply with the BS 7860, IP42 protection rating, seal around conduit with silicone rubber or similar to prevent water entering).
(6) Carefully align the mounting plate and screw into place. Connect the wires to the terminal block. With recessed wiring, ensure the rear gasket seals around the edge of the hole in the ceiling or wall. This is to prevent air draughts affecting the CO gas entering the alarm. If the orifice is not closed off by the gasket it should be sealed with silicone rubber or equiva­lent.
Replace the wiring cover.
Carefully line up the unit on the base and slide on.
Press the test/hush button for 10 seconds. The horn will sound.
CAUTION: Do not attempt to remove the Alarm without first releasing the tamper clip as shown in Figure 1.
(7) Connect the mains power to the alarm circuit. Check the
green light is on. Check the operation of the Alarm as outlined below.
(8) The unit may be tamperproofed further, by removing the
knockout in the sidewall of the mounting plate as shown in Figure 1. Insert the self tapping screw (3mm diameter, 12mm long) after the unit is on the mounting plate
INTERCONNECTING Ei ELECTRONICS CARBON MONOXIDE ALARMS
When one unit detects CO all units alarm. All horns will sound but only units detecting CO will flash their red lights.
A maximum of twelve Ei 261/261D CO Alarms may be interconnected along with an Ei 128C module with relay (see technical specification). (If you wish to interconnect more than twelve alarms contact your distributor). Systems using more than 3 or 4 alarms must be very carefully planned to ensure nuisance alarms are not excessive e.g. from weekly testing.
¥ All alarms must be cleaned and maintained regularly.
¥ A qualified person must be on call to quickly remove any
faulty alarms, which are causing all the alarms to sound.
W
ARNING
: Do not connect these Alarms to any other type of Ei Alarm, or to any other model produced by another manufacturer, apart from those listed above.
Doing this may damage the Alarms and could result in a shock or fire hazard.
The interconnect wire (minimum 0.75mm
2
cable) must be
treated as if it was live. It should be insulated and sheathed.
A maximum of 250 metres (820 ft) of wire can be used (max­imum resistance between detectors 50 ohms). Connect as shown in Figure 5.
These Carbon Monoxide Alarms should be interconnected only within the confines of a single family living unit. If they are connected between different units there may be excessive nuisance alarms. Everybody may not be aware that they are being tested etc.
4. TESTING YOUR CO ALARM
(1) Regularly check that the green mains power light is on. The unit cannot detect CO if the mains power is not on and the rechargeable battery is depleted. (If it is off check circuit breakers, fuses, wiring etc).
(2) Test the unit weekly by pressing the test/hush button. Hold the test button for 5 seconds until the horn sounds for over 5
seconds. This will help to familiarise you and your family with the distinctive on-off sound of the CO Alarm. This test checks that the electronics and horn are working correctly. If the units are interconnected, button test each unit in turn and check all interconnected units alarm.
(3) If the CO Alarm gives a short beep and the amber fault light flashes every 40 seconds it means the self-checking cir­cuit may have detected a fault. Press and hold the test/hush button. If the amber light flashes without the horn sounding, the sensor is faulty. On the Ei 261D the display will show SF indicating Sensor Faulty.
(4) If the Alarm fails to operate when the test/hush button is pressed, disconnect the mains supply at the distribution fuse board, remove unit from mounting plate for 3 minutes. Put unit back on mounting plate. Re-connect the mains and try again. (This procedure resets the microprocessor in the unit).
(5) If the unit beeps every 40 seconds it means the battery is depleted. (On the Ei 261D with depleted cells, the display will show CP to remind you to Connect mains Power). Connect mains (ensure green light is on) to allow cells to charge.
(6) Once a year check the rechargeable cells by switching off mains and pressing the test button for 10 seconds. The horn should sound loudly. Re-connect mains power.
If the CO Alarm fails any of the above tests it must be replaced immediately (see section 9 Getting the CO Alarm Serviced ).
The CO Alarm is fully operational and will provide protection against a build up of Carbon Monoxide gas, 70 seconds after it is connected to the mains supply.
Testing with Carbon Monoxide.
Pressing the test button causes the unit to check for CO 4 seconds later - this is the Fast CO Test Mode. This eliminates the long waiting normally required e.g. up to 30 minutes at 150ppm CO and up to 6 minutes at 350ppm CO. The unit can be tested with CO by using one of the kits that comes with CO either in a glass phial or aerosol can. Follow the instructions on the kit but be sure to press the test button to speed up the CO sampling directly after you expose the unit to the CO. It is best if possible to inject the CO gas into the gas entry holes, see Figure 1. When it senses the CO it will give 3 beeps and the red light will flash as per table B. It then resets to normal mode. (If unit fails to respond press test button again as gas can take some seconds to enter sensor). The Fast CO Test Mode normally does not activate the mem-
ory function. (This can be checked by pressing the test but­ton. If the red light flashes continuously indicating CO was detected, hold the test button for 20 seconds until the red light stops flashing as the memory resets).
How to distinguish between CO Alarm and Smoke Alarm Warnings.
The CO Alarm has a distinctive on-off sound of 3 pulses, fol­lowed by a pause as compared with a typical Smoke Alarm which has a rapid pulsing sound.
In addition, when your CO Alarm is sounding the red alarm light in the centre of the cover will be flashing.
Testing both your CO Alarms and Smoke Alarms weekly will help you and your family to clearly distinguish between them in an emergency.
5. MAINTAINING YOUR CO ALARM
Clean the outside case by occasionally wiping with a clean damp cloth, (disconnect the mains supply at the distribution/fuse board first). Do not use any cleaning agents, bleaches, detergents or polishes, including those in aerosol cans. Avoid spraying air fresheners, hair spray, paint or other aerosols near the CO Alarm. Do not place air fresheners near the unit.
Use the narrow nozzle of a vacuum cleaner to remove fluff and other contamination from the cover slots to ensure CO gas can reach the sensor.
Caution: Do not paint the CO Alarm.
Remove the CO Alarm when decorating. Do not allow water or dust to contaminate the alarm. Warning: Do not open or tamper with the CO Alarm. There are no user serviceable parts inside apart from the sensor module - see below. This can damage the unit and may expose the user to shock or fire hazards.
How to disconnect and remove the alarm:
(1) First disconnect the mains supply to the CO Alarm circuit
at the distribution/fuse board.
(2) Remove tamperproofing screw if fitted (see Figure 1).
(3) Release catch as shown in Figure 1 and slide unit off
mounting plate.
SENSOR MODULE REPLACEMENT Replace the sensor module after 5 years operation (or by the date on the side of the unit).
It must also be replaced if the amber light flashes and the unit beeps every 40 seconds. Remove the alarm from the mount­ing plate as described above. Pull out the sensor module from the rear. Replace with a new sensor module (Ei 261M) (Contact Aico or EI Electronics, for your nearest module sup­plier). Carefully align the module including the three connec­tor pins and push firmly home. Slide the alarm back on to the mounting plate. Reconnect the mains supply. Wait 4 minutes for the new sensor to stabilise and then press the test button
- the horn should sound. Check the alarm as described in section 4 above.
6. LIMITATIONS OF CO ALARMS
(1) The Ei 261/261D CO Alarm will not work without mains power if the rechargeable cells are depleted. The green power light must be on at all times as far as possible.
(2) Carbon Monoxide must enter the unit for it to be detected. There may be Carbon Monoxide in other areas of the house (e.g. downstairs, in a closed room etc). but not in the vicinity of the CO Alarm. Doors, air draughts and obstructions can prevent the CO reaching the Alarm. For these reasons we recommend CO Alarms are fitted both near and in bedrooms, particularly if bedroom doors are closed at night. Additionally install in rooms where members of the household spend much of their time, and in rooms with potential sources of CO gas.
(3) The CO Alarm may not be heard. The sound output is loud but it may not be heard behind a closed door or if it is too far away. Interconnecting CO Alarms greatly improves the prob­ability that they will be heard. The Alarm may not wake up somebody who has taken alcohol or drugs. The alarm sound may be masked by other sounds such as T.V., stereo, traffic noise etc. Fitting CO Alarms on either side of closed doors will improve their chance of being heard. This CO Alarm is not designed for people with impaired hearing.
(4) CO Alarms don t last indefinitely. CO Alarms are sophisti­cated electronic devices with many parts. Although the alarm and its component parts have undergone stringent tests, and are designed to be very reliable, it is possible that parts can fail. Therefore, you should test your CO Alarm weekly. We recommend that the CO Alarm sensor is replaced after 5 years operation. The complete unit should be replaced after 10 years.
(5) CO Alarms are not a substitute for life insurance. House-
9
10
11
13
14
15
16
WIRING
T
Figure 3.
Figure 4.
12
Figure 5
CONDUIT
INSERT SCREWDRIVER TO LIFT AND REMOVE WIRE COVER
KNOCK OUT FOR SURFACE WIRING CONDUIT
L N IC
IC - INTERCONNECT
N - NEUTRAL
L - LIVE
MAINS CABLE
SEALING GASKET
(MUST BE IN PLACE)
TERMINAL SCREWS
L N IC
KNOCK OUT FOR SURFACE WIRING CONDUIT
L - LIVE
N - NEUTRAL
IC - INTERCONNECT
RECESSED WIRING AREA
EARTH (IF PRESENT
L N IC
WIRING CONDUI
L N IC
Loading...
+ 1 hidden pages