Aico Ei141, Ei144, Ei146, Ei161RC, Ei164RC User Instruction

...
© Ei Electronics 2006P/N B16009 Rev0
B16009-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 12
230V~ SMOKE & HEAT ALARMS
ALKALINE PRIMARY BATTERY BACK-UP
Ei141 - Ionisation Ei144 - Heat
RECHARGEABLE LITHIUM CELL BACK-UP
Ei161RC - Ionisation Ei166RC - OpticalEi164RC - Heat
USER INSTRUCTIONS
1. REGULAR CHECKS
Look for:
Constant green light Red light flash every 40 sec.
Ei146 - Optical
Press
test button
for 10 sec.
Alarm will sound loudly.
Vacuum
around
side vents to clean.
O
T
O
R
E
M
O
V
E
P
U
S
H
&
P
U
S
H
C
O
V
E
R
A
W
A
Y
S
C
R
E
W
D
R
I
V
E
R
I
N
T
O
S
L
O
T
2
B16009-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 1
LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM.
THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW
2. ALARM REMOVAL
LOCATE REMOVAL SLOT
INSERT SCREWDRIVER
.
INSERT A FLAT-BLADED SCREWDRIVER HORIZONTALLY
APPROX. 1cm INTO THE CENTRE OF THE REMOVAL SLOT
SLIDE ALARM OFF BASE
WITH THE SCREWDRIVER STILL INSERTED, PUSH THE LOWER HALF OF THE ALARM AWAY FROM THE SCREWDRIVER, IN THE
DIRECTION OF THE ARROW ON THE COVER
REMOVE ALARM
HOLD THE LOWER HALF OF THE ALARM AND REMOVE FROM
THE BASE PLATE BY MOVING IT VERTICALLY DOWNWARDS,
T
WARDS THE FLOOR.
y
ging
3
B16009-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 2
3. IMPORTANT INFORMATION
Do not paint your alarm. Do not allow paint, water or dust to contaminate your alarm.
Your alarm is a mains 230V AC electrical appliance. Do not open or insert an
Regularly check that the green mains indicator light on the cover is lit.
Test weekly - press and hold the test button on the alarm for 10 seconds. The alarm will sound loudly and the red light on the cover should flash rapidly. All the other interconnected alarms should sound.
thing into the alarm.
If alarm beeps once every 40 seconds for over 20 minutes, the battery is probably depleted (models Ei141/144/146 only) and must be replaced.
THE BATTERY" section on page 4).
(see "CHANGING
If a nuisance alarm occurs, press the test/hush button to silence the alarm for 10 minutes.
Clean your alarm regularly. This will reduce the risk of false alarms.
Remove or completely cover your alarm when decorating to prevent dust or other contamination dama
If your alarm sounds for no reason and
the unit.
will not reset, it can be removed by releasing the clip on the base.
(see "ALARM REMOVAL" section on page 2).
4. CHANGING THE BATTERY
(Models Ei141 / 144 / 146 only)
1. Switch off mains power to alarm (green light on cover should go out).
2. Remove unit as shown in “ALARM REMOVAL” section on page 2.
3. Locate battery slot in base of alarm as shown below.
4. Unclip battery from battery snap connectors.
5. Connect new battery by clipping back on to battery snap connectors. Use only 9V Alkaline batteries Duracell MN1604, Energizer 522. Other batteries can cause problems.
We recommend that the “use by date” on the battery should still have at least 2 years to go. Older batteries will give beeps prematurely.
6. Slide unit back on to the base. A click should be heard as the alarm engages. (The unit cannot be replaced on the base unless a battery is installed).
7. Press and hold the test button - horn should sound loudly.
8. Reinstate mains power to alarm (green light on cover should come on).
We recommend that the battery is replaced at least every three years for optimum performance.
5. TESTING & MAINTAINING YOUR ALARM
INSPECTION &TESTING PROCEDURE
Check all your alarms weekly, especially after initial installation or after re-occupation (e.g. following a holiday):
(i) Check that the green mains indicator light is on. (If it is off check circuit breakers, fuses and wiring etc.) Check the red light on the cover flashes every 40 seconds.
(ii) Press the test button for up to 10 seconds to ensure the sensor chamber, electronics and sounder are working. A red light on the cover, will flash while horn is sounding. The alarm
4
B16009-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 3
Loading...
+ 8 hidden pages