AGF Manufacturing 5400 User Manual

AGF Manufacturing Inc.
Model 5400
Owner’s Manual
INST-5400A_V001.3 · 1/15
1
AGF Manufacturing Inc.
TABLE OF CONTENTS
Installation Instructions ............................................................... 4-7
Unpacking .........................................................................................4
Sprinkler System Preparation ...........................................................4
Mounting ...........................................................................................4
Wiring ................................................................................................5
Operating Instructions ................................................................. 7-8
Maintenance Instructions .......................................................... 9-11
Heater Operation ..............................................................................9
Changing Timer Setting ..................................................................10
Maintenance Log ............................................................................11
AGF Manufacturing Inc.
100 Quaker Lane • Malvern, PA 19355
Phone: 610-240-4900
Fax: 610-240-4906
www.testandrain.com
Model 5400 COLLECTa n DRAIN® Owner’s Manual
Model 5400 COLLECTa n DRAIN
®
The COLLECTa n DRAIN® Model 5400 is a heated and insulated auxiliary drain (condensate collector/drum drip) with float switch and alarm for dry pipe sprinkler systems. The M5400 is designed for installation in climates where freezing or below freezing temperatures are present and result in the failure of typical collectors. The M5400 maintains a comfortable temperature above freezing while minimizing power consumption.
System Supply Pipe
Electrical Connection
System Supply Valve
“TEST” Button
Alarm Light
System Drain Valve
Heater
System Drain Pipe
Drain Pipe Cap
AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.testandrain.com
3
Model 5400 COLLECTa n DRAIN® Owner’s Manual
INSTALLATION INSTRUCTIONS
Unpacking:
Unpack the COLLECT1. a n DRAIN® M5400 unit and carefully inspect for any damages from shipping.
Verify box contents:2.
COLLECT• a n DRAIN® M5400 unit Four (4) Rubber Mounting Washers• Two (2) Door Keys• Electrical Wiring Schematic• M5400 System Drawing•
Sprinkler System Preparation:
If installing in a new system, proceed to Mounting Instructions below, otherwise continue with Preparation Instructions.
If adding additional installations, see NFPA 13 Chapters 24 and 26, and NFPA 25 Chapter 14.
Isolate the zone where the COLLECT1. a n DRAIN® will be installed.
Relieve air pressure from the branch line.2.
Remove the existing auxiliary drain.3.
Mounting:
Use the four mounting tabs (3/8” holes x 4) to install the M5400A to a wall or other secure structure. If wall is uneven, use bushings or stand-offs to prevent cabinet from bending when mounted.
Place the rubber washers behind the mounting 1. tabs to hold the M5400 off of the wall. Select fasteners suitable for attachment and capable of supporting the 50 lb. weight of the M5400.
Connect to the 1” NPT Supply Pipe in accor-2. dance with NFPA 13 (8.16.2.5 and 8.16.2.5.3) in regards to low-point drain installations.
Confirm that the Supply Valve (upper valve) is in 3. the open position (vertical) and ready to collect condensation, the Drain Valve (lower valve) is in the closed position (horizontal), and the pipe cap is tight.