Model 5100/5200
100 Quaker Lane, Malvern, PA 19355 • Phone: 610-240-4900 • Fax: 610-240-4906 • www.agfmanufacturing.com
Auxiliary drains collect moisture from the dry sprinkler system
while minimizing the potential for excessive loss of air pressure
(NFPA 13, 8.16.2.5.3.5*, A8.16.2.5.3.5).
The COLLECTa n DRaIn® Family of products are auxiliary drains
(low-point drains, drum drips, condensation collection assemblies) available in several configurations to meet and exceed
NFPA 13 and NFPA 25 requirements addressing drainage in dry
and pre-action sprinkler systems.
Model 5100
Available in Galvanized or Black Pipe
Model 5200
COLLECTa n DRAIN® Features
Deters Vandalism and Improper Maintenance•
2nd Generation 5100ALBV Water Detector•
Highly Visible•
Consistant Appearance•
Fully Assembled•
Model 5100ALBV
High-Quality Brass, Quarter-Turn Ball Valves•
Model 5100A COLLECTa n DRaIn
The COLLECTa n DRAIN® Model 5100A Auxiliary Drain features a
patented, AGF Anti-Trip Plate (ATP) which prevents the opening of
the upper collection or lower drain valve unless the opposite valve is
in the closed position (as per NFPA guidelines) detering vandalism
and improper maintenance. The 5100ALBV (alarm ball valve) detects
water present in the collection assembly then sends audible and
visual alert onsite and/or to a remote control panel.
Model 5200A COLLECTa n DRaIn
The COLLECTa n DRAIN® Model 5200A Auxiliary Drain features a
patented, AGF Anti-Trip Plate (ATP) which prevents the opening of
the upper collection or lower drain valve unless the opposite valve is
in the closed position (as per NFPA guidelines) detering vandalism
and improper maintenance.
®
®
Easy Installation•
Easy Operation•
NFPA Signage•
Operating Instructions•
Reliability, Versatility, Code Compatibility
SS-5100-5200 · 8/17
COLLECTa n DRAIN® Operation
TO SYSTEM
SUPPLY
VALVE
COLLECT
The COLLECTa n DRaIn® Model 5100A
allows you to drain collected water
from isolated sections of dry pipe and
preaction sprinkler systems while
ANTI-TRIP
PLATE
ALARM
DRAIN
VALVE
preventing the accidental discharge
of air from the system. When in the
“COLLECT” position, the supply valve
is open and the Anti-Trip Plate is in its
lowered position preventing the drain
valve from being opened. While in this
position, water in the system collects
in the auxiliary drain assembly.
MODEL 5100A
COLLECTa n DRaIn
DRAIN
The alarm will blink and sound when
water has collected and draining is
required (Model 5100 only). To drain
the collected water, the supply valve
must be completely closed and the
Anti-Trip Plate slid to its upper position
allowing the drain valve to be opened.
To return the COLLECTa n DRaIn® to
the “COLLECT” position after draining,
the drain valve must be completely
closed and the Anti-Trip Plate slid to its
lower position for the supply valve to
be opened. This prevents both valves
from being open at the same time,
which could accidentally release the
®
air from the system.
Meet the COLLECTANDRAIN® Family
5100ALBV
5150ALBV
Patent Pending
AGF Manufacturing Inc.
100 Quaker Lane, Malvern, PA 19355
Phone: 610-240-4900
Fax: 610-240-4906
www.agfmanufacturing.com
5300ALBV 5100A 5400A
5200A5300A