The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument.
Failure to compl
manufacture, and intended use of the instrument. Hewlett-Packard Compan
with these requirements.
compl
BEFORE APPLYING POWER.
Verif
that the product is set to match the available line voltage
and that the correct fuse is installed.
GROUND THE INSTRUMENT.
This product is a Safet
tective earth terminal). To minimize shock hazard, the instrument
chassis and cabinet must be connected to an electrical
The instrument must be connected to the ac power suppl
throu
h a three-conductor power cable, with the third wire firml
connected to an electrical ground(safety ground) at the power
outlet. An
disconnection of the protective earth terminal will cause a potential shock hazard that could result in personal injur
ment is to be ener
volta
e reduction, be certain that the autotransformer common
terminal is connected to the neutral(earthed pole) of the ac power
lines (suppl
DO NOT OPERATE IN AN EXPLOSIVE ATMOSPHERE.
Do not operate the instrument in the presence of flammable
ases or fumes.
KEEP AWAY FROM LIVE CIRCUITS.
Operatin
nent replacement and internal adjustments must be made b
qualified service personnel. Do not replace components with
power cable connected. Under certain conditions, dan
a
es may exist even with the power cable removed. To avoid injuries, alwa
external volta
DO NOT SERVICE OR ADJUST ALONE.
Do not attempt internal service or adjustment unless another person, capable of renderin
with these precautions or with specific warnings elsewhere in this manual violates safety standards of design,
assumes no liability for the customer's failure to
SAFETY SYMBOLS
Instruction manual s
be marked with this s
sar
for the user to refer to the instruction
manual.
Indicate earth(
The WARNING si
calls attention to a procedure, practice,
or the like, which, if not correctl
adhered to, could result inpersonal injur
not proceed be
the indicated conditions are full
and met.
The CAUTION si
attention to an operatin
like, which, if not correctl
adhered to, could result in dama
destruction of part or all of the product. Do
not proceed be
indicated conditions are full
met.
The NOTE si
mation. It calls attention to a procedure, practice, condition or the like, which is essential to
hlight.
hi
er of introducing additional hazards, do not
round) terminal.
Class I instrument (provided with a pro-
round.
mains
interruption of the protective(grounding) conductor or
. If the instru-
ized via an external autotransformer for
mains).
personnel must not remove instrument covers. Compo-
erous volt-
s disconnect power, discharge circuits and remove
e sources before touching components.
first aid and resuscitation, is present.
!
or
DO NOT SUBSTITUTE PARTS OR MODIFY INSTRUMENT.
Because of the dan
install substitute parts or perform an
to the instrument. Return the instrument to a Hewlett-Packard
Sales and Service Office for service and repair to ensure that
safet
features are maintained.
mbol; the product will
mbol when it is neces-
n denotes a hazard. It
performed or
ond a WARNING sign until
n denotes a hazard. It calls
procedure, or the
performed or
ond CAUTION sign until the
understood and
n denotes important infor-
unauthorized modification
. Do
understood
e to or
Instruments that appear damaged or defective should be made inoperative and secured against unintended
operation until the
This manual describes all models in the HP E361xA 60W
Bench Power Suppl
information in this manual applies to all models.
SAFETY REQUIREMENTS
This product is a Safety Class I instrument, which means
that it is provided with a protective earth
This terminal must be connected to an ac source that has a
3-wire
round receptacle. Review the instrument rear panel
and this manual for safet
operatin
at the be
safet
the appropriate places in this manual.
This power suppl
safety and EMC(Electromagnetic Compatibility) requirements:
IEC 348: Safet
Apparatus
IEC 1010-1/EN 61010: Safet
Equipment for Measurement, Control, and Laborator
CSA C22.2 No.231: Safet
Electronic Measurin
UL 1244: Electrical and Electronic Measurin
Equipment.
EMC Directive 89/336/EEC: Council Directive entitled
Approximation of the Laws of the Member States relatin
Electroma
EN 55011(1991) Group 1, Class B/CISPR 11: Limits and
Methods of Radio Interference Characteristics of
Industrial, Scientific, and Medical(ISM) Radio-Frequenc
information. Specific safety information is located at
netic Compatibilit
INSTRUMENT AND MANUAL IDENTIFICA TION
A serial number identifies your power supply. The serial
number encodes the countr
latest si
number. As an illustration, a serial number be
KR306 denotes a power suppl
4=1994, etc), 6th week manufacture in Korea(KR). The
remainin
number assi
nificant design change, and a unique sequential
digits of the serial number are a unique, five-digit
family and unless stated otherwise, the
round terminal.
markings and instructions before
is designed to comply with the followin
Requirements for Electronic Measuring
Requirements for Electrical
Use
Requirements for Electrical and
and Test Equipment
and Testing
to
e Requirements
netic Field
of manufacture, the date of the
inning with
built in 1993 (3=1 993,
ned sequentially.
OPTIONS
Options OE3 and OE9 determine which line voltage is
selected at the factor
Vac ± 10%. For information about chan
The accessory listed below may be ordered from your local
Hewlett-Packard Sales Office either with the power suppl
separatel
address.)
HP Part No.Description
5063-9240Rack Kit for mountin
The rack mount kit is needed for rack mountin
in the HP E361xA power suppl
molded feet.
. (Refer to the list at the rear of the manual for
one or two 3 1/2" high
suppl
in a standard 19" rack
of all models
because these supplies have
or
DESCRIPTION
This power supply is suitable for either bench or rack
mounted operation. It is a compact, well-re
e/Constant Current supply that will furnish full rated
Volta
output volta
continuousl
put can be adjusted both locall
remotel
(See para
The models in this famil
with volta
in Table 1.
The front panel VOLTAGE control can be used to establish
the volta
rent source and the CURRENT control can be used to establish the output current limit when the suppl
constant volta
over from constant volta
vice versa if the output current or volta
set limits.
The front panel includes an autoran
ran
Two 3 1/2 di
the output volta
s for each model are shown in the Specifications and
in
Operatin
e at the maximum rated output current or can be
adjusted throughout the output range. The out-
from the front panel and
changing the settings of the rear panel switches
raph "REMOTE OPERATING MODES", page 1-9).
offer up to 60 watts of output power,
e up to 60 volts and current up to 6 amps as shown
e limit when the supply is used as a constant cur-
e source. The supply will automatically cross
e to constant current operation and
e) digital voltmeter and a single-range digital ammeter.
it voltage and current displays accurately show
e and current respectively. The output rat-
Characteristics Table.
ulated, Constant
is used as a
e exceeds these pre-
(E3614A single-
If the serial number on
on the title pa
CHANGES sheet is supplied with this manual to explain
the difference between
described b
tain information for correctin
this manual. The change sheet may also con-
our supply differs from that shown
e of this manual, a yellow MANUAL
our instrument and the instrument
errors in the manual.
The OVP/CC SET switch is used to check the OVP trip volta
e and current control set value. When pressing this switch,
the volta
rent displa
1-4
e display indicates the OVP trip voltage and the cur-
indicates the current control set value.
The power suppl
nals. Either the positive or ne
has both front and rear output termi-
ative output terminal ma
Page 5
be
g
g
g
g
g
g
y
y
g
g
g
g
g
g
g
g
y
g
g
g
g
g
g
g
g
rounded or the power supply can be operated float-
in
at up to a maximum of 240 Volts off ground. Total out-
put volta
LINE FUSE
Line Volta
100/115 Vac2.0 AT2110-0702
230 Vac1.0 AT2110-0457
e to ground must not exceed 240 Vdc.
eFuseHP Part No.
Table 1. Specifications and Operating Characteristics
SPECIFICATIONS
Detailed specifications for the power supply are given in Table
1. All specifications are at front terminals with a resistive load,
and local sensin
teristics provide useful, but non-warranted information in the
form of the nominal performance.
unless otherwise stated. Operating charac-
*AC INPUT
An internal switch permits operation from 100, 115, or 230 Vac
lines.
100 Vac ± 10%, 47-63 Hz, 163 VA, 125 W
115 Vac ± 10%, 47-63 Hz, 163 VA, 125 W
230 Vac ± 10%, 47-63 Hz, 163 VA, 125 W
DC OUTPUT
Voltage and current can be programmed via front panel control or
remote analo
E3614A:
E3615A:
E3616A:
E3617A:
control over the following ranges;
0 - 8 V, 0 - 6 A
0 - 20 V, 0 - 3 A
0 - 35 V, 0 - 1.7 A
0 - 60 V, 0 - 1 A
*OUTPUT TERMINALS
The output terminals are provided on the front and rear panel.
are isolated from the chassis and either the positive or neg-
The
ative terminal ma
be connected to the ground terminal.
LOAD REGULATION
Constant Voltage - Less than 0.01% plus 2 mV for a full load to no
load chan
Constant Current
maximum chan
e in output current.
- Less than 0.01% plus 250 µA for a zero to
e in output voltage.
LINE REGULATION
Constant Voltage - Less than 0.01% plus 2 mV for any line volt-
e change within the input rating.
a
Constant Current
e change within the input rating.
a
- Less than 0.01% plus 250 µA for any line volt-
PARD (Ripple and Noise)
Constant Voltage: Less than 200 µV rms and 1 mV p-p
Constant Current:
(20 Hz-20 MHz).
E3614A: Less than 5 mA rms
E3615A:
E3616A:
E3617A:
Less than 2 mA rms
Less than 500 µA rms
Less than 500 µA rms
OPERATING TEMPERATURE RANGE
0 to 40oC for full rated output. Maximum current is derated 1%
ree C at 40oC-55oC.
per de
*TEMPERATURE COEFFICIENT
Maximum change in output per oC after a 30-minute warm-up.
Constant Volta
Constant Current:
e: Less than 0.02% plus 500 µV.
E3614A: Less than 0.02% plus 3 mA
E3615A:
E3616A:
E3617A:
Less than 0.02% plus 1.5 mA
Less than 0.02% plus 1 mA
Less than 0.02% plus 0.5 mA
*STABILITY (OUTPUT DRIFT)
Maximum change in output for an 8 hours following a 30 minute
warm-up under constant line, load and ambient temperature.
Constant Volta
Constant Current:
e: Less than 0.1% plus 5 mV
Less than 0.1% plus 10 mA
LOAD TRANSIENT RESPONSE TIME
Less than 50 µsec for output recovery to within 15 mV following a
chan
e in output current from full load to half load, or vice versa.
METER ACCURACY:
B±(0.5% of output + 2 counts)Bat
o
C
± 5
o
C
25
METER (PROGRAMMING) RESOLUTION
Voltage: E3614A 10 mV
Current:
E3615A
E3616A
E3617A
E3614A 10 mA
E3615A
E3616A
E3617A
A continuously acting constant current circuit protects the power
suppl
for all overloads including a direct short placed across the
terminals in constant volta
cuit limits the output volta
ation.
e operation. The constant voltage cir-
e in the constant current mode of oper-
*OVERVOLTAGE PROTECTION
Trip voltage adjustable via front panel control.
Range:2.5-10 V2.5-23 V2.5-39 V5-65 V
Mar
E3614A
in: Minimum setting above output voltage to avoid
false trippin
E3615AE3616AE3617A
: 4% of output + 2 V for all models
*REMOTE ANALOG VOLTAGE PROGRAMMING (25 ± 5oC)
Remotely varied voltage from 0 to 10 V provides zero to maximum rated output volta
Volta
e: Linearity 0.5% Current: Linearity 0.5%
The pro
to ±40 V.
ramming inputs are protected against input voltages up
e or current.
REMOTE SENSING
Meets load-regulation specification when correcting for load-lead
drops of up to 0.5 V per lead with sense wire resistance of less
than 0.5 ohms per sense lead and lead len
meters.
ths of less than 5
1-5
Page 6
Table 1. Specifications and Operating Characteristics (Cont’d)
y
g
g
g
g
y
g
g
g
y
y
y
g
g
g
y
g
g
g
y, y
g
y
y
g
y
g
g
g
y
y
*REMOTE PROGRAMMING SPEED
Maximum time required for output voltage to change from initial
value to within a tolerance band (0.1%) of the newl
value followin
input voltage.
Before shipment, this instrument was inspected and found to be
free of mechanical and electrical defects. As soon as the instrument is unpacked, inspect for an
occurred in transit. Save all packin
is completed. If dama
carrier. The Hewlett-Packard Sales and Service office should be
notified.
e is found, a claim should be filed with the
Mechanical Check
This check should confirm that there are no broken knobs or connectors, that the cabinet and panel surfaces are free of dents and
scratches, and that the meter is not scratched or cracked.
damage that may have
materials until the inspection
DC ISOLATION
± 240 Vdc maximum between either output terminal and earth
round including the output voltage.
*COOLING:
*WEIGHT:
* Operatin
instructions.
Convection cooling is employed.
12.1 lbs/5.5 Kg net, 14.9 lbs/6.75 Kg shipping.
Characteristics
Electrical Check
The instrument should be checked against its electrical specifi-
cations. Para
tains a brief checkout procedure and "PERFORMANCE TEST" in
section SERVICE INFORMATION includes an instrument performance check to verif
raph "TURN-ON CHECKOUT PROCEDURE" con-
proper instrument operation.
INST ALLATION DATA
The instrument is shipped ready for bench operation. It is necessar
only to connect the instrument to a source of power and it is
for operation.
read
Location and Coolin
This instrument is air cooled. Sufficient space should be allowed so
that a free flow of coolin
instrument when it is in operation. It should be used in an area where
the ambient temperature does not exceed 40
derated 1% per
o
C at 40oC-55oC.
Outline Diagram
Figure 1 is a outline diagram showing the dimensions of the
instrument.
Rack Mountin
This instrument may be rack mounted in a standard 19-inch rack
panel either b
ACCESSORY, pa
ries. Each rack-mountin
itself or alongside a similar unit. Please see
air can reach the sides and rear of the
o
C. Maximum current is
e 1-4, for available rack mounting accesso-
kit includes complete installation
Figure 1. Outline Diagram
INPUT POWER REQUIREMENTS
This power supply may be operated from nominal 100, 115, or
230 Vac 47-63 Hertz power source. A label on the rear panel
shows the nominal input volta
necessar
volta
ou can convert the supply to another nominal input
e by following the instructions below
Line Voltage Option Conversion
Line voltage conversion is accomplished by adjusting two components: the line select switch and the rear panel fuse F1. To convert the suppl
as follows:
a. Disconnect power cord.
b. Turn off the suppl
cover upwards after takin
b
inserting a flat-blade screwdriver into the gap on the lower
rear portion of the cover.
c. Set two sections of the line volta
board for the desired line volta
d. Check the ratin
holder and replace with the correct fuse if necessar
and 115 V operation, use a normal blow 2 A fuse and for 230
V use a time dela
1-6
from one line voltage option to another, proceed
and remove the top cover by lifting the
of the fuse F1 installed in the rear panel fuse
1 A fuse.
e set for the unit at the factory. If
it off from both sides of the chassis
e selector switch on the PC
e (see Figure 2).
. For 100
Page 7
e. Replace the cover and mark the suppl
y
g
g
g
gg
y
y
y
y
y
g
g
g
y
g
g
g
j
g
g
g
g
y
g
g
y
g
g
g
y
g
g
y
y
g
g
y
g
y
g
y
y
y
g
g
y
g
y
g
g
g
y
label indicatin
the correct line voltage and fuse that is in
clearly with a tag or
use.
Figure 2. Line Voltage Selector (set for 115 Vac)
Power Cord
To protect operating personnel, the instrument should be
rounded. This instrument is equipped with a three conductor
power cord. The third conductor is the
when the power cord is plu
the suppl
The power suppl
outlet used at
included, contact
is grounded.
was shipped with a power cord for the type of
our location. If the appropriate cord was not
our nearest HP Sales Office to obtain the cor-
ed into an appropriate receptacle,
rect cord.
round conductor and
4. DISPLAY OVP/CC SET Switch: Pressin
the VOLTS displa
shutdown (trip volta
current control set value. Settin
s or remote voltage programmed settings.
5.
settin
OVP Ad
ust Screwdriver Control:
to show voltage setting for overvoltage
e) and the AMPS display to show the
values are either front panel
PLAY OVP/CC SET switch, rotatin
with a small, flat-blade screwdriver increases the settin
overvolta
6. VOLTS Displa
OVP shutdown settin
AMPS Displa
7.
output-current settin
8. CV LED Indicator: Output volta
This means the power suppl
volta
e shutdown.
e mode.
: Di
ital display of actual output voltage, or
.
:
Di
ital display of actual output current, or
.
e is regulated when lighted.
is operating in the constant
9. CC LED Indicator: Output current is re
This means the power suppl
is operating in the constant cur-
this switch causes
While pressin
the DIS-
the control clock-wise
ulated when lighted.
for
rent mode.
10. OVP LED Indicator: Output is shutdown b
of an overvolta
volta
e and turning the power off, then on, resets the power
.
suppl
e when lighted. Removing the cause of over-
the occurrence
TURN-ON CHECKOUT PROCEDURE
The following checkout procedure describes the use of the front
panel controls and indicators illustrated in Fi
that the suppl
is operational:
ure 3 and ensures
OPERATING INSTRUCTIONS
INTRODUCTION
This section explains the operating controls and indicators and
provides information on man
instrument. The front panel controls and indicators are illustrated
in Fi
ure 3.
Figure 3. Front-Panel Controls and Indicators
LINE Switch:
1.
VOLTAGE Control:
2.
a
e.
CURRENT Control:
3.
Pressing this switch turns the supply on, or off.
rent.
operating modes possible with your
Clockwise rotation increases output volt-
Clockwise rotation increases output cur-
MASTER
M/S 1 M/S 2
SLAVE
LOCAL
CVCCSENSE
REMOTE
_
+
OUT+S-S
+
CVCC
+
__
VREF
A1 A2 A3 A4 A5
Figure 4. Switch Settings of Rear-Panel Control for Turn-
On Checkout
a. Disconnect power cord.
b. Check that the rear-panel switch settin
s are as shown in Fig-
ure 4.
c. Check that the rear panel label indicates that the suppl
to match
our input line voltage (If not, refer to "Line Voltage
is set
Option Conversion".).
d. Check that the fuse on the rear panel is correct for
volta
e.
our line
e. Connect the power cord and push the LINE switch to ON.
f. While pressin
OVP/CC SET switch, verify that the OVP
shutdown is set above 8.0, 20.0, 35.0, or 60.0 Vdc for
E3614A, E3615A, E3616A, or E3617A respectivel
. If not,
turn up OVP Adjust with a small flat-blade screwdriver.
. Turn VOLTAGE control fully counter clockwise to ensure that
the output of VOLTS displa
clockwise to ensure that output volta
mum output volta
h. While pressin
trol full
counter clockwise and then fully clockwise to ensure
e.
OVP/CC SET switch, turn the CURRENT con-
decreases to 0 Vdc, then fully
e increases to the maxi-
1-7
Page 8
that the current limit value can be set from zero to maximum
g
y
g
g
g
g
g
g
y
y
g
g
y
g
y
y
y
y
g
g
y
g
g
g
g
y
g
y
g
y
y
g
g
y
y
g
g
j
g
y
y
g
g
g
g
y by
g
g
y
y
y
g
y
g
g
y
g
y g
y
y
y
g
g
g
g
g
g
rated value.
OPERATING MODES
The setting of the rear panel switch determines the operatin
modes of the power supply. The local operating mode is set so
the power suppl
terminals (local sensin
trols (local pro
e sensing and remote programming of output voltage and
volta
current usin
LOCAL OPERA TING MODE
The power supply is shipped from the factory configured in the
local operatin
settin
s of the rear panel, as shown in Figure 4. The power sup-
provides constant voltage(CV) or constant current(CC) output.
pl
Constant Voltage Operaton
To set up a power supply for constant voltage operation, proceed
as follows:
senses the output voltage directly at the output
) for operation using the front panel con-
ramming). Other operating modes are: remote
external voltages.
mode. Local operating mode requires the switch
False OVP shutdowns ma
too close to the suppl
down volta
a
e to avoid false shutdowns from load-induced transients.
Ad
down volta
a. With the VOLTAGE control full
b. While depressin
c. Follow the procedure for CC or CV operaton to set the out-
Resettin
turning power off. Wait one or more seconds, and turn power on
a
ain. If OVP shutdown continue to occur, check the connections
to the load and sense terminals, and check the OVP limit settin
e 4% of output +2.0 V or more above the output volt-
usting OVP.
the power suppl
the OVP Adjust control to the desired OVP shutdown usin
a small, flat-blade screwdriver.
put volta
Follow this procedure to adjust the OVP shut-
e.
e and current
OVP. If OVP shutdown occurs, reset the suppl
occur if you set the OVP shutdown
's operating voltage. Set the OVP shut-
counter clockwise, turn on
.
DISPLAY OVP/CC SET switch, adjust
..
a. Turn on the power suppl
trol for desired output volta
b. While depressin
turn CURRENT control for the desired current limit.
c. With power off connect the load to the output terminals.
d. Turn on the power suppl
actual operation, if a load change causes the current
Durin
limit to be exceeded, the power suppl
cross over to constant current mode and the output voltage
will drop proportionatel
and adjust 10-turn VOLTAGE con-
e (output terminals open).
DISPLAY OVP/CC SET switch, adjust 10-
. Verify that CV LED is lighted.
will automaticall
.
Constant Current Operation
To set up a power supply for constant current operation, proceed
as follows:
a. Turn on power suppl
b. While depressin
CURRENT control for the desired output current.
c. Turn up the VOLTAGE control to the desired volta
d. With power off connect the load to the output terminal.
e. Turn on power suppl
(If CV LED is li
settin
that is greater than the current setting multiplied by the
load resistance in ohms is required for CC operation.) Durin
actual operation, if a load chan
be exceeded, the power suppl
to constant volta
output current will drop proportionatel
.
DISPLAY OVP/CC SET switch, adjust
e limit.
and then verify that CC LED is lighted.
hted, choose a higher voltage limit. A voltage
e causes the voltage limit to
will automatically cross over
e operation at the preset voltage limit and
.
Overvoltage Protection (OVP)
Adjustable overvoltage protection guards your load against over-
e. When the voltage at the output terminals increases (or is
volta
increased b
set b
ables the output causin
zero. Durin
an external source) to the OVP shutdown voltage as
the OVP ADJUST control, the supply's OVP circuit dis-
the output voltage and current to drop to
OVP shutdown the OVP LED lights.
Strong electrostatic discharge to power supply can make
OVP trip and eventuall
effectivel
protect output loads from the hazardous ESD
crowbar the output, which can
current.
CONNECTING LOADS
The output of the supply is isolated from earth ground. Either output terminal ma
240 volts off
exceed 240 Vdc.
Each load should be connected to the power suppl
usin
separate pairs of connecting wires. This will minimize mutual
effects between loads and will retain full advantage of the
couplin
low output impedance of the power suppl
wires should be as short as possible and twisted or shielded to
reduce noise pick-up. (If a shield is used, connect one end to the
power suppl
ted.)
If load considerations require that the output power distribution
terminals be remotel
power suppl
distribution terminals via a pair of twisted or shielded wires and
each load separatel
nals. For this case, remote sensin
raph "Remote Voltage Sensing").
be grounded or the output can be floated up to
round. Total output voltage to ground must not
output terminals
. Each pair of connectin
round terminal and leave the other end unconnec-
located from the power supply, then the
output terminals should be connected to the remote
connected to the remote distribution termi-
should be used (See para-
OPERA TION BEYOND RATED OUTPUT
The output controls can adjust the voltage or current to values up
to 5% over the rated output. Althou
in the 5% overran
uaranteed to meet all of its performance specifications in this
ion.
re
e region without being damaged, it can not be
h the supply can be operated
1-8
Page 9
REMOTE OPERA TING MODES
g
g
g
g
y
g
g
y
g
g
y
g
y
g
y
g
y
g
g
g
y
g
g
y
y
g
g
ging
g
g
y
y
g
y
y
g
y
y
y
g
y
g
g
y
g
y
g
g
g
y
y
g
ying
g
g
Remote operating modes discussed below are remote voltage
sensin
and remote voltage programming. Y ou can set up the unit
for remote operatin
panel switch and connectin
nals to the load or the external volta
2
to 1.5 mm
pl
can be connected to the rear panel terminals by sim-
push fitting. Thinner wires or conductors are inserted into the
connection space after depressin
Turn off the supply while making changes to rear panel
switch settin
of damage to the load and OVP shutdown from unintended output.
Remote Voltage Sensing
Remote voltage sensing is used to maintain good regulation at
the load and reduce the de
occur due to the volta
and the load. By connecting the supply for remote voltage
suppl
, voltage is sensed at the load rather than at the supply's
sensin
output terminals. This will allow the suppl
pensate for the volta
tion.
When the suppl
senses the volta
terminals.
modes by changing the settings of the rear
the leads from the rear panel termi-
e. Solid conductors of 0.75
the orange opening lever.
s or connections. This avoids the possibilit
radation of regulation that would
e drop in the leads between the power
to automatically com-
e drop in the load leads and improve regula-
is connected for remote sensing, the OVP circuit
e at the sense leads and not the main output
Output Noise.
appear at the suppl
ulation. Twist the sense leads to minimize the pickup of exter-
re
An
noise picked up on the sense leads will
's output voltage and may degrade CV load
nal noise and run them parallel and close to the load leads. In
nois
environments, it may be necessary to shield the sense
leads. Ground the shield at the power suppl
the shield as one of the sensin
Stability.
When the suppl
conductors.
is connected for remote sensing, it is
end only. Do not use
possible for the impedance of the load wires and the capacitance
of the load to form a filter, which will become part of the suppl
CV feedback loop. The extra phase shift created b
rade the supply's stability and can result in poor transient
de
response performance or loop stabilit
. In extreme cases, it can
this filter can
cause oscillations. Keep the leads as short as possible and twist
the leads of the load to eliminate the load lead inductance and
keep the load capacitance as small as possible.The load leads
should be of the lar
the volta
e drop in each lead to 0.5 volts.
The sense leads are part of the suppl
est diameter practical, heavy enough to limit
's programming feedback
control loop. Accidental open-connections of sense or load leads
durin
remote sensing operation have various unwanted effects.
Provide secure, permanent connections-especiall
for the sense
leads.
_
MASTER
LOCAL
_
+
_
+
+
's
Remote voltage sensing compensates for a voltage drop of
up to 0.5 V in each load, and there ma
be up to a 0.1 V
drop between the output terminal and the internal sensin
resistor, at which point the OVP circuit is connected. Therefore, the volta
much as 1.1 V more than the volta
load. It ma
when usin
CV Re
ulation.
adds directl
e sensed by the OVP circuit could be as
e being regulated at the
be necessary to re-adjust the OVP trip voltage
remote sensing.
Notice that an
voltage drop in the sense leads
to the CV load regulation. In order to maintain the
specified performance, keep the sense lead resistance to 0.5
ohms per lead or less.
Remote Sensin
chan
settings of the rear panel switch and connecting the
Connections.
Remote sensin
requires
load leads from + and - output terminals to the load and connectin
the sense leads from the +S and -S terminals to the load as
shown in Fi
ure 5.
Observe polarity when connecting the sensing leads to
the load.
SLAVE
CVCCSENSE
REMOTE
+
nqcf
_
OUT
+S
-S
pqvg\BvB B BB B
CVCC
VREF
A1 A2 A3 A4 A5
M/S 1 M/S 2
Figure 5. Remote Voltage Sensin
Remote Analog Voltage Programming
Remote analog voltage programming permits control of the regulated output volta
a
e. The programming (external) voltage should not exceed 10
volts. The stabilit
the stabilit
disabled durin
The supply includes clamp circuits to prevent it from
suppl
or current when the remote pro
reater than 10 Vdc. Do not intentionally operate the sup-
e or current by means of a remotely varied volt-
of the programming voltages directly affects
of the output. The voltage control on the front panel is
remote analog programming.
more than about 120% of rated output voltage
ramming voltage is
1-9
Page 10
ply above 100% rated output. Limit your programming
g
g
g
y
y
g
g
y
y
g
g
g
g
g
ge g
g
g
g
g
g
g
g
g
y
g
y
g
g
g
y
y
y
y
y
g
y
g
y
g
y
y
g
g
y
g
y
g
y
g
volta
e to 10 Vdc.
Remote Programming Connections. Remote programmin
requires changing settings of the switch and connecting external
volta
es to + and - terminals of "CV" or "CC" on the rear panel.
noise picked up on the programming leads will appear on the
An
's output and may degrade regulation. To reduce noise
suppl
pick-up, use a twisted or shielded pair of wires for pro
with the shield
rounded at one end only. Do not use the shield as
ramming,
a conductor.
Notice that it is possible to operate a power suppl
neousl
in the remote sensing and the remote analog program-
modes.
min
Remote Pro
rear panel switch settin
volta
ramming voltage produces a change in output voltage (volt-
pro
ain) as follows: E3614A: 0.8 Vdc, E3615A: 2 Vdc, E3616A:
a
ramming, Constant Voltage. Figure 6 shows the
s and terminal connections for remote-
e control of output voltage. A 1 Vdc change in the remote
simulta-
3.5 Vdc, E3617A: 6 Vdc
_
MASTER
M/S 1 M/S 2
SLAVE
NOTE:
See the supplementar
ramming voltage source.
isolated pro
LOCAL
CVCCSENSE
REMOTE
Manual, if you are not using
_
+
OUT
+S
_
+
+
CVCC
VREF
A1 A2 A3 A4 A5
-S
MULTIPLE-SUPPLY OPERATION
Normal parallel and auto-parallel operation provides increased output current while normal series and auto-series provides increased
output volta
e of more than one supply. You can set up the unit for multiple-
a
suppl
and connectin
Solid conductors of 0.75 to 1.5 mm
panel terminals b
are inserted into the connection space after depressin
openin
NORMAL P ARALLEL OPERATION
Two or more power supplies being capable of CV/CC automatic
cross over operation can be connected in parallel to obtain a total
output current
The total output current is the sum of the output currents of the
individual power supplies. The output of each power suppl
be set separatel
pl
should be set to the desired output voltage; the other power
suppl
with the higher output voltage setting will deliver its constant
pl
current output, and drop its output volta
put of the other suppl
stant volta
output current which is necessar
ure 8 shows the rear panel switch settings and terminal con-
Fi
nections for normal parallel operation of two supplies.
POWER SUPPLY
e. Auto-tracking provides single control of output volt-
operation by changing the settings of the rear panel switch
the leads from the rear panel terminals to the load.
2
can be connected to the rear
simply push fitting. Thinner wires or conductors
the orange
lever.
reater than that available from one power supply.
. The output voltage controls of one power sup-
should be set for a slightly higher output voltage. The sup-
e until it equals the out-
, and the other supply will remain in con-
e operation and only deliver that fraction of its rated
to fulfill the total load demand.
MASTER
LOCAL
_
+
__
+
+
can
Figure 6. Remote Voltage Programming, Constant
Volta
e
Remote Programming, Constant Current. Figure 7 shows the
rear panel switch settin
e control of output current. A 1 Vdc change in the remote
volta
ramming voltage produces a change in output current (cur-
pro
rent
ain) as follows: E3614A: 0.6 Adc, E3615A: 0.3 Adc,
s and terminal connections for remote-
E3616A: 0.17 Adc, E3617A: 0.1 Adc
_
MASTER
M/S 1 M/S 2
SLAVE
NOTE:
See the supplementar
ramming voltage source.
isolated pro
LOCAL
CVCCSENSE
REMOTE
Manual, if you are not using
_
+
OUT
+S
_
+
+
CVCC
VREF
A1 A2 A3 A4 A5
-S
Figure 7. Remote Voltage Programming, Constant
Current
Remote Programming Speed. See the table of Specifications,
e 1-5.
pa
SLAVE
MASTER
SLAVE
CV CCSENSE
REMOTE
LOCAL
CV CCSENSE
REMOTE
OUT
+S-S
LOAD
_
+
OUT
+S
VREF
CV CC
+
-S
CV CC
A1 A2 A3 A4 A5
_
_
+
VREF
A1 A2 A3 A4 A5
M/S 1 M/S 2
POWER SUPPLY
M/S 1 M/S 2
Figure 8. Normal Parallel Operation of Two Supplies
AUTO-PARALLEL OPERATION
Auto-parallel operation permits equal current sharing under all load
conditions, and allows complete control of output current from one
master suppl
units are called slaves. Normall
model number should be connected for auto-parallel operation,
since the supplies must have the same volta
rent monitorin
each slave is approximatel
ure 10 show the rear panel switch settin
for auto-parallel operation of two supplies and three supplies.
. The control unit is called the master; the controlled
, only supplies having the same
e drop across the cur-
resistor at full current rating. The output current of
equal to the master's. Figure 9 and Fig-
s and terminal connections
1-10
Page 11
Settin
g
y
g
y
g
g
g
g
g
g
y
g
g
g
g
y
g
g
y
g
g
y
g
g
g
y
y
g
y
g
g
g
Voltage and Current. Turn the slave unit's CURRENT
control full
desired output volta
in a completel
stant volta
clockwise. Adjust the master unit's controls to set the
e and current. The master supply operates
normal fashion and may be set up for either con-
e or constant current operation as required. Verify that
the slave is in CV operation.
ramming according to the remote-programming instructions.
MASTER POWER SUPPLY
MASTER
LOCAL
_
+
__
+
+
For auto-parallel operation of two supplies, the combined output
volta
e is the same as the master unit's voltage setting, and the
combined output current is two times the master unit's current. In
eneral, for two supplies, the auto-parallel output current(Io) is
Io = Im + Is = 2Im
where Im = master unit's output current
Is = slave unit's output current
Proportional currents from auto-paralleled units require
equal load-lead volta
the load usin
separate pairs of wire with length chosen
to provide equal volta
not feasible, connect each suppl
terminals usin
connect the distribution terminals to the load with a sin
e drops. Connect each supply to
e drops from pair to pair. If this is
to a pair of distribution
equal- voltage-drop wire pairs, and then
le
pair of leads.
MASTER POWER SUPPLY
MASTER
SLAVE
MASTER
SLAVE
CV CCSENSE
CV CCSENSE
M/S 1 M/S 2
SLAVE POWER SUPPLY
M/S 1 M/S 2
LOCAL
REMOTE
LOCAL
REMOTE
_
+
OUT
+S
+S
-S
LOAD
_
+
OUT
-S
+
CV CC
_
+
CV CC
+
+
__
VREF
_
VREF
A1 A2 A3 A4 A5
A1 A2 A3 A4 A5
Figure 9. Auto-Parallel Operation of Two Supplies
M/S 1 M /S 2
CV CC SENSE
SLAVE
SLAVE POWER SUPPLY
MASTER
M/S 1 M /S 2
CV CC SENSE
SLAVE
SLAVE POWER SUPPLY
MASTER
M/S 1 M /S 2
CV CC SENSE
SLAVE
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
OUT
+S
_
+
OUT
+S-S
_
+
OUT
+S
-S
CV CC
LOAD
+
+
CV CC VREF A1 A2 A3 A4 A5
+
+
-S
CV CC
VREF
__
__
VREF
A1 A2 A3 A4 A5
A1 A2 A3 A4 A5
Figure 10. Auto-Parallel Operation of Three Supplies
NORMAL SERIES OPERA TION
Series operation of two or more power supplies can be accomplished up to the output isolation ratin
obtain a hi
her voltage than that available from a single supply.
Series connected supplies can be operated with one load across
both supplies or with a separate load for each suppl
power supplies have a reverse polarit
the output terminals so that if operated in series with other supplies, dama
suppl
e will not occur if the load is short-circuited or if one
is turned on separately from its series partners. When this
connection is used, the output volta
of the individual supplies. Each of the individual supplies must be
adjusted in order to obtain the total output volta
shows the rear panel switch settin
normal series operation of two supplies.
POWER SUPPLY
MASTER
LOCAL
+
of any one supply to
. These
diode connected across
e is the sum of the voltages
e. Figure 11
s and terminal connections for
_
__
+
+
Overvoltage Protection. Adjust the desired OVP shutdown limit
the master unit's OVP Adjust control. Set the slave units'
usin
OVP limits above the master's. When a master-unit shuts down,
the master pro
slave unit shuts down, it shuts onl
rent is
rams the slave units to zero voltage output. If a
itself down. If the required cur-
reat enough, the master will switch from CV to CC opera-
tion.
Remote Sensin
connect remote-sense leads onl
the remote-sensin
Remote Analo
auto-parallel operation, set up onl
. To remote sense with auto-parallel operation,
to the master unit according to
instructions.
Voltage Programming. To remote program with
the master unit for remote pro-
M/S 1 M/S 2
POWER SUPPLY
M/S 1 M/S 2
SLAVE
MASTER
SLAVE
CV CCSENSE
REMOTE
LOCAL
CV CCSENSE
REMOTE
OUT
+S-S
LOAD
_
+
OUT
+S
VREF
CV CC
+
-S
CV CC
A1 A2 A3 A4 A5
_
_
+
VREF
A1 A2 A3 A4 A5
Figure 11. Normal Series Operation of Two Supplies
1-11
Page 12
AUTO-SERIES OPERATION
g
g
g
y
g
g
g
g
y
g
g
g
g
g
g
g
g
g
y
y
g
g
g
g
g
g
g
g
g
g
g
g
y
y
g
g
g
g
(S2)
Auto-series operation permits equal or proportional voltage
sharin
, and allows control of output voltage from one master
unit. The volta
the front panel VOLTAGE control on the master and volta
divider resistor. The master unit must be the most positive suppl
of the series. The output CURRENT controls of all series
units are operative and the current limit is equal to the lowest
settin
. If any output CURRENT controls are set too low, automatic cross over to constant current operation will occur and the
output volta
panel switch settin
operation of two supplies and three supplies. This mode can
ive ±voltage tracking operation of two supplies with two
also
separate loads.
e of the slaves is determined by the setting of
e will drop. Figure 12 and Figure 13 show the rear
s and terminal connections for Auto-series
above the master unit's current settin
to avoid having the slave
switch to CC operation.
When in CC operation the combined output current is the same
e
as the master unit's current settin
combined output volta
slave unit's output volta
Overvolta
e Protection.
e is the sum of the master unit's and the
es.
Set the OVP shutdown volta
unit so that it shuts down at a volta
durin
auto-series operation. When a master unit shuts down, it pro-
, and when in CV operation the
e in each
e higher than its output voltage
rams any slave units to zero output. When a slave unit shuts down,
it shuts down onl
itself (and any slaves below it in the stack). The
master (and all slaves above the shut-down slave) continues to suppl
output voltage.
Mixed model numbers ma
be employed in auto-series combi-
nation without restriction, provided that each slave is specified as
capable of auto-series operation. If the master supply is set
bein
up for constant current operation, then the master-slave combination will act as a composite constant current source.
T otal output voltage to ground must not exceed 240 Vdc.
Determining Resistors.
multiple) of the master unit's volta
the slave unit. Notice that the percenta
e contributed by each supply is independent of the magnitude
a
of the total volta
External resistors control the fraction (or
e setting that is supplied from
e of the total output volt-
e. For two units in auto-series the ratio of R1 to
R2 is
(R1+R2)/R1 = (Vo/Vm)
R2/R1= (Vs/Vm)
Where Vo = auto-series volta
Vm = master unit's output volta
Vs = slave unit's output volta
For example, usin
the E3617A as a slave unit and putting R2=50
e = Vs + Vm
e
e
kΩ (1/4 watt), then from the above equations,
R1 = R2(Vm/Vs) = 50(Vm/Vs) kΩ
In order to maintain the temperature coefficient and stabilit
mance of the suppl
, choose stable, low noise resistors.
perfor-
MASTER POWER SUPPLY
MASTER
SLAVE
MASTER
SLAVE
CV CCSENSE
CV CCSENSE
M/S 1 M/S 2
SLAVE POWER SUPPLY
M/S 1 M/S 2
LOCAL
REMOTE
LOCAL
REMOTE
_
+
OUT
+S-S
LOAD
_
+
OUT
+S
-S
+
CV CC
_
+
CV CC
+
+
__
A1 A2 A3 A4 A5
VREF
R1 R2
_
A1 A2 A3 A4 A5
VREF
Figure 12. Auto-Series Operation of Two Supplies
MASTER POWER SUPPLY
MASTER
M/S 1 M/S 2
SLAVE
SLAVE POWER SUPPLY(S1)
MASTER
LOCAL
CV CCSENSE
REMOTE
LOCAL
LOAD
_
+
OUT
+S
-S
_
+
+
CV CC
+
+
+
__
VREF
A1 A2 A3 A4 A5
R1 R2
__
M/S 1 M/S 2
It is recommended to connect a 0.1 µF capacitor in parallel with R2 in two supplies operation or R2 and R4 in
CV CCSENSE
SLAVE
SLAVE POWER SUPPLY(S2)
MASTER
REMOTE
LOCAL
OUT
+S
-S
_
+
CV CC
+
+
VREF
A1 A2 A3 A4 A5
R3 R4
__
three supplies operation to ensure the stable operation.
Setting Voltage and Current.
set the desired output volta
of the slave unit is disabled. Turnin
master unit will result in a continuous variation of the output of the
series combination, with the contribution of the master's output
e to that of the slave's voltage always remaining in the ratio
volta
of the external resistors. Set the CURRENT control of slave unit
Use the master unit's controls to
e and current. The VOLTAGE control
the voltage control of the
M/S 1 M/S 2
CV CCSENSE
SLAVE
Vo=Vm(1+
ure 13. Auto-Series Operation of Three Supplies
Fi
REMOTE
R2
R4
R2
)
+
R1
R1
R3
OUT
+S
Where Vo = Auto-Series volta
-S
CV CC
Vm = master unit's output volta
Vs1 = slave(S1) unit's output volta
Vs2 = slave
unit's output voltage
VREF
A1 A2 A3 A4 A5
e = Vm + Vs1 + Vs2
e
e
1-12
Page 13
Remote Sensin
g
g
g
g
y
g
g
g
g
y
y
y
g
y
y
y
g
g
g
g
g
g
g
g
g
g
g
g
y
g
g
g
g
g
g
g
g
y
y
g
g
g
g
g
g
g
. To remote sense with auto-series operation,
set SENSE switch of the master unit and set SENSE switch of the
slave unit to remote.
Remote Analo
Voltage Programming. To remote analog pro-
ram with auto-series operation, connect program (external) volt-
es to the "CV" or "CC"" terminal of the master unit and set "CV"
a
or "CC" switch of the master unit to remote.
AUTO-TRACKING OPERATON
Auto-tracking operation of power supplies is similar to auto-series
operation except that the master and slave supplies have the
same output polarit
This operation is useful where simultaneous turn-up, turn-down or
proportional control of all power supplies is required.
Fi
ure 14 and Figure 15 show two and three supplies connected
in auto-trackin
to
ether as a common or ground point. For two units in auto-
a fraction R2/(R1+R2) of the output of the master suppl
trackin
is provided as one of the inputs to the comparison amplifier of the
slave suppl
in an auto-tracking operation must be the positive supply hav-
pl
in
the largest output voltage. Turn-up and turn-down of the
, thus controlling the slave's output. The master sup-
power supplies are controlled b
maintain the temperature coefficient and stabilit
the power suppl
noise, low temperature.
with respect to a common bus or ground.
with their negative output terminals connected
the master supply. In order to
specifications of
, the external resistor should be stable, low
Remote Analo
Programming. To simultaneously remote pro-
ram both units' output voltages, set up only the master unit for
remote volta
instructions. To vary the fraction of the output voltage contri-
min
bution b
in two units operation. To independentl
unit's output current settin
output current accordin
e programming according to the remote program-
the slave unit, connect a variable resistor in place of R2
remote program each
, set up each unit for remote control of
to the instructions under "Remote Pro-
ramming, Constant Current" paragraph.
MASTER POWER SUPPLY
MASTER
SLAVE
MASTER
SLAVE
CV CCSENSE
CV CCSENSE
M/S 1 M/S 2
SLAVE POWER SUPPLY
M/S 1 M/S 2
LOCAL
REMOTE
LOCAL
REMOTE
_
+
OUT
+S-S
LOAD
LOAD
_
+
OUT
+S
-S
+
CV CC
_
+
CV CC
+
+
__
VREF
_
VREF
A1 A2 A3 A4 A5
R1 R2
A1 A2 A3 A4 A5
Figure 14. Auto-Tracking Operation of Two Supplies
Determinin
the master unit's volta
two units in auto-trackin
Resistors. External resistors control the fraction of
e that is supplied from the slave unit. For
the ratio R1 and R2 is
R2/(R1+R2 = (Vs/Vm)
Where Vm = master output volta
Vs = slave output volta
e
e
It is recommended to connect a 0.1 µF capacitor in parallel with R2 in two supplies operation or R2 and R4 in
three supplies operation to ensure the stable operation.
Setting Voltage and Current. Use the master unit's VOLTAGE control to set the output volta
CV operation, the master's output volta
volta
e setting, and the slave's output voltage for two units operation
e from both units. When the master is in
e(Vm) is the same as its
is Vm(R2/(R1+R2)). The VOLTAGE control of the slave unit is disabled. Set the CURRENT controls of master and slave units above
the required currents to assure CV operation of master and slave
units.
Overvolta
unit so that it shuts down at a volta
a
e during auto-tracking operation. When a master unit shuts
down, it pro
unit shuts down, it shuts down onl
Remote Sensin
e Protection. Set the OVP shutdown voltage in each
e higher than its output volt-
rams any slave units to zero output. When a slave
itself.
. To include remote sensing with auto-trackin
operation independently, set up each unit for remote sensin
according to the remote-sensing instructions under previous
raph.
para
MASTER POWER SUPPLY
MASTER
M/S 1 M/S 2
SLAVE
SLAVE POWER SUPPLY(S1)
MASTER
M/S 1 M/S 2
SLAVE
SLAVE POWER SUPPLY(S2)
MASTER
M/S 1 M/S 2
SLAVE
Vs1 =
R1+
Vs2 =
R3+
Fi
ure 15. Auto-Tracking Operation of Three Supplies
CV CCSENSE
CV CCSENSE
CV CCSENSE
R2
Vm
R2
R4
Vs1
R4
LOCAL
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
Where
_
+
OUT
+S
+S
+S
-S
LOAD
LOAD
_
+
OUT
-S
LOAD
_
+
OUT
-S
Vm = masters unit's output volta
Vs1 = slave(S1) unit's output volta
Vs2 = slave(S2) unit's output volta
+
CV CC
+
CV CC
+
CV CC
+
+
+
__
VREF
A1 A2 A3 A4 A5
R1 R2
__
VREF
A1 A2 A3 A4 A5
R3 R4
__
VREF
A1 A2 A3 A4 A5
e
e
e
1-13
Page 14
LOAD CONSIDERATIONS
y
g
g
y
g
g
g
y
g cy
y
g
y
y
g cy
y
g
y
y
g
g
g
g
y
g
y
g
g
y
y
g
g
y
g
y
g
g
g
y
y
g
y
y
g
y
g
This section provides information on operating your supply with
various t
PULSE LOADING
The power supply will automatically cross over from constantvolta
(over the preset limit) in the output current. Althou
limit ma
currents (as occur in pulse loadin
rent limit and cause cross over to occur. If this cross over limitin
is not desired, set the preset limit for the peak requirement and
not the avera
REVERSE CURRENT LOADING
An active load connected to the power supply may actuall
deliver a reverse current to the power supply during a portion of
its operatin
pump current into the suppl
ble dama
these effects, it is necessar
load resistor so that the power supply delivers current through the
entire operatin
pes of loads connected to its output.
e to constant current operation in response to an increase
h the preset
be set higher than the average output current, high peak
) may exceed the preset cur-
e.
cle. An external source can not be allowed to
without loss of regulation and possi-
e to the output capacitor of the power supply. To avoid
to preload the supply with a dumm
cle of the load devices.
a. The output impedance of the power suppl
increasin
b. The recover
resistance chan
c. A lar
load occurs when the load resistance is reduced rapidl
frequency.
time of the output voltage is longer for load
es.
e surge current causing a high power dissipation in the
decreases with
.
REVERSE VOL TAGE LOADING
A diode is connected across the output terminals with reverse
. This diode protects the output electrolytic capacitors and
polarit
the series re
a
e applied across the output terminals. For example, in series
operation of two supplies, if the AC is removed from one suppl
the diode prevents dama
would otherwise result from a reverse polarit
Since series re
a
e, another diode is connected across the series transistor. This
diode protects the series re
operation if one suppl
before the other.
ulator transistors from the effects of a reverse volt-
e to the unenergized supply which
voltage.
ulator transistors cannot withstand reverse volt-
ulators in parallel or auto-parallel
of the parallel combination is turned on
BA TTER Y CHARGING
The power supply's OVP circuit contains a crowbar SCR, which
effectivel
an external volta
output, and OVP inadvertentl
sink a large current from the source; possibly damaging the supply.
To avoid this a diode must be connected in series with the output as
shown in Fi
shorts the output of the supply whenever the OVP trips. If
e source such as a battery is connected across the
triggered, the SCR will continuousl
ure 17.
,
Figure 16. Reverse Current Loading Solution
Figure 17. Recommended Protection Circuit for
Batter
OUTPUT CAP ACITANCE
An internal capacitor, connected across the output terminals of
the power suppl
duration durin
added externall
decrease the safet
hi
h-current pulse may damage load components before the
e output current is large enough to cause the current limit-
avera
circuit to operate.
in
The effect of the output capacitor durin
tion are as follows:
, helps to supply high-current pulses of short
constant voltage operation. Any capacitance
will improve the pulse current capability, but will
Voltage and Current Programming of the E3614A/15A/16A/
17A with a Voltage and Current Source
Remote analog voltage programming permits control of the regulated output voltage
or current by means of a remotely varied voltage or current. The stability of the
programming voltages directly affects the stability of the output. The voltage control
or current control on the front panel are disabled during analog programming.
NOTE The CV(-) terminal on the rear panel is internally connected to the plus output
terminal. In following connections, it is recommended to use Figure 2, Figure 4, or
Figure 6 if the negative terminal of the “Programming Voltage” is not floted from
its circuits.
Constant Voltage Mode
The programming voltage is not isolated from the power supply output. The power
supply may be programmed with a voltage that is common to either the plus output,
or the minus output.
Programming Voltage Common to the Plus output
Figure 1
Set the CV switch down on the rear panel, and all others up.
V
= 1/A x V
in
V
out
= A x V
out
in
WhereV
is the power supply output voltage.
out
V
is the programming voltage.
in
A is the gain factor and the values of each model are as below.
The M/S2 switch must be in the down position. For best results, place a 0.1µF capacitor in
parallel with R2.
V
= (R1/R2) x V
in
V
= (R2/R1) x V
out
WhereV
R1 and R2 should be in the 1KΩ to 100KΩ range.
out
in
is the power supply output voltage.
out
V
is the programming voltage.
in
1-10-2
Page 18
Programming Voltage Common to the Minus Output
Figure 4
The output will always be the same or less than the programming voltage.
The M/S2 switch must be in the down position. For best results, place a 0.1µF capacitor
in parallel with R2.
V
= (R1R2) / R2 x V
in
V
= R2 / R1+R2) x V
out
WhereV
out
in
is the power supply output voltage.
out
V
is the programming voltage.
in
R1 and R2 should be in the 1KΩ to 100KΩ range.
1-10-3
Page 19
Constant Current Mode
The E3614A/15A/16A/17A may be programmed for constant current with an analog
voltage or current. Constant current with analog voltage programming can only be
achieved with a voltage source that is common with the positive output terminal.
Constant Current with Voltage Programming
Figure 5
Set the CC switch down the rear panel, and all others up.
V
= 1/A x I
in
I
= A x V
out
out
in
WhereI
is the power supply output current.
out
V
is the programming voltage.
in
A is the transconductance in Amp/Volt and the values of each
model are as below.
When using current to program the power supply, the source must have a
dynamic range of 10 volts when the programming source is common to the plus
output and 10 volts plus the maximum output voltage expected when the
programming source is common to the minus output of the power supply.
The load to the power supply must be stable for the constant current
output to be accurate. Current transient response is not specified,
and depends on the change of the output voltage of the power supply.
Programming currents can be increased by adding a resistor across the CC+ and CC-. A
10 volts drop across R1 represents full scale current of the power supply. When a 1 kohm
resistor is added across R1, the programming currents are as follows with the
programming current in mA.
Current of the power supply can be monitored across the internal current monitoring
resistor. One side of the resistor is at the +output and A3; the other side of the resistor
is at A1. The table below shows the resistor value and conversion factors. To obtain
the current divide the measured voltage by the resistor value or multiply the amps/V
times the voltage measured.
Voltage and Current Programming of the
E3614A/15A/16A/17A with Resistors
Remote programming with resistors permits control of the regulated output or current
by means of a remotely varied resistor. The sum of the resistance of external
programming resistors (R1 + R2) should be more than 40 kohm. T o have more pr ecise output voltage, use a variable resistor mor e than 40 kohm. The voltage control on the
front panel is disabled during remote resistor programming.
NOTE Do not operate the power supply simultaneously in the remote analog voltage
programming and in the remote resistor programming.
Remote Resistor Programming Connections
Remote resistor programming requires changing the setting of the switches and
connecting external resistors between “+” and “`-” terminals of “CV” and “VREF”
terminal or “+” and “-” terminals of “CC” and “VREF” terminal. Any noise picked up
on the programming leads will appear on the power supply's output and may degrade
regulation. To reduce noise pickup, use a twisted or shielded pair of wires for
programming, with the shield grounded at one end only.
Remote Resistor Programming, Constant Voltage
Figure 7
Set the CV switch down on the rear panel, and all others up.
V
= A x [V
out
WhereV
x {R/(R + R2 + 100)}]
REF
is the power supply output voltage.
out
A is the gain factor and the values of each model are as below.
V
is between 10.11 V and 11.40 V.
REF
R = (92800 x R1)/(92800 + R1)
R1 + R2 > 40 kohm
ModelA
E3614A0.8
E3515A2.0
E3616A3.5
E3617A6.0
1-10-6
Page 22
Remote Resistor Programming, Constant Current
Figure 8
Set the CC switch down on the rear panel, and all others up.
I
= A x [V
out
WhereI
x {R/(R + R2 + 100)}]
REF
is the power supply output current.
out
A is the gain factor and the values of each model are as below.
V