AGF Manufacturing Inc.
TABLE OF CONTENTS
Installation Instructions ...................................................................4
Unpacking .........................................................................................4
Sprinkler System Preparation ...........................................................4
Mounting ...........................................................................................4
Wiring ................................................................................................5
Verify Correct Operation ...................................................................6
Operating Instructions ................................................................. 6-8
Maintenance Instructions ................................................................9
Verify Alarm Operation ......................................................................9
Heater Operation ..............................................................................9
Changing Thermostat Setting .........................................................10
Notes ..............................................................................................10
Maintenance Log ............................................................................11
AGF Manufacturing Inc.
100 Quaker Lane • Malvern, PA 19355
Phone: 610-240-4900
Fax: 610-240-4906
www.testandrain.com
Model 5400A COLLECTa n DRAIN™ Owner’s Manual
Model 5400A COLLECTa n DRAIN
™
The Model 5400A COLLECTa n DRAIN™ is a heated and insulated condensate collector and auxiliary drain with water level alarm for dry pipe sprinkler systems.
The M5400A is designed for installation in climates where freezing or below freezing temperatures are present and result in the failure of typical collectors. The
M5400A maintains a comfortable temperature above freezing while minimizing
power consumption.
System Supply Pipe
Electrical Connection
System Supply Valve
“TEST” Button
Alarm Light
System Drain Valve
Heater
System Drain Pipe
Drain Pipe Cap
AGF Manufacturing Inc. • Phone: 610-240-4900 • Fax: 610-240-4906 • www.testandrain.com
3
Model 5400A COLLECTa n DRAIN™ Owner’s Manual
INSTALLATION INSTRUCTIONS
Unpacking:
Unpack the M5400A COLLECT1. a n DRAIN™ unit and carefully inspect for any
damages from shipping.
Verify box contents:2.
M5400A COLLECT• a n DRAIN™ unit
Four (4) Rubber Mounting Washers•
Two (2) Door Keys•
Electrical Wiring Schematic•
M5400A System Drawing•
Sprinkler System Preparation:
If installing in a new system, proceed to Mounting Instructions below, otherwise
continue with Preparation Instructions.
If adding additional installations, see NFPA 13 Chapters 24 and 26, and NFPA 25
Chapter 14.
Isolate the zone where the COLLECT1. a n DRAIN™ will be installed.
Relieve air pressure from the branch line.2.
Remove the existing auxiliary drain.3.
Mounting:
Use the four mounting tabs (3/8” holes x 4) to install the M5400A to a wall or other
secure structure.
Place the rubber washers behind the mounting 1.
tabs to hold the M5400A off of the wall. Select
fasteners suitable for attachment and capable
of supporting the 50 lb. weight of the M5400A.
Connect to the 1” NPT Supply Pipe in accor-2.
dance with NFPA 13 (8.16.2.5 and 8.16.2.5.3) in
regards to low-point drain installations.
Confirm that the Supply Valve (upper valve) is in 3.
the open position (vertical) and ready to collect
condensation, the Drain Valve (lower valve) is
in the closed position (horizontal), and the pipe
cap is tight.
4