Agilent Technologies, Inc. certifies that this product met its published specifications at the time of shipment from the factory. Agilent
Technologies further certifies that its calibration measurements are traceable to the United States National Institute of Standards and
Technology (formerly National Bureau of Standards), to the extent allowed by that organization's calibration facility, and to the
calibration facilities of other International Standards Organization members.
Warranty
This Agilent Technologies product is warranted against defects in materials and workmanship for a period of one year from date of
shipment. Duration and conditions of warranty for this product may be superseded when the product is integrated into (becomes a part of)
other Agilent products. During the warranty period, Agilent Technologies, Inc. will, at its option, either repair or replace products which
prove to be defective.
For warranty service or repair, this product must be returned to a service facility designated by Agilent Technologies. Buyer shall prepay
shipping charges to Agilent and Agilent shall pay shipping charges to return the product to Buyer. However, Buyer shall pay all shipping
charges, duties, and taxes for products returned to Agilent from another country
Agilent warrants that its software and firmware designated by Agilent for use with a product will execute its programming instructions
when properly installed on that product. Agilent does not warrant that the operation of the product, or software, or firmware will be
uninterrupted or error free.
Limitation Of Warranty
The foregoing warranty shall not apply to defects resulting from improper or inadequate maintenance by Buyer, Buyer-supplied products
or interfacing, unauthorized modification or misuse, operation outside of the environmental specifications for the product, or improper
site preparation or maintenance.
The design and implementation of any circuit on this product is the sole responsibility of the Buyer. Agilent does not warrant the Buyer's
circuitry or malfunctions of Agilent products that result from the Buyer's circuitry. In addition, Agilent does not warrant any damage that
occurs as a result of the Buyer's circuit or any defects that result from Buyer-supplied products.
NO OTHER WARRANTY IS EXPRESSED OR IMPLIED. AGILENT SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Exclusive Remedies
THE REMEDIES PROVIDED HEREIN ARE BUYER'S SOLE AND EXCLUSIVE REMEDIES. AGILENT SHALL NOT BE LIABLE
FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, WHETHER BASED ON
CONTRACT, TORT, OR ANY OTHER LEGAL THEORY.
Notice
The information contained in this document is subject to change without notice. AGILENT TECHNOLOGIES, INC. MAKES NO
WARRANTY OF ANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Agilent shall not be liable for errors
contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this material. This
document contains proprietary information which is protected by copyright. All rights are reserved. No part of this document may be
photocopied, reproduced, or translated to another language without the prior written consent of Agilent Technologies, Inc. Agilent
assumes no responsibility for the use or reliability of its software on equipment that is not furnished by Agilent.
U.S. Government Restricted Rights
The Software and Documentation have been developed entirely at private expense. They are delivered and licensed as "commercial
computer software" as defined in DFARS 252.227- 7013 (Oct 1988), DFARS 252.211-7015 (May 1991) or DFARS 252.227-7014 (Jun
1995), as a "commercial item" as defined in FAR 2.101(a), or as "Restricted computer software" as defined in FAR 52.227-19 (Jun
1987)(or any equivalent agency regulation or contract clause), whichever is applicable. You have only those rights provided for such
Software and Documentation by the applicable FAR or DFARS clause or the Agilet standard software agreement for the product involved
All Editions and Updates of this manual and their creation date are listed below. The first Edition of the manual is Edition 1. The Edition
number increments by 1 whenever the manual is revised. Updates, which are issued between Editions, contain replacement pages to
correct or add additional information to the current Edition of the manual. Whenever a new Edition is created, it will contain all of the
Update information for the previous Edition. Each new Edition or Update also includes a revised copy of this documentation history page.
Instruction manual symbol affixed to
product. Indicates that the user must refer to
product. Indicates that the user must refer to
the manual for specific WARNING or
the manual for specific WARNING or
CAUTION information to avoid personal
CAUTION information to avoid personal
injury or damage to the product.
injury or damage to the product.
Indicates the field wiring terminal that must
be connected to earth ground before
operating the equipment — protects against
electrical shock in case of fault.
WARNING
Alternating current (AC)
Direct current (DC).
Indicates hazardous voltages.
Calls attention to a procedure, practice, or
condition that could cause bodily injury or
death.
Frame or chassis ground terminal—typically
connects to the equipment's metal frame.
CAUTION
Calls attention to a procedure, practice, or
condition that could possibly cause damage to
equipment or permanent loss of data.
WARNINGS
The following general safety precautions must be observed during all phases of operation, service, and repair of this product. Failure to
comply with these precautions or with specific warnings elsewhere in this manual violates safety standards of design, manufacture, and
intended use of the product. Agilent Technologies, Inc. assumes no liability for the customer's failure to comply with these requirements.
Ground the equipment: For Safety Class 1 equipment (equipment having a protective earth terminal), an uninterruptible safety earth
ground must be provided from the mains power source to the product input wiring terminals or supplied power cable.
DO NOT operate the product in an explosive atmosphere or in the presence of flammable gases or fumes.
For continued protection against fire, replace the line fuse(s) only with fuse(s) of the same voltage and current rating and type. DO NOT
use repaired fuses or short-circuited fuse holders.
Keep away from live circuits: Operating personnel must not remove equipment covers or shields. Procedures involving the removal of
covers or shields are for use by service-trained personnel only. Under certain conditions, dangerous voltages may exist even with the
equipment switched off. To avoid dangerous electrical shock, DO NOT perform procedures involving cover or shield removal unless you
are qualified to do so.
DO NOT operate damaged equipment: Whenever it is possible that the safety protection features built into this product have been
impaired, either through physical damage, excessive moisture, or any other reason, REMOVE POWER and do not use the product until
safe operation can be verified by service-trained personnel. If necessary, return the product to an Agilent Technologies Sales and Service
Office for service and repair to ensure that safety features are maintained.
DO NOT service or adjust alone: Do not attempt internal service or adjustment unless another person, capable of rendering first aid and
resuscitation, is present.
DO NOT substitute parts or modify equipment: Because of the danger of introducing additional hazards, do not install substitute parts
or perform any unauthorized modification to the product. Return the product to an Agilent Technologies Sales and Service Office for
service and repair to ensure that safety features are maintained.
6
DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and CEN/CENELEC EN 45014
Manufacturer’s Name:
Manufacturer’s Address:
Agilent Technologies, Incorporated
815 – 14th St. SW
Loveland, Colorado 80537
USA
Declares, that the product
Product Name:
Model Number:
16 Ch GP High Voltage Relay Multiplexer
E1343A
Product Options:This declaration covers all options of the above product(s).
Conforms with the following European Directives:
The product herewith complies with the requirements of the Low Voltage Directive 73/23/EEC and the EMC Directive 89/336/EEC
(including 93/68/EEC) and carries the CE Marking accordingly.
Conforms with the following product standards:
EMCStandard
The produt was tested in a typical configuration with Agilent Technologies or Hewlett-Packard Company test
systems
Safety
IEC 1010-1:1990+A2:1996 / EN 61010-1:1993
Canada: CSA C22.2 No. 1010.1:1992
UL 3111-1 : 1994
Limit
Group 1 Class A
4kV CD, 8kV AD
3 V/m
0.5kV signal lines, 1kV power lines
3 May 2001
Date
Ray Corson
Product Regulations Program Manager
Authorized EU-representative: Agilent Technologies Deutschland GmbH, Herrenberger Straβe 130, D 71034 Böblingen, Germany
Revision: B.01Issue Date: 3 May 2001Document E1343A.DOC
For further information, please contact your local Agilent Technologies sales office, agent or distributor.
DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and CEN/CENELEC EN 45014
Manufacturer’s Name:
Manufacturer’s Address:
Agilent Technologies, Incorporated
815 – 14th St. SW
Loveland, Colorado 80537
USA
Declares, that the product
Product Name:
Model Number:
16 Ch T/C High Voltage Relay Multiplexer
E1344A
Product Options:This declaration covers all options of the above product(s).
Conforms with the following European Directives:
The product herewith complies with the requirements of the Low Voltage Directive 73/23/EEC and the EMC Directive 89/336/EEC
(including 93/68/EEC) and carries the CE Marking accordingly.
Conforms with the following product standards:
EMCStandard
The produt was tested in a typical configuration with Agilent Technologies or Hewlett-Packard Company test
systems
Safety
IEC 1010-1:1990+A2:1996 / EN 61010-1:1993
Canada: CSA C22.2 No. 1010.1:1992
UL 3111-1 : 1994
Limit
Group 1 Class A
4kV CD, 8kV AD
3 V/m
0.5kV signal lines, 1kV power lines
3 May 2001
Date
Ray Corson
Product Regulations Program Manager
Authorized EU-representative: Agilent Technologies Deutschland GmbH, Herrenberger Straβe 130, D 71034 Böblingen, Germany
Revision: B.01Issue Date: 3 May 2001Document E1344A.DOC
For further information, please contact your local Agilent Technologies sales office, agent or distributor.
DECLARATION OF CONFORMITY
According to ISO/IEC Guide 22 and CEN/CENELEC EN 45014
Manufacturer’s Name:
Manufacturer’s Address:
Agilent Technologies, Incorporated
815 – 14th St. SW
Loveland, Colorado 80537
USA
Declares, that the product
Product Name:
Model Number:
16 Channel Relay Multiplexer
E1345A
Product Options:This declaration covers all options of the above product(s).
Conforms with the following European Directives:
The product herewith complies with the requirements of the Low Voltage Directive 73/23/EEC and the EMC Directive 89/336/EEC
(including 93/68/EEC) and carries the CE Marking accordingly.
Conforms with the following product standards:
EMCStandard
Product Options:This declaration covers all options of the above product(s).
Conforms with the following European Directives:
The product herewith complies with the requirements of the Low Voltage Directive 73/23/EEC and the EMC Directive 89/336/EEC
(including 93/68/EEC) and carries the CE Marking accordingly.
Conforms with the following product standards:
EMCStandard
The produt was tested in a typical configuration with Agilent Technologies or Hewlett-Packard Company test
systems
Safety
IEC 1010-1:1990+A2:1996 / EN 61010-1:1993
Canada: CSA C22.2 No. 1010.1:1992
UL 3111-1 : 1994
Limit
Group 1 Class A
4kV CD, 8kV AD
3 V/m
0.5kV signal lines, 1kV power lines
3 May 2001
Date
Ray Corson
Product Regulations Program Manager
Authorized EU-representative: Agilent Technologies Deutschland GmbH, Herrenberger Straβe 130, D 71034 Böblingen, Germany
Revision: B.01Issue Date: 3 May 2001Document E1347A.DOC
For further information, please contact your local Agilent Technologies sales office, agent or distributor.
Using This Chapter
This chapter describes the E1343A 16-Channel High Voltage Relay,
E1344A 16-Channel General Purpose Thermocouple High Voltage Relay,
E1345A 16-Channel Relay, and E1347A 16-Channel Thermocouple Relay
Multiplexer Modules, and shows how to program the modules using SCPI
commands (Standard Commands for Programmable Instruments). This
chapter contains the following sections:
Refer to Figure 1-1 for the following explanations of all four 16-Channel
Relay Multiplexer Modules.
Chapter 1
Getting Started
General DescriptionThe multiplexer module switches (multiplexes) up to 16 channels. Each
channel provides High (H), Low (L), and Guard (G) connections.
The multiplexer module consists of a component assembly and a terminal
module. The channel relay switches are on the component assembly. The
field wiring from user sources (e.g., thermocouples) connects to the terminal
module. The terminal module also provides connections for multimeters,
voltmeters, counters, and other measuring devices.
Multiplexer Channel
Descriptions and
Connections
The channel relay switches are separated into two banks, Bank 0 and
Bank 1. Channels 00 to 07 are in Bank 0 and channels 08 to 15 are in
Bank 1. Each bank has its own H, L, and G Common terminals to which the
channel switches connect.
The channel switches also connect, through the AT and BT Tree Switches,
to the AT and BT Tree Switch Terminals, respectively. The Bank 0 channels
connect to the AT Tree Switch Terminals and the Bank 1 channels connect
to the BT Tree Switch Terminals. An additional tree switch, the AT2 Tree
Switch, provides connection of the Bank 1 channels to AT Tree Switch
Terminals. Use channel numbers 90, 91, and 92 to select the AT, BT, and
AT2 Tree Switches, respectively.
Connecting to the Tree Switch Terminals is the preferred method to connect
measuring devices, like multimeters, to measure the multiplexer channels.
This allows you to connect the measuring device to either the Bank 0 or
Bank 1 channels at any given time, or to the channels of both banks.
Getting Started 11Chapter 1
The AT Tree Switch Terminals also connect to the H, L, and G connections
on the Analog Bus Connector. The BT Tree Switch Terminals also connect
to the I+, I-, and IG connections on the Analog Bus Connector. The Analog
Bus Connector provides direct channel connections between multiple
multiplexer modules, and connections between a multiplexer module and
the E1326/E1411 Multimeters. Cables make the necessary connections
without the need to externally wire the multimeter/multiplexer modules via
the terminal modules.
The 16-Channel Thermocouple Relay Multiplexer Modules (E1344A and
E1347A) uses the RT Tree Switch (Channel 93) to connect the thermistor on
the terminal module to the Bank 1 channel common. The thermistor can be
measured to determine the temperature inside of the terminal module to
compensate for temperature measurements made with thermocouples (see
Chapter 3).
Each channel High (H) line has a jumper on the terminal module that may
be removed to add filter components (see Chapter 2 under the “Adding
Signal Conditioning Components/Current Shunts” heading). Each Bank 0
and Bank 1 common line, the AT and BT Tree Switch, and the Analog Bus
lines all have 100 ohm resistors in series with each line. The resistors
provide relay protection and are located on the component module.
12Getting Started Chapter 1
Figure 1-1. Multiplexer Module Block Diagram
Getting Started 13Chapter 1
Programming the Multiplexer Module
The multiplexer modules are programmed either in a switchbox or scanning
voltmeter configuration. To program the multiplexer modules using the
Standard Commands for Programmable Instruments (SCPI), you must select
the controller language, interface address, and SCPI commands to be used.
See the 75000 Series B Installation and Getting Started Guide or the E1406 Command Module Manual for interface addressing and controller
language information of multiplexer modules in a switchbox or scanning
voltmeter configuration. If using the E1300 Mainframe or E1405
Command Module, you MUST have version 06.00 (or greater)
firmware for the Multiplexer Modules to properly identify.
NoteThis discussion applies to SCPI programming. See Appendix B
(“16-Channel Relay Multiplexer Registers”) for details on multiplexer
modules registers.
Selecting ChannelsTo address specific channels within a multiplexer module in a switchbox or
scanning voltmeter configuration, you must:
• send the appropriate SCPI command string to the switchbox or
scanning voltmeter (e.g.,
CLOSe, OPEN, etc.)
Multiplexer Card
Numbers
• specify the card number
• specify the channel number
The card number identifies the module within a switchbox or scanning
voltmeter configuration. The switch module with the lowest logical address
is always card number 01. The card number with the next successive logical
address is 02, and so on. Figure 1-2 illustrates the card number and logical
address of a typical single module switchbox.
Figure 1-2. Card Numbers for a Single Module Switchbox
14Getting Started Chapter 1
Figure 1-3 illustrates the card numbers and logical addresses of a typical
multiple module switchbox. Figure 1-4 illustrates the card numbers of a
typical multiple module scanning voltmeter.
Figure 1-3. Card Numbers for a Multiple Module Switchbox
The logical addresses noted in Figures 1-2, 1-3, and 1-4 apply to modules
installed in an 75000 Series B Mainframe (Model Number E1300/E1301) or
in a mainframe with an E1405/E1406 Command Module. See the 75000
Series B Installation and Getting Started Guide or the E1406 Command
Module Manual for more information on switchboxes and scanning
voltmeter configurations, and logical addressing. If using the E1300
Mainframe or E1405 Command Module, you MUST have version 06.00
(or greater) firmware for the 16-Channel Multiplexer Modules to
properly identify. For uses in other systems or mainframes, see the
appropriate manuals.
Figure 1-4. Card Numbers for a Multiple Module Scanning Voltmeter
Getting Started 15Chapter 1
Multiplexer Channel
Address
For the 16-Channel Multiplexers, the channel address (channel_list) is in the
form:
(@ccnn) for a single channel;
(@ccnn,ccnn) for multiple channels;
(@ccnn:ccnn) for sequential channels;
(@ccnn:ccnn,ccnn:ccnn) for groups of sequential channels;
or any combination of the above.
where "cc" is the card number and "nn" is the channel number.
For example, the command string to close channel 02 of card number 1 is:
CLOSe (@0102)
Since "cc" (the card number) must be sent, it becomes part of the channel
number. Also, you can ignore leading zeros in the card numbers. Thus, to
close channel 02, send "102" instead of "0102". To close the above channel,
execute:
CLOSe (@102)
SCPI Command
Format Used in This
Manual
You can send SCPI commands in either a short or long form. A long form
example is:
CLOSe (@102)
The same command shown without the lower case letters is the short form.
The command then becomes:
CLOS (@102)
Some commands in this manual are shown with brackets ([ ]). These are
implied or optional commands that you do not have to execute. For example,
the
ROUT command is an implied command and is shown in this manual as:
[ROUT:]CLOS (@102)
Thus, to execute these commands, simply enter:
CLOS (@102)
See Chapter 5 for more explanation about SCPI commands and how to send
them.
16Getting Started Chapter 1
Initial Operation
Use the following program example to verify initial multiplexer operation
by closing a channel and querying channel closure. The example first resets
the switchbox and then closes channel 02 of a single multiplexer module
(card number 1) in the switchbox. The program next queries the channel
closure state. A returned "1" shows that the command to close the channel
has been sent to the switchbox. A returned "0" shows that the command to
close the channel has not been sent to the switchbox.
The computer used in the example is an Series 200/300 computer with
BASIC as the program language. The computer interfaces to the mainframe
using the General Purpose Interface Bus (GPIB)
1
. The GPIB interface select
code is 7, the primary address is 09, and the secondary address is 14. Refer
to the 75000 Series B Installation and Getting Started Guide for addressing
information.
Example: Reset the switchbox and close channel 02
10 OUTPUT 70914;"*RST"
20 OUTPUT 70914;"CLOS (@102)"
30 OUTPUT 70914;"CLOS? (@102)"
40 ENTER 70914;Value
50 PRINT Value
60 END
Opens all channels.
Close channel 02.
Query channel 02 state.
Enter results into Value.
Display result.
1. GPIB is Agilent Technologies’ implementation of IEEE-488.2
Getting Started 17Chapter 1
Notes:
18Getting Started Chapter 1
Chapter 2
Configuring the Relay Multiplexer Modules
This chapter shows how to connect external wiring to the 16-Channel Relay
Multiplexer Modules, and how to configure them:
WARNINGSHOCK HAZARD. Only service-trained personnel who are aware of
the hazards involved should install, remove, or configure the
modules. Before installing any module, disconnect AC power from
the mainframe and from user wiring.
To prevent electrical shock, all wires to the channel connections must
be insulated to at least 120 Vrms (170 V peak).
CautionMAXIMUM VOLTAGE/CURRENT. Maximum voltage that may be
applied between High (H), Low (L), and Guard (G) terminals is 170 V
dc or 120 V rms (170 V peak) for the E1345A/47A or 250 V dc or AC
RMS (354 V peak) for the E1343A/44A. Maximum current is 50mA
(non-conductive) per channel.
STATIC ELECTRICITY. Static electricity is a major cause of
component failure. To prevent damage to the electrical components
in the multiplexer module, observe anti-static techniques whenever
removing a module from the mainframe or whenever working on a
module.
Configuring the Relay Multiplexer Modules 19Chapter 2
Connecting Field Wiring
Figure 2-1 shows the terminal module for the 16-Channel High Voltage
Relay (E1343A), 16-Channel Relay (E1345A), 16-Channel General
Purpose Thermocouple High Voltage Relay (E1344A), and 16-Channel
Thermocouple Relay Multiplexer Modules (E1347A). Use the following
guidelines for wire connections.
Wiring Guidelines• If possible, use shielded cables with the shields connected to the Guard
(G) terminals and to the low connection near the measurement point.
• Be sure the wires make good connections on the screw terminals.
• For thermocouples, connect the Guard terminal to the thermocouple's
shield lead and the low connection near the measurement point.
Figure 2-1. Multiplexer Modules Connector Blocks
20Configuring the Relay Multiplexer Modules Chapter 2
Wiring a Terminal Module
Configuring the Relay Multiplexer Modules 21Chapter 2
Connecting the Analog Bus
Figure 2-2 shows how to connect the analog bus between multiple
multiplexer modules and to the E1326 Multimeter. Use the cables shipped
with the multiplexer modules to connect the analog bus of the multiplexer
modules. Use the cable shipped with the E1326 Multimeter to connect the
analog bus of the multiplexer module to the Multimeter input.
These cables are needed to connect the MUX when mounted in the E1403
Module Carrier to the E1411A/B DMM in a C-size cardcage. They must be
ordered separately.
1. Connecting E1411 to RELAY MUXs: use E1326-61611
(long analog bus cable).
2. Connecting RELAY to RELAY or RELAY to FET MUX:
use E1400-61605.
Figure 2-2. Analog Bus Connections Between Multiplexer/Multimeter Modules
22Configuring the Relay Multiplexer Modules Chapter 2
Setting the Card ID
The Card ID Jumpers indicate which terminal assembly is used. Since the
E1343-66201 and E1345-66201 assembly is used with a variety of terminal
modules, the ID jumpers may be changed. To reduce setup time and avoid
configuration errors, check the jumpers to make sure they match the terminal
module used.
When the relay multiplexers are shipped from the factory, the Card ID
Jumpers are set according to the terminal module (E1343/44/45/47/55/56)
shipped with them. The system is able to identify the multiplexer with or
without the terminal module attached.
NoteIf the jumper setting does not match the terminal module attached, the
system will identify the card based on the jumper setting.
Setting the Logical Address Switch
The address switch (LADDR) factory setting is 112. You may have changed
the setting during module installation. Valid address values are from 0 to
255. Refer to the 75000 Series B System Installation and Getting Started Guide or the E1406 Command Module Manual for addressing information.
Otherwise, to change the setting, refer to the Figure 2-3.
Figure 2-3. Locate and Set the Logical Address Switch
Configuring the Relay Multiplexer Modules 23Chapter 2
Using the Multiplexer Module with an Agilent Mainframe
or Command Module
To program the multiplexer modules with an E1300A/01A Mainframe or an
1405B/E1406A Command Module, the modules must be configured as an
instrument. If using the E1300 Mainframe or E1405 Command Module,
you MUST have version 06.00 (or greater) firmware for the 16-Channel
Multiplexer Modules to properly identify. An instrument configuration
for the multiplexer modules must be a:
• Scanning Voltmeter - Used with an E1326B/E1411A Multimeter.
• Switchbox - Used with other switch type modules, like other
multiplexer modules, etc.
(The above requirements are not necessary if using register-based
programming to program the modules.)
Using the Scanning
Voltmeter
Configuration
Use this configuration for:
1. Easiest system programming.
2. Fastest execution speed.
3. Thermocouple measurements if using the E1326B/E1411B
temperature function.
To use this configuration, set the multimeter's logical address to a multiple
of 8. Also set the first multiplexer module's logical address to the next
address value, the second module to the next address value, and so on. The
following shows the logical address settings of a Scanning Voltmeter with
the multimeter address set to 24.
Logical AddressModuleChannels
24E1326B/E1411AN/A
25E1345A/E1347A100-115
26E1345A/E1347A200-215
To program the scanning voltmeter, use the programming information in the
appropriate multimeter manual.
24Configuring the Relay Multiplexer Modules Chapter 2
Using the
Use this configuration when:
Switchbox
Configuration
Verifying Correct
Logical Address
Settings
1. Simultaneously closing multiple channels on multiple modules.
2. Other multimeters/modules cannot control the multiplexer modules.
To use this configuration, set the first multiplexer module's logical address
to a multiple of 8. Set the next multiplexer module's logical address to the
next address value, the third module to the next address value, and so on.
The following shows the logical address settings of a switchbox with the
first multiplexer module address set to 112.
Logical AddressModuleChannels
112E1345A/E1347A100-115
113E1345A/E1347A200-215
114E1345A/E1347A300-315
To program the switchbox, use the programming information in this manual.
To verify that the modules have the correct logical address setting, query the
E1300A/E1301A Mainframe or E1405B/E1406A Command Module as
follows:
E1301A Mainframe - From the “Select a Instrument” prompt of the front
panel, select the following menus:
SYSTEM
CONFIG?
LADDS
E1300A Mainframe, E1405B, or E1406A Command Module with an
RS-232 Terminal - From the “Select an Instrument” prompt, select the
following menus:
SYSTEM
CONFIG?
LADDS
If no front panel or RS-232 terminal is available, send the following SCPI
query command to the mainframe/command module:
VXI:CONF:DLAD?
The returning string contains all logical addresses in the system.
Configuring the Relay Multiplexer Modules 25Chapter 2
Selecting the Interrupt Priority
The multiplexer modules generate interrupts after a channel relay closing or
opening completes. These interrupts set the selected line on the VXI
peripheral interrupt bus true.
The VXI peripheral interrupt bus consists of 7 interrupt priority lines that
carry the interrupt signal to the commander. Line 1 has the highest priority
and line 7 the lowest. The multiplexer module's default setting is line 1, since
it is the most commonly used interrupt line.
The E1300A/E1301A Mainframe default operation is to monitor all seven
interrupt lines. The E1405B/E1406A Command Module's default operation
is to manage only one line. The Command Module does, however, use an
interrupt line allocation table that allows you to select which lines the
command module is to monitor. For embedded controllers, refer to the
appropriate controller documentation to determine which of the line(s) the
controller monitors.
When using an E1300A/E1301A Mainframe or E1405B/E1406A Command
Module for register-based programming (instead of the SCPI driver) and
where the program generates an interrupt, be sure to use the multiplexer
module's interrupt line that does not interfere with the program. Use the line
that is not used by the SCPI driver to generate interrupts.
Refer to Figure 2-4 to change the interrupt priority. Unsolder and remove
two jumpers from the old priority location. Install the jumpers in the new
priority location (Figure 2-4 shows a priority change from 1 to 7).
Figure 2-4. Changing the Priority Interrupt Level Jumpers
26Configuring the Relay Multiplexer Modules Chapter 2
5 Volt Excitation for Strain Gages
The E1345-66201 is used with a variety of terminal modules including the
E1355A and E1356A Strain Gage Multiplexers. When used with these strain
gages, the jumpers JM1 and JM2 may be installed to provide 5 volt
excitation to the strain gage bridge. This voltage is fused at 4A. Channel x93
is used to sense it.
Jumpers JM1 and JM2 must be removed when used with the E1347A
Thermocouple terminal module. This must be done because the connector
pins in this case are used to sense the 5k Ohm thermistor on the terminal
module.
When the relay multiplexer is shipped from the factory, the jumpers are not
installed.
Adding Signal Conditioning Components/Current Shunts
The multiplexer module's terminal module allows you to add components on
each channel for:
-- Low-Pass Filters
-- Attenuators
-- Current Shunts (for current measurements using a voltmeter)
Figure 2-5 shows how to install the appropriate components for the above
configurations. In the figure, channel 12 shows a low pass filter
configuration, channel 07 an attenuator configuration, and channel 04 a
current shunt configuration.
Configuring the Relay Multiplexer Modules 27Chapter 2
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.