No part of this manual may be reproduced
in any form or by any means (including
electronic storage and retrieval or translation into a foreign language) without prior
agreement and written consent from Agilent Technologies, Inc. as governed by
United States and international copyright
laws.
Certification
Agilent Technologies certifies that this
product met its published specifications at
the time of shipment from the factory. Agilent Technologies further certifies that its
calibration measurements are traceable to
the United States National Institute of
Standards and Technology (NIST, formerly
NBS), to the extend allowed by the Institute’s calibration facility, and to the calibration facilitiesof the other International
Standards Organization members.
Manual Part Number
11713-90024
Edition
First edition, October 2007
Printed in Malaysia
Agilent Technologies, Inc.
Phase 3 Bayan Lepas Free Industrial Zone
Penang, 11900 Malaysia
Warranty
The material contained in this document is provided “as is,” and is subject to being changed, without notice,
in future editions. Further, to the maximum extent permitted by applicable
law, Agilent disclaims all warranties,
either express or implied, with regard
to this manual and any information
contained herein, including but not
limited to the implied warranties of
merchantability and fitness for a particular purpose. Agilent shall not be
liable for errors or for incidental or
consequential damages in connection
with the furnishing, use, or performance of this document or of any
information contained herein. Should
Agilent and the user have a separate
written agreement with warranty
terms covering the material in this
document that conflict with these
terms, the warranty terms in the separate agreement shall control.
Technology Licenses
The hardware and/or software described in
this document are furnished under a
license and may be used or copied only in
accordance with the terms of such license.
Restricted Rights Legend
computer software” as defined in FAR
52.227-19 (June 1987) or any equivalent
agency regulation or contract clause. Use,
duplication or disclosure of Software is
subject to Agilent Technologies’ standard
commercial license terms, and non-DOD
Departments and Agencies of the U.S. Government will receive no greater than
Restricted Rights as defined in FAR
52.227-19(c)(1-2) (June 1987). U.S. Government users will receive no greater than
Limited Rights as defined in FAR 52.227-14
(June 1987) or DFAR 252.227-7015 (b)(2)
(November 1995), as applicable in any
technical data.
Safety Notices
CAUTION
A CAUTION notice denotes a hazard. It calls attention to an operating procedure, practice, or the like
that, if not correctly performed or
adhered to, could result in damage
to the product or loss of important
data. Do not proceed beyond a
CAUTION notice until the indicated
conditions are fully understood and
met.
WARNING
A WARNING notice denotes a
hazard. It calls attention to an
operating procedure, practice, or
the like that, if not correctly performed or adhered to, could result
in personal injury or death. Do not
proceed beyond a WARNING
notice until the indicated conditions are fully understood and met.
If software is for use in the performance of
a U.S. Government prime contract or subcontract, Software is delivered and
licensed as “Commercial computer software” as defined in DFAR 252.227-7014
(June 1995), or as a “commercial item” as
defined in FAR 2.101(a) or as “Restricted
General Safety Information
The following general safety precautions must be observed during all phases of operation of this instrument. Failure to comply with these precautions or with specific warnings elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. Agilent
Technologies, Inc. assumes no liability for the customer’s failure to comply with these regulations.
NOTE
The 11713B/C complies with INSTALLATION CATEGORY II as well as POLUTION DEGREE 2 in
IEC61010-1. The 11713B/C is an INDOOR USE product.
Before applying power
Verify that all safety precautions are taken. Make all connections to the unit before applying power.
Gound the instrument
This product is provided with protective earth terminals. To minimize shock hazard, the instrument must
be connected to the ac power mains through a grounded power cable, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet. Any interruption of the protective
(grounding) conductor or disconnection of the protective earth terminal will cause a potential shock
hazard that could result in personal injury.
DO NOT operate the product in an explosive atmosphere or in the presence
of flammable gases or fumes
DO NOT use repaire fuses or short-circuited fuse holders
For continued protection against fire, repalce the line fuse(s) only with fuse(s) of the same voltage and
current rating and type.
Do Not Remove the Instrument Cover
Only qualified, service-trained personnel who are aware of the hazards involved should remove the
instrument covers. Always disconnect the power cable and any external circuits before removing the
instrument cover.
Do Not Modify the Instrument
Do not install substiture parts or perform any unauthorized modification to the instrument. Return the
instrument to an Agilent Sales and Service Office for service and repair to ensure that safety features
are maintained.
In Case of Damage
Instruments that appear damaged or defective should be made inoperative and secured against unintended operation until they can be repaired by qualified, service-trained personnel.
11713B/C Operating and Service Manual3
Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC
This product complies with the WEEE Directive (2002/96/EC)
marking requirements. The affixed label indicates that you must not
discard this electrical/electronic product in domestic household
waste.
Product Category:
With reference to the equipment types in the WEEE Directive Annex
1, this product is classed as a “Monitoring and Control
Instrumentation” product.
The affixed product label is shown as below:
Do not dispose in domestic household waste.
To return unwanted products, contact your local Agilent office, or
visit:
www.agilent.com/environment/product
for more information.
411713B/C Operating and Service Manual
Safety Symbols
The following symbols on the instrument aand in the documentation
indicate precautions that must be taken to maintain safe operation of
the instrument.
Alternating current
Earth (grounding) terminal
Off (supply)
On (supply)
Caution, risk of danger (refer to this manual for specific
Warning or Caution information)
11713B/C Operating and Service Manual5
Contacting Agilent
For more information, please contact your nearest Agilent office.
Americas
Canada
Latin America
United States
(877) 894-4414
305 269 7500
(800) 829-4444
Asia Pacific
Australia
China
Hong Kong
India
Japan
Korea
Malaysia
Singapore
Taiwan
Thailand
Austria
Belgium
Denmark
Finland
France
Germany
Ireland
Italy
Netherlands
Spain
Sweden
Switzerland(French)
Switzerland(German)
United Kingdom
Other European Countries:
Bench Operation27
Figure 5. Handle Positioning for Bench Operation27
Rack Mounting One Instrument (Option 908)28
Figure 6. Illustrations of steps 2 and 328
Rack Mounting Two Instruments (Option 909)29
Figure 7. Illustration of completed setup29
Connecting to Agilent Attenuators and Switches30
Table 5. Summary of switches and attenuators connections to
11713B/C30
Table 6. 11713CB/C Front Panel and Back Panel Properties32
Driving Four-Section Attenuators and Switches33
Figure 8. Typical connection for a programmable four-section
Safety Considerations41
Compliance With Electromagnetic Compatibility (EMC)41
Compliance With German Noise Requirement41
4Verification
5Local Operations
Regularity Markings42
Declaration of Conformity43
Operator’s Check for Local Operation46
Recommended Test Equipment46
Table 10. Recommended Test Equipment46
Procedure47
Figure 12. Switching System for Verification47
Operator’s Check for Remote Operation48
Getting Started with 11713B/C50
Step One: Turn on 11713B/C50
Step Two: Configure 11713B/C settings to drive attenuators and
switches51
Step Three: Configure 11713B/C connections to attenuators and
switches55
Table 11. Connection between 11713B/C and programmable
attenuators55
Table 12. Connection between 11713B/C and switches55
811713B/C Operating and Service Manual
Main Menu of 11713B/C56
Save/Recall State Menu62
6Remote Operations
Configuring Remote Interface66
Programming Guide (SCPI)68
SYSTEM Menu56
ATT E N M enu57
CYCLE Menu58
IO Menu59
INFO Menu59
UTILITY Menu60
Preset Menu61
List of Default Values63
Interface Selection66
GPIB Configuration66
USB Configuration67
LAN Configuration67
SCPI Command Syntax68
Rules for Using a Channel or Scan List68
Commands Relevant to Attenuators69
Commands Relevant to Switches71
Programming Guide (Legacy)73
Data Message Input Format73
SCPI and Legacy Commands Compatibility74
7Remote Interface Configurations
Connecting the 11713B/C to Your Computer76
Connecting Over GPIB76
Connecting Over USB78
Connecting Over LAN79
Exploring the 11713B/C Web Interface Over LAN85
Launching the Web Interface85
Figure 13. 11713B/C Web Interface’s Welcome Window86
Navigation Bar86
Displaying the Browser Web Control Page87
Figure 14. 11713B/C Brower Web Control Interface87
8Replacing Major Assemblies
Replaceable Parts90
11713B/C Operating and Service Manual9
Table 13. Major Assemblies Reference Designator and Part
Number90
Table 14. Front Panel Module Reference Designator and Part
Number90
Table 15. Rear Panel Module Reference Designator and Part
Number91
Table 16. PPMC PCA Module Reference Designator and Part
Number91
Table 17. Fan Module Reference Designator and Part Number92
Table 19. Power Supply Module Reference Designator and Part
Number93
Table 18. Motherboard Reference Designator and Part Number93
Top Module Cover Removal/Replacement94
To R em ove Top Mod ul e C ove r94
To Replace Top Module Cover94
Front Panel Module Removal/Replacement95
To Remove Front Panel Module95
To Replace Front Panel Module96
Rear Panel Module Removal/Replacement97
To Remove Rear Panel Module97
To Replace Rear Panel Module98
PPMC PCA Removal/Replacement99
To Remove PPMC PCA99
To Replace PPMC PCA99
Fan Module Removal/Replacement100
To R em ove Fa n M od u le100
To Replace Fan module100
Motherboard Removal/Replacement101
To Remove Motherboard101
To Replace Motherboard102
Power Supply Module Removal/Replacement103
To Remove Power Supply Module103
To Replace Power Supply Module103
9Servicing the Attenuator/Switch Driver
Preparing a Static-Safe Workstation106
Reducing ESD Damage107
Maintainance and Adjustments108
Fuse Removal/Replacement108
Adjustment108
1011713B/C Operating and Service Manual
Troubleshooting109
Isolating a Malfunction109
Front Panel Troubleshooting110
Rear Panel Troubleshooting111
Figure 15. Motherboard with Marked Location of Figure 17 and Figure
18111
Figure 16. Location of TP1 and TP2 on motherboard112
Figure 17. Location of TP3, TP4 and TP5 on Motherboard113
11713B/C Operating and Service Manual11
1211713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
1
Introduction
Key Features of Agilent 11713B/C Attenuator/Switch Drivers 14
Compatible Agilent Attenuators and Switches 15
“Connecting Accessories
11713B Front and Rear Panels at a Glance 17
11713C Front and Rear Panels at a Glance 20
This chapter provides you the overview of Agilent 11713B/C
attenuator/switch drivers that includes the instruments’
functions and capabilities, compatibility with Agilent
switching components and physical appearances.
Agilent Technologies
13
1Introduction
Key Features of Agilent 11713B/C Attenuator/Switch Drivers
The 11713B attenuator/switch driver is a GPIB compatible
instrument that concurrently drives up to two four- section
programmable step attenuators and two microwave coaxial switches,
or up to 10 SPDT switches. The 11713B is fully backward compatible
with 11713A in terms of functionality and fit. Connectivity using
USB and LAN are optional.
The 11713C attenuator/switch driver is a GPIB/USB/LAN compatible
instrument that concurrently drives up to four four-section
programmable step attenuators and four microwave coaxial switches,
or up to 20 SPDT switches. The 11713C comes with tri- voltage
selection of +5 V, +15 V and +24 V and also permits user- defined
voltage supply capability.
NOTE
The 11713B/C attenuator/switch drivers output continuous current and do not
support pulse drive. Please ensure your switching devices can withstand continuous
current or have a built-in current interrupt feature.
Tab le 1Key Features of 11713B/11713C
Key Features11713B11713C
Manually-controlled using front panel push buttonsYesYes
Automatically-control through:
GPIB
USB
LAN
Integrated LCD displayYesYes
Self-contained power supply with current limitingYesYes
The 11713B/C attenuator/switch drivers are designed to drive the
following Agilent attenuators and switches. If you are using
attenuators and switches made by another supplier, check the
switching characteristics against those specified in Chapter 3,
“Specifications. Refer to Agilent 11713B/C Configuration Guide,
literature number 5989- 7277EN, for the most updated list.
8494G/H (33320G/H), 84904K/L/M (33324K/L)11 dB, 1 dB steps
8495G/H/K (33321 G/H/K), 84907K/L (33327K/L)70 dB, 10 dB steps
8496G/H (33322G/H)110 dB, 10 dB steps
8497K ( 33323K), 84906K/L ( 33326K/L)90 dB, 10 dB steps
84905M60 dB, 10 dB steps
84908M65 dB, 5 dB steps
11713B/C Operating and Service Manual15
1Introduction
Connecting Accessories
Various types of connecting accessories are available to drive Agilent
attenuators and switches using the 11713B/C attenuator/switch
drivers. Table 4 lists available accessories.
Tab le 4Connecting Accessories for Agilent 11713B/11713C
Connecting
Accessories
11716AInterconnect kit (Type-N connectors)
11716CInterconnect kit (SMA connectors)
11713B-001
11713C-001
11713B-101
11713C-101
11713B-201
11713C-201
11713B-301
11713C-301
11713B-401
11713C-401
11713B-501
11713C-501
11713B-601
11713C-601
11713B-701
11713C-701
11764-60004, Viking connector to 10-pin DIP connector, 60 inches long
8120-2703, Viking connector to Viking connector, 60 inches long
5061-0969, Viking connector to 12-Pin conductor cable, bare wire (for
five switches), 60 inches long
11761-60001, Viking connector to (4) ribbon cables, connect up to four
switches, 60 inches long
11713-60042, Dual Viking connector to 16-Pin DIP connector, 60 inches
long
11713-60043, Viking connector to (4) 9-Pin Dsub connectors, connect
up to four switches, 60 inches long
11713-60044, Viking connector to 16-Pin DIP connector, 60 inches long
5064-7848, Viking connector to 14-pin DIP connector, 60 inches long
Description
*
*
11713B-801
11713C-801
11713B-908
11713C-908
11713B-909
11713C-909
* Order this kit to connect two programmable step attenuators in series
11713-60047, Viking connector to (4) 10-pin DIP connectors, connect up
to 4 switches, 50 inches long
5063-9240, Rack mount kit for one instrument
5061-9694 & 5063-9212, Rack mount kit for two instruments
Refer to Agilent 11713A/B/C Attenuator/Switch Driver Configuration
Guide, literature number 5989- 3703EN, for configuration details.
1611713B/C Operating and Service Manual
11713B Front and Rear Panels at a Glance
This section briefly describes the function of the front panel keys of
11713B.
Introduction1
2
9
3
4
6
8
7
12
1
1
1
10
Figure 111713B Front Panel Features
1 LCD screen.
2 Softkeys. These unmarked keys are referred to by the text on
display next to them.
5
3 Menu/Enter. Press this key to select the highlighted parameter
On/Off or select the highlighted field or go back to the main
menu.
4 Preset. Press this key to preset the driver.
5 Config. Press this key to access the configuration menu. You can
set the atttenuator type, supply voltage and TTL condition through
this menu.
6 Save/Recall. Press this key to save current settings or recall saved
settings.
7 Navigation buttons. The arrow keys are used to navigate
parameters displayed on the LCD screen or change parameters
such as GPIB address.
11713B/C Operating and Service Manual17
1Introduction
8
Switches. In the local mode, pushbutton switches 9 and 0 change
the position of a coaxial switch connected to rear panel banana
jacks S9 A/B and S0 A/B respectively.
9 Attenuator Y. In the local mode, pushbuttons 5, 6, 7, and 8
change the attenuation setting of an attenuator or change the
position of coaxial switch(es) connected to the ATTEN Y
connector on the rear panel.
10 Attenuator X. In the local mode, pushbuttons 1, 2, 3, and 4
change the attenuation setting of an attenuator or change the
position of coaxial switch(es) connected to the ATTEN X
connector on the rear panel.
11 On/Standby. Press this key to switch between on and standby.
When power is supplied, the background LED is red. Pressing the
key once, switches the driver on and the background LED turns to
green.
12 Local. Press this key to control the driver from the front panel
when it is operating via the remote interfaces.
1811713B/C Operating and Service Manual
Introduction1
This section briefly describes the function of the rear panel
connectors of 11713B.
3
1
11
2
10
4
9
5
6
8
Figure 211713B Rear Panel Features
1 ATTEN X. Viking connector for connection to attenuator or
switch(es).
7
2 ATTEN Y. Viking connector for connection to attenuator or
switch(es).
3 S9 A/B. Banana jack connectors for connection to coaxial switch.
4 24 VDC COM. Banana jack connector to provide common +24 Vdc
in driving the coaxial switches connected to S9 and/or S0.
5 S0 A/B. Banana jack connectors for connection to coaxial switch.
6 Receptacle. Matches transformer primary to line voltage via power
cable.
7 Alert symbol. This symbol is used to point out a necessary
reference for the user.
8 GPIB Connector. The interface connector from a source device to
a listening device for the remote mode of operation.
9 LAN Connector. The interface connector for LAN cable (option
LXI only).
10 USB Connector. The interface connector for Type mini B 5- pin
USB cable (option LXI only).
11 Instrument Markings.
11713B/C Operating and Service Manual19
1Introduction
11713C Front and Rear Panels at a Glance
This section briefly describes the function of the front panel keys of
11713C.
17
16
1
15
14
2
12
13
11
3
4
5
6
7
10
8
9
Figure 311713C Front Panel Features
1 LCD screen.
2 Softkeys. These unmarked keys are referred to by the text on
display next to them.
3 Navigation buttons. The arrow keys are used to navigate
parameters displayed on the LCD screen or change parameters
such as GPIB address.
4 Menu/Enter. Press this key to select the highlighted parameter
On/Off or select the highlighted field or go back to the main
menu.
5 Preset. Press this key to preset the driver.
6 Config. Press this key to access the configuration menu. You can
set the atttenuator type, supply voltage and TTL condition through
this menu.
7 Save/Recall. Press this key to save current settings or recall saved
settings.
8 Supply Voltage for Bank 1. Indicates supply voltage setting
(background LED in red) for bank 1.
2011713B/C Operating and Service Manual
Introduction1
Supply Voltage for Bank 2. Indicates supply voltage setting
9
(background LED in red) for bank 2.
10 Switches for Bank 1. In the local mode, pushbutton switches 9
and 0 change the position of a coaxial switch connected to rear
panel banana jacks S9 A/B and S0 A/B respectively, for bank 1.
11 Switches for Bank 2. In the local mode, pushbutton switches 9
and 0 change the position of a coaxial switch connected to rear
panel banana jacks S9 A/B and S0 A/B respectively for, bank 2.
12 Attenuator Y for Bank 1. In the local mode, pushbuttons 5, 6, 7,
and 8 change the attenuation setting of an attenuator or change
the position of coaxial switch(es) connected to the ATTEN Y
connector on the rear panel, for bank 1.
13 Attenuator Y for Bank 2. In the local mode, pushbuttons 5, 6, 7,
and 8 change the attenuation setting of an attenuator or change
the position of coaxial switch(es) connected to the ATTEN Y
connector on the rear panel, for bank 2.
14 Attenuator X for Bank 1. In the local mode, pushbuttons 1, 2, 3,
and 4 change the attenuation setting of an attenuator or change
the position of coaxial switch(es) connected to the ATTEN X
connector on the rear panel, for bank 1.
15 Attenuator X for Bank 2. In the local mode, pushbuttons 1, 2, 3,
and 4 change the attenuation setting of an attenuator or change
the position of coaxial switch(es) connected to the ATTEN X
connector on the rear panel, for bank 2.
16 On/Standby. Press this key to switch between on and standby.
When power is supplied, the background LED is red. Pressing the
key once, switches the driver on and the background LED turns to
green.
17 Local. Press this key to control the driver from the front panel
when it is operating via the remote interfaces.
11713B/C Operating and Service Manual21
1Introduction
This section briefly describes the function of the rear panel
connectors of 11713C.
3
1
2
18
5
4
17
7
6
8
16
9
11
10
12
13
15
14
Figure 411713C Rear Panel Features
1 ATTEN X Bank 1. Viking connector for connection to attenuator
or switch(es), for bank 1.
2 ATTEN X Bank 2. Viking connector for connection to attenuator
or switch(es), for bank 2.
3 ATTEN Y Bank 1. Viking connector for connection to attenuator
or switch(es), for bank 1.
4 ATTEN Y Bank 2. Viking connector for connection to attenuator
or switch(es), for bank 2.
5 S9 A/B Bank 1. Banana jack connectors for connection to coaxial
switch, for bank 1.
6 S9 A/B Bank 2. Banana jack connectors for connection to coaxial
switch, for bank 2.
7 VDC COM Bank 1. Banana jack connector to provide common
Vdc in driving the coaxial switches connected to S9 and/or S0, for
bank 1.
8 VDC COM Bank 2. Banana jack connector to provide common
Vdc in driving the coaxial switches connected to S9 and/or S0, for
bank 2.
2211713B/C Operating and Service Manual
Introduction1
S0 A/B Bank 1. Banana jack connectors for connection to coaxial
9
switch, for bank 1.
10 S0 A/B Bank 2. Banana jack connectors for connection to coaxial
switch, for bank 2.
11 External VDC. Banana jack connector to provide user-defined
Vdc, for both banks.
12 Ground. Banana jack connector to provide grounding, for both
banks.
13 Receptacle. Matches transformer primary to line voltage via power
cable.
14 Alert symbol. This symbol is used to point out a necessary
reference for the user.
15 GPIB Connector. The interface connector from a source device to
a listening device for the remote mode of operation.
16 LAN Connector. The interface connector for LAN cable.
17 USB Connector. The interface connector for Type mini B 5- pin
USB cable.
18 Instrument Markings.
11713B/C Operating and Service Manual23
1Introduction
2411713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
2
Installation
Initial Inspection 26
Preparing for Use 27
“Bench Operation
“Rack Mounting One Instrument (Option 908)
“Rack Mounting Two Instruments (Option 909)
Connecting to Agilent Attenuators and Switches 30
Driving Four-Section Attenuators and Switches 33
Driving Additional Coaxial Switches 34
Driving Relays 36
This chapter provides you important information on how to
unpack and check your instrument, how to prepare your
instrument for bench operation and tips on configuring
11713B/C with Agilent attenuators and switches.
Agilent Technologies
25
2Installation
Initial Inspection
1 Unpack and inspect the shipping container and its contents
thoroughly to ensure that nothing was damaged during shipment.
If the shipping container or cushioning material is damaged, the
contents should be checked both mechanically and electrically.
2 If the contents are damaged or defective, contact your nearest
Agilent Technologies Service and Support Office. Refer to the
Service and Support information in the front matter of this
manual. Agilent Technologies will arrange for repair or
replacement of the damaged or defective equipment. Keep the
shipping materials for the carrier's inspection.
3 If you are returning your instrument for service, repackaging the
attenuator/switch driver requires original shipping containers and
materials or their equivalents. Agilent Technologies can provide
packaging materials identical to the original materials. Refer to
"Service and Support" on page v for the Agilent Technologies
nearest you.
2611713B/C Operating and Service Manual
Preparing for Use
Bench Operation
Installation2
Pull the handle outwards, and adjust it into one of the two positions
illustrated in Figure 5.
• (Top) Handle placed underneath the instrument to assure
self- alignment of the instruments when stacked
• (Bottom) Handle tilted to raise the front of the instrument for
easier viewing of the front panel
Figure 5Handle Positioning for Bench Operation
11713B/C Operating and Service Manual27
2Installation
Rack Mounting One Instrument (Option 908)
1 Remove the handle and front/rear bumpers
2 Fit the rack mount flanges (part number 5063- 9240)
3 Ready for installation
Figure 6Illustrations of steps 2 and 3
CAUTION
When installing the product in a cabinet, the convection into and out of the
product must not be restricted. The ambient temperature (outside the cabinet)
must be less than the maximum operating temperature of the product by 4 °C for
every 100 watts dissipated in the cabinet. If the total power dissipated in the
cabinet is greater than 800 watts forced convection must be used.
2811713B/C Operating and Service Manual
Rack Mounting Two Instruments (Option 909)
1 Remove the handle and front/rear bumpers
2 Fit one small mounting flange to opposite sides of each
instrument (part numbers 5061- 9694 and 5063- 9212)
3 Fit two front linking plates to each instrument
4 Engage the linking plates at the front of the instruments
5 Attach the rear linking brackets
6 Ready for installation
Installation2
Figure 7Illustration of completed setup
CAUTION
When installing the product in a cabinet, the convection into and out of the
product must not be restricted. The ambient temperature (outside the cabinet)
must be less than the maximum operating temperature of the product by 4 °C for
every 100 watts dissipated in the cabinet. If the total power dissipated in the
cabinet is greater than 800 watts forced convection must be used.
11713B/C Operating and Service Manual29
2Installation
Connecting to Agilent Attenuators and Switches
The 11713B/C attenuator/switch drivers can be used to drive various
switches and attenuators. Table 5 shows the summary of switches
and attenuators connections to 11713B/C, with various interface
cables for point- to- point connection. Table 6 shows the properties of
11713B/C’s front panel and rear panel.
For configuration details, please refer to Agilent 11713B/C
Configuration Guide, literature number 5989- 7277EN.
Tab le 5Summary of switches and attenuators connections to 11713B/C
Switches/Attenuators11713B/C
Cable
*
Option
Switches
• 8761A/B
Switches
• 8762A/B/C/F
• 8763A/B/C
2011NoYes
2012YesYes
• 8764A/B/C
Switches
• 8765A/B/C/D/F
Switches
• 8766K
Switches
• N1810UL/TL
• N1811TL
• N1812UL
Switches
‡
‡
‡
• 87222C/D/E
201, 3012YesYes
001, 101
201, 5012YesYes
201, 8012YesNo
• L7222C
# of
channels
required
2
Control by
ATTEN X (1-4)
†
ATTEN Y (5-8)
Control by
SWITCHES
(9/0)
Ye sYe s
Switches
• 8767K
Attenuators
001, 1013YesYes
• 8495G/H
Switches
• 8767M
Attenuators
0013YesYes
• 84905M
• 84907K/L
3011713B/C Operating and Service Manual
Installation2
Tab le 5Summary of switches and attenuators connections to 11713B/C
Switches
• 8768K
Attenuators
• 8494G/H
001, 1014YesYes
• 8496G/H
• 8495K, 8497K
Switches
• 8768M
Attenuators
• 84904K/L/M
0014YesYes
• 84906K/L
• 84908M
Switches
• 87104A/B/C/D
• 87204A/B/C
201, 6014
**
Ye s
• L7104A/B/C
• L7204A/B/C
Ye s
Switches
• 8769K
Switches
• 8769M
Switches
1015YesYes
7015YesYes
• 87106A/B/C/D
• 87206A/B/C
• L7106A/B/C
201, 4016
††
Ye sYe s
• L7206A/B/C
• 87406B, 87606B
* Type of interface cable required depends on the DC connector on the switching device
† One channel represent control with one pushbutton
‡ Ensure switch is equiped with current interrupt (option 403) to protect switch from overhetaing and
destruction as this switch cannot withstand continuous current
**If option 601 is used, number of channels required is 5, to cater for open all path function controlled via
S9/S0
††If option 401 is used, number of channels required is 7, to cater for open all path function controlled via
S9/S0
11713B/C Operating and Service Manual31
2Installation
Tab le 611713CB/C Front Panel and Back Panel Properties
Front Panel Pushbuttons
*
Pushbutton NumberPushbutton
LEDs
SWITCHES
ONATTEN X-3 (S9-A)Gray
9
OFFATTEN X-4 (S9-B)White/Red
ONATTEN Y-3 (S0-A)Gray
0
OFFATTEN Y-4 (S0-B)White/Red
ATTENUATORS
XY
OFF5Violet
15
ON6Yellow
OFF7Black
26
ON8Green
Rear Panel Connectors
Pin NumbersWire Color Code
1Red (Vcc)
2White/Brown (Gnd)
†
37
OFF9Orange
ON10Blue
OFF11Brown
48
ON12White
* The ON/OFF status of the pushbutton LEDs indicates which cable wire or pin on the rear panel
connector is grounded. As an example, if ATTENUATOR X pushbutton 3 is illuminated, pin 10 of the
ATTEN X connector (blue wire from cable) is grounded and pin 9 floats at a high impedance. For
SWITCHES, if pin 3 is grounded (LED on), pin 4 is connected to +Vcc.
† With reference to interface cable option 201 (Viking connector to 12-pin bare), consists of 12
color-coded wires
3211713B/C Operating and Service Manual
11713B
Installation2
Driving Four-Section Attenuators and Switches
• To use one four- section attenuator assembly, connect an
attenuator interface cable either to the ATTEN X output (A6J1) or
ATTEN Y output (A6J2). Connect all outputs (two for 11713B and
four for 11713C) to have more than four attenuator segments.
• A typical connection for a programmable four- section attenuator
to 11713B is illustrated in Figure 8, together with pin number for
each connector.
• Using these same connections to Agilent 8762 or 8765 series
coaxial switches, control can be extended to number of switches
in multiple of four. If S9 and S0 outputs are utilized, 11713B and
11713C can drive up to 10 switches and 20 switches respectively.
11713B
Vcc
Vcc
TWO ATTENUATOR CABLES
ARE SUPPLIED WITH 11713B
Figure 8Typical connection for a programmable four-section attenuator
11713B/C Operating and Service Manual33
2Installation
Driving Additional Coaxial Switches
• Make switch connections to S0 outputs, S9 outputs, or to rear
panel ATTEN X output or ATTEN Y output.
• Figure 9 below shows the rear panel connections to S0 outputs
and the corresponding switch positions reflected by pushbutton
indicators.
• Connections to Agilent 8762 or 8765 series coaxial switches can
also be made to the ATTEN X output or ATTEN Y output as
illustrated in Figure 8.
Figure 9Typical connection for 8762 and 8765 series coaxial switches
3411713B/C Operating and Service Manual
Installation2
• Connections to Agilent 8761 series coaxial switches can only be
made to S0 outputs and S9 outputs.
• Figure 10 illustrates the rear panel connections to S9 outputs and
the corresponding switch positions reflected by pushbutton
indicators.
Figure 10 Typical connection for 8761 series coaxial switches
11713B/C Operating and Service Manual35
2Installation
Driving Relays
• To drive ten devices for 11713B, connect attenuator cables at
ATTEN X and Y and switch cables to S9 and S0.
• A total of 10 relays may be on at one time if the total curent is
less than 1.7 A. However, since there are dual transistor and relay
drivers, where one driver is on while the other is off, a total of 20
relays may be controlled.
NOTE
CAUTION
11713C is capable of driving double the amount of devices that 11713B can.
However, the total load current can be consumed is still 1.7 A.
If the total load current of 1.7 A is exceeded, damage may result.
• Figure 11 below shows the connections for a simplified relay
driving circuit. The circuit is adaptable for simple non-latching
relays.
Figure 11 Typical connection for relay driving circuit
NOTE
3611713B/C Operating and Service Manual
It is also recommended that two 28.7 V zener diodes be connected back-to-back
across the relay coils to reduce voltage transients.
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
Agilent 11713B/C attenuator/switch drivers are designed to fully
comply with Agilent Technologies’ product operating environmental
specifications shows in table below.
Tab le 911713B/C Environmental Specifications
Temperature
• Operating
• Storage
Humidity
• Operating
• Storage
• Condensing
Shock
• End-user handling
• Bench Handling
• Functional
• Transportation
0
°C to +50°C
°C to +70°C
-40
95% RH at 40
90% RH at 65
95% RH at 40
Half-sine: 2-3 ms duration, 60 in/s (1.6 ms) delta-V
Half-sine: 11 ms duration, 30 grms
Trapezoital: 18-22 ms duration, 337 in/s (8.56 ms) delta-V
Per MIL-PRF-28800F
°C, 5 days cyclic
°C, 24 hours
°C, 5 hours (condensation 15 minutes)
Vibration
• Operating
• Survival
Altitude
• Operating
• Non-operating
Random: 0.21G rms, 5 to 500 Hz, 10 min/axis
Random: 2.09G rms, 5 to 500 Hz, 10 min/axis
Swept-sine: 0.5 G rms, 5 to 500 Hz, 10 min/axis
This product has been designed and tested in accordance with IEC
61010- 1:2001, Safety Requirements for Electronic Measuring
Apparatus, and has been supplied In a safe condition. The
Instruction documentation contains information and warnings which
must be followed by the user to ensure safe operation and to
maintain the product In safe condition.
Compliance With Electromagnetic Compatibility (EMC)
This product conforms with the protection requirements of EMC
Directive 2004/108/EC for Electromagnetic Compatibility.
The conformity assessment requirements have been met using the
technical Construction file route to compliance, using EMC test
specifications EN 55011:1990 (Group 1, Class A).
Specifications3
In order to preserve the EMC performance of the product, any cable
which becomes worn or damaged must be replaced with the same
type and specifications.
Refer to the “Declaration of Conformity" on page 43.
Compliance With German Noise Requirement
Acoustic Noise EmissionThis is to declare that this instrument is in
conformance with the German Regulation on Noise Declaration for
Machines.
• LpA < 70 dB
• Operator position
• Normal position
• per ISO 7779
GerauschemissionLaermangabe nach der
Maschinenlaermrerordnung- 3.GSGV Deutschland.
• LpA < 70 dB
• am Arbeitsplatz
• normaler Betrieb
• nach DIN 45635 t.19
11713B/C Operating and Service Manual41
3Specifications
Regularity Markings
The following markings can be found on the rear panel.
The CE mark shows that the product complies with all the
relevant European Legal Directives.
ICES/NMB-001 indicates that this ISM device complies
with Canadian ICES-001.
Cet appareill ISM est conforme a la norme NMB-001 du
Canada.
The CSA mark is a registered trademark of the Canadian
Standards Association. A CSA mark with the indicators
“C” and “US” means that the product is certified for both
the U.S. and Canadian markets, to the applicable
American and Canadian standards.
This is the symbol of an Industrial Scientific and Medical
Group 1 Class A product.
The C-Tick mark is a registered trademark of the
Spectrum Management Agency of Australia. This
signifies compliance with the Australian EMC Framework
Regulations under the terms of the Radio
communications Act of 1992.
4211713B/C Operating and Service Manual
Declaration of Conformity
Specifications3
11713B/C Operating and Service Manual43
3Specifications
4411713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
4
Verification
Operator’s Check for Local Operation 46
“Recommended Test Equipment
“Procedure
Operator’s Check for Remote Operation 48
This chapter provides you simply instructions to verify
Agilent 11713B/C attenuator/switch drivers’ functionality in
both local operation and remote (GPIB/USB/LAN) operation.
Agilent Technologies
45
4Verification
Operator’s Check for Local Operation
Recommended Test Equipment
Table 10 lists the test equipment required for performance test
verification and equipment troubleshooting. Equipment other than
the recommended models can be used, provided minimum
specifications are satisfied.
Tab le 10 Recommended Test Equipment
Instrument TypeCritical SpecificationsUse
Digital Voltmeter0 to +30 VdcT
Attenuators (2 required)Programmable, 4 sectionsP, T
Switches (2 required)+5 Vdc, +15 Vdc or +24 Vdc
drive source
* P = Performance, T = Troubleshooting
P, T
*
4611713B/C Operating and Service Manual
Procedure
Verification4
1 Configure switching system illustrated in Figure 12 by following
all steps found in Chapter 5, “Local Operations.
Figure 12 Switching System for Verification
2 Once configuration is completed, press and depress the 10
numbered pushbuttons on the driver front panel. Each LED
should alternate between off and on as each key is pressed.
3 In addition, if any switching devices is connected (attenuators,
relays or switches), an audible click should be heard from the unit
actuated. Pressing any numbered pushbutton should not cause any
other push button to change state.
11713B/C Operating and Service Manual47
4Verification
Operator’s Check for Remote Operation
These procedure verify that the driver can be controlled remotely
using GPIB, USB and/or LAN.
1 Refer to Chapter 7, “Remote Interface Configurations, to connect
11713B/C to your computer through GPIB, USB and/or LAN.
2 Once remote connection is available, send the following SCPI
commands to the driver and note the changes on front panel
LEDs.
DescriptionCommandObservation
Close switching paths from
channel 1 to channel 4 (bank1)
Open switching paths from
channel 5 to channel 8 (bank 1)
Query status on channel 2 (bank 1)ROUTe:CLOSe? (@102)Return value “1” (LED for
Query status on channel 7 (bank 1)ROUTe:CLOSe? (@107)Return value “0” (LED for
ROUTe:CLOSe (@101:104)LEDs for pushbuttons 1 to
4 light ON
ROUTe:OPEn (@105:108)LEDs for pushbuttons 5 to
8 light OFF
pushbutton 2 light ON)
pushbutton 7 light OFF)
If the above checks are successful, the driver’s remote operation is
working correctly. These procedures do not check all of the drivers’s
program codes that can be executed. However, if the driver work
correctly from the front panel, there is a high probability that the
driver will respond to all the program codes.
4811713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
5
Local Operations
Getting Started with 11713B/C 50
“Step One: Turn on 11713B/C
“Step Two: Configure 11713B/C settings to drive attenuators and switches
“Step Three: Configure 11713B/C connections to attenuators and
switches
Main Menu of 11713B/C 56
“SYSTEM Menu
“ATTEN Menu
“CYCLE Menu
“IO Menu
“INFO Menu
“UTILITY Menu
Preset Menu 61
Save/Recall State Menu 62
List of Default Values 63
This chapter outlines the some simple steps to begin using
the 11713B/C in local operations. Also, functionality of all
menus are described to assist operations using 11713B/C.
Agilent Technologies
49
5Local Operations
Getting Started with 11713B/C
Agilent 11713B/C attenuator/switch driver can be easily configured
to drive programmable attenuators and/or switches through the front
panel operations. The following three simple steps will guide you
through the configuration of 11713B/C.
Step One: Turn on 11713B/C
NOTE
NOTE
For Step One, all details on 11713C is applicable to 11713B
1 Connect AC power supply to 11713B/C. You should see:
• background LED of the power button is red which indicates
that 11713B/C is in standby mode
Allow 10 seconds before pressing the power button to turn on 11713B/C. This
duration is needed to power up the processor within.
2 Press power button once to turn on the 11713B/C. You should see:
• background LED turns green
• six menus displayed on the LCD screen
• all numbered buttons are lighted up
1
3 Ensure Local button is lighted up to enable operation through
front panel. If not, press button once.
4 Now, you are ready to configure the 11713B/C.
1 At factory default setting. Last state is followed if instrument was configured before shut
down.
5011713B/C Operating and Service Manual
Local Operations5
Step Two: Configure 11713B/C settings to drive attenuators and switches
To drive programmable attenuators
NOTE
Step Two - to drive programmable attenuators, only item 2 is applicable to
11713B. When Config button is pressed, the next screen is CONFIGURATION
MENU.
ItemActionIllustration
1 Select bank
(only for
11713C)
2 Select
attenuator
type
a Press Config button
b At SELECT BANK
screen, you can see
two softkey
selections: BANK1
and BANK2
c Press BANK1 softkey
to select bank 1
d Press BANK2 softkey
to select bank 2
a At CONFIGURATION
MENU screen, press
ATTEN TYPE softkey
b At ATTENUATOR
MODEL screen, scroll
to highlight the
desired attenuator
model number using
the navigation keys.
c Once the attenuator
model is determined,
press ATTEN X or
ATTEN Y softkey to
assign the selected
attenuator model
d Repeat step b and c if
needed
e Model assigned to
ATTEN X and ATTEN Y
is marked <X> (e.g.
8494G/H) and <Y>
(e.g. 8496G/H)
respectively
f To return to the
previous screen, press
BACK softkey
11713B/C Operating and Service Manual51
5Local Operations
ItemActionIllustration
3 Select
voltage type
(only for
11713C)
a At CONFIGURATION
MENU screen, press
Voltage LEVEL softkey
b At OUTPUT VOLTAGE
screen, scroll to
highlight the desired
voltage (e.g. +5V)
c Press SET softkey to
assign highlighted
voltage
d At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel
e Ouput voltage
assigned is marked
<*>
f To exit this screen,
press BACK softkey
5211713B/C Operating and Service Manual
To drive switches
Local Operations5
NOTE
Step Two - to drive switches, only applicable to 11713C as 11713B is predefined
with +24 Vdc supply and no TTL drive
ItemActionIllustration
1 Select bank
(only for
11713C)
2 Select
voltage type
(only for
11713C)
a Press Config button
b At SELECT BANK
screen, you can see
two softkey
selections: BANK1
and BANK2
c Press BANK1 softkey
to select bank 1
d Press BANK2 softkey
to select bank 2
a At CONFIGURATION
MENU screen, press
TTL ON/OFF softkey
b At TTL MODE ON/OFF
screen, scroll to
highlight the TTL
OPTION or Non TTL
(e.g. TTL OPTION)
c Press SET softkey to
assign highlighted
voltage
d At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel
e Selection is marked
<*>
f To exit this screen,
press BACK softkey
\
11713B/C Operating and Service Manual53
5Local Operations
ItemActionIllustration
3 Select
voltage type
(only for
11713C)
a At CONFIGURATION
MENU screen, press
Voltage LEVEL softkey
b At OUTPUT VOLTAGE
screen, scroll to
highlight the desired
voltage (e.g. +5V)
c Press SET softkey to
assign highlighted
voltage
d At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel
e Ouput voltage
assigned is marked
<*>
f To exit this screen,
press BACK softkey
5411713B/C Operating and Service Manual
Local Operations5
Step Three: Configure 11713B/C connections to attenuators and switches
1 Determine interface cable option of the 11713B/C
2 Determine DC connector option of the attenuator(s) or switch(es)
3 Check for compatibility using Table 11 for programmable
attenuators and Table 12 for switches:
Tab le 11 Connection between 11713B/C and programmable attenuators
* If TTL is required, include Option 401. Must order switch with Option 403 (current interrupt) as switch
cannot withstand continuous current supplied by 11713B/C
*
202)
*
201)
4 For more details, refer to 11713B/C Configuration Guide,
literature number 5989- 7277EN.
11713B/C Operating and Service Manual55
5Local Operations
Main Menu of 11713B/C
The main menu can be displayed on the LCD screen by pressing the
Menu/Enter button. The six submenus, each with their own
functionality, are described in the subsequent sections.
SYSTEM Menu
FunctionActionIllustration
Display
attenuator
type(s)
configured for
11713B/C
a Navigate to the
SYSTEM icon using
the navigation keys
b Press Menu/Enter
button when SYSTEM
icon is highlighted
c On display are
attenuator models
assigned to ATTEN X
and ATTEN Y for each
bank (e.g. 8494G/H,
8496G/H, N/A, N/A)
d Press Menu/Enter
button again to return
to main menu
5611713B/C Operating and Service Manual
ATTEN Menu
FunctionActionIllustration
Local Operations5
Display
attenuation
levels of each
bank
a Navigate to the ATT EN
icon using the
navigation keys
b Press Menu/Enter
button when ATTEN
icon is highlighted
c On display are
attenuation level for
ATTEN X and ATTEN
Y (e.g. 11 dB, 110 dB,
0, 0)
d Press Menu/Enter
button again to return
to main menu
Attenuation value on display changes according to input from front
panel pushbuttons or through the virtual web interface:
• Pushbutton LED ON - attenuation card selected (attenuation
applied) on corresponding attenuator section
• Pushbutton LED OFF - thru path selected (attenuation lifted) on
corresponding attenuator section
11713B/C Operating and Service Manual57
5Local Operations
CYCLE Menu
FunctionActionIllustration
Display number
of cycles of
switching path
for each
channel
• 10 channels
for 11713B
(CH1 to CH9,
CH0)
• 20 channels
for 11713C
(B1-1 to
B1-10, B2-1
to B2-10)
Clear cycle for
selected
channel(s)
a Navigate to the CYCLE
icon using the
navigation keys
b Press Menu/Enter
button when CYCLE
icon is highlighted
c On display are number
of relay cycles for
each channel
d Press Menu/Enter
button again to return
to main menu
a Scroll to the desired
bank-channel (e.g. B1-1) using the
navigation keys
b Press CLEAR CYCLE
c At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel
d Note that relay cycle
for B1-1 is 0
5811713B/C Operating and Service Manual
FunctionActionIllustration
Local Operations5
Clear cycle for
all channels
a Press CLEAR ALL
b At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel.
c Note that relay cycle
for all channels is 0
IO Menu
Refer to Chapter 7, “Remote Interface Configurations.
INFO Menu
FunctionActionIllustration
Display system
info for
11713B/C
• Model
• Serial
• Firmware
• GPIB address
• LAN IP
• USB adress
• MAC address
number
revision
a Navigate to the INFO
icon using the
navigation keys
b Press Menu/Enter
button when INFO
icon is highlighted
c Press Menu/Enter
button again to return
to main menu
11713B/C Operating and Service Manual59
5Local Operations
UTILITY Menu
FunctionActionIllustration
Display system
utility settings
for 11713B/C
and adjust beep
volume
Beep volume
range from 0
(mute) to 8
(loudest)
Set factory
default
• For more
information:
“List of
Default
Values" on
page 63
a Navigate to the
UTILITY icon using the
navigation keys
b Press Menu/Enter
button when UTILITY
icon is highlighted
c Scroll to highlight
Beep VOL using the
navigation keys
d Adjust beep volume
using Volume up and
Volume down softkey
e Press Menu/Enter
button again to return
to main menu
a Scroll to highlight
Factory default using
the navigation keys,
then press Ye s softkey
b At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel.
6011713B/C Operating and Service Manual
FunctionActionIllustration
Reset LANa Scroll to highlight LAN
RESET using the
navigation keys, then
press Ye s softkey
b At the next screen,
press OK softkey to
confirm decision or
press Cancel softkey
to cancel.
Local Operations5
Preset Menu
The preset function is used to apply full attenuation or open all
switching paths (all LEDs light ON). For more information: “List of
Default Values" on page 63.
11713B/C Operating and Service Manual61
5Local Operations
Save/Recall State Menu
The save state function is important to enable user to store up to
four different configurations and the recall state function allows user
to reinstate one of the four saved states for use. This greatly helps to
minimize the amount of works required to make “standard”
configuration changes.
FunctionActionIllustration
To save statea Press Save/Recall
button
b Scroll to the desired
state to store
configuration (e.g.
STATE 0) using the
navigation keys
c Press Save State
softkey to store
configuration
d Press Menu/Enter
button again to return
to main menu
To r ec al l s ta tea Press Save/Recall
button
b Scroll to the desired
state to recall
configuration (e.g.
STATE 2) using the
navigation keys
c Press Recall State
softkey to reinstate
configuration
a Press Menu/Enter
button again to return
to main menu
6211713B/C Operating and Service Manual
List of Default Values
Local Operations5
Key OperationFactory-shipped
setting
Factory
Default
Key
Preset
(*RST)
Backup Save/
Recall
Available
means of
defining a
setting
ChannelAll Lights ON
*
<<
†
<<**K/C
‡
Attenuator TypeN/A<<**K/C
Supply Voltage+24V<<**K/C
TTLOFF<<**K/C
Beep Volume8<<*K
GPIB Address28<<*K
IP ConfigAUTO<<*K
Manual IP Addr“192.168.1.101”<<*K
Manual Gateway“0.0.0.0”<<*K
Manual Subnet Mask “255.255.255.0”<<*K
* When channel light is ON, it means attenuation is being applied (when attenuator is connected) or
switch path is open (when switch is connected)
† “<<“ symbol shows that the setup is the same as that in the box to the left.
‡ K = Using front panel. C = Using SCPI command.
Definition
Factory DefaultAll data that the user can set are cleared. Relay cycle count is not cleared.
PresetStatus when you press Preset key
*RSTStatus when you execute *RST in your program
BackupSettings that are backed up (set state not affected by turning power
ON/OFF)
In the table, a setting that is automatically backed up is denoted in the
following manner:
*: Backup operation performed
Blank: Backup operation not performed
Save/RecallSettings that permit Save/Recall of a setup state
In the table, states that can be saved/recalled are denoted in the following
manner:
*: Save/Recall can be performed
Blank: Save/Recall cannot be performed
11713B/C Operating and Service Manual63
5Local Operations
6411713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
“SCPI Command Syntax
“Rules for Using a Channel or Scan List
“Commands Relevant to Attenuators
“Commands Relevant to Switches
Programming Guide (Legacy) 73
“Data Message Input Format
SCPI and Legacy Commands Compatibility 74
This chapter provides the programming guide for 11713B/C
in SCPI commands and legacy command.
Agilent Technologies
65
6Remote Operations
Configuring Remote Interface
This section briefly describes how to configure the GPIB, USB and
LAN remote interfaces.
NOTE
For more detailed information on remote interface connectivity configuration
refer to the Agilent Technologies USB/LAN/GPIB Interfaces Connectivity Guide. If you have installed the IO Libraries Suite, you can access the
Connectivity Guide via the Agilent IO Libraries Control icon. Alternatively, you
can access the Connectivity Guide via the Web at
www.agilent.com/find/connectivity.
Interface Selection
You can choose to control the 11713B/C remotely using the GPIB,
USB or LAN interfaces.
For information on selecting and configuring the remote interface
manually from the driver front panel or remotely via virtual front
panel, refer to Chapter 5, “Local Operations.
NOTE
It is expected that most users will use the front panel keys to set up the remote
interfaces. The remote interface commands are provided for completeness (for
front panel operation).
GPIB Configuration
Each device on the GPIB (IEEE- 488) interface must have a unique
address. You can set the 11713B/C’s address to any value between 0
an 30. The attenuator/switch driver is shipped with a default address
set to 28. The GPIB address is stored in non- volatile memory and
does not change when the driver is switched off or after a remote
interface reset.
For information on setting the GPIB address manually from the front
panel, refer to “Connecting Over GPIB" on page 76.
6611713B/C Operating and Service Manual
USB Configuration
The USB interface requires no front panel or remote configuration.
The USB cannot be changed - it is set at the factory and is unique
for each 11713B/C.
Remote Operations6
NOTE
NOTE
NOTE
For further information on USB configuration, refer to “Connecting Over
USB" on page 78.
Before connecting the USB cable, make sure that I/O software is installed on
your computer.
For more information about Agilent IO Libraries software refer to the
Connectivity Guide. If you have installed other I/O software refer to
documentation that accompanies the software.
LAN Configuration
The 11713B/C has three LAN operating modes:
• Dynamic mode(Dynamic Host Configuration Protocol or DHCP)
• Auto IP mode (Local PC Control or isolated LAN)
• Static mode (Manual mode)
Refer to “Connecting Over LAN" on page 79 to configure the above
LAN operating modes.
11713B/C Operating and Service Manual67
6Remote Operations
Programming Guide (SCPI)
SCPI Command Syntax
The following conventions are used for SCPI command syntax for
remote interface programming.
• Square brackets ([]) indicate optional keywords or parameters
• Braces ({}) enclose paramter choices within a command string
• Angle brackets (<>) enclose parameters for which you must specify
a value
• A vertical bar (|) separates multiple parameters
Rules for Using a Channel or Scan List
Many of the SCPI commands include a channel list or scan list
parameter which allows you to specify one or more channels. The
channel number has the form (@bnn), where b is the bank number
and nn is the channel number.
NOTE
Channel list is from 101 to 110 for bank 1 and 201 ro 210 for bank
2.
11713B has only one bank. Therefore, by default, b = 1.
You can specify a bank, a single channel, multiple channels or a
range of channels as describe below.
• The following command closes a single channel (channel 4) on
bank 1:
ROUTe:CLOSe (@104)
• The following command closes multiple channels onmodules in
banks 1 and 2:
ROUTe:CLOSe (@104,107, 201, 206)
• The following command closes a range of channels. When you
specify a range of channels, the range may contain invalid
channels (they are ignored), but the first and last channel in the
list must be valid:
ROUTe:CLOSe (@101:109)
6811713B/C Operating and Service Manual
Commands Relevant to Attenuators
To Configure Attenuator Type
The commands below set the attenuator type (model number) for
corresponding attenuators.
For AG849xh, use AG849xg. For AG84904l/m, use AG84904k. For 84906l, use
AG84906k. For AG84907l, use AG849907k.
To Set Attenuation Level
The commands below are used to set the attenuation level of
corresponding attenuator(s).
• ATTenuator:[BANK1]:X <attenuation value in dB>
• ATTenuator:[BANK1]:Y <attenuation value in dB>
• ATTenuator:BANK2:X <attenuation value in dB>
• ATTenuator:BANK2:Y <attenuation value in dB>
To Query Attenuation Level
The commands below return the current attenuation value for
corresponding attenuator(s).
• ATTenuator:[BANK1]:X?
• ATTenuator:[BANK1]:Y?
• ATTenuator:BANK2:X?
• ATTenuator:BANK2:Y?
11713B/C Operating and Service Manual69
6Remote Operations
To Set Supply Voltage
The commands below set the supply voltage for each bank.
• CONFigure:BANK1 {OFF|P5v|P15v|P24v|USER}
• CONFigure:BANK2 {OFF|P5v|P15v|P24v|USER}
To Query Supply Voltage
The commands below query the supply voltage set for each bank.
Value to be returned: OFF, P5, P15, P24 or USER.
• CONFigure:BANK1?
• CONFigure:BANK2?
To Query Number of Relay Cycles
The command below query the number of relay cycles for each
channel. Value to be returned: number of cycles.
• DIAGnostic:RELay:CYCles? <channel list>
To Clear Relay Cycles
The commands below clear relay cycle for selected or all channels.
• DIAGnostic:RELay:CLEAr <channel list>
• DIAGnostic:RELay:CLEAr:ALL
7011713B/C Operating and Service Manual
Commands Relevant to Switches
To Open/Close Switch
The commands below close/open switching path(s).
• [:ROUTe]:CLOSe <channel list>
• [:ROUTe]:OPEn <channel list>
• [:ROUTe]:CLOSe:ALL
• [:ROUTe]:OPEn:ALL
To Query Switch Status
The commands below query the status of switching path(s). Value to
be returned: “1” if true and “0” if false.
• [:ROUTe]:CLOSe? <channel list>
• [:ROUTe]:OPEn? <channel list>
Remote Operations6
To Set Supply Voltage
The commands below set the supply voltage for each bank.
• CONFigure:BANK1 {OFF|P5v|P15v|P24v|USER}
• CONFigure:BANK2 {OFF|P5v|P15v|P24v|USER}
To Query Supply Voltage
The commands below query the supply voltage set for each bank.
Value to be returned: OFF, P5, P15, P24 or USER.
• CONFigure:BANK1?
• CONFigure:BANK2?
To Set TTL ON/OFF
The commands below set TTL ON/OFF for each bank.
• CONFigure:BANK1:TTL {OFF|ON}
• CONFigure:BANK2:TTL {OFF|ON}
To Query TTL status
The commands below query the supply voltage status for each bank.
Value to be returned: “1” if true and “0” if false.
• CONFigure:BANK1:TTL?
• CONFigure:BANK2:TTL?
11713B/C Operating and Service Manual71
6Remote Operations
To Query Number of Relay Cycles
The command below query the number of relay cycles for each
channel. Value to be returned: number of cycles.
• DIAGnostic:RELay:CYCles? <channel list>
To Clear Relay Cycles
The commands below clear relay cycle for selected or all channels.
• DIAGnostic:RELay:CLEAr <channel list>
• DIAGnostic:RELay:CLEAr:ALL
7211713B/C Operating and Service Manual
Programming Guide (Legacy)
Data Message Input Format
Remote Operations6
NOTE
NOTE
Legacy commands cannot be utilize to control Bank 2 of 11713C.
The programming data string for the driver consists of a string of
ASCII coded characters composed of one or both of the following
fields:
[Adm] [Bdn]
where: A or a = general ON command; B or b = general OFF
command
dm = any digits 0 through 9 (excluding dn)
dn = any digits 0 through 9 (excluding dm)
The driver responds to an alphanumeric data string such as
“A12B34” when the driver is in the remote state and addressed to
listen.
The alpha characters in the data string can be either upper or lower case.
NOTE
NOTE
11713B/C Operating and Service Manual73
The maximum number of character in a data string is 12.
The data string is further defiined as follows:
• Ax Bx = data string for ATTEN X (x can be none, one or more of
digits 1, 2, 3 or 4)
• Ay By = data string for ATTEN Y (y can be none, one or more of
digits 5, 6, 7 or 8)
If Ax (Ay) uses a digit, then that digit may not be used in Bx (By).
• A/B 9 = legacy command for switch S9
• A/B 0 = legacy command for swtich S0
6Remote Operations
SCPI and Legacy Commands Compatibility
Front PanelRear
Pushbutton
Number
1
2
3
4
5
6
7
8
9ON
Pushbutton
LED
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
Connector
*
ATTEN X5
ATTEN Y5
Connector
Panel
Number
S9A (3)
Pin
6
7
8
9
10
11
12
6
7
8
9
10
11
12
B (4)
Command Result
(Legacy) A
(SCPI) [:ROUTe]:CLOSe:
<channel list>
H
L
H
L
H
L
H
L
H
L
H
L
H
L
H
L
G
+Vcc
(Legacy) B
(SCPI) [:ROUTe]:OPEn:
<channel list>
L
H
L
H
L
H
L
H
L
H
L
H
L
H
L
H
+Vcc
G
0ON
OFF
ON
OFF
*Note:
LED lights on = attenuation applied (for attenuators)/switching path opened (for switches).
LED lights off = no attenuation (for attenuators)/switching path closed.
S0A (3)
B (4)
G
+Vcc
+Vcc
G
Legends
H = Open (Low)
L = Closed (High)
G = Connected to ground
7411713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
7
Remote Interface Configurations
Connecting the 11713B/C to Your Computer 76
“Connecting Over GPIB
“Connecting Over USB
“Connecting Over LAN
Exploring the 11713B/C Web Interface Over LAN 85
“Launching the Web Interface
“Displaying the Browser Web Control Page
This chapter provides you information and steps to achieve
remote operations of Agilent 11713B/C attenuator/switch
drivers via GPIB, USB and LAN. You will also be introduced
to 11713B/C web interface over LAN.
Agilent Technologies
75
7Remote Interface Configurations
Connecting the 11713B/C to Your Computer
NOTE
NOTE
To easily connect the 11713B/C to your PC, configure and verify your connection,
you can use the Agilent IO Library Suite, the E2094M Agilent IO Libraries for
Windows, or and equivalent.
• Agilent IO Libraries Suite for Windows 98/2000/ME/XP. For
information and to install, use the Automation Ready CD with the Agilent IO Libraries Suite, which is shipped with the
11713B/C.
• E2094M Agilent IO Libraries Suite for Windows
98/NT/2000/ME/XP. You can find information and install this
application via the Web at www.agilent.com/find/iolib.
• You can also access other information about Agilent IO Libraries
at www.agilent.com/find/iolib.
The procedures in this section refer to the Agilent Technologies USB/LAN/GPIB
Interfaces Connectivity Guide. If you have installed the IO Libraries Suite, you can
access the Connectivity Guide via the Agilent IO Libraries Control icon. Or, you can
access the Connectivity Guide via the Web at
www.agilent.com/find/connectivity.
Connecting Over GPIB
1 Make sure you have installed the required I/O software on your
computer.
2 Follow the instructions included with your GPIB interface card to
install the GPIB hardware in your computer.
3 Connect the GPIB cable (not provided) between the computer and
the 11713B/C.
4 Make sure power is applied to your computer and verify that the
operating system is fully booted. Then apply power to 11713B/C.
5 Configure your GPIB hardware as instructed by the documentation
provided by the hardware venfor.
6 Use the Connection Expert utility of the Agilent IO Libraries Suite
to add the 11713B/C and verify a connection.
NOTE
If you have installed any other I/O software, refer to documentation included with
that software.
7611713B/C Operating and Service Manual
Remote Interface Configurations7
The 11713B/C is shipped from the factory with a default GPIB
7
address of 28. To change the address, refer to table below:
StepActionIllustration
1 Changing
GPIB
address
(integer
between 0 to
30)
a At IO SETUP screen,
press GPIB ADDR
softkey
b Current GPIB address
is display on screen
(default address is 28)
c Use navigation key to
change value
d Press SAVE ADDR to
save and GPIB ADDR
SAVED is displayed at
the bottom of LCD
e Press BACK soffkey to
return to IO SETUP
8 Now you can use various programming environments to control
the 11713B/C. For an overview on programming instruments via
GPIB, refer to the Connectivity Guide.
11713B/C Operating and Service Manual77
7Remote Interface Configurations
Connecting Over USB
The USB interface requires no front panel configuration.
NOTE
NOTE
NOTE
Before connecting the USB cable, make sure that I/O software is installed on your
computer. See “Connecting the 11713B/C to Your Computer" on page 76 for more
information on installing the Agilent IO Libraries software.
1 After I/O software is installed on your computer, connect a
11713B/C to your computer using a Type Mini- B 5 pin USB cable.
2 Make sure power is applied to your computer and verify that the
operating system is fully booted. Then apply power to the
11713B/C.
3 The Found New Hardware Wizard will automatically start and
guide you through configuring the 11713B/C as a USB device. To
install the software automatically, accept all defaults.
If you have installed the Agilent I/O Libraries Software, this also install the
required low-level software drivers. Therefore you do not need to insert the CD
when the Found New Hardware Wizard instructs you to do so.
If you have installed any other I/O interface software, refer to documentation
included in that software.
4 Use the Connectivity Expert utility of the Agilent I/O Libraries
Suite to verify that the 11713B/C is displayed under the USB
interface.
5 Now you can use various programming environments to control
the 11713B/C. For an overview on programming instructions via
USB, refer to the Connectivity Guide.
7811713B/C Operating and Service Manual
Connecting Over LAN
The 11713B/C has two LAN operating modes:
• Auto mode
• Manual mode
Selecting the LAN Network Type
You can connect and configure your 11713B/C for Site LAN or
isolated (non- site) LAN operation.
• A Site LAN network is defined as a local area network (LAN) in
which computers and LAN- enabled instruments are connected to
a site LAN (workgroup LAN, Intranet, or enterprise LAN) via
optional routers, hubs, and/or switches.
• An Isolated LAN network is defined as a local area network
(LAN) in which computers and LAN- enabled instruments are not
connected to a site LAN.
Remote Interface Configurations7
11713B/C Operating and Service Manual79
7Remote Interface Configurations
Auto Mode
This mode is used when you are connecting 11713B/C via site LAN.
In auto mode, the IP Adress, Subnet Mask, and Default Gateway
values are obtained from the DHCP server or automatically assigned
and the values cannot be configured from the front panel.
To prepare 11713B/C for auto mode,
StepActionIllustration
1 Ensure your
computer
and
11713B/C
are turned on
and
connected to
LAN
2 Verif y
11713B/C
LAN
configuration
is ready for
auto mode
a Connect your computer and 11713B/C to LAN outlets using standard
LAN cable
b Make sure power is applied to your computer and verify that the
operating system is fully booted
c Apply power to 11713B/C and background LED color turns red,
indicating standby mode.
d Allow 11713B/C to warm up for 15 seconds, then press the ON
button (LED turn from red to green)
a Press Menu/Enter
button on the front
panel of 11713B/C
b Select IO using
navigation keys and
press Menu/Enter
c At IO SETUP screen,
press LAN CONFIG
softkey
d At LAN
CONFIGURATION
screen, ensure IP
Configuration is AUTO
e If needed, press
Auto/Manual softkey
until AUTO is
displayed and SAVE
f Press BACK softkey to
go back to IO SETUP
screen
8011713B/C Operating and Service Manual
Remote Interface Configurations7
StepActionIllustration
3 Verify LAN
status on
11713B/C
a At IO SETUP screen,
select IP ADDR
softkey
b At IP ADDRESS
screen, select LAN
STAT softkey
c Verify values
CURRENT IP
ADDRESS, CURRENT
SUBNET and
CURRENT GATEWAY
are valid
d Ensure LAN STATUS
is NORMAL
e If LAN STATUS is
FAULT, check your
LAN connection and
then press Restart
Netw softkey and wait
f Press BACK softkey to
go back to IP
ADDRESS screen
NOTE
Now you can use the 11713B/C Web Browser Interface to access and
control the instrument. See “Exploring the 11713B/C Web Interface
Over LAN" on page 85.
If you plan to program the instrument over LAN or use such
programs, make sure you have installed the required I/O software on
your computer.
Use the Connectivity Expert utility of the Agilent IO Libraries Suite
to add the 11713B/C and verify a connection. When identifying the
instrument, it is easiest if you use the IP address noted in step 3
above.
If you have installed any other I/O software, refer to documentation included with
that software.
Now you can use various programming environments to control the
11713B/C. For an overview on programming instructions via USB,
refer to the Connectivity Guide.
11713B/C Operating and Service Manual81
7Remote Interface Configurations
Manual Mode
In a manual mode, you must set up the IP Address, Subnet Mask
and Default Gateway that is compatible with your network
infrastructure. If it is not correctly setup, 11713B/C will not be
visible on your network.
To prepare 11713B/C for manual mode,
StepActionIllustration
1 Ensure your
computer is
connected to
11713B/C
and turned
on.
2 Verif y
11713B/C
LAN
configuration
is ready for
manual
mode
a Connect your computer to 11713B/C using CAT5 crossover cable
b Make sure power is applied to your computer and verify that the
operating system is fully booted
c Apply power to 11713B/C and background LED color turns red,
indicating standby mode.
d Allow 11713B/C to warm up for 15 seconds, then press the ON
button (LED turn from red to green)
a Press Menu/Enter
button on the front
panel of 11713B/C
b Select IO using
navigation keys and
press Menu/Enter
c At IO SETUP screen,
press LAN CONFIG
softkey
d At LAN
CONFIGURATION
screen, ensure IP
Configuration is
Manual
e If needed, press
Auto/Manual softkey
until Manual is
displayed and SAVE
f Press BACK softkey to
go back to IO SETUP
screen
8211713B/C Operating and Service Manual
Remote Interface Configurations7
StepActionIllustration
3 Manually
enter IP
ADDRESS,
SUBNET and
GATEWAY
4 Verify LAN
status on
11713B/C.
a At IO SETUP screen,
press IP ADDR
softkey
b At IP ADDRESS
screen, press
MANUAL IP softkey
c At MANUAL IP
ADDRESS screen,
enter IP ADDRESS,
SUBNET and
GATEWAY (scroll
using NEXT ITEM
softkey)
d Then SAVE.
e Press BACK softkey to
go back to IP
ADDRESS screen
a At IO SETUP screen,
select IP ADDR
softkey
b At IP ADDRESS
screen, select LAN
STAT softkey
c Verify values
CURRENT IP
ADDRESS, CURRENT
SUBNET and
CURRENT GATEWAY
are valid
d Ensure LAN STATUS
is NORMAL
e If LAN STATUS is
FAULT, check your
LAN connection and
then press Restart
Netw softkey and wait
f Press BACK softkey to
go back to IP
ADDRESS screen
11713B/C Operating and Service Manual83
7Remote Interface Configurations
Now you can use the 11713B/C Web Browser Interface to access and
control the instrument. See “Exploring the 11713B/C Web Interface
Over LAN" on page 85.
If you plan to program the instrument over LAN or use such
programs, make sure you have installed the required I/O software on
your computer.
Use the Connectivity Expert utility of the Agilent IO Libraries Suite
to add the 11713B/C and verify a connection. When identifying the
instrument, it is easiest if you use the IP address noted in step 3
above.
NOTE
If you have installed any other I/O software, refer to documentation included with
that software.
Now you can use various programming environments to control the
11713B/C. For an overview on programming instructions via USB,
refer to the Connectivity Guide.
8411713B/C Operating and Service Manual
Exploring the 11713B/C Web Interface Over LAN
Remote Interface Configurations7
You can use the 11713B/C’s Web Browser Interface for remote access
and control of the instrument via a Java
as Microsoft® Internet Explorer. Using the Web Interface, you can
configure, troubleshoot and monitor your system remotely. This
section provides an overview of the 11713B/C Web Interface.
NOTE
The following tasks assume you have configured the 11713B/C for LAN
communication and have verified connection to a LAN network. See “Connecting
Over LAN" on page 79 for more information.
Launching the Web Interface
1 Open your Internet browser from your computer
2 From the Tools>Internet Options menu, navigate to Connections
(exact navigation depends on your browser), and then select LAN
Settings
3 From the LAN Settings dialog, select/activate bypass proxy server
for local addresses (exact terminology depends on your browser)
4 Exit the Options window
5 Enter the IP address of the 11713B/C in the Address field and
press return. Use the 11713B/C’s front panel utility menu to read
the IP address
™
- enabled Web browser, such
NOTE
6 After entering the appropriate IP address, the 11713B/C Web
Interface’s Welcome Window should appear
The procedure in this section will help you understand tasks commonly performed
using the 11713B/C Web Interface. For additional help on using the interface, click
the ?Help with the Page tab on the lower-left cornner of the Web Interface
window.
11713B/C Operating and Service Manual85
7Remote Interface Configurations
Figure 13 11713B/C Web Interface’s Welcome Window
Navigation Bar
Welcome page Display various setting information
Browser Web Control Virtual front panel and sending/reading
SCPI commands
View & Modify Configuration Displays and modifies various
setting information
Get Image Receives image
Print Display Calls the printing function of the browser
Help with this Page Displays the Help file
8611713B/C Operating and Service Manual
Displaying the Browser Web Control Page
1 From the Welcome Window, click the Browser Web Control tab
on the left side of the window
2 You will notice a pop- up window, requesting for password
3 Enter password (default password is “agilent”) and click submit
4 You can view the virtual front panel of 11713B/C
Remote Interface Configurations7
5 Now, you can control the switching devices remotely, similar to
the front panel of the actual instrument
Figure 14 11713B/C Brower Web Control Interface
11713B/C Operating and Service Manual87
7Remote Interface Configurations
8811713B/C Operating and Service Manual
Agilent 11713B/C Attenuator/Switch Drivers
Operating and Service Manual
8
Replacing Major Assemblies
Replaceable Parts 90
Top Module Cover Removal/Replacement 94
Front Panel Module Removal/Replacement 95
Rear Panel Module Removal/Replacement 97
PPMC PCA Removal/Replacement 99
Fan Module Removal/Replacement 100
Motherboard Removal/Replacement 101
Power Supply Module Removal/Replacement 103
In this chapter, you will procedures for removal and
replacement of major assemblies in 11713B/C and list of
replaceable parts.
Agilent Technologies
89
8Replacing Major Assemblies
Replaceable Parts
Tab le 13 Major Assemblies Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
M134401-86020Bumper kit (front and rear)
M25041-7717Top clamshell
M35041-7718Bottom clamshell
M4-111713-60021Front panel module (11713C)
M4-211713-60027Front panel module (11713B-STD)
M4-311713-60035Front panel module (11713B-LXI)
M5-111713-60027Rear panel module (11713C)
M5-211713-60034Rear panel module (11713B-STD)
M5-311713-60036Rear panel module (11713B-LXI)
M611713-600388-pin cable assembly
Tab le 14 Front Panel Module Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
A12090-0964LCD module
A211713-60020Front panel board
A3-111713-40001Keypad (11713C)
A3-211713-40002Keypad (11713B)
A4-111713-20017Window
A5-111713-00025Front panel bezel (11713C)
A5-211713-00028Front panel bezel (11713B)
A6-111713-80005Front panel label (11713C)
A6-211713-80006Front panel label (11713B-STD)
A6-311713-80008Front panel label (11713B-LXI)
A70515-0430Screw M3
A811713-00034EMI gasket for front panel
9011713B/C Operating and Service Manual
Replacing Major Assemblies8
Tab le 15 Rear Panel Module Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
B1-111713-60023Rear panel plate (11713C)
B1-211713-60030Rear panel plate (11713B-STD)
B1-311713-60031Rear panel plate (11713B-LXI)
B20960-2776Line filter module
B3E5810-61605GPIB cable assembly
B4-1E3631-20011Red top binding post
B4-2E3631-20012Green top binding post (11713C)
B4-3E3631-20013Black top binding post
B80380-4870Hex screw standoff
B70510-0079Retaining ring
B90515-0390Screws
B62360-0198Flathead screw
B52950-0144Plastic hex nut
B1011713-20018EMI absorber
B1111713-00032GPIB gasket
B12-111713-6003910-pin cable assembly (11713C)
B12-211713-6004110-pin cable assembly (11713B)
B1311713-600402-pin cable assembly (11713C)
B14-111713-60022Rear panel board (11713C)
B14-211713-60028Rear panel board (11713B)
Tab le 16 PPMC PCA Module Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
C10515-1940Screw M2.5
C211713-60048PPMC PCA - programmed
C311713-00035EMI bracket
C40636-0170RFI strip
11713B/C Operating and Service Manual91
8Replacing Major Assemblies
Tab le 17 Fan Module Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
D111713-60025Fan assembly
9211713B/C Operating and Service Manual
Replacing Major Assemblies8
Tab le 18 Motherboard Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
E10515-0433Screw M4
E211713-60046Motherboard - programmed
Tab le 19 Power Supply Module Reference Designator and Part Number
Reference DesignationAgilent Part NumberDescription
F13030-1382Screw
F23050-2287Spring washer
F33050-2326Flat washer
F411713-00033PSU cover
F50515-0372Screws M3
F611713-60032Power supply
11713B/C Operating and Service Manual93
8Replacing Major Assemblies
Top Module Cover Removal/Replacement
CAUTION
To Re m o v e Top Mod u l e C over
NOTE
This module contains components that can be damaged or destroyed by
electrostatic discharge. It should be serviced at a static-safe workstation.
Refer to “preparing a static-safe workstation” in chapter 9.
1 Remove bumper kit (M1)
2 Turn the driver over with bottom facing up
3 Loosen captive screws with T20 Torx bit
Captive screws are torqued with 21 in-lbs.
4 Turn the driver over with top facing up
5 Gently, lift top clamshell (M2)
6 Disconnect:
• 8- pin cable (M6) from J5 connector on motherboard
• Line module cables (green/blue/brown) from power supply
module
7 Now you can remove the top module cover
To Replace Top Module Cover
1 Hold top clamshell (M2) near the driver
2 Connect:
• 8- pin cable (M6) from J5 connector on motherboard
• Line module cables (green/blue/brown) from power supply
module
3 Gently, place and secure the top clamshell (M2) onto the bottom
clamshell (M3)
4 Turn the driver over with bottom facing up
5 Tighten captive screws using 21 in- lbs torque driver/wrench with
T20 Torx bit
6 Fix bumper kit (M1) onto driver, as needed
9411713B/C Operating and Service Manual
Front Panel Module Removal/Replacement
Replacing Major Assemblies8
CAUTION
To Remove Front Panel Module
This module contains components that can be damaged or destroyed by
electrostatic discharge. It should be serviced at a static-safe workstation.
Refer to “preparing a static-safe workstation” in chapter 9.
1 Remove top clamshell (M2), refer “To Remove Top Module
Cover" on page 94
2 Disconnect:
• 50- pin cable from J6 connector on motherboard
• LCD flex cable from J8 connector on motherboard
• LCD power cable (red/black) from J11 connector on
motherboard
Front Panel Module
50-Pin Cable
LCD Flex Cable
LCD Power Cable
3 Slide front panel module (M4) upwards to detach from bottom
clamshell (M3)
4 Front panel module (M4) can be further disassembled to the
following parts/modules:
• LCD module (A1)
• Front panel board (A2)
• Keypad (A3)
• Window (A4)
• Front panel bezel (A5)
• Front panel label (A6)
11713B/C Operating and Service Manual95
8Replacing Major Assemblies
A5
A5
A6
To Replace Front Panel Module
1 Slot front panel module (M4) into groove at the bottom clamshell
(M3)
2 Connect the following cables to motherboard:
• 50- pin cable from J6 connector on motherboard
A1
A7
A2
A3
A4
• LCD flex cable from J8 connector on motherboard
• LCD power cable (red/black) from J11 connector on
motherboard
3 Replace top clamshell (M2), refer “To Replace Top Module
Cover" on page 94
9611713B/C Operating and Service Manual
Rear Panel Module Removal/Replacement
Replacing Major Assemblies8
CAUTION
To Remove Rear Panel Module
This module contains components that can be damaged or destroyed by
electrostatic discharge. It should be serviced at a static-safe workstation.
Refer to “preparing a static-safe workstation” in chapter 9.
1 Remove top clamshell (M2), refer “To Remove Top Module
Cover" on page 94
2 Disconnect:
• 50- pin cable from J7 connector on motherboard
• 10- pin cable (B12) from J12 connector on motherboard
• GPIB cable assembly from PPMC PCA
• 2- pin (B13) cable from J9 connector on motherboard (11713C
only)
Rear panel module
50-pin cable
GPIB cable assembly
10-pin cable (B12)
3 Slide rear panel module (M5) upwards to detach from bottom
clamshell (M3)
4 Rear panel module (M3) can be further disassembled to the
following parts/modules:
• Rear panel plate (B1)
• Line filter module (B2)
• GPIB assembly (B3)
• Binding posts (B4)
• Rear panel board (B14)
11713B/C Operating and Service Manual97
8Replacing Major Assemblies
To Replace Rear Panel Module
1 Slot rear panel module (M5) into groove at the bottom clamshell
2 Connect:
3 Replace top clamshell (M2), refer “To Replace Top Module
(M3)
• 50- pin cable from J7 connector on motherboard
• 10- pin cable (B12) from J12 connector on motherboard
• GPIB cable assembly from PPMC PCA
• 2- pin (B13) cable from J9 connector on motherboard (11713C
only)
Cover" on page 94
9811713B/C Operating and Service Manual
PPMC PCA Removal/Replacement
Replacing Major Assemblies8
CAUTION
To Re m o v e PPMC P C A
This module contains components that can be damaged or destroyed by
electrostatic discharge. It should be serviced at a static-safe workstation.
Refer to “preparing a static-safe workstation” in chapter 9.
1 Remove top clamshell (M2), refer “To Remove Top Module
6 Replace to clamshell, refer “To Replace Top Module Cover" on
page 94
11713B/C Operating and Service Manual99
8Replacing Major Assemblies
Fan Module Removal/Replacement
CAUTION
To Re m o v e Fan Mo d u l e
This module contains components that can be damaged or destroyed by
electrostatic discharge. It should be serviced at a static-safe workstation.
Refer to “preparing a static-safe workstation” in chapter 9.
1 Remove top clamshell (M2), refer “To Remove Top Module
Cover" on page 94
2 Disconnect cable from J10 connector on motherboard
3 Fan module (D1) can now be removed
Fan assembly (D1)
To Re p l a c e Fan m o d u l e
1 Press fit fan module (D1) into slot
2 Connect cable to J10 connector in motherboard
3 Replace top clamshell (M2), refer “To Replace Top Module
Cover" on page 94
10011713B/C Operating and Service Manual
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.