AGF Manufacturing 5100A, 5200A, 5100ALBV User Manual

AGF Manufacturing Inc.
Model 5100A, 5200A,
and 5100ALBV
Owner’s Manual
INST-COLLECTan DRAIN_V001.9
Model 5100ALBV
Model 5100A
Model 5200A
Model 5100A, 5200A and 5100ALBV Owner’s Manual
COLLECTa n DRAIN™ Anti-Trip Auxiliary Drains for
Dry Pipe and Pre-Action Fire Sprinkler Systems
Supply Side (Upper) Ball Valve
Condensate Nipple
Anti-Trip Plate
Water Detection
Alarm
Test Button
(On Back Side)
Model 5100A
Anti-Tamper Lock
Drain Side (Lower) Ball Valve
Plug
Table of Contents
Installation Instructions
Model 5100A/5200A ............................................................................................. 3
Model 5100ALBV ..............................................................................................3-4
Operation Instructions
Model 5100A/5200A ............................................................................................. 4
Model 5100ALBV ..............................................................................................5-7
WARNING: The COLLECTa n DRaIn™ Anti-Trip Plate is designed to make sure that the auxiliary drain is operated in the proper manner and correct sequence as per NPFA guidelines to avoid accidental tripping, improper maintenance, and acts of vandalism. The M5100ALBV Water Detection Alarm detects the presence of water in the COLLECTa n DRaIn™ and alerts personnel when maintenance is needed. COLLECTa n DRaIn™ Model 5100A and 5200A are not designed to prevent freezing or automatically drain condensation from the system. Failure to drain condensation
from system may result in catastrophic system failure due to freezing. System must be maintained per NFPA 25 4.6, 4.6A and 4.1.
Model 5100A/5200A Installation Instructions
Retro-fitting into an Existing System
Isolate branch line or zone where the 1. COLLECTa n DRaIn™ is to be installed.
Relieve air pressure from the branch line.2.
Remove existing auxiliary drain/condensation collection assembly.3.
Install the 4. COLLECTa n DRaIn™ by attaching the supply valve (upper) to the sprinkler system pipe in accordance with NFPA 13 (2013 edition) 8.16.2.5 and
8.16.2.5.3 with regards to low-point drains (auxiliary drains).
Confirm that the supply valve (upper) is in the open position and ready to collect 5. condensation, the drain valve (lower) is closed, and the plug is tight.
Return system back to normal operating conditions.6.
Installation into a New System
Install the 1. COLLECTa n DRaIn™ by attaching the supply valve (upper) to the sprinkler system pipe in accordance with NFPA 13 (2013 edition) 8.16.2.5 and
8.16.2.5.3 with regards to low-point drains (auxiliary drains).
Confirm that the supply valve (upper) is in the open position and ready to collect 2. condensation, the drain valve (lower) is closed, and the plug is tight.
Activate system for normal operating conditions.3.
Note: The presence of even a small amount of water in the COLLECTa n DRaIn Model 5100A will activate the Model 5100ALBV Alarm’s visual and audible alerts signaling the need for attention. The COLLECTa n DRaIn™ must be drained completely to silence the alarm. Please call 610-240-4900 for instructions on how to locally silence the audible alert if directly wired to a Fire Control Panel or BMS.
Model 5100A/5200A Operating Instructions
To Collect Condensate per NFPA 25 (2011 edition) A.13.4.4.3.2, 13.4.4.3.2*
Close the drain valve (lower) by making sure the valve handle is perpendicular 1. to the collection assembly.
Apply Teflon2. the bottom of the drain valve.
Slide the Anti-Trip Plate to its lowest position.3.
Open the supply valve (upper) by making sure the valve handle is in line with 4. the collection assembly.
If equipped, install the anti-tamper lock.5.
AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmanufacturing.com
®
tape to the plug and make sure the plug is tightly threaded into
Loading...
+ 5 hidden pages