5
Oil Inlet R1/4 (1/4” BSP Taper Ext)
Electrical Supply 230V ~ 50Hz 3 amp Fused
Flue Outlet 100 mm
CO
2
% IN FLUE MANIFOLD 6.5 - 7.0
(COLD)
CO (MAX) 62 ppm (Nominal rate)
NOx (MAX) 106 ppm (Nominal rate)
Smoke 0 - 1
Fuel - Kerosene Class C2
Unpacked Weight of Appliance - 478 Kg
Firing Rate - 0.25 l/hr
Approximate Weekly Consumption -40 litres
(8.8 gallons)
TECHNICAL DATA - CONTINUED
BURNER NOZZLE (US g/h)
0.30 @ 60° H (DANFOSS)
5.2 (80)
15
9.5
4.1 cc/min
2.52 kW
OIL PRESSURE Bar (psi)
OIL BURNING RATE cc/m (FIRING)
HEAT INPUT kW (FIRING)
OIL BURNING RATE (AVERAGE)
OIL BURNING RATE (AVERAGE)
BURNER
IMPORTANT:
z
This appliance must only be used with Kerosene
Class C2 complying with BS. 2869.
z
A fire valve MUST be fitted in the oil supply line.
z
The supplied in line filter MUST be fitted.
The installation of the appliance must be in accordance
with the relevant standards. It should also be in
accordance with the relevant Codes of Practice.
Appliance Hearth: The surface temperature of the floor
below the appliance does not exceed 100ºC. However
this appliance must be installed on a solid floor or base of
incombustible material which is capable of supporting the
total weight.
The location chosen for the appliance must permit the
installation and the provision of a satisfactory flue and an
adequate air supply. The location must also provide
adequate space for servicing and for air circulation around
the appliance. See ‘Installation of the Appliance’.
The space in which the appliance is to be fitted must have
the following minimum dimensions:
Between wall and LH side of appliance - 10mm
Between wall and RH side of appliance - 10mm
SHOULD THE WALL PROJECT BEYOND THE FRONT
OF THE APPLIANCE. WHEN IT MUST BE INCREASED
TO 116mm.
Above the raised insulating cover - 60mm
In addition, adequate clearance must be available at the
front of the appliance to enable it to be operated and
serviced. Flue pipes and fittings must not be closer than
25mm to combustible materials and where passing
through a combustible partition such as a ceiling or roof,
must be enclosed in a non-combustible sleeve providing
an air space of at least 25mm.
Spaces around flue pipes passing through walls or floors
should be sealed against the passage of smoke and
flame.
Where the cooker is to stand in a recess or against a wall
which is to be tiled, in no circumstances should the tiles
overlap the cooker top plate.
INTRODUCTION
REGULATIONS
LOCATION
Site requirements