1.6 Accessories available
1.5 HRS - HRS W range unit technical data
(1)
Values referring to the nominal air flow rate including recovery unit and filters
(2) Noise pressure level: values referring to 1.5 metres from machine intake in free field. The operational noise level differs from the values indicated according to the functioning conditions, the reflex
noise and peripheral noise
(3) Input power at the electric mains.
(4) Can be adjusted electronically with WM regulator
MODELLO / MODEL HRS 030 060 090 160 190 230 300 390
Portata aria nominale / Nominal air flow m³/h 300 620 920 1580 1850 2250 2950 3920
Pressione statica utile / External static pressure
(1)
Pa 45 55 65 70 77 80 100 100
Assorbimento max. totale macchina / Total max absorbed current
A 0,75 1,8 2,2 4,4 4,8 5,2 8,3 5
Pressione sonora / Sound pressure level
(2)
db (A) 43 51 50 53 52 51 54 56
VENTILATORI / FANS 030 060 090 160 190 230 300 390
Potenza disponibile all'asse / Power input W 92 x 2
(3)
90 x 2 147 x 2 350 x 2 350 x 2 350 x 2 550 x 2 750 x 2
Poli / Poles n° 4
Numero velocità / Speed number n° 1
(4)
3
(5)
1
(6)
Grado di protezione / Enclosure protection IP 44 55 44 55
Classe di isolamento / Insulation class F
Alimentazione elettrica / Electrical supply V/ph/Hz 230/1/50 400/3/50
Heat Recovery Units Installation, Use and Maintenance Manual
page 8
It is possible to intake or expel the air frontally and
laterally by simply changing the position of the
panels, as illustrated at the side.
This can simplify the realisation of the air ducts
greatly, bringing an effective saving to installation
times.
Accessories compatibility
HRS 090 HRS 160 HRS 190 HRS 230 HRS 300 HRS 390
HRS 030 HRS 060 HRS 090W HRS 160W HRS 190W HRS 230W HRS 300W HRS 390W
HRS090CS ✔
HRS160CS ✔
HRS190CS ✔
HRS230CS ✔
HRS300CS ✔
HRS390CS ✔
HRS090ED ✔
HRS160ED ✔
HRS190ED ✔
HRS230ED ✔✔ ✔
HRS090S ✔
HRS160S ✔✔
HRS230S ✔✔ ✔
HRS030SC ✔
HRS060SC ✔
HRS01AT * ✔✔✔✔✔ ✔
PX ✔✔✔✔✔
PX2 ✔✔✔✔✔
* Accessory installed in the factory, compatible only with HRS W version, to be requested when placing the order.
• HRS_CS: Section of water cooling/heating (with
stainless steel condensate drip tray).
• HRS_ED: Regulation shutter.
• HRS_S: N° 4 circular connection kits for direct
connection of the unit to the circular conduits.
- HRS090S (ø 315 mm)
- HRS160S (ø 355 mm)
- HRS230S (ø 400 mm)
• HRS_SC: Electronic speed regulator.Anti-freeze
thermostat, allows to control that the temperature does not fall below a pre-established value. .
Accessory installed in the factory, to be
requested when placing the order for the
HRS W version.
• PX: Control panel with switch-over.
Wall installation. (from size 090 to 300)
• PX2: Control panel with switch-over. Wall instal-
lation (from size 090 to 300)