The signal words DANGER, WARNING,
CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is
only used on product labels to signify an immediate
hazard. The signal words WARNING, CAUTION,
and NOTE will be used on product labels and
throughout this manual and other manual that may
apply to the product.
DANGER− Immediate hazards which will result in
severe personal injury or death.
WARNING− Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION − Hazards or unsafe practices which
may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
Signal Words in Manuals
The signal word WARNING is used throughout
this manual in the following manner:
!
WARNING
The signal word CAUTION is used throughout
this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
Safety−alert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
START−UP, ADJUSTMENT, AND SAFETY CHECK4...........
Use of the AHRI Certified TM Mark indicates a
manufacturer’s participation in the program.
For verification of certification for individual
products, go to www.ahridirectory.org .
Printed in U.S.A.440 04 4801 00 7/3/2014
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury, or
property damage. Consult a qualified installer, service agency,
or your distributor or branch for information or assistance. The
qualified installer or agency must use factory−authorized kits or
accessories when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes,
the current editions of the National Fuel Gas Code (NFCG)
NFPA 54/ANSI Z223.1, and the National Electrical Code (NEC)
NFPA 70.
In Canada refer to the current editions of the National standards
of Canada CAN/CSA−B149.1 and .2 Natural Gas and Propane
Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety−alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words; DANGER, WARNING, and
CAUTION. These words are used with the safety−alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons could
result in equipment malfunction, property damage,
personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with proper tools and test
instruments.
Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI
Z223.1, and National standards of Canada
CAN/CSA−B149.1 and .2 Natural Gas and Propane
Installation Codes.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one power
switch.
!
WARNING
WARNING
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow safety warnings could result in personal
injury, death, and/or property damage.
This furnace is not designed for use in mobile homes,
trailers or recreational vehicles.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in damage
personal injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
furnaces.
2
Specifications are subject to change without notice.
440 04 4801 00
SERVICE AND TECHNICAL MANUALGas Furnace: (F/G)9MVE
START−UP CHECK SHEET
For Variable Speed Models (F/G)9MVE
(This sheet is optional. Keep for future reference.)
Date of Start−Up:
Dealer Name:
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Setup Checks
Check the box when task is complete.
Calculated Input (BTU) Rate: (See Checks and Adjustments
Section).
Heating Check
Measured Line Pressure During High Heat:
Measured Manifold Pressure: High Heat
Low Heat
Temperature of Supply Air: High Heat
Low Heat
Temperature of Return Air:
Temperature Rise (Supply − Return): High Heat
Low Heat
In Rise Range (see furnace rating plate)?
Static Pressure (Ducts) High Heat: Supply
Return
All Electrical Connections Tight?
Have hoses been relocated for furnace U/D/H application?
Condensate Drain Connected?
Condensate Drain Trapped?
Manual Gas Shut−off Upstream of Furnace/Drip Leg
Gas Valve turned ON?
Type of Gas: Natural: Propane:
Filter Type and Size:
Shade in Final Furnace Settings Below:
O
N
Optional Check: CO?
CO2?
Cooling Check
Temperature of Supply Air:
Temperature of Return Air:
Temperature Difference:
Static Pressure (Ducts) Cooling: Supply
Return
Dealer Comments:
O
N
440 01 4801 003
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
START−UP, ADJUSTMENT, AND SAFETY
CHECK
NOTICE
IMPORTANT INSTALLATION AND START−UP
PROCEDURES
Failure to follow this procedure may result in a nuisance smoke
or odor complaint.
The manifold pressure, gas rate by meter clocking, temperature
rise and operation must be checked after installation. Minor
smoke and odor may be present temporarily after start−up from
the manufacturing process. Some occupants are more
sensitive to this minor smoke and odor. It is recommended that
doors and windows be open during the first heat cycle.
General
1. Furnace must have a 115-v power supply properly
connected and grounded.
NOTE: Proper polarity must be maintained for 115-v wiring.
Control status indicator light flashes code 10 and furnace does
not operate if polarity is incorrect or if the furnace is not
grounded.
2. Thermostat wire connections at terminals R, W/W1, G,
and Y/Y2 must be made at 24-v terminal block on
furnace control.
3. Natural gas service pressure must not exceed 0.5 psig
(14- in. w.c., 350 Pa), but must be no less than 0.16 psig
(4.5-in. w.c., 1125 Pa).
4. Blower door must be in place to complete 115-v electrical
circuit and supply power to furnace components.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
These furnaces are equipped with a manual reset limit
switch in burner assembly. This switch opens and shuts
off power to the gas valve if an overheat condition (flame
rollout) occurs in burner assembly. Correct inadequate
combustion−air supply or improper venting condition
before resetting switch. DO NOT jumper this switch.
Before operating furnace, check flame rollout manual reset
switch for continuity. If necessary, press button to reset switch.
EAC-1 terminal is energized whenever blower operates. HUM
terminal is only energized when blower is energized in heating.
Setup Switches
There are four sets of setup switches on the furnace control
board. These switches configure the furnace for correct
application requirement. They also select the airflow settings for
Air Conditioning and Continuous Fan CFM.
The Setup Switch locations are shown and described on
Figure 4, Figure 5 and Table 5.The setup switches are also
shown on the unit wiring label.
Setup Switches (SW1)
The furnace control has 8 setup switches that may be set to
meet the application requirements. To set these setup switches
for the appropriate requirement:
1. Remove blower door.
2. Locate setup switches on furnace control.
3. Configure the set-up switches as necessary for the
application.
4. Replace blower door.
NOTE: If a bypass humidifier is used, setup switch SW1-3
(Low Heat Rise Adjust) should be in ON position. This
compensates for the increased temperature in return air
resulting from bypass.
Setup Switch (SW2)
Setup switches SW2 are used for applications used for
Twinning two furnaces of the same model and BTU’s and to
adjust airflow. SW2−2 is used to adjust airflow. Refer to the
Adjustments section for set up switch configurations. Refer to
Figure 5 for configuration of SW2 airflow options.
1. Remove blower door.
2. Locate setup switch SW2 on furnace control.
3. Configure the switches as necessary for the application.
4. Replace blower door.
Continuous Fan (CF) Setup Switches (SW2−5,
SW2−4, SW2−3)
The CF setup switches are used to select desired airflow when
thermostat is in continuous fan mode or to select low-cooling
airflow for two-speed cooling units. Refer to the Adjustments
section for set up switch configurations.
To set the desired cooling airflow:
1. Remove blower door.
2. Locate CF setup switches on furnace control.
3. Determine air conditioning tonnage used for low cooling
(when used) or desired continuous fan airflow.
4. Configure the switches for the required airflow.
5. Replace blower door.
Air Conditioning (A/C) Setup Switches (SW2−6,
SW2−7, SW2−8)
The air conditioning setup switches are used to match furnace
airflow to required cooling airflow or high stage cooling airflow
when a two−stage outdoor unit is used. Refer to the
Adjustments section for set up switch configurations.
To set the desired cooling airflow:
1. Remove blower door.
2. Locate A/C setup switches on furnace control.
3. Determine air conditioning tonnage used.
4. Configure the switches for the required cooling airflow.
5. Replace blower door.
NOTE: Incorrect airflow caused by improper A/C switch setup
may cause condensate blow-off or frozen indoor coil in the
cooling mode.
4440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Prime Condensate Trap with Water
!WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow these warnings could result in personal injury
or death.
Failure to use a properly configured trap or NOT
water-priming trap before operating furnace may allow
positive pressure vent gases to enter the structure through
drain tube. Vent gases contain carbon monoxide which is
tasteless and odorless.
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit
operation or performance satisfaction.
Condensate trap must be PRIMED or proper draining may
not occur. The condensate trap has two internal chambers
which can ONLY be primed by pouring water into the
inducer drain side of condensate trap.
1. Remove upper and middle collector box drain plugs
opposite of the condensate trap. (See Figure 1)
2. Connect field-supplied 5/8-in. (16 mm) ID tube with
attached funnel (see Figure 1) to upper collector box
drain connection.
3. Pour one quart (liter) of water into funnel/tube. Water
should run through collector box, overfill condensate
trap, and flow into open field drain.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to middle
collector box drain port.
6. Pour one quart (liter) of water into funnel/tube. Water
should run through collector box, overfill condensate
trap, and flow into open field drain.
7. Remove funnel and tube from collector box and replace
collector box drain plug.
Figure 1Priming Condensate Drain
Purge Gas Lines
If not previously done, purge the lines after all connections
have been made and check for leaks.
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Never purge a gas line into a combustion chamber. Never
test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection
of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of
life.
WARNING
Adjustments
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.
This can result in unregulated manifold pressure and result
in excess overfire and heat exchanger failures.
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
DO NOT redrill orifices. Improper drilling (burrs,
out−of−round holes, etc.) can cause excessive burner noise
and misdirection of burner flames. This can result in flame
impingement of heat exchangers, causing failures. (See
Figure 2)
Figure 2Orifice Hole
WARNING
!
CAUTION
BURNER
ORIFICE
For proper operation and long term reliability the furnace input
Representative drawing only, some models may vary in appearance.
L11F065
440 04 4801 005
Specifications subject to change without notice.
rate must be within +/− 2 percent of input rate on furnace rating
plate, or as adjusted for altitude.
A93059
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
The gas input rate on rating plate is for installation at altitudes
up to 2000 ft. (610 M).
NOTICE
The NATURAL GAS manifold pressure adjustments in Table 3
compensate for BOTH altitude AND gas heating value. DO
NOT apply an additional de−rate factor to the pressures shown
in Table 3.
The heating content of natural gas at altitude may already
provide for a reduction in capacity or altitude. Refer to Table 3.
No adjustments to the furnace may be necessary at altitude for
certain gas heating values.
Refer to the instructions provided in the factory-specified
Propane conversion kit for instructions for setting gas manifold
pressures for Propane applications.
In the USA, the input rating for altitudes above 2000 ft. (610 M)
must be reduced by 2 percent for each 1000 ft. (305 M) above
sea level refer to Table 1. The natural gas manifold pressures
in Table 3 adjust for BOTH altitude and natural gas heating
value.
In Canada, the input rating must be reduced by 5 percent for
altitudes of 2000 ft. (610 M) to 4500 ft. (1372 M) above sea
level. The natural gas manifold pressures in Table 3 adjust for
BOTH altitude and natural gas heating value.
Table 1Altitude Derate Multiplier for U.S.A.
ALTITUDE
FT. (M)
0–2000
(0−610)
2001–3000
(610−914)
3001–4000
(914−1219)
4001–5000
(1219−1524)
5001–6000
(1524−1829)
6001–7000
(1829−2134)
7001–8000
(2134−2438)
8001–9000
(2438−2743)
9001–10,000
(2743−3048)
* Derate multiplier factors are based on midpoint altitude for altitude range.
NOTE: For Canadian altitudes of 2000 to 4500 ft. (610 to
1372 M), use USA altitudes of 2001 to 3000 ft. (610 to 914
M) in Table 3.
To adjust manifold pressure to obtain the proper input rate, first,
determine if the furnace has the correct orifice installed. At
higher altitudes or different gas heat contents, it may be
necessary to change the factory orifice to a different orifice.
Tables have been provided in the furnace Service and
Technical Manual to match the required orifice to the manifold
pressure to the heat content and specific gravity of the gas. to
do this:
1. Obtain average yearly gas heat value (at installed
altitude) from local gas supplier.
2. Obtain average yearly gas specific gravity from local gas
supplier.
3. Find installation altitude in Table 3.
4. Find closest natural gas heat value and specific gravity in
Table 3. Follow heat value and specific gravity lines to
point of intersection to find orifice size and low−and
6440 04 4801 00
PERCENT
OF DERATE
01.00
4−60.95
6−80.93
8−100.91
10−120.89
12−140.87
14−160.85
16−180.83
18−200.81
DERATE MULTIPLIER
FACTOR*
Specifications subject to change without notice.
high−heat manifold pressure settings for proper
operation.
5. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
NOTICE
If orifice hole appears damaged or it is suspected to have been
redrilled, check orifice hole with a numbered drill bit of correct
size. Never redrill an orifice. A burr−free and squarely aligned
orifice hole is essential for proper flame characteristics.
6. Replace orifice with correct size, if required by Table 3.
Use only factory−supplied orifices. See EXAMPLE.
EXAMPLE 1:
0 - 2000 ft. (0 - 609.6M) altitude
Heating value = 1050 Btu/cu ft.
Specific gravity = 0.62
Therefore: Orifice No. 44
(Furnace is shipped with No. 44 orifices. In this example, all
main burner orifices are the correct size and do not need to be
changed to obtain proper input rate.)
Manifold pressure: 3.4-in. w.c. (847 Pa) for high heat, 1.4-in.
w.c. (349 Pa) for low heat
NOTE: To convert gas manifold Table pressures to Pascals,
multiply the in.w.c. value by 249.1 Pa/in. w.c. (1 in. wc. = 249.1
Pa).
Check Inlet Gas Pressure
The inlet gas pressure must be checked with the furnace
operating in maximum heat. This is necessary to make sure the
inlet gas pressure does not fall below the minimum pressure of
4.5 in. w.c. (1121 Pa).
1. Make sure the gas supply is turned off to the furnace and
at the electric switch on the gas valve.
2. Remove the 1/8 in. NPT plug from the inlet pressure tap
on the gas valve.
3. Connect a manometer to the inlet pressure tap on gas
valve.
4. Turn on furnace power supply.
5. Turn gas supply manual shutoff valve to ON position.
6. Turn furnace gas valve switch to ON position.
7. Jumper the R to W/W1 and W2 thermostat connections
at the furnace control board.
8. When main burners ignite, confirm inlet gas pressure is
between 4.5 in. w.c. (1125 Pa) and 13.6 in. w.c.(3388
Pa).
9. Remove jumper across thermostat connections to
terminate call for heat. Wait until the blower off delay is
completed.
10. Turn furnace gas valve electric switch to OFF position.
11. Turn gas supply manual shutoff valve to OFF position.
12. Turn off furnace power supply.
13. Remove manometer from the inlet pressure tap of the
gas valve.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Re−install manifold pressure tap plug in gas valve to
prevent gas leak.
14. Apply pipe dope sparingly to end of inlet gas pipe plug
and re−install in the gas valve.
WARNING
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Adjust Manifold Pressure
1. Adjust manifold pressure to obtain low fire input rate.
(See Figure 3)
a. Turn gas valve ON/OFF switch to OFF.
b. Remove manifold pressure tap plug from gas valve.
c. Connect a water column manometer or similar device
to manifold pressure tap.
d. Turn gas valve ON/OFF switch to ON.
e. Move setup SW1—2 on furnace control to ON
position to lock furnace in low−heat operation. (See
Figure 4 and Figure 5)
f. Manually close blower door switch.
g. Jumper R and W/W1 thermostat connections on
control to start furnace. (See Figure 4)
h. Remove regulator adjustment cap from low heat gas
valve pressure regulator (See Figure 3) and turn
low−heat adjusting screw (3/16 or smaller flat−tipped
screwdriver) counterclockwise (out) to decrease input
rate or clockwise (in) to increase input rate.
NOTICE
DO NOT set low−heat manifold pressure less than 1.3−in. w.c.
(324 Pa) or more than 1.7−in. w.c. (423 Pa) for natural gas. If
manifold pressure is outside this range, change main burner
orifices.
i. Install low−heat regulator adjustment cap.
j. Re−install manifold pressure tap plug from gas valve.
k. Move setup switch SW1−2 to OFF position after
completing low−heat adjustment.
l. Leave manometer or similar device connected and
proceed to Step 2.
2. Adjust manifold pressure to obtain high fire input rate.
(See Figure 3)
a. Jumper R to W/W1 and W2 thermostat connections
on furnace control. This keeps furnace locked in
high−heat operation.
b. Remove regulator adjustment cap from high−heat
gas valve pressure regulator (See Figure 3) and turn
high heat adjusting screw (3/16−in. or smaller
flat−tipped screwdriver) counterclockwise (out) to
decrease input rate or clockwise (in) to increase input
rate.
Figure 3
1/2” NPT Inlet
1/8” NPT Inlet
Pressure Tap
Redundant Automatic Gas Control
Valve (2−Stage)
ON/OFF Switch
Regulator Seal Cap
Regulator Adjustment
Regulator Seal Cap under Cap
1/8” NPT Manifold
Pressure Tap
1/2” NPT Outlet
A11152
NOTICE
DO NOT set high−heat manifold pressure less than 3.2−in. w.c.
(797 Pa) or more than 3.8 in. w.c. (947 Pa) for natural gas. If
required manifold pressure is outside this range, change main
burner orifices to obtain manifold pressure in this range.
c. When correct input is obtained, replace caps that
conceal gas valve regulator adjustment screws. Main
burner flame should be clear blue, almost
transparent. (See Figure 14)
d. Re−install manifold pressure tap plug to gas valve.
e. Remove jumpers R to W/W1 and R to W2.
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Re−install manifold pressure tap plug in gas valve to
prevent gas leak.
3. Verify natural gas input rate by clocking meter.
NOTE: Contact your HVAC distributor or gas supplier for metric
gas meter Tables, if required.
a. Turn off all other gas appliances and pilots served by
the meter.
b. Move setup switch SW1−2 to ON position. This
keeps furnace locked in low−heat operation when
only W/W1 is energized.
c. Jumper R to W/W1.
d. Run furnace for 3 minutes in low−heat operation.
e. Measure time (in sec) for gas meter to complete 1
revolution and note reading. The 2 or 5 cubic feet dial
provides a more accurate measurement of gas flow.
f. Refer to Table 2 for cubic ft. of gas per hr.
g. Multiply gas rate cu ft./hr by heating value (Btuh/cu
ft.) to obtain input.
h. If clocked rate does not match required input from
Step 1, increase manifold pressure to increase input
or decrease manifold pressure to decrease input.
Repeat steps b through e until correct low−heat input
is achieved. Re−install low heat regulator seal cap on
gas valve.
i. Jumper R to W/W1, and W2. This keeps furnace
locked in high−heat operation when both W/W1 and
W2 are energized.
j. Repeat items (d) through (h) for high−heat operation,
repeating Step 2 and adjusting the high−heat regular
screw, as required.
4. Restore furnace to normal operating condition.
a. Turn gas valve On/Off switch to OFF.
b. Remove water column manometer or similar device
from manifold pressure tap.
c. Replace manifold pressure tap plug to gas valve.
d. Turn gas valve On/Off switch to ON.
e. Move setup SW1−2 on furnace control to position
required for attached thermostat (OFF for
single−stage thermostats, ON for two−stage
thermostats).
f. Check for gas leaks and verify furnace operation.
WARNING
440 04 4801 007
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
(
)
Figure 4Example of Variable Speed Furnace Control for Variable Speed ECM Blower Motor
SW1 SETUP
SWITCHES AND
BLOWER OFF-
DELAY
COMMUNICATION
CONNECTOR
24-V THERMOSTAT
TERMINALS
STATUS AND COMM
LED LIGHTS
MODEL PLUG
CONNECTOR
OUTDOOR
AIR TEMP
CONNECTOR
AIR CONDITIONING (A/C) &
CONTINUOUS FAN (CF)
AIRFLOW SETUP SWITCHES
HUMIDIFIER
TERMINAL (24-VAC
0.5 AMP MAX.)
FLASH
UPGRADE
CONNECTOR
(FACTORY
ONLY)
ACRDJ – AIR
CONDITIONING
RELAY DISABLE
JUMPER
PL1 – LOW VOLTAGE MAIN
HARNESS CONNECTOR
3-AMP FUSE
TRANSFORMER 24-VAC
CONNECTIONS
115-VAC (L2) NEUTRAL
CONNECTIONS
115-VAC (L1) LINE
VOLTAGE CONNECTIONS
EAC-1 TERMINAL
115-VAC 1.0 AMP MAX.
PL2 – HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
SOFTWARE
VERSION
L14F003
8440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
NOTE: Blower door must be installed when taking temperature
rise reading. Leaving blower door off will result in incorrect
temperature measurements, due to possible changes in duct
static pressure and airflow.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in:
SOverheating the heat exchangers or condensing
flue gases in heat exchanger areas not designed
for condensate.
SShortened furnace life.
SComponent damage.
Temperature rise must be within limits specified on furnace
rating plate. Recommended operation is at midpoint of rise
range or slightly above.
Furnace must operate within ranges of temperature rise
specified on the furnace rating plate.
When setup switch SW1−4 is ON, operation will be near the
high end of the rise range for improved comfort.
Determine air temperature rise as follows:
1. Place thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not see
heat exchanger so that radiant heat does not affect
readings. This practice is particularly important with
straight−run ducts.
2. When thermometer readings stabilize, subtract return−air
temperature from supply−air temperature to determine air
temperature rise.
NOTE: Temperature rise can be determined for low−heat
operation by locking the furnace in each mode of operation.
The mode of operation is based on the position of set up switch
SW1−2 on the furnace control board.
This furnace is capable of automatically providing proper
airflow to maintain the temperature rise within the range
specified on furnace rating plate. If temperature rise is outside
this range, proceed as follows:
a. Check gas input for low− and high−heat operation.
b. Check derate for altitude if applicable.
c. Check all return and supply ducts for excessive
restrictions causing static pressure greater than
0.5−in. w.c.
d. Ensure Low Heat Rise Adjust switch SW1−3 on
furnace control is in ON position when a bypass
humidifier is used. (See Figure 4 for switch location.)
e. Check Troubleshooting Guide for Variable−Speed
Condensing Furnaces.
To lock the furnace in Low Heat:
1. Turn SW1-2 ON at the furnace control. Set up switch
2. Connect a jumper across R and W/W1 at the thermostat
terminals at the furnace control.
3. Allow the burners to ignite and the blower to turn on.
4. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in Low Heat:
440 04 4801 0011
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
1. Remove jumpers from R and W/W1.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1-3. When set to
ON, airflow is raised 18% for Low Heat. Factory default
position is OFF.
5. Turn 115 VAC power on.MN7A
6. Re--check Low Heat Temperature Rise
To lock the furnace in High Heat:
1. Connect a jumper across R and W/W1 and W2 at the
thermostat terminals at the furnace control.
2. Allow the burners to ignite and the blower to turn on.
3. Allow the supply temperature to stabilize and verify the
proper rise range.
If the temperature rise is too high or too low in High Heat:
1. Remove jumpers from R and W/W1 and W2.
2. Wait until the blower off delay is completed.
3. Turn 115 VAC power off.
4. Check the position of Set up switch SW1-4. When set to
OFF and SW1-3 is set to OFF, airflow is raised 7% for
Low Heat and 10% for High Heat. Factory default
position is ON. If SW1-3 is ON and SW1-4 is OFF, airflow
is raised 18% for Low Heat and 10% for High Heat
5. Turn 115 VAC power on.
6. Re-check High Heat Temperature Rise.
After the temperature rise has been verified:
1. Remove jumpers from thermostat terminals.
2. Allow the blower off delay to complete.
3. Turn Set up switches SW1-2 to the desired position.
4. Proceed to “Adjust Blower Off Delay” or install blower
door if complete
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
Reinstall manifold pressure tap plug in gas valve to
prevent gas leak.
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace
life.
Recheck temperature rise. It must be within limits specified
on the rating plate. Recommended operation is at the
mid−point of rise range or slightly above.
.
WARNING
CAUTION
Adjust Blower Off Delay (Heat Mode)
a. Remove blower door if installed.
b. Turn Dip switch SW1−7 or SW1−8 ON or OFF for
desired blower off delay. (See Table 4 and Figure 4,
Figure 5)
Table 4Blower Speed Taps
DESIRED HEATING MODE
BLOWER OFF DELAY
(SEC.)
90OFFOFF
120ONOFF
150OFFON
180ONON
SETUP SWITCH (SW1-7 and -8)
POSITION
Adjust Cooling Airflow − High−Speed and
Low−Speed Cooling
The ECM blower can be adjusted for a range of airflows for
low−speed or high−speed cooling. See Table 5−Air Delivery −
CFM (with Filter) and Figure 5. Furnace Setup Switches and
Descriptions. Depending on the model size, the cooling airflow
can be adjusted from 1.5 tons to 6 tons of nominal cooling
based on 350 CFM ton.
NOTE: 6 ton airflow will truncate at 2200 CFM on applicable
models.
The high−speed or single−speed cooling airflow is adjusted by
turning setup switches SW2−6, SW2−7 and SW2−8 either ON
or OFF. Select the required airflow from Table 5. Table 5 is
based on 350 CFM per ton. For other CFM per ton setup switch
selections, see Figure 4, Figure 5 and Figure 16.
The Continuous Fan airflow selection via setup switches
SW2−3, SW2−4 and SW2−5 is also the airflow for low−speed
cooling when the furnace is used with a two−speed cooling or
heat pump unit. Adjust the Continuous Fan CFM setup
switches SW2−3, SW2−4 and SW2−5 to match the airflow
required for low−speed cooling. Select the required airflow from
Table 5 and Figure 5.
NOTE: The airflow selected via SW2−3, SW2−4 and SW2−5
(low−speed cooling airflow) cannot exceed the airflow selected
via SW2−6, SW2−7 and SW2−8 (high−speed cooling airflow).
For other CFM per ton setup switch selections, see Figure 4
and Figure 5.
For a complete explanation of cooling airflow, refer to the
section titled “Sequence of Operation.”
Adjust Continuous Fan Airflow/Low Speed
Cooling Airflow
NOTE: When the furnace is used with a two−speed cooling or
heat pump unit, the airflow selected for Continuous Fan via
setup switch SW2−3, SW2−4 and SW2−5 will also be the
airflow used for low−speed cooling, and vice versa.
NOTE: When the furnace is used with a two−speed cooling or
heat pump unit, adjust the Continuous Fan CFM setup
switches SW2−3, SW2−4 and SW2−5 to match the airflow
required for low−speed cooling.
Select the required Continuous Fan airflow using setup
switches SW2−3, SW2−4 and SW2−5 as shown in Figure 5
and Table 5.
12440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 5Furnace Setup Switch Description
RCL
LHT
LHR
C/E
CFM
TST
OFF
DLY
TWN
CFM
CFAC
SW1
SW2
SETUP
SWITCH
SW11
1
2
SW12
3
4
SW13
5
6
SW14
7
8
SW15
SW16
SW17 &
SW18
SW21TwiningOFF
1
2
SW22
3
4
5
SW26, 7, 8
6
7
8
SW23, 4, 5
SWITCH
NAME
Status Code
Recovery
Low Heat
Only
(Adaptive
Heat Mode
when SW12
is OFF)
Low Heat
Rise
Adjustment
Comfort/
Efficiency
Adjustment
CFM perton
adjust
Component
Self Test
BlowerOFF
delay
CFM perton
Adjust
AC
(Cooling
Airflow)
CF
(Continuous
Fan)
NORMAL
POSITION
DESCRIPTION OF USE
Turn ON to retrieve up to 7 stored status codes for troubleshooting assistance when R
OFF
thermostat lead is disconnected.
When SW12 is OFF allows two-stage operation with a single stage thermostat. Turn
ON when using two-stage thermostat to allow Low Heat operation when R to W/W1
OFF
closes and High Heat operation when R to W/W1 and W2 close.
Turn ON to increase Low Heat airflow by 18 percent. This compensates for increased
OFF
return air temperature caused with bypass humidifier.
Turn ON to decrease Low Heat airflow by approximately 7 percent and High Heat air
ON
flow by approximately 10 percent for maximum comfort.
OFFTurn ON for 400 CFM per ton, Turn OFF for 350 CFM per ton. See also SW2.
Turn ON to initiate Component Self Test for troubleshooting assistance when R
OFF
thermostat lead is disconnected. Turn OFF when Self Test is completed.
AllowsforselectionoffurnaceMain (OFF) or Secondary (ON) when Twinnedfurnacesetup isrequired. See kitinstructionsforfurtherdirectionsoninstallationandsetup.
325 CFM per ton (nominal) when SW22 ON and SW15 OFF
350 CFM per ton (nominal) when SW22 OFF and SW15 OFF
OFF
370 CFM per ton (nominal) when SW22 ON and SW15 ON
400 CFM per ton (nominal) when SW22 OFF and SW15 ON
See Air Delivery Tablesformodelspecific CFM vs.static pressure
The AC setup switchesselectdesiredcoolingorhighstagecooling (two-stageunits)
OFF
airflow. See Cooling Air Delivery Tables for specific switch settings.
The CF setup switchesselectdesired Continuous Fan Airflow
The CF switch positionisthelowcoolingairflowselectionfortwo-stagecoolingunits.
OFF
The CFM valuesareshowninthe Air Delivery Tablesbelowfor SW2settings. SW23, 4,
5cannotbesetforairflowhigherthan SW 26, 7, 8.
See Continuous Fan Air Flow Tableforspecificswitchsettings.
BASED ON 350 CFM/TON (Factory Default: SW1−5 = OFF, SW2−2 = OFF)
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Adjust Thermostat Heat Anticipator
a. Mechanical thermostat. Set thermostat heat
anticipator to match the amp. draw of the electrical
components in the R−W/W1 circuit. Accurate amp.
draw readings can be obtained at the wires normally
connected to thermostat subbase terminals, R and W.
The thermostat anticipator should NOT be in the
circuit while measuring current.
(1.) Set SW1−2 switch on furnace control board to
ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter as shown in Figure 6
across the R and W subbase terminals or R and
W wires at wall.
(4.) Record amp. draw across terminals when
furnace is in low heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
(6.) Turn SW1−2 switch OFF.
(7.) Install blower door.
b. Electronic thermostat: Set cycle rate for 3 cycles per
hr.
Figure 6Amp. Draw Check with Ammeter
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
HOOK-AROUND
AMMETER
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
EXAMPLE:
5.0 AMPS ON AMMETER
10 TURNS AROUND JAWS
0.5 AMPS FOR THERMOSTAT
=
ANTICIPATOR SETTING
A96316
Check Safety Controls
The flame sensor, gas valve, and pressure switch were all
checked in the Start−up procedure section as part of normal
operation.
1. Check Main Limit Switch
This control shuts off combustion system and energizes
air−circulating blower motor, if furnace overheats. By
using this method to check limit control, it can be
established that limit is functioning properly and will
operate if there is a restricted return−air supply or motor
failure. If limit control does not function during this test,
cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of
cardboard or sheet metal until the limit trips.
c. Unblock return air to permit normal circulation.
d. Burners will re−light when furnace cools down.
2. Check Pressure Switch(es)
This control proves operation of the draft inducer blower.
a. Turn off 115−v power to furnace.
b. Disconnect inducer motor lead wires from wire
harness.
c. Turn on 115−v power to furnace.
d. Set thermostat to “call for heat” and wait 1 minute.
When pressure switch is functioning properly, hot
surface igniter should NOT glow and control
diagnostic light flashes a status code 3. If hot surface
igniter glows when inducer motor is disconnected,
shut down furnace immediately.
e. Determine reason pressure switch did not function
properly and correct condition.
f. Turn off 115−v power to furnace.
g. Reconnect inducer motor wires, replace door, and
turn on 115−v power.
h. Blower will run for 90 seconds before beginning the
call for heat again.
i. Furnace should ignite normally.
Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify that switches SW1−1 and SW1−6 are OFF and
other setup switches are set as desired. Verify that
switches SW1−7 and SW1−8 for the blower OFF DELAY
are set as desired per Table 4.
3. Verify that blower and control doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s
instructions.
6. Review Home Owner’s Information with owner.
7. Attach literature packet to furnace.
14440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Table 5COOLING4 AND HEATING AIR DELIVERY - CFM (Bottom Return5 with filter)
(SW1-5 and SW2−2 set to OFF, except as indicated. See notes 1 and 2)
Unit SizeCooling Switch SettingsExternal Static Pressure (ESP)
1. Nominal 350 CFM/ton cooling airflow is delivered with SW1−5 and SW2−2 set to OFF.
Set both SW1−5 and SW2−2 to ON for +7% airflow (nominal 370 CFM/ton).
Set SW1−5 to ON and SW2−2 to OFF for +15% airflow (nominal 400 CFM/ton).
Set SW2−2 to ON and SW1−5 to OFF for −7% airflow (nominal 325 CFM/ton).
The above adjustments in airflow are subject to motor horspower range/capacity.
2. Maximum cooling airflow is achieved when switches SW2−6, SW2−7, SW2−8 and SW1−5 are set to ON, and SW2−2 is set to OFF.
3. All heating CFM’s are when low heat rise adjustment switch (SW1−3) and comfort/efficiency adjustment switch (SW1−4) are both set to OFF.
4. Ductwork must be sized for high−heating CFM within the operational range of ESP. Operation within the blank areas of the chart is not
recommended because high−heat operation will be above 1.0 ESP.
5. All airflows of 1880 CFM or less on 21” and 24.5” casing size furnaces are 5% less on side return only installations.
6. Airflows over 1800 CFM require bottom return, two−side return, or bottom and side return. A minimum filter size of 20” x 25” is required.
7. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.
8. Airflow not stable at this ESP.
16440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
SERVICE AND MAINTENANCE
PROCEDURES
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. A qualified
service person should inspect the furnace once a year.
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
The ability to properly perform maintenance on this
equipment requires certain knowledge, mechanical
skills, tools, and equipment. If you do not possess
these, do not attempt to perform any service and
maintenance on this equipment other than those
procedures recommended in the Owner’s Manual.
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in
environmental pollution.
Remove and recycle all components or materials (i.e.
oil, refrigerant, control board, etc.) before unit final
disposal.
!
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position and install a lockout tag. There may be more
than one disconnect switch. Lock out and tag switch
with a suitable warning label. Verify proper operation
after servicing.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in improper
furnace operation or failure of furnace.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation.
General
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of
the furnace, and conditioned air is discharged upward. Since
this furnace can be installed in any of the 4 positions shown in
Figure 7, you must revise your orientation to component
location accordingly.
WARNING
!
CAUTION
WARNING
!
CAUTION
Figure 7Multipoise Orientations
A93041
Electrical Controls and Wiring
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
There may be more than one electrical supply to the
furnace. Check accessories and cooling unit for
additional electrical supplies that must be shut off
during furnace servicing. Lock out and tag switch with
a suitable warning label.
The electrical ground and polarity for 115−v wiring must be
properly maintained. Refer to Figure 8 for field wiring
information and to Figure 16 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash code 10 and prevent the furnace from heating.
The control system also requires an earth ground for proper
operation of the control and flame−sensing electrode.
The 24−v circuit contains an automotive−type, 3−amp. fuse
located on the control. (See Figure 4) Any shorts of the 24−v
wiring during installation, service, or maintenance will cause
this fuse to blow. If fuse replacement is required, use ONLY a
3−amp. fuse. The control LED display will be off when fuse
needs to be replaced.
Troubleshooting
Refer to the service label. (See Figure 15—Service Label)
The Troubleshooting Guide − Flow Chart (See Figure 17) can
be a useful tool in isolating furnace operation problems.
Beginning with the word “Start,” answer each question and
follow the appropriate arrow to the next item.
The Guide − Flow Chart will help to identify the problem or
failed component. After replacing any component, verify correct
operation sequence.
Proper instrumentation is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light−Emitting Diode) to aid in installation, servicing, and
troubleshooting. Status codes can be viewed at the indicator in
blower door. The amber furnace control LED is either a
heartbeat, off or a code composed of 1 or 2 digits. The first digit
is the number of short flashes, the second digit is the number of
long flashes.
440 04 4801 0017
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 8Heating and Cooling Application Wiring Diagram with Single−Stage Thermostat
FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING
BLOWER
DOOR
SWITCH
BLK
WHT
GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
BLK
WHT
JUNCTION
BOX
FIVE
WIRE
THREE-WIRE
HEATING-
ONLY
FURNACE
W2
C
COM
O
N
W/W1
T
Y/Y2
R
O
R
L
G
24-VOLT
TERMINAL
BLOCK
NOTE 2
WC YRG
NOTE 1
NOTES: 1.
Connect Y/Y2-terminal as shown for proper operation.
Some thermostats require a "C" terminal connection as shown.
2.
If any of the original wire, as supplied, must be replaced, use
3.
same type or equivalent wire.
1-STAGE
THERMOSTAT
TERMINALS
CONDENSING
UNIT
FIELD-SUPPLIED
FUSED DISCONNECT
GND
208/230- OR
460-VOLT
THREE
PHASE
208/230VOLT
SINGLE
PHASE
For an explanation of status codes, refer to service label
located on control door or Figure 15, and the troubleshooting
guide which can be obtained from your distributor.
Retrieving Stored Fault Codes
The stored status codes will NOT be erased from the control
memory, when 115− or 24−v power is interrupted. The control
will store up to the last 7 Status Codes in order of occurrence.
1. To retrieve status codes, proceed with the following:
NOTE: NO thermostat signal may be present at control, and all
blower−OFF delays must be completed.
a. Leave 115−v power to furnace turned on.
b. Look into blower door indicator for current LED
status.
c. Remove blower door.
NOTE: The Status Codes cannot be retrieved by
disconnecting the limit switch. To retrieve Status Codes, follow
the procedure below.
2. Turn Setup Switch, SW1−1 “ON.”
3. Manually close blower door switch.
4. Control will flash up to 7 Status Codes.
5. The last Status Code, or 8th Code, will be a heartbeat.
6. Turn SW1−1 “OFF.”
7. A heartbeat amber LED will appear and indicates proper
operation.
8. Release blower door switch, install control door and
refer to the SERVICE label on the control door for more
information.
Component Self−Test
Component Test can ONLY be initiated by performing the
following:
1. Remove blower door.
2. Remove the wire from the “R” terminal of the control
board.
A11401
3. Turn Setup Switch, SW−1−6 “ON.”
4. Manually close blower door switch.
Blower door switch opens 115−v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this switch for
service purposes.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, or death.
Blower door switch opens 115−v power to furnace
control. No component operation can occur unless
switch is closed. Exercise caution to avoid electrical
shock from exposed electrical components when
manually closing this switch for service purposes.
5. Component Test sequence will function as follows:
a. Inducer motor starts on high−speed and continues to
run until Step (d.) of component test sequence.
b. Hot surface igniter is ON for 15 sec, then OFF.
c. Blower operates for 15 sec, then turns off.
d. Inducer motor goes to low−speed for 10 seconds,
then turns off.
e. After component test is completed, one or more
status codes (heartbeat, 2+5) will flash. See
component test section of service label for
explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1−6
OFF then back ON.
f. Turn setup switch SW1−6 OFF.
18440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
6. Release blower door switch, reattach wire to “R” terminal
on furnace control board and replace blower door.
Care and Maintenance
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never store flammable or combustible materials on,
near, or in contact with the furnace, such as:
1. Spray or aerosol cans, rags, brooms, dust
mops, vacuum cleaners, or other cleaning
tools.
2. Soap powders, bleaches, waxes or other
cleaning compounds, plastic or plastic
containers, gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids, or other volatile fluids.
3. Paint thinners and other painting compounds,
paper bags, or other paper products. Exposure
to these materials could lead to corrosion of the
heat exchangers.
For continuing high performance and to minimize possible
furnace failure, periodic maintenance must be performed on
this furnace. Consult your local dealer about proper frequency
of maintenance and the availability of a maintenance contract.
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace
and install lockout tag before performing any
maintenance or service. Follow the operating
instructions on the label attached to the furnace.
WARNING
WARNING
3. Check electrical connections for tightness and controls
for proper operation each heating season. Service as
necessary.
4. Inspect burner compartment before each heating season
for rust, corrosion, soot or excessive dust. If necessary,
have furnace and burner serviced by a qualified service
agency.
5. Inspect the vent pipe/vent system before each heating
season for water leakage, sagging pipes or broken
fittings. Have vent pipes/vent system serviced by a
qualified service agency.
6. Inspect any accessories attached to the furnace such as
a humidifier or electronic air cleaner. Perform any service
or maintenance to the accessories as recommended in
the accessory instructions.
Cleaning and/or Replacing Air Filter
The air filter type may vary depending on the application or
orientation. The filter is external to the furnace casing. There
are no provisions for an internal filter with this furnace. See
“Filter Arrangement” under the “Installation” section of this
manual.
NOTE: If the filter has an airflow direction arrow, the arrow
must point toward the blower.
To clean or replace filters, proceed as follows:
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow this warning could result in personal
injury or death, or property damage.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position and install a lockout tag. There may be more
than one disconnect switch. Lock out and tag switch
with a suitable warning label. Verify proper operation
after servicing.
!
CARBON MONOXIDE POISONING AND FIRE
HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
Never operate furnace without a filter or filtration
device installed. Never operate a furnace with filter or
filtration device access doors removed.
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs.
Use care and wear appropriate protective clothing,
safety glasses and gloves when handling parts, and
servicing furnaces.
The minimum maintenance on this furnace is as follows:
1. Check and clean air filter each month or more frequently
if required. Replace if torn.
2. Check blower motor and wheel for cleanliness each
heating and cooling season. Clean as necessary.
WARNING
!
CAUTION
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by
spraying cold tap water through filter in opposite direction
of airflow. Rinse filter and let dry. Oiling or coating of the
filter is not recommended.
5. If equipped with factory specified disposable media filter,
replace only with a factory specified media filter of the
same size.
6. Slide filter into cabinet.
7. Replace filter cabinet door.
8. Turn on electrical supply to furnace.
Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean
accumulated dirt and grease from blower wheel and motor
annually.
The inducer and blower motors are pre−lubricated and require
no additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
The following items should be performed by a qualified service
technician. Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
2. Remove blower door.
440 04 4801 0019
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
3. All factory wires can be left connected, but field
thermostat and accessory wiring may need to be
disconnected depending on their length and routing.
4. If the vent and combustion air pipe passes through the
blower compartment, it will be necessary to remove the
pipes from the blower compartment.
Disconnect the vent and combustion air pipe by:
a. Loosen the clamps on the vent couplings and
combustion air pipe external to the furnace.
b. Separate the pipes from the couplings and move
them aside.
c. Loosen the clamps on the vent couplings and
combustion air pipe located on the blower shelf.
d. Separate the pipes from the blower compartment and
set aside.
e. Remove the couplings from the pipe adapters and set
aside.
f. After servicing the blower, reverse steps a through e.
g. Tighten all clamps 15 lb−in.
See Figure 9 for steps 5 through 14.
5. Remove screws securing blower assembly to blower
shelf and slide blower assembly out of furnace. Detach
ground wire and disconnect blower motor harness plugs
from blower motor.
NOTE: Blower wheel is fragile. Use care.
6. Clean blower wheel and motor by using a vacuum with
soft brush attachment. Be careful not to disturb balance
weights (clips) on blower wheel vanes. Do not bend
wheel or blades as balance will be affected.
7. If greasy residue is present on blower wheel, remove
wheel from the blower housing and wash it with an
appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before
disassembly to ensure proper reassembly.
b. Loosen setscrew holding blower wheel on motor
shaft.
NOTE: Mark blower mounting arms and blower housing so
each arm is positioned at the same hole location during
reassembly.
c. Mark blower wheel orientation and cutoff plate
location to ensure proper reassembly.
d. Remove screws securing cutoff plate and remove
cutoff plate from housing.
e. Remove bolts holding motor mounts to blower
housing and slide motor and mounts out of housing.
f. Remove blower wheel from housing.
g. Clean wheel per instructions on degreaser cleaner.
Do not get degreaser in motor.
8. Reassemble motor and blower wheel by reversing items
7b through 7f. Ensure wheel is positioned for proper
rotation.
9. Torque motor mounting bolts to 40 +/− 10 lb−in. when
reassembling.
10. Torque blower wheel set screw to 160 +/− 20 lb−in. when
reassembling.
11. Verify that blower wheel is centered in blower housing
and set screw contacts the flat portion of the motor shaft.
Loosen set screw on blower wheel and reposition if
necessary.
Figure 9Blower Assembly
MOTOR SHAFT FLAT
SET SCREW
GROMMET
SCREW LOCATION
BLO HSG ASSY
BRACKET
BRACKET
ENGAGEMENT
DETAIL A
SEE DETAIL A
CUTOFF, BLOWER
WHEEL, BLOWER
BRACKET
POWER CHOKE
OR CAPACITOR
WHEN REQUIRED
SCREW
(GND)
MOTOR WHEEL HUB
A11584A
MOTOR ARM
SCREW
A11584B
A11584C
A11584D
BLOWER HSG ASSY
MOTOR, BLOWER
A11584E
20440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
12. Spin the blower wheel by hand to verify that the wheel
does not rub on the housing.
13. Reinstall blower assembly in furnace.
14. Reinstall 2 screws securing blower assembly to blower
deck.
15. Reconnect blower leads to furnace control. Refer to
furnace wiring diagram, and connect thermostat leads if
previously disconnected.
NOTE: Be sure to attach ground wire and reconnect blower
harness plugs to blower motor.
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace
and install lockout tag before performing any
maintenance or service. Follow the operating
instructions on the label attached to the furnace.
!
WARNING
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower door switch opens 115−v power to control. No
component operation can occur unless switch is closed.
Caution must be taken when manually closing this
switch for service purposes.
16. Downflow or horizontal furnaces with vent pipe through
furnace only:
a. Install and connect short piece of vent pipe inside
furnace to existing vent.
b. Connect vent connector to vent elbow.
17. Turn on electrical supply. Manually close blower door
switch. Use a piece of tape to hold switch closed. Check
for proper rotation and speed changes between heating
and cooling by jumpering R to G and R to Y/Y2 on
furnace control thermostat terminals. If outdoor
temperature is below 70_F (21_C), turn off circuit breaker
to outdoor unit before running furnace in the cooling
cycle. Turn outdoor circuit breaker on after completing
cooling cycle. (See Figure 4)
NOTE: If R−W/W1 thermostat terminals are jumpered at the
time blower door switch is closed, blower will run for 90 sec
before beginning a heating cycle.
a. Perform component self−test as shown at the bottom
of the SERVICE label, located on the control door.
b. Verify blower is rotating in the correct direction
18. If furnace is operating properly, RELEASE BLOWER
DOOR SWITCH. Remove any jumpers or reconnect any
disconnected thermostat leads. Replace blower door.
19. Turn on gas supply and cycle furnace through one
complete heating cycle. Verify the furnace temperature
rise as shown in Adjustments Section. Adjust
temperature rise as shown in Adjustments Section.
Cleaning Burners and Flame Sensor
The following items must be performed by a qualified service
technician. If the burners develop an accumulation of light dirt
or dust, they may be cleaned by using the following procedure:
NOTE: Use a back-up wrench on the gas valve to prevent the
valve from rotating on the manifold or damaging the mounting
to the burner assembly.
Refer to Figure 10.
1. Disconnect power at external disconnect, fuse or circuit
breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect the gas pipe from gas valve and remove pipe
from the furnace casing.
6. Remove individual wires from terminals on gas valve (All
other models).
7. Disconnect Hot Surface Igniter (HSI) wires from HSI.
8. Disconnect Flame Sensor wire from Flame Sensor.
9. Support the manifold and remove the 4 screws that
secure the manifold assembly to the burner assembly
and set aside. Note the location of the green/yellow wire
and ground terminal.
10. Inspect the orifices in the manifold assembly for
blockages or obstructions. Remove orifice and clean or
replace orifice.
11. Remove the four screws that attach the top plate of the
casing to the furnace.
12. Raise top plate up slightly and prop it up with a small
piece of wood or folded cardboard.
13. Support the burner assembly and remove the screws
that attach the burner assembly to the heat exchanger
cell panel.
14. Remove wires from both rollout switches.
15. Slide one−piece burner out of slots on sides of burner
assembly.
16. Remove the flame sensor from the burner assembly.
17. (Optional) Remove the Hot Surface Igniter (HSI) and
bracket from the burner assembly.
18. Check igniter resistance. Nominal resistance is 40 to 70
ohms at room temperature and is stable over the life of
the igniter.
19. Clean burner with a brush and a vacuum.
20. Clean the flame sensor with fine steel wool (0000 grade).
Do not use sand paper or emery cloth.
To reinstall burner assembly:
1. Install the Hot Surface Igniter (HSI) and bracket in burner
assembly.
2. Install flame sensor on burner.
440 04 4801 0021
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
3. Align the edges of the one-piece burner with the slots in
the burner assembly and slide the burners forward until
they are fully seated in the burner assembly.
4. Align the orifices in the manifold assembly with the
support rings on the end of the burner.
5. Insert the orifices in the support rings of the burners.
NOTE: If manifold does not fit flush against the burner, do not
force the manifold on the burner assembly. The burners are not
fully seated forward in the burner assembly. Remove the
manifold and check burner positioning in the burner assembly
assembly before re-installing the manifold.
Figure 10Burner Assembly
BURNER SUPT. ASSY
BURNER ASSY
FLAME ROLL−OUT SWITCH
FLAME SENSOR
(
BELOW BURNER)
Representative drawing only, some models may vary in appearance.
L11F064
6. Attach the green/yellow wire and ground terminal to one
of the manifold mounting screws.
7. Install the remaining manifold mounting screws.
8. Check the igniter alignment. See Figure 10, Figure 11
and Figure 12.
Figure 11Igniter Position − Top View
1-1/4-in.
2-1/2-in.
A11271
9. Attach the wires to the roll-out switches.
10. Align the burner assembly with the openings in the
primary cell inlet panel and attach the burner assembly to
the cell panel.
11. Connect the wire for the flame sensor.
12. Connect the wire for the Hot Surface Igniter.
NOTE: Use propane-resistant pipe dope to prevent leaks. Do
not use Teflon tape.
13. Install the gas pipe to the gas valve.
Figure 12Igniter Position − Side View
2ïin.
50 mm
3/8ïin.
9.6 mm
3/16ïin.
4.6 mm
+ 1/32
1/10ïin.
ï 1/16ïin.
+0.8
2.5 mm
ï1.5 mm
L12F041
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
14. Check for gas leaks with a commercially available soap
solution made specifically for the detection of leaks.
15. Turn gas on at electric switch on gas valve and at
external shut-off or meter
16. Turn power on at external disconnect, fuse or circuit
breaker.
17. Run the furnace through two complete heating cycles to
check for proper operation
18. Install control door when complete.
Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter
resistance before removal. Refer to Figure 10, Figure 11 andFigure 12.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect igniter wire connection.
4. Check igniter resistance. Igniter resistance is affected by
temperature. Only check resistance when the igniter is at
room temperature.
a. Using an ohm meter, check resistance across both
igniter leads in connector.
b. Cold reading should be between 40 ohms and 70
ohms.
22440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
5. Remove igniter assembly.
a. Using a 1/4−in. driver, remove the two screws
securing the igniter mounting bracket to the burner
assembly. (See Figure 10)
b. Carefully withdraw the igniter and bracket assembly
through the front of the burner assembly without
striking the igniter on surrounding parts.
c. Inspect igniter for signs of damage or failure.
d. If replacement is required, remove the screw that
secures the igniter on igniter bracket and remove the
igniter.
6. To replace igniter and bracket assembly, reverse items
5a through 5d.
7. Reconnect igniter harness to the igniter, dressing the
igniter wires to ensure there is no tension on the igniter
itself. (See Figure 10)
8. Turn on gas and electrical supplies to furnace.
9. Verify igniter operation by initiating control board self−test
feature or by cycling thermostat.
10. Replace control door.
Flushing Collector Box and Drainage System
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Turn off the gas and electrical supplies to the furnace
and install lockout tag before performing any
maintenance or service. Follow the operating
instructions on the label attached to the furnace.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect pressure switch tube from pressure switch
port.
NOTE: Ensure the pressure switch tube disconnected from the
pressure switch is higher than the collector box opening or
water will flow out of tube.
4. Remove the collector box plug from the top port on the
upper corner of the collector box. (See Figure 1)
5. Attach a funnel with a flexible tube to port on the collector
box.
6. Flush inside of collector box with water until discharge
water from condensate trap is clean and runs freely.
7. Repeat steps 4 thru 6 with middle plug on upper corner
of collector box.
8. Remove the pressure switch tube from the collector box.
NOTE: Do NOT blow into tube with tube connected to the
pressure switch.
9. Clean pressure switch port on collect box with a small
wire. Shake any water out of pressure switch tube.
10. Reconnect tube to pressure switch and pressure switch
port.
11. Remove the relief tube from the port on the collector box
and the trap.
12. Clean the relief port on collect box and the trap with a
small wire. Shake any water out of the tube.
13. Reconnect relief tube to trap and collector box ports.
WARNING
Cleaning Condensate Drain and Trap
NOTE: If the condensate trap is removed, a new gasket
between the trap and collector box is required. Verify a
condensate trap gasket is included in the service kit or obtain
one from your local distributor.
1. Disconnect power at external disconnect, fuse or circuit
breaker.
2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect external drain from condensate drain elbow
or drain extension pipe inside the furnace and set aside.
6. Disconnect the condensate trap relief hose from collector
box port and condensate trap.
NOTE: If condensate has a heat pad attached to the trap,
trace the wires for the pad back to the connection point and
disconnect the wires for the heat pad.
7. Remove the screw that secures the condensate trap to
the collector box, remove the trap and set aside.
8. Remove the trap gasket from the collector box if it did not
come off when the trap was removed.
9. Discard the old trap gasket.
10. Rinse condensate trap in warm water until trap is clean.
11. Flush condensate drain lines with warm water.
Remember to check and clean the relief port on the
collector box.
12. Shake trap dry.
13. Clean port on collector box with a small wire.
To re-install Condensate Drain and Trap:
1. Remove adhesive backing from condensate trap gasket
2. Install gasket on collector box
3. Align the condensate trap with the drain opening on the
collector box and secure the trap with the screw
4. Attach the relief hose to the relief port on the condensate
trap and collector box.
5. Secure tubing to prevent any sags or traps in the tubing.
6. Connect condensate drain elbow or drain extension
elbow to the condensate trap
7. Connect the leads of the condensate heat pad (if used)
8. Connect external drain piping to the condensate drain
elbow or drain extension pipe.
9. Turn gas on at electric switch on gas valve and at
external shut-off or meter
10. Turn power on at external disconnect, fuse or circuit
breaker.
11. Run the furnace through two complete heating cycles to
check for proper operation
12. Install control door when complete.
Checking Heat Pad Operation (If Applicable)
In applications where the ambient temperature around the
furnace is 32_F (0_C) or lower, freeze protection measures are
required. If this application is where heat tape has been
applied, check to ensure it will operate when low temperatures
are present.
NOTE: The Heat Pad, when used, should be wrapped around
the condensate drain trap. There is no need to use heat tape
within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of
the tape. Check the following:
1. Check for signs of physical damage to heat tape such as
nicks, cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage
or discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
440 04 4801 0023
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Cleaning Heat Exchangers
The following items must be performed by a qualified service
technician.
Primary Heat Exchangers
If the heat exchangers get an accumulation of light dirt or dust
on the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of
soot and carbon, both the primary and secondary heat
exchangers should be replaced rather than trying to clean them
thoroughly due to their intricate design. A build−up of soot and
carbon indicates that a problem exists which needs to be
corrected, such as improper adjustment of manifold pressure,
insufficient or poor quality combustion air, improper vent
termination, incorrect size or damaged manifold orifice(s),
improper gas, or a restricted heat exchanger (primary or
secondary). Action must be taken to correct the problem.
1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect wires or connectors to flame rollout switch,
gas valve, igniter, and flame sensor.
4. Using backup wrench, disconnect gas supply pipe from
furnace gas control valve.
5. Remove two screws attaching top filler plate and rotate
upwards to gain access to screws attaching burner
assembly to cell panel.
6. Remove screws attaching burner assembly to cell panel.
(See Figure 10)
NOTE: Burner cover, manifold, gas valve, and burner
assembly should be removed as one assembly.
7. Clean heat exchanger openings with a vacuum and a
soft brush. (See Figure 13)
Figure 13Cleaning Heat Exchanger Cell
Figure 14Burner Flame
Burner Flame
Burner
Manifold
A11461
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
Never purge a gas line into a combustion chamber.
Never test for gas leaks with an open flame. Use a
commercially available soap solution made
specifically for the detection of leaks to check all
connections. A fire or explosion may result causing
property damage, personal injury or loss of life.
13. Replace main furnace door.
Secondary Heat Exchangers
The condensing side (inside) of the secondary heat exchanger
CANNOT be serviced or inspected without complete removal of
the heat exchanger assembly. Detailed information on heat
exchanger removal can be obtained from your Distributor.
Winterization
NOTE: After cleaning, inspect the heat exchangers to ensure
they are free of all foreign objects that may restrict flow of
combustion products.
8. Reverse items 6 through 1 for reassembly.
9. Refer to furnace wiring diagram and reconnect wires to
flame rollout switch, gas valve, igniter, and flame sensor.
10. Turn on gas and electrical supplies to furnace.
11. Check furnace operation through two complete heat
operating cycles. Look at burners. Burner flames should
be clear blue, almost transparent. (See Figure 14)
12. Check for gas leaks.
!
CAUTION
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in unit
component or property damage.
If the furnace is installed in an unconditioned space
where the ambient temperatures may be 32_ F (0_ C) or
lower, freeze protection measures must be taken to
prevent property or product damage.
Since the furnace uses a condensing heat exchanger, some
water will accumulate in the unit as a result of the heat transfer
process. Therefore, once it has been operated, it cannot be
turned off and left off for an extended period of time when
temperatures will reach 32_F (0_C) or lower unless winterized.
Follow these procedures to winterize your furnace:
24440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
6. Insert a field supplied funnel into the tube.
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
furnace and other property damage.
Do not use ethylene glycol (automotive antifreeze
coolant or equivalent). Failure of plastic components
may occur.
1. Obtain propylene glycol (RV/swimming pool antifreeze or
equivalent).
2. Turn off gas and electrical supplies to your furnace.
3. Remove furnace control door.
4. Remove the top unused rubber plug from the port on the
collector box opposite the condensate trap. (See
Figure 1)
5. Connect a field supplied 3/8−in. (9.5−mm) ID tube to the
open port on the collector box
7. Pour 1 quart of anti−freeze solution into the funnel/tube.
Antifreeze should run through the collector box, overfill
condensate trap and flow to an open drain.
8. Replace the rubber plug in the port on the collector box.
9. Remove the middle unused rubber plug from the port on
the collector box opposite the condensate trap. See
Figure 1.
10. Repeat Steps 5 through 8.
11. If a condensate pump is used, check with pump
manufacturer to verify pump is safe for use with
antifreeze used. Allow pump to start and pump
anti−freeze to open drain.
12. Replace main door.
13. When furnace is re−started, flush condensate pump with
clear water to check for proper operation before
re−starting furnace.
14. Propylene glycol need not be removed before re−starting
furnace.
440 04 4801 0025
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 15Service Label
340688−2 REV A
440 04 4801 0026
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 16Wiring Diagram
340688−2 REV B
27440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
g
Figure 17Troubleshooting Guide − Flow Chart
NO
Guide
NO
NONO
NO
Close the door switch.
NO
Is circuit breaker closed?
Check for continuity in wire from circuit
breaker to furnace.
Close circuit breaker and go back to
START.
Check room thermostat or
interconnecting cable.
Is 24V present at W/W1, W2, Y1, Y/Y2 or
NO
YES
Is door switch closed?
Is there 115V going to switch?
NO
Replace door switch.
Replace transformer.
- Gas valve relay stuck open.
The control is locked out and will auto-
- Software check error.
reset after 1 hour. Lockout could be due
to any of the following:
- Flame sense circuit failure.
Reset power to clear lockout. Replace
control if code repeats.
Does the control respond to W/W1, W2,
YES
G thermostat terminals on the furn ace
Y1, Y/Y2, and G (24V) thermostat
YES
control?
Disconnect all the thermostat wires from
the furnace control.
YES
signals?
Run system through a low-heat, high-
heat, or cooling cycle to check operation.
Status codes are erased after 72 hours
or can be manually erased by putting
setup switch SW1-1 in the ON position
and jumpering R, W/W1, and Y/Y2
NO
Does the problem repeat when using a
jumper wire?
The thermostat is not compatible with the
furnace control. Either install a ballast
resistor, connect the Com24V thermostat
terminal to the thermostat, or replace the
thermostat.
YES
simultaneously until the heartbeat
flashes.
Replace furnace control.
NO
Troubleshootin
NO
the R thermostat connection, reset
power, and put setup switch SW1-1 in
the ON position. The AMBER LED will
flash the status codes in the order of
occurrence. Record status codes until
heartbeat flashes. After heartbeat
flashes several times the status codes
will repeat. Status codes are erased
after 72 hours or can be manually erased
by putting setup switch SW1-1 in the ON
position and jumpering R, W/W1, and
Y/Y2 simultaneously until the heartbeat
flashes. When done put setup switch
The laststatus code has cleared. To
model plug PL4 is installed. The wiring
schematic shows all valid model plugs.
Is the correct model plug installed?
Replace model plug PL4.
recall a previous status code disconnect
YES
NO
NO
SW1-1 in the OFF position.
Was there a previous status code other
than the heartbeat?
YES
Is there 115V at L1 and L2?
YES
YESYESYES
Is there 24V at SEC-1 and SEC-2?
YES
Is the 24V fuse open?
Replace fuse then disconnect thermostat
leads to isolate short circuit.
Replace furnace control.
Check to make sure that the correct
NO
YES
YES
START
like a heartbeat, or flashing ON and
Is AMBER LED status light ON solid,
alternately flashing bright-dim-bright-dim
OFF?
Is AMBER LED status light ON solid?
heartbeat?
Is AMBER LED status light alternately
flashing bright-dim-bright-dim like a
short flashes and the second number
after the plus (+) sign is the number of
is a single or two digitnumber with the
first number determined b y the numb er of
long flashes?
Go to section below for the status code
that was flashed.
Determine status code. The status code
440 04 4801 0028
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
permanent memory. This will happen if you forget to install the model
and is defaulting to the model selection stored in memory. If status code 2 +
5 flashes continuously it could indicate any of the following:
occurs if the limit or flame rollout switch is
- Model plug PL4 is missing and there is no valid model stored in
open longer than 3 minutes or 10
successive limit trips occurred during high-
heat. Control will auto-reset after 3 hours.
plug PL4 on a service replacement control.
- Thermostat call with SW1-1 ON.
Refer to status code #4.
only flashes 4 times on power-up the control is missing its model plug PL4
2 + 5 INVALID MODEL SELECTION OR SETUP ERROR –If status code 2 + 5
7 LIMIT CIRCUIT LOCKOUT – Lockout
software version V24 or later.
- Thermostat call with SW1-6 ON.
- SW1-1 and SW1-6 both ON.
- Two different furnace mo del s t winne d.
- Service replacement control is incorrect. Need non-modulating board with
Check for 115V between pin 3 and
NEUTRAL-L2 on the control. Was 115V
Unplug igniter harness from control and
repeat component test by turning setup
switch SW1-6 OFF and then back ON.
present for the 15 second period?
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect
voltmeter across gas valve connections.
Does gas valve receive 24V?
Does gas valve open and allow gas to
flow?
Do the main burners ignite?
(115V OR 24V) – Normal operation.
Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-
W/W1 closed) or when (R-W/W1 opens)
- Refer to status code #3.
- Control relay may be defecti v e.
- Stuck closed gas valve relay on control.
NOT auto reset. Turn off power and wait
5 minutes to retry. Che ck for:
- Miswire or short to gas valve wire.
8 GAS HEATING LOCKOUT – Control will
- Gas valve is miswired.
RELAY DID NOT CLOSE OR
REOPENED - Check for:
9 HIGH-HEAT PRESSURE SWITCH OR
transformer phasing.
voltage polarity. If units are twinne d,
check for proper low-voltage (24V)
10 POLARITY – Check for correct line
1 + 2 BLOWER ON AFTER POWER UP –
during the blower on-delay period.
6 + 1 IGNITION LOCKOUT –System failed to
Do the main burners stay on?
Repeat call for heat and check flame
sensor current during trial for ignition
period. Is the DC microamps below 0.5?
hours. Refer to status code #6.
ignite gas and prove flame in 4
attempts. Control will auto-reset after 3
Clean flame sensor with fine steel wool
and recheck current. Nominal current is
4.0 to 6.0 microamps.
Is current near typical value? Repla ce el ect ro de.
Will main burners ignite and stay on?Replace furnace control.
Fixed.
NO
YES
component test. Does the igniter glow
orange/white by the end of the 15 second warm-
the control, reset power, and put setup switch
up period?
SW1-6 in the ON position to start the
To determine whether the problem is in the gas
valve, igniter, or flame sensor the system can be
operated in component test mode. To check the
igniter remove the R thermostat connection from
tubing.
compartment.
- Disconnected or obstructed pressure
- Air leak between vestibule and blower
- Low inlet gas pressure (if LGPS used).
Check for:
2 PRESSURE SWITCH DID NOT OPEN –
- Obstructed pressure tube.
NOT CLOSE OR REOPENED – If opens
during blower on-dela y period, blower will
come on for the selected blower off-delay.
If open longer than 5 minutes inducer
shuts off for 15 minutes before retry.
- Pressure switch stuck closed.
3 LOW-HEAT PRESSURE SWITCH DID
Check for:
29440 04 4801 00
- Restricted vent.
- Proper vent sizing.
Specifications subject to change without notice.
pipe.
- Low inducer voltage (115 VAC)
- Defective Inducer mot or .
- Water in vent piping, possible sagging
- Defective or miswired pressure switches
- Excessive wind.
- Plugged condensate drain.
limit or a flame rollout switch is open or the
4 LIMIT CIRCUIT FAULT – Indicates the
trips. Blower will run for 4 min. or until
open switch remakes whichever is longer.
furnace is operating in high-heat only
mode due to 2 successive low-heat limit
blower shuts off. Flame rollout switch
If open longer than 3 min., code changes
to lockout #7. If open less than 3 min.
status code #4 continues to flash until
adjustment.
requires manual reset. Check for:
- Defective switch or connections.
- Improper low- or high-heat gas input
- Loose blower whe el.
Flame is proved while gas valve is de-
energized. Inducer will run until fault is
cleared. Check for:
- Improper limit switch or no limit gasket.
- Dirty filter or restricted duct system.
- Stuck open or leaky gas valve.
not sensed during the trial for ignition
period, the control will repeat the ignition
5 ABNORMAL FLAME-PROVING SIGNAL
6 IGNITION PROVING FAILURE – If flame is
the following before going to the next step.
sequence 3 more times before lockout #6 +
1 occurs. If flame signal is lost during the
blower on-delay period, blower will come on
- GREEN/YELLOW wire MUST be
for the selected blower off-delay. Check
- Gas valve turned off.
- Manual shut-off valve.
connected to furnace sheet metal.
- Flame sensor must not be grounded.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Sequence of Operation
NOTE: Furnace control must be grounded for proper operation
or else control will lock out. Control is grounded through
green/yellow wire routed to gas valve and burner box screw.
Using the schematic diagram in Figure 16, follow the sequence
of operation through the different modes. Read and follow the
wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat
(W/W1 or W/W1−and−W2), the control will start a 90−second
blower−only ON period two seconds after power is restored, if
the thermostat is still calling for gas heating. The amber LED
light will flash code 1+2 during the 90−second period, after
which the LED will flash a heartbeat (bright−dim), as long as no
faults are detected. After the 90−second period, the furnace will
respond to the thermostat normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot−surface igniter HSI, and gas valve GV.
1. Two−Stage Heating (Adaptive Mode) with
Single−Stage Thermostat
NOTE: The low−heat only switch SW1−2 selects either the
low−heat only operation mode when ON, (see item 2. below) or
the adaptive heating mode when OFF in response to a call for
heat. (See Figure 5) When the W2 thermostat terminal is
energized it will always cause high−heat operation when the
R−to−W circuit is closed, regardless of the setting of the
low−heat only switch. This furnace can operate as a two−stage
furnace with a single−stage thermostat because the furnace
control CPU includes a programmed adaptive sequence of
controlled operation, which selects low−heat or high−heat
operation. This selection is based upon the stored history of the
length of previous gas−heating periods of the single−stage
thermostat.
The furnace will start up in either low− or high−heat. If the
furnace starts up in low−heat, the control CPU determines the
low−heat on−time (from 0 to 16 minutes) which is permitted
before switching to high−heat.
If the power is interrupted, the stored history is erased and the
control CPU will select low−
switch to high−heat, as long as the thermostat continues to call
for heat. Subsequent selection is based on stored history of the
thermostat cycle times.
The wall thermostat “calls for heat”, closing the R−to−W circuit.
The furnace control performs a self−check, verifies the
low−heat and high−heat pressure switch contacts LPS and
HPS are open, and starts the inducer motor IDM in
high−speed.
a. Inducer Prepurge Period
(1.) If the furnace control CPU selects low−heat
operation the inducer motor IDM comes up to
speed, the low−heat pressure switch LPS closes,
and the furnace control CPU begins a
15−second prepurge period. If the low−heat
pressure switch LPS fails to remain closed the
inducer motor IDM will remain running at
high−speed. After the low−heat pressure switch
re−closes the furnace control CPU will begin a
15−second prepurge period, and continue to run
the inducer motor IDM at high−speed.
(2.) If the furnace control CPU selects high−heat
operation, the inducer motor IDM remains
running at high−speed, and the high−heat
pressure switch relay HPSR is de−energized to
close the NC contact. When sufficient pressure is
available the high−heat pressure switch HPS
closes, and the high−heat gas valve solenoid
440 04 4801 0030
heat for up to 16 minutes and then
Specifications subject to change without notice.
GV−HI is energized. The furnace control CPU
begins a 15−second prepurge period after the
low−heat pressure switch LPS closes. If the
high−heat pressure switch HPS fails to close and
the low−heat pressure switch LPS closes, the
furnace will operate at low−heat gas flow rate
until the high−heat pressure switch closes for a
maximum of 2 minutes after ignition.
b. Igniter Warm−Up−At the end of the prepurge period,
the Hot−Surface Igniter HSI is energized for a
second igniter warm−up period.
17−
c. Trial−For−Ignition Sequence−When the igniter
warm−up period is completed the main gas valve
relay contact GVR closes to energize the gas valve
solenoid GV−M. The gas valve solenoid GV−M
permits gas flow to the burners where it is ignited by
the HSI. Five seconds after the GVR closes, a
2−second flame proving period begins. The HSI
igniter will remain energized until the flame is sensed
or until the 2−second flame proving period begins. If
the furnace control CPU selects high−heat operation,
the high−heat gas valve solenoid GV−HI is also
energized.
d. Flame−Proving− When the burner flame is proved
at the flame−proving sensor electrode FSE, the
inducer motor IDM switches to low−speed unless the
furnace is operating in high−heat, and the furnace
control CPU begins the blower−ON delay period and
continues to hold the gas valve GV−M open. If the
burner flame is not proved within two seconds, the
control CPU will close the gas valve GV−M, and the
control CPU will repeat the ignition sequence for up
to three more Trials−For−Ignition before going to
Ignition−Lockout. Lockout will be reset automatically
after three hours, or by momentarily interrupting 115
vac power to the furnace, or by interrupting 24 vac
power at SEC1 or SEC2 to the furnace control CPU
(not at W/W1, G, R, etc.). If flame is proved when
flame should not be present, the furnace control CPU
will lock out of Gas−Heating mode and operate the
inducer motor IDM on high speed until flame is no
longer proved.
e. Blower−On delay− If the burner flame is proven the
blower−ON delays for low−heat and high−heat are as
follows:
Low−heat − 45 seconds after the gas valve GV−M is
opened the blower motor BLWM is turned ON at
low−heat airflow.
High−heat
opened the BLWM is turned ON at high−heat airflow.
Simultaneously, the humidifier terminal HUM and
electronic air cleaner terminal EAC−1 are energized
and remain energized throughout the heating cycle.
f. Switching from Low− to High−Heat− If the furnace
control CPU switches from low−heat to high−heat, the
furnace control CPU will switch the inducer motor
IDM speed from low to high. The high−heat pressure
switch relay HPSR is de−energized to close the NC
contact. When sufficient pressure is available the
high−heat pressure switch HPS closes, and the
high−heat gas valve solenoid GV−HI is energized.
The blower motor BLWM will transition to high−heat
airflow five seconds after the furnace control CPU
switches from low−heat to high−heat.
g. Switching from High− to Low−Heat−The furnace
control CPU will not switch from high−heat to
low−heat while the thermostat R−to−W circuit is
closed when using a single−stage thermostat.
h. Blower−Off Delay−When the thermostat is satisfied,
the R to W circuit is opened, de−energizing the gas
− 25 seconds after the gas valve GV−M is
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
valve GV−M, stopping gas flow to the burners, and
de−energizing the humidifier terminal HUM. The
inducer motor IDM will remain energized for a
15−second post−purge period. The blower motor
BLWM and air cleaner terminal EAC−1 will remain
energized at low−heat airflow or transition to low−heat
airflow for 90, 120, 150, or 180 seconds (depending
on selection at blower−OFF delay switches). The
furnace control CPU is factory−set for a 120−second
blower−OFF delay.
2. Two−Stage Thermostat and Two−Stage Heating
See Figure 18−Figure 21 for thermostat connections.
NOTE: In this mode the low−heat only switch SW1−2 must be
ON to select the low−heat only operation mode in response to
closing the thermostat R−to−W1 circuit. Closing the thermostat
R−to−W1−and−W2 circuits always causes high−heat operation,
regardless of the setting of the low−heat only switch.
The wall thermostat “calls for heat”, closing the R−to−W1 circuit
for low−heat or closing the R−to−W1−and−W2 circuits for
high−heat. The furnace control performs a self−check, verifies
the low−heat and high−heat pressure switch contacts LPS and
HPS are open, and starts the inducer motor IDM in
high−speed.
The start up and shut down functions and delays described in
item 1. above apply to the 2−stage heating mode as well,
except for switching from low− to high−Heat and vice versa.
a. Switching from Low− to High−Heat− If the
thermostat R−to−W1 circuit is closed and the
R−to−W2 circuit closes, the furnace control CPU will
switch the inducer motor IDM speed from low to high.
The high−heat pressure switch relay HPSR is
de−energized to close the NC contact. When
sufficient pressure is available the high−heat pressure
switch HPS closes, and the high−heat gas valve
solenoid GV−HI is energized. The blower motor
BLWM will transition to high−heat airflow five seconds
after the R−to−W2 circuit closes.
b. Switching from High− to Low−Heat−If the
thermostat R−to− W2 circuit opens, and the R−to−W1
circuit remains closed, the furnace control CPU will
switch the inducer motor IDM speed from high to low.
The high−heat pressure switch relay HPSR is
energized to open the NC contact and de−energize
the high−heat gas valve solenoid GV−HI. When the
inducer motor IDM reduces pressure sufficiently, the
high−heat pressure switch HPS will open. The gas
valve solenoid GV−M will remain energized as long
as the low−heat pressure switch LPS remains closed.
The blower motor BLWM will transition to low−heat
airflow five seconds after the R−to−W2 circuit opens.
3. Cooling mode
The thermostat “calls for cooling”.
Single−Speed Cooling−
a.
See Figure 18 and Figure 20 for thermostat
connections
The thermostat closes the R−to−G−and−Y circuits.
The R−to− Y circuit starts the outdoor unit, and the
R−to−G−and−Y/Y2 circuits start the furnace blower
motor BLWM on cooling airflow. Cooling airflow is
based on the A/C selection shown in Table 5. The
electronic air cleaner terminal EAC−1 is energized
with 115 vac when the blower motor BLWM is
operating.
When the thermostat is satisfied, the R−to−G−and−Y
circuits are opened. The outdoor unit will stop, and
the furnace blower motor BLWM will continue
operating at cooling airflow for an additional 90
seconds. Jumper Y/Y2 to DHUM to reduce the
cooling off−delay to 5 seconds. (See Figure 4)
b. Two−Stage Thermostat and Two−Speed Cooling
See Figure 19 and Figure 21 for thermostat
connections
The thermostat closes the R−to−G−and−Y1 circuits for
low−cooling or closes the R−to−G−and−Y1−and−Y2 circuits for
high−cooling. The R−to−Y1 circuit starts the outdoor unit on
low−cooling speed, and the R−
to−G−and−Y1 circuit starts the
furnace blower motor BLWM at low−cooling airflow which is the
CF (continuous fan) selection as shown in Figure 5. The
R−to−Y1−and−Y2 circuits start the outdoor unit on high−cooling
speed, and the R−to− G−and−Y/Y2 circuits start the furnace
blower motor BLWM at high−cooling airflow. High−cooling
airflow is based on the A/C (air conditioning) selection shown in
Figure 5.
The electronic air cleaner terminal EAC−1 is energized with 115
vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R−to−G−and−Y1 or R−to−
G−and−Y1−and−Y2 circuits are opened. The outdoor unit
stops, and the furnace blower BLWM and electronic air cleaner
terminal EAC−1 will remain energized for an additional 90
seconds. Jumper Y1 to DHUM to reduce the cooling off−delay
to 5 seconds. (See Figure 16)
4. Dehumidfy Mode
See Figure 18−Figure 24 for thermostat connections.
The H output on the humidify sensing thermostat should
be connected to the furnace control thermostat terminal
DHUM. When there is a dehumidify demand, the DHUM
input is activated, which means 24 vac signal is removed
from the DHUM input terminal. In other words, the DHUM
input logic is reversed. The DHUM input is turned ON
when no dehumidify demand exists.
Activation/Deactivation
Once 24 vac is detected by the furnace control on the
DHUM input, the furnace control operates in dehumidify
mode. If the DHUM input is low for more than 48 hours,
the furnace control reverts back to non−dehumidify
mode.
The cooling operation described in Item 3, Cooling
mode. above also applies to operation with a humidity
sensing thermostat. The exceptions are listed below:
a. Low Cooling−When the R−to−G−and−Y1 circuit is
closed and there is a demand for dehumidification,
the low cooling airflow demand is reduced by 10
percent.
b. High
−Cooling−When the R−to−G−and−Y/Y2 circuit is
closed and there is a demand for dehumidification,
the high cooling airflow demand is reduced by 10
percent.
c. Cooling off−delay−When the “call for cooling” is
satisfied and there is a demand for dehumidification,
the cooling blower−off delay is decreased from 90
seconds to 5 seconds.
5. Continuous Blower Mode
When the R−to−G circuit is closed by the thermostat, the
blower motor BLWM will operate at continuous blower
airflow. Continuous blower airflow selection is initially
based on the CF (continuous fan) selection shown in
Figure 5. Factory default is shown in Figure 5. Terminal
EAC−1 is energized as long as the blower motor BLWM
is energized.
During the call for heat, the furnace control CPU will keep
the blower motor BLWM to continuous blower airflow.
The blower motor BLWM will remain ON until the main
burners ignite then shut OFF and remain OFF for the
blower−ON delay (45 seconds in low−heat, and 25
seconds in high−heat), allowing the furnace heat
exchangers to heat up more quickly, then restarts at the
end of the blower−ON delay period at low−heat or
high−heat airflow, respectively.
31440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
The blower motor BLWM will revert to continuous−blower
airflow after the heating cycle is completed. In high−heat,
the furnace control CPU will drop the blower motor
BLWM to low−heat airflow during the selected
blower−OFF delay period before transitioning to
continuous−blower airflow.
When the thermostat “calls for low−cooling”, the blower
motor BLWM will switch to operate at low−cooling airflow.
When the thermostat is satisfied, the blower motor
BLWM will operate an additional 90 seconds at
low−cooling airflow before transitioning back to
continuous−blower airflow.
When the thermostat “calls for high−cooling”, the blower
motor BLWM will operate at high cooling airflow. When
the thermostat is satisfied, the blower motor BLWM will
operate an additional 90 seconds at high−cooling airflow
before transitioning back to continuous−blower airflow.
When the R−to−G circuit is opened, the blower motor
BLWM will continue operating for an additional 5
seconds, if no other function requires blower motor
BLWM operation.
6. Heat pump
See Figure 20 and Figure 21 for thermostat
connections. When installed with a heat pump, the
furnace control automatically changes the timing
sequence to avoid long blower off times during demand
defrost cycles. Whenever W/W1 is energized along with
Y1 or Y/Y2, the furnace control CPU will transition to or
bring on the blower motor BLWM at cooling airflow,
low−heat airflow, or whichever is lowest. The blower
motor BLWM will remain on until the main burners ignite
then shut OFF and remain OFF for 25 seconds before
coming back on at heating airflow. When the W/W1 input
signal disappears, the furnace control begins a normal
inducer post−purge period while changing the blower
airflow. If Y/Y2 input is still energized the furnace control
CPU will transition the blower motor BLWM airflow to
cooling airflow. If Y/Y2 input signal disappears and the
Y1 input is still energized the furnace control CPU will
transition the blower motor BLWM to low−cooling airflow.
If both the Y1 and Y/Y2 signals disappear at the same
time, the blower motor BLWM will remain on at low−heat
airflow for the selected blower−OFF delay period. At the
end of the blower− OFF delay, the blower motor BLWM
will shut OFF unless G is still energized, in which case
the blower motor BLWM will operate at continuous
blower airflow.
Component Self Test
Refer to page 18 for instructions.
Figure 18
NOTE9
Figure 19
NOTE9
Variable Speed Furnace with Single
Stage Air Conditioner
Variable Speed Furnace with
Two−Stage Air Conditioner
L09F027
440 04 4801 0032
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 20
NOTE9
Variable Speed Furnace with Single
Stage Heat Pump (Dual Fuel)
Figure 22
Figure 23
Variable Speed Furnace and
Humidifier Only
L09F029
AC with Variable Speed Furnace,
Humidifier, and Dehumidification
Figure 21
NOTE9
L09F026
Variable Speed Furnace with
Two−Stage Heat Pump (Dual Fuel)
L09F029
L09F028
33440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
Figure 24
HP with Variable Speed Furnace,
Humidifier, and Dehumidification
L09F030
NOTES FOR FIGURES Figure 18 − Figure 24
1. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.
2. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.
3. Refer to ICP thermostat Installation Instructions for additional information and setup procedure.
4. When using a Humidity Sensing Thermostat, set DEHUMIDIFY OPTIONS to H DE−ENRGZD FOR DEHUM.
5. Optional connection. If wire is connected SW1−2 on VS furnace control should be set in ON position to allow ICP Thermostat
to control the furnace staging.
6. HUM connection is 24 VAC and is energized when the blower turns on during a call for heat.
7. When connecting 115 VAC to humidifier use a separate 115 VAC supply.
8. When using a humidifier on a HP installation connect humidifier to hot water.
9. Thermostat signals may vary. Consult thermostat installation instructions for more information.
440 04 4801 0034
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
PARTS REPLACEMENT INFORMATION GUIDE
Casing Group
Control door
Blower door
Top filler plate
Bottom filler plate
Door Knob Assembly
Electrical Group
Control box
Junction box
Limit switch(es)
Circuit board
Door switch
Transformer
3−Amp fuse
Flame Rollout switch
Main Wiring harness
Blower Motor harness (when used)
Filter Group
Filter(s)
Blower Group
Cut−off Plate
Blower housing
Blower motor
Blower wheel
Capacitor (when used)
Capacitor strap (when used)
Power choke (where used)
Gas Control Group
Manifold
Burner
Orifice
Flame sensor
Hot surface igniter
Gas valve
Pressure switch(es)
Inducer assembly
Inducer
Inducer motor
Motor Module (when used)
Inducer motor capacitor (when used)
Collector box
Condensate trap
Condensate trap elbow
Gaskets
WARNING
!
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, personal injury, death or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire,
electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service
agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only
factory-authorized and listed kits or accessories when modifying this product.
Have available the product/model number and the serial number located on the unit rating plate to ensure correct replacement parts.
TO OBTAIN INFORMATION ON PARTS: Consult your installing dealer or the classified section of your local telephone directory
under the “Heating Equipment“ or “Air Conditioning Contractors and Systems” headings for dealer listing by brand name.
International Comfort Products
Consumer Relations Department
P.O. Box 128
Lewisburg, TN 37091, USA
931−270−4100
35440 04 4801 00
Specifications subject to change without notice.
SERVICE AND TECHNICAL SUPPORT MANUALGas Furnace: (F/G)9MVE
PRODUCT NOMENCLATURE
DIGIT POSITION
G = Mainline Look 1
F = Mainline Look 2
N = Entry
9 = 90% − 100% EFFICIENCY
M = Multiposition
H = Horizontal
U = Upflow
D = Downflow
A = Modulating Variable Speed ECM
V = Variable Speed
X = ECM
S = Single−stage
T = Two−stage
B = Base AFUE Efficiency
E = Extra AFUE Efficiency
C = Communicating
D = Dual Certified 2−pipe or 1−pipe
R = 2−pipe only
S = Single−stage
T = Two−stage
N = Standard
L = Low Nox
040 = 40,000 BTU/hr
060 = 60,000 BTU/hr
080 = 80,000 BTU/hr
100 = 100,000 BTU/hr
120 = 120,000 BTU/hr
14 = 14−3/16”
17 = 17−1/2”
21 = 21”
24 = 24−1/2”
10 = 1000 CFM (max)
14 = 1400 CFM (max)
16 = 1600 CFM (max)
20 = 2000 CFM (max)
22 = 2200 CFM (max)
SALES (MAJOR) REVISION DIGIT
ENGINEERING (MINOR) REVISION DIGIT
123456, 7, 89, 1011, 121314
G
9MVE0601714A2
FEATURE
FEATURE
FEATURE
INPUT HEAT
CABINET WIDTH
COOLING AIRFLOW
440 04 4801 0036
Specifications subject to change without notice.
Copyright 2014 International Comfort Products
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.