AERMEC NRL Technical Manual Installation Maintenance

CHILLERS- Technical manual - installation - maintenance
° COMPACT L COMPACT LOW NOISE H STANDARD COMPACT HEAT PUMP HL SILENCED COMPACT HEAT PUMP
NRL
EN
INRLPY. 02.10 4086916_01
Dear Customer, Thank you for choosing AERMEC. It is the fruit of many years of experience and special design studies and has been made of the highest grade materials and with cutting edge technology. In addition, all our products bear the EC mark indicating that they meet the require­ments of the European Machine Directive regarding safety. The standard of quality is permanently being monitored and AERMEC products are therefore a synonym for Safety, Quality and Reliability.
The data may undergo modifications considered necessary for the improvement of the product, at any time and without the obligation for any notice thereof.
Thank you again.
AERMEC S.p.A
Summary
16.1. Pressure drop.............................................................. 28
1. General warnings ........................................................ 6
1.1. Conserving the documentation ................................ 6
1.2. Safety precautions and installation .......................... 6
2. Description and choice of the unit ...........................7
2.1. Versions available .......................................................7
2.2. Versions available .......................................................7
2.3. Confi gurator ................................................................. 8
3. Chiller circuit................................................................. 9
3.1. Frame and fans............................................................9
3.2. Hydraulic components ............................................... 9
3.3. Safety and control components ............................. 10
3.4. Electrical components .............................................. 10
4. Accessories ................................................................11
5. Starting current reduction in presence of dre
accessories ................................................................. 13
6. Technical data ..........................................................13
6.1. Technical data versions [°-l] ..................................... 13
7. Technical data ..........................................................15
7.1. Technical data versions [h-hl] .................................. 15
8. Technical data ..........................................................17
8.1. Technical data versions [c] ...................................... 17
9. Operating limits .......................................................... 18
9.1. Cooling mode ............................................................18
9.2. Heating mode ........................................................... 18
9.3. Condenser unit operation ........................................ 18
10. Correction factors ..................................................... 19
10.1. Cooling capacity and input power ....................... 19
10.2. Heating capacity and input power ........................ 20
10.3. For ∆t different from the rated value....................... 20
10.4. Fouling factors ...........................................................20
17. M
18. Sound data ................................................................ 30
19. Selection and place of installation .........................32
20. Positioning ..................................................................32
20.1. Minimum technical spaces (mm)............................ 32
20.2. Dimensional tables ....................................................33
21. Weight distribution and center of gravity ............... 36
21.1. Nrl ° - l 2800 - 3000 - 3300 -3600 ................................36
21.2. Nrl ° - l - h 2800 - 3000 - 3300 -3600 ........................... 38
22. Hydraulic circuit ......................................................... 40
22.1. External hydraulic circuit recommended ............... 40
22.2. System load ............................................................... 40
22.3. Emptying the system ................................................. 40
23. Electrical wirings ........................................................ 43
23.1. Recommended section of electric cables ............ 43
23.2. Connection to the power supply ............................ 44
23.3. Electrical power connection ...................................44
23.4. Auxiliary connections at the user/installer expense 44
24. Control and fi rst start-up ...........................................45
24.1. Preparation for commissioning ................................ 45
24.2. First commissioning of the machine ........................ 45
24.3. Season changeover.................................................. 45
25. Functioning characteristics ...................................... 46
25.1. Cooling set point ....................................................... 46
25.2. Heating set point ....................................................... 46
25.3. Compressor start delay ............................................. 46
25.4. Circulation pump ......................................................46
25.5. Anti-freeze alarm .......................................................46
25.6. Water fl ow rate alarm ............................................... 46
26. Regular maintenance ............................................... 46
easurements of the chillers lines versions (c) .......... 29
11. Pressure drops ............................................................21
11.1. Total pressure drops (°-l) ...........................................21
11.2. Total pressure drop (h-hl) .......................................... 22
12. Accumulator ..............................................................24
12.1. Maximum/minimum water content in the system 24
13. Capacity controls ...................................................... 25
14. Glycol .......................................................................... 26
14.1. How to read the glycol curves ................................26
15. Desuperheater ........................................................... 27
15.1. Pressure drops ............................................................ 27
16. Total recovery ............................................................28
27. Extraordinary maintenance ..................................... 46
AERMEC S.p.A. 37040 Bevilacqua (VR) Italy – Via Roma, 996 Tel. (+39) 0442 633111 Telefax 0442 93730–(+39) 0442 93566 www.aermec.com - info@aermec.com
NRL
SERIAL NUMBER
CONFORMITY DECLARATION We, the undersigned, declare on our own exclusive responsibility that the object in
question, so defined:
NAME NRL
TYPE AIR - WATER CHILLER/HEAT PUMP
MODEL
and to which this declaration refers, complies with the following standardised regulations:
CEI EN 60335-2-40 Safety regulation regarding electric heat pumps, air conditioners and dehumidifiers
CEI EN 61000-6-1 CEI EN 61000-6-3
CEI EN 61000-6-2 CEI EN 61000-6-4
EN378 Refrigerating system and heat pumps - Safety and environmental requirements
UNI EN 12735 UNI EN 14276
thus meeting the essential requisites of the following directives:
- LV Directive: 2006/95/EC
- Electromagnetic Compatibility Directive 2004/108/EC
- Machine Directive 2006/42/EC
- PED Directive relating to pressure equipment 97/23/EC
In compliance with Directive 97/23/EC, the product meets the Total Quality Warranty procedure (module H) with certificate no. 06/270-QT3664 Rev.3 issued by the notified body no. 1131 CEC via Pisacane 46 Legnano (MI) - Italy
Electromagnetic immunity and emission in residential environment
Electromagnetic immunity and emission in industrial environment
Round welding-free copper pipes for air conditioning and cooling Pressure equipment for refrigerating systems and heat pumps
The person authorized to compile the technical file is: Massimiliano Sfragara - 37040 Bevilacqua (VR) Italy–Via Roma, 996
Bevilacqua 28/12/2009
Marketing Director
Signature
1. GENERAL WARNINGS
Standards and directives to be followed in the design and manufacture of the unit:
Safety system: Machine Directive
2006/42/EC
Low voltage directive
LVD 2006/95/EC
Electromagnetic compatibility directive
EMC 2004/108/EC
Pressure containers directive
PE
D 97/23/CE EN 378, UNI EN 14276 Electrical part: EN 60204-1
Protection rating
IP 24
Acoustic part:
SOUND POWER (EN ISO 9614-2) SOUND PRESSURE (EN ISO 3744) Certifications: Eurovent Refrigerant GAS: This unit contains fluorinated greenhouse gases covered by the Kyoto Protocol. Maintenance and disposal operations must be only carried out by qualified staff. R410A GWP=1900
The AERMEC NRL units are built according to the recognised standards and safety regulations. They have been designed for air conditioning and production of hot water and must be used for this purpose in accordance with their performance characteristics. be contractually liable for any damage to people, animals or objects, for failures caused by errors during installation, adjustment and maintenance or incorrect use. All the uses not expressly indicated in this manual are not allowed.
The company shall not
or non-contractually
1.1. CONSERVING THE DOCUMENTATION
Deliver the following instructions plus all the complementary documentation to the system user, who shall be responsible for keeping the instructions so that they are always available when needed. Read carefully this chapter; all the procedures must be carried out by qualified personnel according to the regulations in force in the different countries(M.D. 329/2004). It must be installed in such a way as to make all maintenance and/or repair operations possible (SEE INSTALLER SECTION page 33). The warranty of the device does not in any case cover costs owing to ladder trucks, lifts or other lifting systems that may be required in order to carry out the interventions under guarantee. Do not modify or tamper the with chiller as this may cause dangerous situations and the manufacturer shall not be liable for any damages. The warranty shall not
be valid if the indications mentioned above are not observed.
1.2. SAFETY PRECAUTIONS AND INSTALLATION
the chiller must be installed by an
authorised and qualified technician, in compliance with the national legislation in force in the country of destination (MD 329/2004).
Aermec shall not be held responsible for any damage whatsoever resulting from the non­compliance with these instructions.
Before starting any kind of work, it is
necessary TO READ CAREFULLY THE INSTRUCTIONS, AND TO PERFORM THE SAFETY CHECKS TO AVOID ANY RISKS. All the personnel in charge must know the operations and the risks that may arise when all the unit installation operations begin.
6
INRLPY. 02.10 4086916_01
2. DESCRIPTION AND CHOICE OF THE UNIT
The NRL is a set of devices designed to produce cold water for technological systems. ACCORDING TO
several coolingand hydraulic circuits, and according to the version, they can have desuperheaters, total recovery, only pumping unit or accumulator with pumping
unit.
The presence of more than one scroll type compressor allows the NRL chillers various capacity controls of the cooling capacity. By means of a microprocessor, the electronic regulation controls and manages all the components and working parameters of the unit; an internal memory registers the working conditions in the moment when an alarm condition arises, in order to visualise it on the display.
2.1. VERSIONS AVAILABLE
“COOLING ONLY” (° - L)
maximum outside temperature allowed 42°C;
processed water temperature 18°C;
“HEAT PUMP” (H - HL)
in cooling mode, the operating limits arrive at a maximum external air temperature of 42°C;
processed water temperature 18°C;
in heating mode, the operating
limits arrive at a maximum external air temperature of 42°C;
processed water temperature 50°C;
NRLH do not offer the following
configurations:
YH (with processed water lower than
4°C
)
HC (condensing heat pump)
the size of several
2.2. VERSIONS AVAILABLE
HEAT RECOVERY UNITS with desuperheater inserted in series (D).
WARNING: in the heat pump versions, the desuperheater must be intercepted during heat pump operation: otherwise, the guarantee will no longer be considered valid.
Total heat recovery (T) With plate-type exchanger inserted in parallel with the coils
Both versions (D - T) use:
a hot gas bypass device upstream from the evaporator
Water filter before the recovery exchanger.
The units with desuperheater (D) or total recovery (T) are not available in the versions:
YD
YT
XT (only for temperature lower than
XD (only for temperature lower than
The NRL-C condensing units are not available in the versions:
HC (condensing heat pump)
TC (condensing units with total recovery)
DC (condensing units with desuperheater)
4°C
4°C
)
)
Mechanical thermostatic valve (Y):
version Y: this is the version that
allows you to produce chilled water below the standard value of +4°C, to a minimum of -6°C. For lower
values, contact the company headquarters.
Danger!
The refrigerant circuit is under steam. High temperatures are also possible. The unit may only be opened by a service technician (SAT) or by an authorised technician. The operations in the cooling circuit can only be performed by a qualified refrigeration technician.
GAS R410A
The chiller is delivered with the correct refrigerant load.The R410A is free of chlorine, it is not flammable and does not harm the ozone layer. However, any interventions are always competence of the technical service assistance (SAT) or an authorised technician.
INRLPY. 02.10 4086916_01
7
2.3. CONFIGURATOR
1.2.3 4.5.6 7 8 9 10 11 12 13 14 15, 16
NRL280 0°°°°°°°00
field
1, 2, 3 Code NRL
4, 5, 6 Size
280, 300, 330, 360
7 Compressors
0 Standard compressor
8 Thermostatic valve
°
Standard mechanical thermostatic valve (to +4°C)
Y Low water temperature mechanical thermostatic valve (to -6°C) x
Electronic thermostatic valve also for low water temperature (to -6°C)
9 Model
° Cooling only C Condenser unit H Heat pump
10 Heat recovery
° Without recovery units D Desuperheater T Total recovery
11 Version
° L
Compact version
Compact low noise version
12 Coils
° Made of aluminium R Made of copper S Tinned copper V Varnished
13 Fans
° Standard M J
Enlarged
Inverter
14 Fuel feed
° 400V-3N-50Hz with thermomagnetic switches 1 230V-3-50Hz with thermomagnetic switches 2 500V-3-50Hz with thermomagnetic switches
15, 16 Accumulation
00 01 02 03 04 05 06 07 08 09 10 P1
Without water accumulator
Low-head water accumulator and single pump
Low-head water accumulator and reserve pump
High-head water accumulator and single pump
High-head water accumulator and reserve pump
Water accumulator with holes for supplementary electric heater, low head and single pump
Water accumulator with holes for supplementary electric heater, low head and reserve pump
Water accumulator with holes for supplementary electric heater, high head and single pump
Water accumulator with holes for supplementary electric heater, high head and reserve pump
Double hydraulic ring
Double hydraulic ring with supplementary electric heater
Without water accumulator, with low-head pump
P2 Without water accumulator, with low-head pump and reserve pump P3 P4
Without water accumulator, with high-head pump
Without water accumulator, with high-head pump and reserve pump
WARNING NB: for heat pump versions, M fans are not available, only ° and J.
8
INRLPY. 02.10 4086916_01
3. CHILLER CIRCUIT
Compressors
High effi ciency scroll-type hermetic compressors, assembled on elastic anti­vibration supports, driven by a 2-pole electric motor with internal thermal protection of the electric heater casing included as standard. The heater is automatically powered when the unit stops, provided that the unit is kept under tension.
Air side heat exchanger High effi ciency device made of copper pipes and aluminium blades locked into place via mechanical pipe expansion.
Water side heat exchanger
Of the plate-type (AISI 316), externally insulated with closed cell material to reduce thermal dispersion. Fitted, as standard, with
antifreeze heater.
LIQUID SEPARATOR (HEAT PUMP ONLY)
Located on the suction point of the compressor, to protect against any fl owback of liquid refrigerant, fl ooded start-ups, operation in the presence of liquid.
Liquid accumulation (only for heat pumps and total recovery)
To compensate the difference in volume between the fi nned coil and the plate-type exchanger, holding back excess liquid.
Filter drier
Of the mechanical type, made of ceramics and hygroscopic material able to trap impurities and any traces of humidity in the chiller circuit.
Sight glass
For checking the refrigerating gas load and any humidity in the refrigerating circuit.
Thermostatic valve
The mechanical type valve, with outside equaliser on the evaporator outlet, modulates the gas fl ow to the evaporator on the basis of the thermal load, in such a way as to ensure the proper degree of overheating of the intake gas.
Electronic valve (optional)
Liquid and discharge taps (cooling-only versions)
They allow the refrigerant to be cut off during extraordinary maintenance.
Solenoid valve
The valve closes when the compressor turns off, preventing the fl ow of refrigerant gas towards the evaporator.
Bypass solenoid valve (only for heat pumps)
To bypass the thermostat-controlled valve during the defrosting cycle.
Cycle reversing valve (heat pump only)
Inverts the fl ow of refrigerant when operation is switched between summer/winter, and during defrosting cycles.
Non-return valve
Allows the fl ow of refrigerant in one direction only.
Desuperheater (only upon request)
Of the plate-type (AISI 316), externally insulated with closed cell material to reduce thermal dispersion.
Total recovery (only upon request)
Of the plate-type (AISI 316), externally insulated with closed cell material to reduce thermal dispersion.
3.1. FRAME AND FANS
Fan unit
Screw type, statically and dynamically balanced. The electric fans are protected electrically with thermomagnetic switches and mechanically with metal anti-intrusion grilles, in accordance with the standard CEI EN 60335-2-40.
Enlarged fans (M)
These offer a useful head to overcome the pressure drops in the system
Inverter fans (J)
Load-bearing structure
Made of hot-galvanised steel sheet of a suitable thickness, varnished with polyester powders able to resist atmospheric agents over time.
3.2. HYDRAULIC
Circulation pump
Depending on the
characteristics of
the pump chosen, it
offers a useful head
to overcome the pressure drops in the system. There is also the
possibility to have a reserve pump. The reserve pump is managed by the electronic card.
Flow switch (installed as standard)
This checks that the water is circulating. If this
is not the case, it shuts down the unit.
Water fi lter(installed as standard)
Allows you to block and eliminate any
impurities in the hydraulic circuits. Inside, it
has a fi ltering mesh with holes not greater
than one millimetre. It is essential for avoiding
serious damage to the plate-type exchanger.
COMPONENTS
INRLPY. 02.10 4086916_01
9
Accumulator tank
In stainless steel, with a 700-litre capacity. In order to reduce the thermal dispersion and eliminate the phenomenon of the formation of condensation, it is insulated with polyurethane material of a suitable thickness. One antifreeze electric heater of 300W (down to -20°C outside temperature and tank water temperature 5°C) assembled as standard and commanded from the card via an antifreeze sensor inserted in the tank.
Drain valve (all versions)
Of the automatic type, assembled on the upper part of the hydraulic system; it releases any air bubbles that may be present in the system.
Filling assembly (versions with accumulator)
This has a pressure gauge showing the pressure in the system.
Expansion tank (versions with accumulator)
Of the membrane type, with nitrogen pre­charge.
Hydraulic circuit safety valve (only for versions with pump or with accumulator)
Calibrated to 6 bar and with ductable discharge, it releases overpressure in the event of abnormal working pressure levels.
3.3. SAFETY AND CONTROL COMPONENTS
Low pressure switch (BP)
Cooling-only (L)
Of fixed calibration, located on the low pressure side of the refrigerating circuit, it stops the operation of the compressor in the event of anomalous work pressures.
High pressure switch (AP)
Cooling-only (L)
Heat pump (HL)
With fixed calibration, placed on the high pressure side of the chiller circuit, it shuts down compressor operation in the case of abnormal operating pressure.
Low pressure transducers (TP2)
Cooling-only (L) “accessory”
Heat pumps (HL) "standard"
Placed on the high pressure side of the chiller circuit, it communicates to the control card the operating pressure, sending a pre-alarm in case of abnormal pressure.
High pressure transducer (TP3)
Standard for all the versions
Placed on the high pressure side of the chiller circuit, it communicates to the control card the operating pressure, sending a pre-alarm in case of abnormal pressure.
Anti-freeze heater (installed as standard)
Its operation is commanded by the antifreeze probe located in the plate-type evaporator. It is activated when the water temperature is +3°C, and deactivated when the water temperature is +5°C. The dedicated software in the regulation card manages the heater.
Refrigerating circuit safety valve
This intervenes by releasing overpressure in the event of abnormal working pressure levels.
- Calibrated at 45 bar on the HP branch
- Calibrated at 30 bar on the BP branch
Evaporator antifreeze heating element
Its operation is commanded by the antifreeze probe located in the plate-type evaporator. It is activated when the water temperature is +3°C, and deactivated when the water temperature is +5°C. The dedicated software in the regulation card manages the heater.
3.4. ELECTRICAL COMPONENTS
ELECTRICAL PANEL
Contains the power section and the management of the controls and safety devices. In accordance with standards: CEI EN 61000-6-1 CEI EN 61000-6-2 CEI EN 61000-6-4 (immunity and electromagnetic emissions for the industrial sector). and Directives EMC 89/336/EEC and 92/31/EEC concerning electromagnetic compatibility, Low Voltage Directive LVD 2006/95/EC.
DOOR LOCK KNIFE SWITCH
IT is possible to access the electrical panel by disconnecting the voltage, then using the opening lever of the panel itself. This lever can be blocked with one or more padlocks during maintenance, in order to prevent the machine being powered up accidentally.
CONTROL KEYPAD
Provides full control functions. For a detailed description refer to the user manual.
Remote control panel
This allows the chiller command operations to be given from a distance.
compressor protection thermomagnetic switch; fan protection thermomagnetic switch; auxiliary protection thermomagnetic switch; discharge gas temperature control thermostat.
(only for heat pumps)
ELECTRONIC REGULATION MICROPROCESSOR CARD
Consisting of a management/control card and a visualisation card.
• Functions carried out:
adjustment of water temperature at evaporator inlet, with thermostat control for up to 4 levels and integral­proportional fan speed control (with DCPX accessory);
compressor start-up delay;
compressor sequence rotation;
count of compressor work hours;
start/stop;
reset;
permanent alarms memory;
autostart after voltage drop;
multi-lingual messages;
operation with local or remote control.
Machine status display:
ON/OFF compressors;
alarms summary.
• Alarm management:
high pressure;
flow switch;
low pressure;
anti-freeze;
compressor overload;
fan overload;
pump overload.
Display of the following parameters:
water inlet temperature;
accumulator temperature;
water outlet temperature;
delta T;
high pressure;
low pressure;
waiting time for restart;
alarms visualisation.
• Settings:
a) without password:
cooling set; total differential.
b) with password:
antifreeze set;
low pressure exclusion time; display language; access code.
For further information, refer to the user manual.
10
INRLPY. 02.10 4086916_01
4. ACCESSORIES
280 300 330 360
AER485
°• L•
H•
HI
AVX (00)
785 791 791 791
785 791 791 791
AVX (01-02-03-04)
° L
H
HI
AVX (P1-P2-P3-P4)
° L
H
HI
° L
H
HI
786 792 792 792
786 792 792 792
787 793 793 793
787 793 793 793
GP
260x2 260 350 350x2 350x2
260x2 260 350 350x2 350x2
Through this accessory it is possible to connect the unit with BMS supervision systems with electrical standard RS 485 and MODBUS type protocol.
•••
•••
•••
•••
Sprung anti-vibration supports. Select the model using the compatibility table.
Sprung anti-vibration supports. Select the model using the compatibility table.
Sprung anti-vibration supports. Select the model using the compatibility table.
Protect the external coils from accidental knocks.
PGS
° L
H
HI
AERWEB30
° L
H
HI
Card to be inserted in the electronic card of the unit. Allows you to programme two time bands per day (two switch on/off cycles) and to have differentiated programming for each day of the week.
AERWEB30: the AERWEB device allows the remote control of a chiller from a common PC, using a serial connection. Using additional modules, the device allows the chiller to be controlled via the telephone line, using the AERMODEM accessory, or via the GSM network, using the AERMODEM GSM accessory. AERWEB can pilot up to 9 chillers, but each of these must be equipped with accessory AER485 or AER485P2.
•••
•••
•••
•••
•••
•••
•••
•••
INRLPY. 02.10 4086916_01
11
280 300 330 360
Current rephaser. Parallel connection with the motor makes the reduction
REF
° L
H
HI
°78798181 L standard
H 78 80 82 82
HI standard
°78808282 L standard
RIFNRL2800 RIFNRL3000 RIFNRL3300 RIFNRL3600
RIFNRL2800 RIFNRL3000 RIFNRL3300 RIFNRL3600
DCPX
DCPX M
DUALCHILLER
°• L•
H•
HI
MULTICHILLER
°• L•
H•
HI
TRX1
°• L•
H•
HI
PRM 1
° •--- L •---
H •---
HI •---
PRM 2
° - L -
H -
HI -
of input current possible. It can only be installed when the machine is being made and must therefore be specified when the order is placed.
This accessory allows correct operation with outside temperatures below 10°C and down to -10°C. It is made up of an electronic regulation card that varies the fan rpm on the basis of the condensation pressure (read by the high pressure transducer), to keep it sufficiently high for the proper functioning of the unit. It also allows correct heating operation with outside temperatures greater than 30°C and up to 42°C.
DCPX only for configurations with enlarged fans (M).
Simplified control system to switch on and off, and command, two chillers (using Aermec GR3 command) in a single system, as if they were a single unit.
•••
•••
•••
•••
Control system to switch the individual chillers on and off, and command them, in a system in which several units are installed in parallel, always ensuring a constant delivery to the evaporators.
•••
•••
•••
•••
The water accumulators with holes and supplementary electric heaters leave the factory with plastic protection caps. Before loading the system, if the installation of an electric heater is not envisaged it is compulsory to replace the plastic caps with the special TRX1.
•••
•••
•••
•••
FACTORY-ASSEMBLED ACCESSORY. Pressure switch with manual reset (using a tool), electrically connected in series to the high pressure switch on the compressor delivery pipe.
FACTORY-ASSEMBLED ACCESSORY. Pressure switch with manual reset (using a tool), electrically connected in series to the high pressure switch on the compressor delivery pipe.
•••
•••
•••
•••
[1] The useful heads refer to the nominal air flow rate
* The water connections are all of the Victaulic type
12
INRLPY. 02.10 4086916_01
5. STARTING CURRENT REDUCTION IN PRESENCE OF DRE ACCESSORIES
MODEL SINGLE CIRCUIT DOUBLE CIRCUIT THREE-CIRCUIT FOUR-CIRCUIT FIVE-CIRCUIT SIX-CIRCUIT
CURRENT REDUCTION
-30% -26% -22% -20% -18% -16%
6. TECHNICAL DATA
6.1. TECHNICAL DATA VERSIONS [°-L]
COOLING 2800 3000 3300 3600
°
Cooling output kW
Total input power kW
Water flow rate l/h
Total pressure drops kPa
Energy indices
EER W/W
ESEER W/W
ELECTRICAL DATA
Fuel feed A
Input current A
Maximum current A
Peak current A
COMPRESSORS (SCROLL)
Number/Circuit
FANS (AXIAL)
Quantity no.
Air fl ow rate m³/h
Input power kW
Input current A
Useful heads
FANS (ENLARGED M)
Quantity no.
Input power kW
Input current A
Useful heads
[1]
[1]
no./
no.
Pa
Pa
676 750 824 898
L 604 672 733 786
284 322 350 374
° L 314 354 384 416
116270 129000 141730 154460
° L 103890 115580 125900 135190 °
73.0 78.6 59.5 58.8
L 59.1 63.8 47.9 45.9
°
2.38 2.33 2.35 2.40
L 1.92 1.90 1.90 1.89 ° 3.76 3.68 3.72 3.79 L 3.65 3.61 3.62 3.59
° L
498 572 610 638
° L 538 616 656 696 °
580 638 716 782
L °
789 847 984 1050
L
°
10/4 12/4 12/4 12/4
L
°
8 8 12 12
L °
154000 152000 216600 212400
L 115400 121600 151620 148680 ° 10.0 10.0 15.0 15.0 L 7.5 7.5 11.3 11.3
21.6 21.6 32.4 32.4
° L 16.2 16.2 24.3 24.3
45 45 40 40
° L----
°
8 8 12 12
L °
13.9 13.9 20.9 20.9
L ---- ° 29.6 29.6 44.4 44.4 L ---- ° 45 45 40 40 L----
400V - 3 - 50 Hz
INRLPY. 02.10 4086916_01
13
HYDRAULIC CIRCUIT
Accumulator capacity L
Accumulator antifreeze heater
Expansion tank capacity No./l
LOW-HEAD CIRCULATION PUMP
Input power KW
Input current A
Useful head kPa
HIGH-HEAD CIRCULATION PUMP
Input power KW
Input current A
Useful head kPa
SOUND DATA [1] The useful heads refer to the chiller operation
Sound power (1) dBA
Sound pressure (2) dBA
DIMENSIONS
Height mm
Width mm
Depth mm
Weight when empty kg
° L °
W
L
A E
2800 3000 3300 3600
° 9.6 9.6 13.0 13.0 L 9.6 9.6 13.0 13.0 ° 16.3 16.3 22.0 22.0 L 16.3 16.3 22.0 22.0 ° 102 88 109 99 L 133 116 134 130
2800 3000 3300 3600
° 17.2 17.2 24.7 24.7 L 17.2 17.2 24.7 24.7 ° 29.2 29.2 42.4 42.4 L 29.2 29.2 42.4 42.4 ° 246 220 246 237 L 279 258 271 267
° 93.5 93.5 95.0 95.0 L 90.5 90.5 92.0 92.0 ° 61.5 61.5 63.0 63.0 L 58.5 58.5 60.0 60.0
°
2450 2450 2450 2450
L °
2200 2200 2200 2200
L °
8100 8100 8100 8100
L °
5630 6020 6220 6420
L
2 x 700
2 x 300
4 x 25
[1] The useful heads refer to the nominal air flow rate.
(1) Sound power
Aermec determines the sound power value on the basis of measurements taken in accordance with standard 9614-2, in compliance with the Eurovent certifi cation.
(2) Sound pressure
Sound pressure in an unrestricted range on a refl ective plane (directional fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
NOMINAL REFERENCE CONDITIONS
Inlet water temperature 12°C
Outlet water temperature 7°C
Outside air temperature d.b. 35°C
− ∆t 5°C
14
INRLPY. 02.10 4086916_01
7. TECHNICAL DATA
7.1. TECHNICAL DATA VERSIONS [H-HL]
COOLING 2800 3000 3300 3600
H
Cooling output kW
Total input power kW
Water flow rate l/h
Total pressure drops kPa
HEATING 2800 3000 3300 3600
Heating capacity kW
Total input power kW
Water flow rate on heating l/h
Total pressure drop on heating kPa
Energy indices
EER W/W
ESEER W/W
COP W/W
ELECTRICAL DATA
Fuel feed A
Input current on cooling A
Input current on heating A
Maximum current A
Peak current A
COMPRESSORS (SCROLL)
Number/Circuit
FANS (AXIAL)
Quantity no.
Air fl ow rate, cooling only m³/h
Heat pump air fl ow rate m³/h
Input power kW
Input current A
Useful heads[1] Pa
FANS (INVERTER J)
Quantity no.
Input power kW
Input current A
Useful heads[1] Pa
no./
no.
666 734 846 908
HL 604 664 746 794
H
280 318 332 358
HL 308 348 374 408
114550 126250 145510 156180
H
HL 103890 114210 128310 136570
H
40.2 40.4 46.9 45.7
HL 33.4 33.6 37.0 35.5
H
768 854 936 1006
HL
H
252 282 310 332
HL
H
132.100 146.890 160.990 173.030
HL
H
53.7 55.4 58.8 57.8
HL
H 2.38 2.31 2.54 2.54
HL 1.96 1.90 1.99 1.95
H 3.57 3.50 3.53 3.60
HL 3.47 3.43 3.44 3.41
H
3.05 3.03 3.02 3.03
HL
H
HL
482 551 592 618
H
HL 521 594 641 673
H
454 522 558 579
HL
H
588 646 730 796
HL
H
797 855 998 1064
HL
H
10/4 12/4 12/4 12/4
HL
H
HL 12 12 16 16
H 174800 173600 248400 244800
HL 131000 138800 173800 171400
H
HL
H
HL 13.6 13.6 20.4 20.4
H
HL 28.8 28.8 43.2 43.2
H55 54 47 45
HL - - - -
H
HL --- -
H
HL --- -
H
HL --- -
H
HL - - - -
8 8 12 12
169800 168000 234600 229200
13.6 13.6 20.4 20.4
28.8 28.8 43.2 43.2
8 8 12 12
13.6 13,.6 20.4 20.4
28.8 28.8 43.2 43.2
55 54 47 45
400V - 3 - 50 Hz
* The water connections are all of the Victaulic type [1] The useful heads refer to the nominal air flow rate
INRLPY. 02.10 4086916_01
15