AERMEC HRS 060, HRS 090, HRS 090W, HRS 160, HRS 160W Installation, Use And Maintenance Manual

...
HEAT RECOVERY UNIT Installation, Use and Maintenance Manual
HRS-HRS W
4530600_00 dated 0904
A the Manufacturer is constantly committed in the continuous improvement of its entire production, the aes­thetic and dimensional features, the technical data, equipment and accessories may be subject to variation.
This instruction book is an integral part of the appliance and as a consequence must be kept carefully and must ALWAYS accompany the appliance even if transferred to other owners or users or transferred to another plant. If damaged or lost, request another copy from the Manufacturer.
Repair and maintenance interventions must be carried out by authorised staff or staff qualified according to that envisioned by this book. Do not modify or tamper with the appliance as dangerous situations can be created and the appliance manu­facturer will not be liable for any damage caused.
After having removed the packaging ensure the integrity and completeness of the content. If this is not the case, contact the Company that sold the appliance.
The appliances must be installed by enabled companies in compliance with the Law 5 March n° 46 which, at the end of the job issues a declaration of conformity regarding installation to the owner, i.e. in compliance with the Standards in force and the indications supplied in this book.
Any contractual or extracontractual liability of the Manufacturer is excluded for injury/damage to persons, animals or objects owing to installation, regulation and maintenance errors or improper use.
We remind you that the use of products that employ electrical energy and water requires that a number of essential safety rules be followed, including:
This appliance must not be used be children and unaided disabled persons.
It is prohibited to touch the appliance when you are barefoot and with parts of the body that are wet or damp.
It is prohibited to perform any maintenance or cleaning operation before having disconnected the appliance from the mains electricity network, by positioning the plant master switch at "off"
It is prohibited to modify the safety or adjustment devices without the manufacturer’s authorisation and precise instruc­tions
It is prohibited to pull, detach or twist the electrical cables coming from the unit even if it is disconnected from the electri­cal mains
It is prohibited to climb onto the unit, sit on it and/or rest any type of object on it.
It is prohibited to spray or jet water directly onto the unit.
It is prohibited to open the doors for accessing the internal parts of the appliance without first having switched off the mas­ter switch of the "system".
It is prohibited to disperse, abandon or leave the packing materials within the reach of children, as they are a potential source of danger
page 2
Heat Recovery Units Installation, Use and Maintenance Manual
Important Note The heat recovery unit is a machine designed and built exclusively to change air in the civil environments, incompatible with toxic and inflammable gases. Therefore it cannot be used in those environments where the air is mixed and/or altered by other gaseous composites and/or solid particles. The use of the same for different purposes from those envisioned, not conform to that described in this manual, will make any direct and/or indirect liability of the Manufacturer automatically become null and void.
SYMBOLS
!
WARNING
!
DANGER
i
DANGER RISK F ELECTRIC SHOCK
f
ATTENTION ONLY AUTHORISED STAFF
PROHIBITION
page 3
Heat Recovery Units Installation, Use and Maintenance Manual
INDEX
SECTION 1 - GENERAL FEATURES
1.1 Manual presentation page 5
1.2 Construction features page 5
1.3 Orientations possible for HRS range horizontal models page 6
1.4 HRS range unit technical data page 7
1.5 HRS - HRSW range unit technical data page 8
1.6 Accessories available page 8
SECTION 2 - TRANSPORT
2.1 Packaging page 11
2.2 Handling and transport
2.3 Control and receipt
2.4 Storage
SECTION 3 - INSTALLATION AND START-UP
page 11
3.1 Safety Standards
3.2 Preliminary operations page 12
3.3 Choosing the place of installation page 12
3.4 Positioning the machine page 12
3.5 Connection to the ducts page 13
3.6 Hydraulic connections
3.7 Any installation of the section with water coil HRS_CS page 14
3.8 Hydraulic connection of the section with water coil HRS_CS page 15
SECTION 4 - ELECTRIC CONNECTIONS page 15
4.1 Electronic speed adjuster HRS_SC page 16
4.2 Wiring diagrams page 17
SECTION 5 - CONTROLS BEFORE START-UP page 22
SECTION 6 - ROUTINE MAINTENANCE
6.1 Warnings page 22
6.2 Monthly checks
6.3 Yearly checks page 24
SECTION 7 - DISPOSAL page 24
DECLARATION OF CONFORMITY page 25
page 4
Heat Recovery Units Installation, Use and Maintenance Manual
INTRODUCTION
The heat recovery units for horizontal installation are characterised by small dimensions and easy assembly. The heat recovery units allow to join maximum environmental comfort with sure energy saving. Forced ventilation must be created in current air conditioning and treatment plants, which leads to the expulsion of treated air, determining large energy consumption and increase in costs. The HRS heat recovery unit range intend to solve these problems using a static heat recovery unit that saves more than 50% of the energy that would otherwise be lost.
SECTION 1 - GENERAL FEATURES
1.1 Manual presentation
This manual states the information and that deemed necessary for transport, installation, use and maintenance of the HRS range heat recovery units. The user will find that which is normally useful to know for correct safe installation of the heat recovery units described. Failure to comply with that described in this manual and inadequate installation of the heat recovery unit causes the annulment of the warranty that the Manufacturer gives its heat recovery units. Moreover, the Manufacturer is not liable for any direct and/or indirect damage due to incorrect installation or damage caused by units installed by unskilled and unauthorised staff. On pur­chase, check that the machine is integral and complete. Any claims must be made in writing within 8 days from receipt of the goods.
1.2 Construction features
• Panels realised in Aluzink sheet steel, removable for inspection and maintenance.
• Acoustic and heat insulation of the panels using polyethylene/polyester with average thickness of 20 mm.
• Fresh air intake and double intake centrifugal type expulsion fans (for the HRS 30 model with simple intake) with directly cou­pled electric motor.
• Fan body mounted onto anti-vibration mounts so as not to transmit any vibrations.
• Air filters with G3 efficiency, easily extractable laterally, to allow periodical cleaning. for the HRS range
• Terminal boards on machine to ease the electric connections and fan control.
• Condensate drip tray in ABS with low condensate drain connection.
page 5
Heat Recovery Units Installation, Use and Maintenance Manual
1.3 HRS possible orientations and clearance
• STANDARD ORIENTATION TYPE 03
Depending on the configuration of the network and the space available, it is possible to choose the other 3 orientations AT THE TIME OF PLACING THE ORDER, (TYPE 01 - 02 - 04).
Heat Recovery Units Installation, Use and Maintenance Manual
page 6
Gli orientamenti raffigurati sono relativi alla macchina vista dall’alto
La batteria di post-riscaldamento (ad acqua) disponibile solo sulla versione HRS-W /
The configurations are referred to the top view
The post-heating water coils is available only for model HRS-W
ORIENTAMENTO TIPO 01 / CONFIGURATION TYPE 01
ORIENTAMENTO TIPO 02 /  02
ORIENTAMENTO TIPO 03 / 
(Tipo standard / )$')-&)
ORIENTAMENTO TIPO 04 / 
Aria espulsa / Exhaust air Aria di rinnovo / Fresh air
Aria espulsa / Exhaust air Aria di rinnovo / Fresh air
Aria espulsa / Exhaust air Aria di rinnovo / Fresh air
Aria espulsa / Exhaust air Aria di rinnovo / Fresh air
Orientamento 1 e 2 / Configuration 1 and 2 Orientamento 1 e 2 / Configuration 3 and 4
HRS mod. 030 - 060
HRS mod. 090-160-190-230-300-390
La batteria di post-riscaldamento ad acqua disponibile solo sulla versione MRS_W /
T
he post-heating water coils is available only for model HRS-W
Heat Recovery Units Installation, Use and Maintenance Manual
page 7
MODEL
HRS 030 HRS 060
HRS 090
HRS 090W
HRS 160
HRS160W
HRS 190
HRS190W
HRS 230
HRS 230W
HRS 300
HRS 300W
HRS 390
HRS 390W
Size A mm 990 990 1140 1300 1380 1650 1650 1750 B mm 290 290 410 500 500 600 600 600 C mm 750 750 860 860 960 1230 1230 1230 D mm / / 260 290 310 410 410 410
D1 mm / / 95 77 87 91 91 116
E mm / / 210 310 330 410 410 410 F mm / / 220 225 225 288 321 321
F1 mm / / 115 109 129 152 135 160
G mm / / 200 255 255 255 280 280
G1 Ø gaz / / 3/4 3/4 3/4 3/4 3/4 3/4
Y mm / / 50 75 75 162 125 125 Ø mm 160 200 / / / / / /
Øi mm 460 355 / / / / / /
Weight kg 41 45 80 125 138 160 174 190
1.4 HRS range unit technical data
1.6 Accessories available
1.5 HRS - HRS W range unit technical data
(1)
Values referring to the nominal air flow rate including recovery unit and filters
(2) Noise pressure level: values referring to 1.5 metres from machine intake in free field. The operational noise level differs from the values indicated according to the functioning conditions, the reflex
noise and peripheral noise (3) Input power at the electric mains. (4) Can be adjusted electronically with WM regulator
MODELLO / MODEL HRS 030 060 090 160 190 230 300 390
Portata aria nominale / Nominal air flow m³/h 300 620 920 1580 1850 2250 2950 3920
Pressione statica utile / External static pressure
(1)
Pa 45 55 65 70 77 80 100 100
Assorbimento max. totale macchina / Total max absorbed current
A 0,75 1,8 2,2 4,4 4,8 5,2 8,3 5
Pressione sonora / Sound pressure level
(2)
db (A) 43 51 50 53 52 51 54 56
VENTILATORI / FANS 030 060 090 160 190 230 300 390
Potenza disponibile all'asse / Power input W 92 x 2
(3)
90 x 2 147 x 2 350 x 2 350 x 2 350 x 2 550 x 2 750 x 2
Poli / Poles 4
Numero velocità / Speed number 1
(4)
3
(5)
1
(6)
Grado di protezione / Enclosure protection IP 44 55 44 55
Classe di isolamento / Insulation class F
Alimentazione elettrica / Electrical supply V/ph/Hz 230/1/50 400/3/50
Heat Recovery Units Installation, Use and Maintenance Manual
page 8
It is possible to intake or expel the air frontally and laterally by simply changing the position of the panels, as illustrated at the side.
This can simplify the realisation of the air ducts greatly, bringing an effective saving to installation times.
Accessories compatibility
HRS 090 HRS 160 HRS 190 HRS 230 HRS 300 HRS 390
HRS 030 HRS 060 HRS 090W HRS 160W HRS 190W HRS 230W HRS 300W HRS 390W
HRS090CS HRS160CS HRS190CS HRS230CS HRS300CS HRS390CS
HRS090ED HRS160ED HRS190ED HRS230ED ✔✔ ✔
HRS090S HRS160S ✔✔ HRS230S ✔✔ ✔
HRS030SC HRS060SC
HRS01AT * ✔✔✔✔✔ ✔ PX ✔✔✔✔✔ PX2 ✔✔✔✔✔
* Accessory installed in the factory, compatible only with HRS W version, to be requested when placing the order.
HRS_CS: Section of water cooling/heating (with
stainless steel condensate drip tray).
• HRS_ED: Regulation shutter.
• HRS_S: N° 4 circular connection kits for direct
connection of the unit to the circular conduits.
- HRS090S (ø 315 mm)
- HRS160S (ø 355 mm)
- HRS230S (ø 400 mm)
• HRS_SC: Electronic speed regulator.Anti-freeze
thermostat, allows to control that the temperatu­re does not fall below a pre-established value. .
Accessory installed in the factory, to be requested when placing the order for the HRS W version.
• PX: Control panel with switch-over.
Wall installation. (from size 090 to 300)
• PX2: Control panel with switch-over. Wall instal-
lation (from size 090 to 300)
Heat Recovery Units Installation, Use and Maintenance Manual
page 9
1.7 Accessories technical data
HRS_W UNIT WITH WATER POST-HEATING SECTION
The use of the coil is requested when post-heating is necessary and must be fixed directly inside the heat recovery unit.
Values referring to the following conditions: Water 70/60 °C; Air inp. T = 8°C; Nominal air flow rate.
HRS_ED ADJUSTMENT DAMPER
The adjustment damper is made up from a galvanised sheet steel frame with adjustable louvered fins.
Model B (mm) A (mm)
HRS090ED 260 210 HRS160ED 290 310 HRS190ED 330 310
HRS230-ED 410 410
BATTERIA POST-RISCALDAMENTO
WATER HEATING COIL - BCR
090 160 190 230 300 390
Resa termica / Heating capacity kW 8.2 12.2 14.4 20.3 24.2 29.9 Geometria / Geometry 25x22 25x22 25x22 25x22 25x22 25x22 Tubi per rango / Pipes per row 14 18 18 22 22 22 Ranghi / Rows 2 2 2 2 2 2 Passo alette / Fins spacing mm 2.5 2.5 2.5 2.5 2.5 2.5 Temp. uscita aria / Outlet air temperature °C 33.4 30.8 30.2 33.2 31.3 29.7 Perdita di carico lato aria / Air pressure drop Pa 25 32 35 24 36 38
Perdita di carico lato acqua / Water pressure drop kPa 8 14 15 17 22 30
Diametro collettori / Connection diameter Ø gas 3/4 3/4 3/4 3/4 3/4 3/4 Peso / Weight kg 2.5 2.5 2.5 5 5 6.5
HRS_CS SECTION WITH WATER COIL
The HRS_CS module contains a water coil and must be positioned outside the machine in front of the introduction vent. The condensate drip tray in stainless steel with low condensate drain connection.
Model 090 160 190 230 390
A (mm) 500 600 700 700 700 B (mm) 410 500 500 600 600 C (mm) 450 450 480 660 710 D (mm) 260 290 310 410 410
E (mm) 210 310 330 410 410 Ø1 (gas) 3/4" 3/4" 3/4" 3/4" 1" Ø2 (mm) 22 22 22 22 22