AERMEC 1602, 1802, 2002, 2202, 2352 Technical Installation Manual

...
CHILLERS- Technical manual - installation - maintenance
NS
m
n
R134a
EN
INSPY. 1007. 4138305_03
Aermec adhere to the EUROVENT Certi­fication program up to 600 kW. The products concerned appear in the EUROVENT Certified product guide.
INSPY. 1003. 4138305_03
2
INSPY. 1003. 4138305_03
3
AERMEC S.p.A. reserves the right at all times to make any modification for the improvement of its product and is not obliged to add these modification to machines of previous manufacture that have already been delivered or are being built.
Dear Customer, Thank you for choosing AERMEC. It is the fruit of many years of experience and special design studies and has been made of the highest grade materials and with cutting edge technology. In addition, all our products bear the EC mark indicating that they meet the requirements of the European Machine Directive regarding safety. The standard of quality is permanently being monitored and AERMEC products are therefore a synonym for Safety, Quality and Reliability.
The data may undergo modifications considered necessary for the improvement of the product, at any time and without the obligation for any notice thereof.
Thank you again.
AERMEC S.p.A
INSPY. 1003. 4138305_03
4
1. General warnings ........................................................8
1.1. Conserving the documentation ................................8
1.2. Safety precautions and installation ..........................8
2. Product identifi cation .................................................8
3. Description and choice of the unit ...........................8
3.1. Models available ........................................................ 8
3.2. Available versions ........................................................8
3.3. Description and choice of the unit ...........................9
4. Components description ..........................................10
4.1. Chiller circuit...............................................................10
4.2. Frame and fans..........................................................10
4.3. Hydraulic components .............................................11
4.4. Safety and control components .............................11
4.5. Electrical components ..............................................11
4.6. Electronic regulation .................................................12
5. Accessories ................................................................13
5.1. Electric regulation accessories ............................... 13
5.2. Electrical accessories ................................................13
5.3. General accessories .................................................13
6. Technical data ..........................................................15
6.1. Technical data ns 1251 … 1802 ...............................15
6.2. Technical data ns 2002 … 3402 ...............................18
6.3. Technical data ns 3602 … 5702 ...............................21
6.4. Technical data ns 6003 … 7203 ...............................24
7. Operating limits ..........................................................27
7.1. Operating limits graph versions «° and l» ................27
7.2. Operating limits graph versions «a and e»
for 5402-5702 ..............................................................27
7.3. Design data ............................................................... 27
7.4. Operating limits graph versions «a and e» .............27
8. Correction factors .....................................................28
8.1. Standard version ........................................................28
8.2. Standard version in silenced form ...........................28
8.3. High effi ciency Version except for the sizes 5402 and
5702 .............................................................................29
8.4. High effi ciency version in silenced version except for
the sizes 5402 and 5702 .............................................29
8.5. High effi ciency version except for the sizes 5402 and
5702 .............................................................................30
8.6. High effi ciency version in silenced version except for
the sizes 5402 and 5702 .............................................30
8.7. For Δt different from the rated value.......................31
8.8. Fouling factors ........................................................... 31
9. Glycol ..........................................................................32
9.1. How to read the glycol curves ................................32
10. Total pressure drops ..................................................33
10.1. Minimum water content recommended ...............33
11. Desuperheater ...........................................................37
11.1. Pressure drops ............................................................37
12. Total recovery ............................................................38
12.1. Pressure drops ............................................................38
12.2. Pressure drops total recovery ..................................38
13. Pumps .........................................................................39
13.1. Selection of pumps ...................................................39
14. Sound data ................................................................40
14.1. Sound levels at full load standard NS «°» ................40
14.2. Sound levels at full load standard ns in silenced
version «L» ...................................................................40
14.3. Sound levels at full load standard NS high effi ciency
«A» ...............................................................................41
14.4. Sound levels at full load standard ns high effi ciency in
silenced version «E» ................................................... 41
14.5. Sound levels at full load standard ns e with the kit ..
accessory AK, (L/E) ....................................................42
15. Safety and check parameter setting .....................42
16. Safety components calibration ...............................43
17. Selection and place of installation ........................45
18. Positioning ..................................................................45
CONTENTS
INSPY. 1003. 4138305_03
5
18.1. Minimum technical spaces (mm)............................45
19. Dimensional tables carpentry by 3780 (mm) .........46
19.1. Carpentry by 3780 (mm) NS 1251 - 1401 - 1601 - 1801 °°(°/L°°00…PA…PK) NS 1251 - 1401 - 1601 °°(A/E°°00…PA…PK) NS 1402 - 1602 - 1802 °°(°/L°°00…PA…PK)
NS 1402 - 1602 °°(A/E°°00…PA…PK) ........................46
19.2. Carpentry by 4770 (mm) NS 2101 - 2401 °°(°/L°°00…PA…PK) NS 1801 °°(A/E°°00…PA…PK) NS 2002 - 2202 - 2352 - 2502 °°(°/L°°00…PA…PK)
NS 1802 °°(A/E°°00…PA…PK) ...................................50
19.3. Carpentry by 5750 8 fans (mm)
NS 2652 - 2802 °°(°/L°°00…PA…PK) ..........................54
19.4. Carpentry by 5750 10 fans (mm) NS 2101 - 2401 - 2002 - 2202 - 2352 - 2502 - 2652 - 2802
°°(A/E°°00…PA…PK) ..................................................55
19.5. Carpentry by 7160 (mm) standard electrical box NS 3002 - 3202 °°(°/L°°00…PA…PK)
NS 3002 - 3202 °°(A/E°°00…PA…PK) ........................58
19.6. .Carpentry by 7160 (mm) electrical box two circuits
NS 3402 - 3602 °°(°/L°°00…PA…PK) ..........................60
19.7. Carpentry by 8150 (mm) NS 3902 - 4202 °°(°/L°°00…PA…PK)
NS 3402 °°(A/E°°00…PA…PK) ...................................62
19.8. Carpentry by 8150 (mm) NS 4502 - 4802 °°(°/L°°00…PA…PK)
NS 3602 °°(A/E°°00…PA…PK) ...................................64
19.9. Carpentry by 10120 (mm)
NS 3902 - -4202 °°(A/E°°00…PA…PK) .......................66
19.10. Carpentry by 11100 (mm) NS 5702 °°(°/L°°00…PA…PK) NS 4502-4802 °°(A/E°°00…PA…PK)
ns 5002-5202-5402-5702 °°(a/e°°00…pa…pk) ........68
19.11. Carpentry by 10120 (mm)
NS 5002 °°(°/L°°00…PA…PK) .....................................70
19.12. Carpentry by 10120 (mm)
NS 5202 °°(°/L°°00…PA…PK) .....................................72
19.13. Carpentry by 10120 (mm)
NS 5402 °°(°/L°°00…PA…PK) .....................................74
19.14. Carpentry by 10120 (mm)
NS 6303 -6603 °°(°/L°°00…PA…PK) ...........................76
19.15. Carpentry by 13510 (mm)
NS 6903 -7203 °°(°/L°°00…PA…PK) ...........................78
20. Hydraulic circuit .........................................................81
20.1. External hydraulic circuit recommended ...............81
20.2. System load ...............................................................81
20.3. Emptying the system .................................................81
21. Electrical wirings ........................................................82
21.1. Recommended section of electric cables ............82
21.2. Connection to the power supply ............................82
21.3. Electrical power connection ...................................82
21.4. Auxiliary connections at the user/installer expense ....83
21.5. Electric data versions «°/l» ........................................ 84
21.6. Electric data versions «a/e» ......................................85
22. Control and fi rst start-up ...........................................86
22.1. Preparation for commissioning ................................86
22.2. First commissioning of the machine ........................86
22.3. Season changeover..................................................86
23. Functioning characteristics ......................................87
23.1. Cooling set point ....................................................... 87
23.2. Compressor start delay .............................................87
23.3. Circulation pump ...................................................... 87
23.4. Anti-freeze alarm .......................................................87
23.5. Water fl ow rate alarm ............................................... 87
24. Regular maintenance ...............................................87
25. Extraordinary maintenance .....................................87
INSPY. 1003. 4138305_03
6
INSPY. 1003. 4138305_03
7
SERIAL NUMBER
CONFORMITY DECLARATION We, the undersigned, declare on our own exclusive responsibility that the object in
question, so defined:
NAME NS TYPE AIR - WATER CHILLER MODEL
And to which this declaration refers, complies with the following standardised regulations:
CEI EN 60335-2-40 Safety regulation regarding electric heat pumps, air conditioners and dehumidifiers CEI EN 61000-6-1
CEI EN 61000-6-3
Electromagnetic immunity and emission in residential environment
CEI EN 61000-6-2 CEI EN 61000-6-4
Electromagnetic immunity and emission in industrial environment
EN378 Refrigerating system and heat pumps - Safety and environmental requirements UNI EN 12735
UNI EN 14276
Round welding-free copper pipes for air conditioning and cooling Pressure equipment for refrigerating systems and heat pumps
thus meeting the essential requisites of the following directives:
- LV Directive: 2006/95/EC
- Electromagnetic Compatibility Directive 2004/108/EC
- Machine Directive 2006/42/EC
- PED Directive relating to pressure equipment 97/23/EC In compliance with Directive 97/23/EC, the product meets the Total Quality Warranty procedure (module H)
with certificate no. 06/270-QT3664 Rev.5 issued by the notified body no. 1131 CEC via Pisacane 46 Legnano (MI) - Italy
The person authorized to compile the technical file is: Massimiliano Sfragara - 37040 Bevilacqua (VR) Italy–Via Roma, 996
Bevilacqua 15/01/2010
Marketing Director
Signature
NS
AERMEC S.p.A. 37040 Bevilacqua (VR) Italy – Via Roma, 996 Tel. (+39) 0442 633111 Telefax 0442 93730–(+39) 0442 93566 www .aermec. com - info @ aermec. com
INSPY. 1003. 4138305_03
8
1. GENERAL WARNINGS
NS AERMEC is built according to recognised technical standards and safety regulations. They have been designed for air conditioning and must be used for this purpose in accordance with their performance characteristics. The company shall not be contractu­ally or non-contractually liable for any damage to people, animals or objects, for failures caused by errors during installation, adjustment and mainte­nance or incorrect use. All the uses not expressly indicated in this manual are not allowed.
1.1. CONSERVING THE DOCUMENTATION
Deliver the following instructions plus all the complementary documentation to the system user, who shall be responsible for keeping the instructions so that they are always available when needed. Read carefully this chapter; all the procedures must be carried out by qualified personnel according to the regulations in force in the different countries (M.D. 329/2004). It must be installed so as to enable maintenance and/or repair operations The warranty of the device does not in any case cover costs owing to ladder trucks, lifts or other lifting systems that may be required in order to carry out the interventions under guarantee. Do not modify or tamper the with chiller as this may cause dangerous situations and the manufacturer shall not be liable for any damages. The warranty shall not be valid if the indications men­tioned above are not observed.
1.2. SAFETY PRECAUTIONS AND INSTALLATION
the chiller must be installed by an
authorised and qualified techni­cian, in compliance with the national legislation in force in the country of destination (MD 329/2004).
AERMEC shall not be held responsi-
ble for any damage whatsoever
resulting from the non-compli-
ance with these instructions.
Before starting any kind of work, it is necessary TO READ CAREFULLY THE INSTRUCTIONS, AND TO PERFORM THE SAFETY CHECKS TO AVOID ANY RISKS. All the personnel in charge must know the operations and
the risks that may arise when
all the unit installation operations
begin.
2. PRODUCT IDENTIFICATION
NS are identified by the following:
PACKAGING LABEL that includes the product identifica­tion data
TECHNICAL CARD Placed on the right strut side (see fig.1)
NOTE If the identification plate, or any other means to identify the product, is tampered with, removed or missing, installation and maintenance opera­tions are hampered
3. DESCRIPTION AND
CHOICE OF THE UNIT
Air-cooled liquid chillers with axial fans FOR OUTDOOR INSTALLATION. are equipped with one or several cooling circuits. The evaporators are the pipe bundle type with dry expansion. The entire series can have up to three two-screw compressors. All the units are tested and delivered complete with refrigerant load and oil, (it will be necessary only to make hy­draulic and electrical connections on site, by the installer).
3.1. MODELS AVAILABLE
"COOLING ONLY"
version ° and L
maximum outside air temperature allowed 42 °C Processed water temperature 15 °C
version A and E
maximum outside air temperature allowed 48 °C (46° for sizes 5402-
5702) Processed water temperature 15 °C
3.2. AVAILABLE VERSIONS
NS series chillers are available in 32 sizes. By combining the numerous op­tions available, it is possible to con­figure each model in the NS series in such a way as to meet the most varied system requirements. The following con­figurator shows the methods by which the commercial code of 15 fields that make it up representing the options available is compiled.
Standards and directives to be followed in the design and manufacture of the unit:
Safety system: Machine Directive
2006/42/EC
Low voltage directive
LVD 2006/95/EC
Electromagnetic compatibility directive
EMC 2004/108/EC
Pressure containers directive PE
D 97/23/CE EN 378,
UNI EN 14276
Electrical part:
EN 60204-1
Protection rating
IP 24
Acoustic part:
SOUND POWER (EN ISO 9614-2) SOUND PRESSURE
(EN ISO 3744)
Certifications: Eurovent Aermec adhere to the EUROVENT Certification program up to 600 kW. The products concerned appear in the EUROVENT Certified product guide.
Refrigerant GAS: This unit contains fluorinated greenhouse gases covered by the Kyoto Protocol. Maintenance and disposal operations must be only carried out by qualified staff. R134a GWP=1900
fig. 1
TECHNICAL LABEL
INSPY. 1003. 4138305_03
9
1.2 3,4,5,6 7 8 9 10 11 12 13 14,15
NS 1251 Y ° ° A ° ° ° 00
3.3. DESCRIPTION AND CHOICE OF THE UNIT
Field Code 1, 2 NS
3, 4, 5, 6 Size 1251, 1401, 1601, 1801, 2101, 2401, 1402, 1602, 1802, 2002, 2202
2352, 2502, 2652, 2802, 3002, 3202, 3402, 3602, 3902, 4202, 4502, 4802, 5002, 5202, 5402, 5702, 6003, 6303, 6603, 6903, 7203
7 Compressor
° Standard thermostatic valve - Produced water up to 4 °C Y Standard thermostatic valve - Produced water up to - 6 °C X
(1)
Electronic thermostatic valve - Produced water up to - 6 °C
8 Model
° Cooling only C Condensing system
9 Heat recovery
° Without heat recovery D Desuperheater (plate heat exchanger) T Total heat recovery (plate heat exchanger)
10 Version
° Standard L Standard in silenced version A High efficiency E High efficiency, low noise operation
11 coils
° Made of aluminium R Made of copper S Tinned copper V In painted aluminium
12 Fans
° Standard M Enlarged J Inverter
13 Power supply
° Standard 400-3-50 Hz with fuses 2 230V-3-50 Hz with fuses *
4 230V-3-50Hz with thermomagnetic switches
* (not available with sizes 1251÷2401, 2352÷7203)
5 500V-3-50 Hz with fuses * 8 400V-3-50Hz with thermomagnetic switches 9 500V-3-50Hz with thermomagnetic switches
** (not available with sizes 1801÷2401, 3402÷7203)
14 - 15 Pumps
00
Without pumps
PA
Pump A
PB
Pump A with reserve pump
PC
Pump B
PD
Pump B with reserve pump
PE
Pump C
PF
Pump C with reserve pump
PG
Pump D
PH
Pump D with reserve pump
PJ
Pump E
PK
Pump E with reserve pump
The models NS5002-5202-5402­5702 have always and only electronic thermostatic valve «X», there is no mechanical valve ver­sion. «Y»
(1)
INSPY. 1003. 4138305_03
10
4. COMPONENTS DESCRIPTION
4.1. CHILLER CIRCUIT
Compressor/s
Semi hermetic high-efficiency screw com­pressors, with a cooling capacity regulation
by means of continuous modulation from 40 to 100% (from 25 to 100% with electronic valve) and fitted with:
Thermal motor protection
Oil discharge temperature check
Electric heater for the heating of the oil
casing with the compressor at a stand­still
Reset button.
Water side heat exchanger
Pipe bundle exchanger of the direct expan­sion type, suitably scaled to get high level performances. Steel housing with closed cell foam elas­tomer anticondensation mattress. The pipe bundle is made with copper tubes, with a special profile that allows high heat exchange together with efficient drainage.
If so requested, the exchanger can be
fitted with an anti-freeze electrical heating element, (ACCESSORY ONLY TO BE FITTED
IN THE FACTORY), that keeps the exchanger
from outside temperatures up to -10°C, for the purpose of avoiding the formation of
ice in standby mode. With the unit working, protection is assured
by the outlet water temperature probe
.
Filter drier
Of the mechanical type with cartridges,
made of ceramics and hygroscopic mate-
rial able to trap impurities and any traces of
humidity in the chiller circuit.
Sight glass
For checking the refrigerating gas load and any humidity in the refrigerating circuit.
Thermostatic valve
In standard version, NS fi ts the thermostatic
mechanical valve, with external equaliser on the evaporator outlet, modulates the gas fl ow to the evaporator according to the thermal load, in such a way as to ensure the proper degree of overheating of the intake gas.
- Electronic thermostatic valve
As a confi guration option, it is possible to have the electronic thermostatic valve for the standard models NS5002-5202­5402-5702.
Taps Present in the liquid and discharge lines, and allow to intercept the refrigerant in case of extraordinary maintenance.
Solenoid valve
The valve closes when the compressor turns off, preventing the fl ow of refrigerant gas towards the evaporator.
Desuperheater (plate heat, optional) (1 per parallel circuit)
Of the plate type (AISI 316), externally insu­lated with closed cell material to reduce thermal dispersion.
Total recover (plate heat, optional)
Of the plate type (AISI 316), externally insu­lated with closed cell material to reduce thermal dispersion.
4.2. FRAME AND FANS
Fan unit
Helical form with protection class IP54, statically and dynamically balanced. The electric fans are protected electrically with thermomagnetic switches and mechanical­ly with metal anti-intrusion grilles, in accord­ance with the standard CEI EN 60335-2-40.
Load-bearing structure
Made of hot-galvanised steel sheet of a suitable thickness, varnished with polyester powders able to resist atmospheric agents
The available models can be:
1. Single module - single circuit 1251, 1401, 1601, 1801, 2101, 2401
2. Single module - two circuits 1402, 1602, 1802, 2002, 2202, 2352, 2502, 2652, 2802,
3. Double module - two circuits 3002, 3202,3402, 3602, 3902,4202,4502, 4802, 5002, 5202, 5402, 5702
4. Triple module - three circuits 6003, 6303, 6603, 6903, 7203
WARNING THE HIGH EFFICIENCY TRIPLE MODULES «A-E» ARE SENT SEPARATELY
INSPY. 1003. 4138305_03
11
over time.
Acoustic protection cover
(2)
Standard on all the NS versions, it consists of a compartment in very thick steel sheet and insulated entirely with soundproofi ng material. It permits the acoustic power emitted by the unit to be reduced and furthermore protects the compressors from the atmospheric agents.
4.3. HYDRAULIC COMPONENTS
Circulation pump No. 1/2 for optional circuit configurator
Depending on the characteristics of the pump chosen, it offers a useful head to overcome the pressure drops in the system. Whenever the reserve pump is present, this is managed by the electronic board.
Expansion tank 2 per circuit (2x25 l) (only in the versions with pump)
membrane type with nitrogen preloading.
4.4. SAFETY AND CONTROL COMPONENTS
Differential pressure switch IP54 1 per circuit
Located between the inlet and outlet of the evaporator, it has the task of checking that there is water circulation; otherwise, the unit blocks.
Low pressure transducer
Allows displaying, on the microprocessor card display, the value of the compressor's suction pressure (one per circuit) on the low-pressure side of the refrigerant circuit
High pressure transducer
Allows displaying, on the microprocessor card display, the value of the compressor's delivery pressure (one per circuit) On the high pressure side of the refrigerant circuit
Double high pressure switch (manual + tool)
Factory-calibrated, it is placed on the high pressure side of the cooling circuit, it shuts down compressor operation in the case of abnormal operating pressure.
Refrigeration circuit safety valves (HP, LP)
Calibrated at 22 bar HP - 16.5 LP, they cut in relieving the overpressure in the case of
abnormal operating pressures.
Fuses or thermomagnetic switches for compressors protection to be specified when ordered
Fan protection thermomagnetic switch
Secondary thermomagnetic switch
protection
4.5. ELECTRICAL COMPONENTS
Electrical panel
Contains the power section and the management of the controls and safety devices.
Door-block disconnecting switch
IT is possible to access the electrical panel by disconnecting the voltage, then using the opening lever of the panel itself. This lever can be blocked with one or more padlocks during maintenance, in order to prevent the machine being powered up accidentally.
Control keypad
Provides full control functions.
NB For a detailed description refer to the user manual.
Remote control panel (PVR3)
This allows the chiller command operations to be given from a distance.
Pump version (example)
(2) IT IS POSSIBLE TO HAVE A FUR­THER NOISE REDUCTION, WITH DCPX AND AK ACCESSORIES. For further information refer to the chapter ACCESSORIES.
HYDRAULIC CIRCUIT KEY:
1. Evaporator input
2. Pump unit
3. Shut-off valves
4. Expansion tanks 2x25 litres
5. Water outlet with attachment
6. Total recovery
7. Inlet total recovery
8. Output total recovery
In any versions with or without pumps, desuperheater and total recovery, the water connections are VICTAULIC with supplied joint to weld
N.B.: the drawing is only an example and reflects only the version with pumps and total recovery.
All the electric cables are wired for immediate recognition of the electrical components
INSPY. 1003. 4138305_03
12
4.6. ELECTRONIC REGULATION
Electronic regulation on the NS chillers consists of control cards for each compres­sor connected to each other in a network and a control panel with display, see figure.
In the case of models with more than one compressor, the card that controls com­pressor 1 is the “MASTER” card, while the others are “SLAVE”. On each card, trans­ducers, loads and alarms are connected to the compressor that commands while the general machine ones are connected only on the master card. The program and parameter pre-set are stored permanently
in the controller’s FLASH memory, to ensure that they are kept in memory even when the system is not powered (without the
need for an auxiliary battery). The connection to the serial supervision as­sistance line in accordance with the RS485 standard, is performed through the serial card ACCESSORY RS485P1 and the com-
munication protocol.
• The terminal, which is always controlled by microprocessor, is equipped with a display,
a keypad and a set of LEDs, and is used
for programming control parameters (Set Points, differential band, alarm threshold)
and for fundamental user operations (ON/ OFF, display controlled values). The terminal does not need to be con-
nected to the pCO for normal controller op-
eration, and is necessary only when initially programming the basic parameters.
Microprocessor
Remote on/off with external contact without power
Multi-lingual menu
Phase sequence control
Independent control of individual
compressors
Ammetric transformer
Cumulative failure block signalling
Alarm log function
Daily/weekly programming
Inlet/outlet water temperature display
Alarm display
Full proportional regulation of the out-
put water temperature
Programmable timer function
Function with double setting point con-
nected to an external contact
Fan regulation
Interfaceability with the Modbus proto-
col (accessory)
Pump/s control
Compressor rotation control
Analogue input from 4 to 20 mA
Outside air temperature sensor
Function "Always Woking" In the case
of critical conditions (e.g. ambient tem­perature that is too high) the machine does not stop but is able to regulate itself and provide the maximum power that can be generated in those condi­tions.
Self adapting operating differential “Switching Histeresys” to ensure the cor-
rect compressor functioning at all times even in plants with a low water content or insufficient flow rates. This system reduces the compressor wear
The AFFP “Anti Freezing Fan Protection”
system that turns on the fans periodi­cally when the external temperatures are very low
The PDC “Pull Down Control” system
to prevent the activation of the power steps when the water temperature is approaching the set point quickly. It optimises the operation of the machine both when running normally or when there are load variations, thereby assuring top machine efficiency in all
situations. For further information, refer to the user manual.
pCO3MASTER
pCO3SLAVE
pCO3SLAVE
SINGLE
Compressor
BI
Compressor
TRI
COMPRESSOR
Terminal on the machine
INSPY. 1003. 4138305_03
13
5. ACCESSORIES
5.1. ELECTRIC REGULATION ACCESSORIES
AER485P1: Through this accessory,
it is possible to connect the unit with BMS supervision systems with electri­cal standard RS 485 and MOFDBUS type protocol
NOTE: disclosure must be provided for compressor No. 1 .
AERWEB30: the AERWEB device al-
lows remote control of a chiller via a serial link from a standard PC. Using additional modules, the device allows to control the chiller via the telephone network, using the AER­MODEM accessory; or via the GSM network, using the AERMODEM GSM accessory. AERWEB can pilot up to 9 chillers, but each of these must be equipped with the AER485 or AER485P1 accessory.
MULTICHILLER: Control system to
switch the individual chillers on and off, and command them, in a system in which several units are installed in parallel, always ensuring a constant delivery to the evaporators.
PRV3: This allows the chiller com-
mand operations to be given from a distance.
5.2. ELECTRICAL ACCESSORIES
RIFNS: current phase advancer.
Parallel connection with the motor makes the reduction of input cur­rent possible. It can only be installed when the machine is being made and must therefore be specified when the order is placed.
DCPX: STANDARD for the VERSIONS:
1. SILENCED «A-E»
2. WITH DESUPERHEATER «D»
This accessory allows proper opera­tion with outdoor temperatures below 20 ° C and up to - 10 ° C. It is made up of an electronic regulation card that varies the fan rpm on the basis of the condensation pressure, once the high pressure transducer is read for the purposes of keeping it sufficiently high FOR the proper functioning of the unit.
KRS: Electric resistor exchangers for outside temperatures down to -10 ° C
5.3. GENERAL ACCESSORIES
GP: (TO INSTALL IN FACTORY)Pro­tects the external coil from shocks and prevents accidental access to the area where the compres­sors and the refrigeration circuit are placed.
AK: (TO INSTALL IN FACTORY) This accessory allows additional reduction of the noise by means of:
Hood of the compressor optimised by high density lead free materials which allow further reduction of vibrations.
AVX (Antivibration spring) to re- duce the transmission of vibrations to the support structure of the unit, consider the installation of shock absorbers at each point of support (see compatibility table).
pCO3MASTER
pCO3SLAVE
pCO3SLAVE
RS485
RS485P1
Modbus
RS485
Modbus
RS485
Modbus
RS485P1 RS485P1
AER485P1
AER485P1
AER485P1
CARD
AER485P1
Compatibility of accessories
Mod. NS 1251 1401 1601 1801 2101 2401 1402 1602
AER485P1 •••••••(x2) •(x2) MULTICHILLER •••••••• AK-ACUSTIC KIT
(1)(4)
••••••••
PRV3 •••••••• AERWEB30 •••••••• KRS
(1)
° - L
KRS10 KRS10 KRS10 KRS10 KRS11 KRS11 KRS10 KRS10
KRSDES KRS10DES KRS10DES KRS10DES KRS10DES KRS11DES KRS11DES KRS18DES KRS18DES KRSREC KRS10REC KRS10REC KRS10REC KRS10REC KRS11REC KRS11REC KRS10REC KRS10REC KRS
(1)
A - E
KRS10 KRS10 KRS11 KRS10 KRS11 KRS11 KRS11 KRS11
KRSDES KRS10DES KRS10DES KRS11DES KRS10DES KRS11DES KRS11DES KRS19DES KRS19DES KRSREC KRS10REC KRS10REC KRS11REC KRS10REC KRS11REC KRS11REC KRS11REC KRS11REC
Mod. NS 1802 2002 2202 2352 2502 2652 2802 3002
AER485P1 •(x2) •(x2) •(x2) •(x2) •(x2) •(x2) •(x2) •(x2) MULTICHILLER •••••••• AK-ACUSTIC KIT
(1)(4)
••••••••
PRV3 •••••••• AERWEB30 •••••••• KRS
(1)
° - L
KRS10 KRS10 KRS10 KRS10 KRS10 KRS11 KRS11 KRS12
KRSDES KRS18DES KRS18DES KRS18DES KRS18DES KRS18DES KRS19DES KRS19DES KRS12DES KRSREC KRS10REC KRS10REC KRS10REC KRS10REC KRS10REC KRS11REC KRS11REC KRS12REC KRS
(1)
A - E
KRS10 KRS10 KRS11 KRS11 KRS11 KRS11 KRS11 KRS13
KRSDES KRS18DES KRS18DES KRS19DES KRS19DES KRS19DES KRS19DES KRS19DES KRS13DES KRSREC KRS10REC KRS10REC KRS11REC KRS11REC KRS11REC KRS11REC KRS11REC KRS13REC
Mod. NS 3202 3402 3602 3902 4202 4502 4802 5002
AER485P1 •••••••(x2) •(x2) MULTICHILLER •••••••• AK-ACUSTIC KIT
(1)(4)
••••••••
PRV3 •••••••• AERWEB30 •••••••• KRS
(1)
° - L
KRS12 KRS12 KRS12 KRS13 KRS13 KRS14 KRS14 KRS14
KRSDES KRS12DES KRS12DES KRS12DES KRS13DES KRS13DES KRS14DES KRS14DES KRS14DES KRSREC KRS12REC KRS12REC KRS12REC KRS13REC KRS13REC KRS14REC KRS14REC KRS14REC KRS
(1)
A - E
KRS14 KRS13 KRS12 KRS13 KRS13 KRS14 KRS14 KRS14
KRSDES KRS14DES KRS13DES KRS12DES KRS13DES KRS13DES KRS14DES KRS14DES KRS14DES KRSREC KRS14REC KRS13REC KRS12REC KRS13REC KRS13REC KRS14REC KRS14REC KRS14REC
INSPY. 1003. 4138305_03
14
(1) Accessories can only be fitted in the factory (2) Accessories available only with supply power
400V-3-50Hz
(3) Standard accessory in silenced VERSIONS and
with DESUPERHEATER
(4) Accessories available only in SILENCED versions
The number between brackets, e.g. (x2), indicates the quantity of the required accessories
Mod. NS °/L
(1)
1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002
GP 300M (2) •••• GP 400M (2) •• GP 300B (2) ••• GP 400B (2) •••• GP 500B (2) •• GP 300M+300M (2)
Mod. NS °/L
(1)
3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203
GP 300M+300M •• GP 300M+400M ••• GP 400M+400M •• GP 400M+500M • GP 500M+500M ••• GP 300M+300M+400M • GP 300M+400M+400M •• GP 400M+400M+400M ••
Mod. NS A/E
(1)
1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002
GP 300M ••• GP 400M GP 500M •• GP 300B •• GP 400B GP 500B •••••• GP 300M+300M
Mod. NS A/E
(1)
3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203
GP 300M+300M • GP 300M+400M • GP 400M+400M • GP 400M+500M •• GP 500M+500M •••••• GP 400M+400M+500M • GP 400M+500M+500M •• GP 500M+500M+500M ••
Mod. NS °/L 1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002 AVX 502 502 502 501 506 506 502 502 503 504 505 505 505 511 511 509 DCPX
(3)
65 65 65 65 69 69 69 68 68 68 68 68 68 68 68 68
RIFNS
(2)
1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2602 2802 3002
Mod. NS °/L 3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203 AVX 509 509 507 508 508 516 516 532 533 533 534 517 515 515 523 523 DCPX
(3)
68 68 68 72 72 73 73 73 73 73 73 68+76 72+76 72+76 73+76 73+76
RIFNS
(2)
3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203
Mod. NS °/L 1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002 DCPX enlarged fans
69 69 69 69 69 69 68 68 68 68 68 68 68 68 68 73
Mod. NS °/L 3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203 DCPX enlarged fans
73 73 73 73 73 73 73 73 73 74 75 73+76 73+76 73+76 73+76 73+76
Mod. NS A/E 1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002 AVX 502 502 502 506 510 510 503 503 504 511 511 511 511 511 511 509 DCPX
(3)
65 65 65 69 69 69 68 68 68 68 68 68 68 68 68 68
RIFNS
(2)
1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2602 2802 3002
Mod. NS A/E 3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203 AVX 509 513 516 519 519 521 521 535 535 535 535 526 528 528 531 531 DCPX
(3)
68 72 73 73 73 73 73 73 73 73 73 73+76 73+76 73+76 73+76 73+76
RIFNS
(2)
3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203
Mod. NS A/E 1251 1401 1601 1801 2101 2401 1402 1602 1802 2002 2202 2352 2502 2652 2802 3002 DCPX enlarged fans
69 69 69 69 70 70 68 68 68 73 73 73 73 73 73 73
Mod. NS A/E 3202 3402 3602 3902 4202 4502 4802 5002 5202 5402 5702 6003 6303 6603 6903 7203 DCPX enlarged fans
73 73 73 74 74 75 75 75 75 75 75 73+77 74+77 74+77 75+77 75+77
Mod. NS 5202 5402 5702 6003 6303 6603 6903 7203
AER485P1 •(x2) •(x2) •(x2) •(x3) •(x3) •(x3) •(x3) •(x3) MULTICHILLER •••••••• AK-ACUSTIC KIT
(1)(4)
••••••••
PRV3 •••••••• AERWEB30 •••••••• KRS
(1)
° - L
KRS14 KRS14 KRS14 KRS15 KRS16 KRS16 KRS17 KRS17
KRSDES KRS14DES KRS14DES KRS14DES KRS15DES KRS16DES KRS16DES KRS17DES KRS17DES KRSREC KRS14REC KRS14REC KRS14REC KRS15REC KRS16REC KRS16REC KRS17REC KRS17REC KRS
(1)
A - E
KRS14 KRS14 KRS14 KRS15 KRS16 KRS16 KRS17 KRS17
KRSDES KRS14DES KRS14DES KRS14DES KRS15DES KRS16DES KRS16DES KRS17DES KRS17DES KRSREC KRS14REC KRS14REC KRS14REC KRS15REC KRS16REC KRS16REC KRS17REC KRS17REC
INSPY. 1003. 4138305_03
15
6. TECHNICAL DATA
NS Vers. U.M. 1251 1401 1601 1801 2101 2401 1402 1602 1802
Cooling capacity:
°
kW
259 294 336 385 443 493 282 317 358
L 238 265 308 361 412 454 259 287 325
A 276 314 347 420 466 533 304 345 397
E 252 291 330 391 432 497 273 314 364
Total input power
°
kW
91 108 117 145 166 180 102 121 138
L 97 113 124 150 170 185 106 125 142
A 88 97 104 134 150 165 97 109 127
E 90 101 109 140 155 172 101 115 130
Evaporator water flow rate
°
l/h
44550 50570 57790 66220 7620 8480 4850 54520 61580
L 40940 45580 52980 62090 70860 78090 44550 49360 5590
A 47470 54010 59680 72240 80150 91680 52290 59340 68280
E 43340 50050 56760 67250 74300 85480 46960 54010 62610
Evaporator pressure drops
°
kPa
42 44 45 58 37 43 39 47 53
L 353638513236333944
A 453925453847303935
E
38 33 23 39 33 41 24 32 29
ENERGY INDICES
EER
°
W/W
2,85 2,72 2,87 2,66 2,67 2,75 2,77 2,62 2,59
L 2,45 2,34 2,48 2,41 2,42 2,45 2,44 2,29 2,28
A 3,14 3,24 3,34 3,13 3,11 3,23 3,13 3,17 3,13
E 2,80 2,88 3,03 2,79 2,79 2,89 2,70 2,73 2,80
ESEER
° 3,81 3,75 3,70 3,73 3,78 3,76 3,88 3,72 3,69 L 3,70 3,64 3,59 3,62 3,67 3,65 3,76 3,61 3,58
A 4,22 4,24 4,30 4,24 4,20 4,28 4,20 4,22 4,20
E
4,09 4,11 4,17 4,11 4,07 4,15 4,07 4,09 4,07
ELECTRICAL DATA
400V-3-50Hz
Total input current
°
A
159 187 197 238 280 301 177 207 218
L 162 192 206 244 284 307 180 212 221
A 154 172 181 222 256 279 171 190 215
E 152 170 182 225 255 283 170 194 214
Maximum current
°/L 236 236 236 331 348 388 269 309 345
A/E 236 236 236 338 355 395 269 309 352
Peak current
°/L 381 425 425 486 614 678 245 283 325
A/E
381 425 425 493 621 685 245 283 332
Charge
Oil kg
19 19 19 35 35 35 15 + 15 15 + 15 15 + 15
COMPRESSOR (TWIN-SCREW)
No. of compressors/circuits ALL no./no. 1/1 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/2 Capacity control
Standard thermostatic valve
% 40-100
Capacity control
Electronic thermostatic valve
%
25-100
FANS (AXIAL)
Quantity
°/L
666688666
A/E 6 6 6 8 10 10 6 6 8
Total power input (1.4)
°/L
kW
8,4 8,4 8,4 8,4 11,2 11,2 8,4 8,4 8,4
A/E 8,4 8,4 8,4 11,2 14 14 8,4 8,4 11,2
Total input current (3)
°/L
A
18 18 18 18 24 24 18 18 18
A/E 18 18 18 24 30 30 18 18 24
Air fl ow rate
°
m³/h
116000 116000 110000 110000 150000 145000 116000 116000 110000
L 82000 82000 82000 82000 110000 104000 82000 82000 82000
A 110000 106000 106000 136000 180000 174000 106000 106000 144000
E
70000 74000 81500 94000 113000 118000 74000 77000 96000
6.1. TECHNICAL DATA NS 1251 … 1802
NOMINAL REFERENCE CONDITIONS
Inlet water temperature 12°C Outlet water temperature 7°C Outside air temperature d.b. 35°C Δt 5°C
INSPY. 1003. 4138305_03
16
NOMINAL REFERENCE CONDITIONS DESUPERHEATER
Outlet water temperature 45°C Δt 5°C
TO THE TOTAL RECOVERY
Outlet water temperature 45°C Δt 5°C
NS Vers. U.M. 1251 1401 1601 1801 2101 2401 1402 1602 1802 ENLARGED FANS (AXIAL)
Quantity
°/L
666688666
A/E 66681010668
Total input power
°
kW
12 12 12 12 16 16 12 12 12
L 7,8 7,8 7,8 7,8 10,4 10,4 7,8 7,8 7,8
A 121212162020121216
E 7,8 7,8 7,8 10,4 13 13 7,8 7,8 10,4
Total input current
°
A
24 24 24 24 32 32 24 24 24
L 15,6 15,6 15,6 15,6 20,8 20,8 15,6 15,6 15,6
A 242424324040242432
E 15,6 15,6 15,6 20,8 26 26 15,6 15,6 20,8
Air fl ow rate
°
m³/h
116000 116000 110000 110000 150000 145000 116000 116000 110000
L 82000 82000 82000 82000 110000 104000 82000 82000 82000
A 110000 106000 106000 136000 180000 174000 106000 106000 144000
E
70000 74000 81500 94000 113000 118000 74000 77000 96000
FANS INVERTER (AXIAL)
Quantity
°/L
666688666
A/E 66681010668
Total input power
°
kW
12 12 12 12 16 16 12 12 12
L 7,8 7,8 7,8 7,8 10,4 10,4 7,8 7,8 7,8
A 121212162020121216
E 7,8 7,8 7,8 10,4 13 13 7,8 7,8 10,4
Total input current
°
A
24 24 24 24 32 32 24 24 24
L 15,6 15,6 15,6 15,6 20,8 20,8 15,6 15,6 15,6
A 242424324040242432
E 15,6 15,6 15,6 20,8 26 26 15,6 15,6 20,8
Air fl ow rate
°
m³/h
116000 116000 110000 110000 150000 145000 116000 116000 110000
L 82000 82000 82000 82000 110000 104000 82000 82000 82000
A 110000 106000 106000 136000 180000 174000 106000 106000 144000
E
70000 74000 81500 94000 113000 118000 74000 77000 96000
EVAPORATOR (TUBE CORE)
Water contents
°/L dm
3
80 77 74 74 106 165 77 77 77
A/E dm
3
80 74 106 113 165 165 106 106 108
Water connections (VICTAULIC)
°/L
ø
4"
4"
5" 4"
A/E 5"
Electric resistor (Effi ciency/std/opt.)
NO
Water fi lter (dim/std/opt.) Quantity
1
DESUPERHEATERS (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
65 73.5 84 96 111 123 70.5 79 89.5
L 59.5 66.5 77 90 103 113.5 65 72 81
A 70 78.5 88.2 105 116.5 133.5 76 86.5 98
E 63 73 82.5 98 108 124 68 78.5 91
Quantity all no. 1 2
Water fl ow rate
°
l/h
11180 12642 14448 16512 19092 21156 12126 13588 15394
L 10234 11438 13244 15480 17716 19522 11180 12384 13932
A 61060 69316 76196 93396 103544 117648 67596 76540 88064
E 61060 69316 76196 93396 103544 117648 67596 76540 88064 Pressure drop of the exchanger all kPa 4 Water connections (VICTAULIC) diam
2"
Desuperheater weight All kg 30 30 30 40 50 60 40 40 40
HEAT RECOVERY (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW 355 403 443 543 602 684 393 445 512
L
A
E Quantity
all
1 Water fl ow rate l/h 61060 69316 76196 93396 103544 117648 67596 76540 88064 Pressure drop of the exchanger kPa 44 57 69 51 62 65 54 69 45 Water connections (VICTAULIC) Ø
4"
PUMP/S No. 1 - 2 x circuit OPTIONAL
PUMPS
PA PC PE PG PJ
Input power kW 4 5,5 7,5 9,2 11 Input current A
5,5 7,5 10 12,5 15 Weight kg 109 117 121 140 148 Water connections (VICTAULIC) Ø
According to the fitted evaporator
INSPY. 1003. 4138305_03
17
Sound power
Aermec determines the sound power value on the basis of measurements taken in accordance with standard 9614-2, in compliance with the Eurovent certification.
Sound pressure
Sound pressure in an unrestricted range on a reflec­tive plane (directional fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
NS Vers. U.M. 1251 1401 1601 1801 2101 2401 1402 1602 1802 EXPANSION TANK
Capacity
-
dm
3
25 Calibration pressure Bar 1.5 Quantity 2
SOUND DATA
Sound power
°
dB(A)
94 95 97 97 98 98 96 97 97
L 868789899090888989
Sound pressure
° 61,8 62,8 64,8 64,8 65,6 65,6 63,8 64,8 64,8 L 53,8 54,8 56,8 56,8 57,6 57,6 55,8 56,8 56,8
Sound power
A 949597979898969797
E 868789899090888989
Sound pressure
A 61,8 62,8 64,8 64,6 65,5 65,5 63,8 64,8 64,6
E
53,8 54,8 56,8 56,6 57,5 57,5 55,8 56,8 56,6
DIMENSIONS°/L
Height
ALL
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450 Width 2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 3780 3780 3780 3780 4770 4770 3780 3780 3780 Weight when empty
Kg
2910 3060 3150 3650 4230 4570 3250 3270 3460 Weight when empty with desuperheater
2940 3090 3180 3690 4280 4630 3290 3310 3500 Weight when empty with total heat recovery
3130 3280 3370 3914 4516 4889 3470 3490 3724 Weight during operation
2990 3137 3224 3724 4336 4735 3327 3347 3537
DIMENSIONS A/E
Height
ALL
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450 Width 2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 3780 3780 3780 4770 5750 5750 3780 3780 4770 Weight when empty
Kg
3050 3230 3250 4330 4920 5150 3420 3560 3900 Weight when empty with desuperheater
3080 3260 3280 4370 4970 5210 3460 3500 3940 Weight when empty with total heat recovery
3270 3450 3470 4594 5206 5469 3640 3780 4164 Weight during operation
3130 3304 3356 4443 5085 5315 3526 3666 4008
INSPY. 1003. 4138305_03
18
6.2. TECHNICAL DATA NS 2002 … 3402
NOMINAL REFERENCE CONDITIONS
Inlet water temperature 12°C Outlet water temperature 7°C Outside air temperature d.b. 35°C Δt 5°C
NS Vers. U.M. 2002 2202 2352 2502 2652 2802 3002 3202 3402
Cooling capacity:
°
kW
404 450 486 503 541 578 629 671 721
L 372 420 443 459 495 530 573 616 669
A 450 495 519 543 577 612 661 695 767
E 410 453 478 503 539 574 622 660 721
Total input power
° 154 171 177 187 202 216 225 235 262 L 160 181 185 198 211 230 237 248 274
A 144 157 166 173 182 197 201 208 238
E 150 161 171 181 192 207 210 218 249
Evaporator water flow rate
°
l/h
69490 77400 83590 86520 93050 99420 108190 115410 124010
L 63980 72240 76200 78950 85140 91160 98560 105950 115070
A 77400 85140 89270 93400 99240 105260 113690 119540 131920
E 70520 77920 82220 86520 92710 98730 106980 113520 124010
Evaporator pressure drops
°
kpa
36 40 48 50 47 53 44 38 50
L 313540423945373243
A 443942464855322535
E
37 33 36 39 42 48 28 23 31
ENERGY INDICES
EER
°
W/W
2,62 2,63 2,74 2,70 2,68 2,67 2,79 2,86 2,75
L 2,32 2,33 2,39 2,32 2,34 2,30 2,41 2,48 2,44
A 3,13 3,15 3,13 3,14 3,17 3,11 3,29 3,34 3,22
E 2,73 2,81 2,80 2,78 2,81 2,77 2,96 3,03 2,90
ESEER
° 3,59 3,56 3,82 3,81 3,73 3,78 3,68 3,68 3,68 L 3,48 3,45 3,71 3,70 3,62 3,67 3,57 3,57 3,57
A 4,23 4,24 4,23 4,25 4,25 4,21 4,28 4,30 4,26
E
4,10 4,11 4,10 4,12 4,12 4,08 4,15 4,17 4,13
ELECTRICAL DATA
Total input current
°
A
261 295 306 322 347 371 384 394 435
L 266 301 310 333 354 381 398 411 450
A 248 274 288 301 320 339 353 362 403
E 247 277 290 303 320 344 352 364 407
Maximum current
°/L 372 392 425 458 458 458 472 472 567
A/E 372 392 425 458 458 458 472 472 567
Peak current
°/L 403 420 480 507 551 553 567 567 628
A/E
410 427 487 514 558 560 567 567 635
Charge
Oil kg 15 + 22
22 + 22 22 + 19 19 + 19 19 + 19 19 + 19 19 + 19 19 + 19 19 + 35
COMPRESSOR (TWIN-SCREW)
No. of compressors/circuits ALL no./no. 2/2 Capacity control
Standard thermostatic valve
% 40-100
Capacity control
Electronic thermostatic valve
%
25-100
FANS (AXIAL)
Quantity
°/L
888888121212
A/E 10 10 10 10 10 10 12 12 14
Total input power
°/L
kW
11,2 11,2 11,2 11,2 11,2 11,2 16,8 16,8 16,8
A/E 14 14 14 14 14 14 16.8 16.8 19.6
Total input current
°/L
A
24 24 24 24 24 24 36 36 36
A/E 30 30 30 30 30 30 36 36 42
Air fl ow rate
°
m³/h
145000 145000 145000 145000 152000 152000 226000 220000 220000
L 104000 104000 104000 104000 108000 108000 164000 164000 164000
A 187500 180000 176500 173000 173000 173000 212000 212000 242000
E
124500 120000 123000 126000 130000 136000 155500 163000 175500
INSPY. 1003. 4138305_03
19
NS Vers. U.M. 2002 2202 2352 2502 2652 2802 3002 3202 3402 ENLARGED FANS (AXIAL)
Quantity
°/L
888888121212
A/E 10 10 10 10 10 10 12 12 14
Input power
°
kW
16 16 16 16 16 16 24 24 24
L 10,4 10,4 10,4 10,4 10,4 10,4 15,6 15,6 15,6
A 202020202020242428
E 13 13 13 13 13 13 15,6 15,6 18,2
Input current
°
A
32 32 32 32 32 32 48 48 48
L 20,8 20,8 20,8 20,8 20,8 20,8 31,2 31,2 31,2
A 404040404040484856
E 26 26 26 26 26 26 31,2 31,2 36,4
Air fl ow rate
°
m³/h
145000 145000 145000 145000 152000 152000 226000 220000 220000
L 104000 104000 104000 104000 108000 108000 164000 164000 164000
A 187500 180000 176500 173000 173000 173000 212000 212000 242000
E
124500 120000 123000 126000 130000 136000 155500 163000 175500
FANS INVERTER (AXIAL)
Quantity
°/L
888888121212
A/E 10 10 10 10 10 10 12 12 14
Input power
°
kW
16 16 16 16 16 16 24 24 24
L 10,4 10,4 10,4 10,4 10,4 10,4 15,6 15,6 15,6
A 202020202020242428
E 13 13 13 13 13 13 15,6 15,6 18,2
Input current
°
A
32 32 32 32 32 32 48 48 48
L 20,8 20,8 20,8 20,8 20,8 20,8 31,2 31,2 31,2
A 404040404040484856
E 26 26 26 26 26 26 31,2 31,2 36,4
Air fl ow rate
°
m³/h
145000 145000 145000 145000 152000 152000 226000 220000 220000
L 104000 104000 104000 104000 108000 108000 164000 164000 164000
A 187500 180000 176500 173000 173000 173000 212000 212000 242000
E
124500 120000 123000 126000 130000 136000 155500 163000 175500
EVAPORATOR (TUBE CORE)
Water contents
°/L dm
3
108 108 108 108 103 103 77+74 74+74 74+74
A/E dm
3
108 103 103 103 98 98 74+106 106+106 106+113
Water connections (VICTAULIC)
°/L
ø4"
A/E
Electric resistor (Effi ciency/std/opt.)
øNO
Water fi lter (dim/std/opt.) Quantity 1 2
DESUPERHEATERS (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
101 112 121 126 135 144 157.5 168 180
L 93 105 111 115 123 132 143.5 154 167
A 111 123.8 129.8 135.7 146.2 156.7 166.5 176.5 193
E 102.5 113 119.5 126 135 143.5 155.5 165 180
Quantity all 2 2 2222222
Water fl ow rate
°
l/h
17372 19264 20812 21672 23220 24768 27090 28896 30960
L 15996 18060 19092 19780 21156 22704 24682 26488 28724
A 19092 21294 22326 23340 25146 26952 28638 30358 33196
E 17630 19436 20554 21672 23220 24682 26746 28380 30960 Pressure drop of the exchanger all kPa 4 4 4444444 Water connections (VICTAULIC) Ø
2"
Desuperheater weight All kg 40 50 50 50 60 60 60 70 70
HEAT RECOVERY (PLATE HEAT) OPTIONAL
Recovered effi ciency
° kW 580 638 671 702 745 795 845 886 985
L kW 580 638 671 702 745 795 845 886 985
A kW 580 638 671 702 745 795 845 886 985
E kW 580 638 671 702 745 795 845 886 985 Quantity All 1 2 Water fl ow rate All l/h 99760 109736 115412 120744 128140 136740 145340 152392 169420 Pressure drop of the exchanger All kPa 58 70 63 68 62 71 60 66 60 Water connections (VICTAULIC) Ø
4"
Weight All kg 286 286 319 319 385 385 440 440 484
PUMP/S No. 1 - 2 x circuit OPTIONAL
PUMPS
PA PC PE PG PJ
Input power kW 4 5,5 7,5 9,2 11 Input current A
5,5 7,5 10 12,5 15 Weight kg 109 117 121 140 148 Water connections (VICTAULIC) diam
According to the fitted evaporator
NOMINAL REFERENCE CONDITIONS DESUPERHEATER
Outlet water temperature 45°C Δt 5°C
TO THE TOTAL RECOVERY
Outlet water temperature 45°C Δt 5°C
INSPY. 1003. 4138305_03
20
NS Vers. U.M. 2002 2202 2352 2502 2652 2802 3002 3202 3402 EXPANSION TANK
Capacity dm
3
25 Calibration pressure Bar 1.5 Quantity 24
SOUND DATA
Sound power
°
dB(A)
98 98 97 98 98 98 99 99 99
L 909090909091909191
Sound pressure
° 65,6 65,6 64,6 65,6 65,5 65,5 66,4 66,4 66,4 L 57,6 57,6 57,6 57,6 57,5 58,5 57,4 58,4 58,4
Sound power
A 989897989898999999
E 909090909091909191
Sound pressure
A 65,5 65,5 64,5 65,5 65,5 65,5 66,4 66,4 66,3
E 57,5 57,5 57,5 57,5 57,5 58,5 57,4 58,4 58,3
DIMENSIONS°/L
Height
All
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450
Width
°/L
2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 4770 4770 4770 4770 5750 5750 7160 7160 7160 Weight when empty
Kg
4270 4740 4800 4900 5320 5330 6180 6270 6770 Weight when empty with desuper­heater
4310 4790 5190 5360 5380 5390 6240 6340 6840 Weight when empty with total heat
recovery
4556 5026 5119 5219 5705 5715 6620 6710 7254 Weight during operation 4378 4848 4908 5008 5423 5433 6331 6418 6918
DIMENSIONS A/E
Height
All
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450 Width
A/E
2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 5750 5750 5750 5750 5750 5750 7160 7160 8150 Weight when empty
Kg
4700 5270 5390 5500 5510 5520 6450 6520 7540 Weight when empty with desuperheater
4740 5320 5440 5550 5570 5580 6510 6590 7610 Weight when empty with total heat recovery
4986 5556 5709 5819 5895 5905 6890 6960 8024 Weight during operation 4808 5373 5493 5603 5608 5618 6630 6732 7759
Sound power
Aermec determines the sound power value on the basis of measurements taken in accordance with standard 9614-2, in compliance with the Eurov­ent certification.
Sound pressure
Sound pressure in an unrestricted range on a reflec­tive plane (directional fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
INSPY. 1003. 4138305_03
21
6.3. TECHNICAL DATA NS 3602 … 5702
NS Vers. U.M.
3602 3902 4202 4502 4802 5002 5202 5402 5702
Cooling capacity:
°
kW
771 828 879 936 987 1063 1140 1185 1230
L 722 773 815 866 907 984 1060 1105 1150
A 839 885 953 999 1066 1155 1244 1287 1330
E 782 822 888 928 994 1088 1160 1198 1236
Total input power
°
kW
290 311 324 345 359 390 420 432 444
L 300 320 335 355 370 405 440 454 467
A 268 284 298 314 329 360 390 408 426
E 280 295 312 327 344 376 407 426 444
Evaporator water flow rate
°
l/h
132610 142420 151190 160990 169760 182838 196082 203822 211562
L 124180 132960 140180 148950 156000 169250 182322 190062 197802
A 144310 152220 163920 171830 183350 198662 213970 221366 228763
E 134500 141380 152740 159620 170970 187138 199522 206058 212594
Evaporator pressure drops
°
kPa
58 46 50 40 43 40 36 39 42
L 514043343634313437
A 454146434742373942
E
39 35 40 37 41 37 32 34 36
ENERGY INDICES
EER
°
W/W
2,66 2,66 2,71 2,71 2,75 2,73 2,71 2,74 2,77
L 2,41 2,42 2,43 2,44 2,45 2,43 2,41 2,44 2,46
A 3,13 3,12 3,20 3,18 3,24 3,21 3,19 3,15 3,12
E 2,79 2,79 2,85 2,84 2,89 2,89 2,85 2,82 2,78
ESEER
°
W/W
3,68 3,73 3,73 3,73 3,67 3,71 3,71 3,69 3,69
L 3,57 3,62 3,62 3,62 3,56 3,60 3,60 3,58 3,58
A 4,19 4,18 4,24 4,17 4,17 4,25 4,26 4,20 4,15
E
4,06 4,05 4,11 4,04 4,04 4,12 4,13 4,07 4,03
ELECTRICAL DATA
Total input current
°
A
477 519 540 582 603 648 693 715 736
L 488 527 551 591 613 670 726 750 774
A 444 478 501 535 558 614 655 685 715
E 450 480 508 538 566 626 670 700 735
Maximum current
°/L
A
662 679 719 736 776 866 924 968 1012
A/E 676 693 733 750 790 880 938 975 1012
Peak current
°/L
A
654 778 825 900 900 1051 1109 1228 1227
A/E
661 792 839 914 914 1065 1123 1235 1227
Charge
Oil kg
35 + 35 35 + 35 35 + 35 35 + 35 35 + 35 35 + 35 35 + 35 35 + 35 35 + 35
COMPRESSOR (TWIN-SCREW)
No. of compressors/circuits ALL no./no. 2/2 Capacity control
Standard thermostatic valve
% 40-100
Capacity control
Electronic thermostatic valve
%
25-100
FANS (AXIAL)
Quantity
°/L
12 14 14 16 16 16 16 18 20
A/E 16 18 18 20 20 20 20 20 20
Input power
°/L
kW
16.8 19.6 19.6 22.4 22.4 22.4 22.4 25.2 28
A/E 22.4 25.2 25.2 28 28 28 28 28 28
Input current
°/L
A
36 42 42 48 48 48 48 54 60
A/E 48 54 54 60 60 60 60 60 60
Air fl ow rate
°
m³/h
220000 260000 255000 295000 290000 297000 304000 324000 360000
L 164000 192000 186000 214000 208000 212000 216000 240000 267000
A 272000 316000 310000 354000 348000 346000 346000 346000 346000
E 188000 207000 212000 231000 236000 254000 272000 283500 295000
NOMINAL REFERENCE CONDITIONS
Inlet water temperature 12°C Outlet water temperature 7°C Outside air temperature d.b. 35°C Δt 5°C
INSPY. 1003. 4138305_03
22
NS Vers. U.M.
3602 3902 4202 4502 4802 5002 5202 5402 5702
ENLARGED FANS (AXIAL)
Quantity
°/L
12 14 14 16 16 16 16 18 20
A/E 16 18 18 20 20 20 20 20 20
Total input power
°
kW
24 28 28 32 32 32 32 36 40
L 15.6 18.2 18.2 20.8 20.8 20.8 20.8 23.4 26
A 323636404040404040
E 20.8 23.4 23.4 26 26 26 26 26 26
Total input current
°
A
48 56 56 64 64 64 64 72 80
L 31.2 36.4 36.4 41.6 41.6 41.6 41.6 46.8 52
A 647272808080808080
E 41.6 46.8 46.8 52 52 52 52 52 52
Air fl ow rate
°
m³/h
220000 260000 255000 295000 290000 297000 304000 324000 360000
L 164000 192000 186000 214000 208000 212000 216000 240000 267000
A 272000 316000 310000 354000 348000 346000 346000 346000 346000
E 188000 207000 212000 231000 236000 254000 272000 283500 295000
FANS INVERTER (AXIAL)
Quantity
°/L
12 14 14 16 16 16 16 18 20
A/E 16 18 18 20 20 20 20 20 20
Input power
°
kW
24 28 28 32 32 32 32 36 40
L 15.6 18.2 18.2 20.8 20.8 20.8 20.8 23.4 26
A 323636404040404040
E 20.8 23.4 23.4 26 26 26 26 26 26
Input current
°
A
48 56 56 64 64 64 64 72 80
L 31.2 36.4 36.4 41.6 41.6 41.6 41.6 46.8 52
A 647272808080808080
E 41.6 46.8 46.8 52 52 52 52 52 52
Air fl ow rate
°
m³/h
220000 260000 255000 295000 290000 297000 304000 324000 360000
L 164000 192000 186000 214000 208000 212000 216000 240000 267000
A 272000 316000 310000 354000 348000 346000 346000 346000 346000
E 188000 207000 212000 231000 236000 254000 272000 283500 295000
EVAPORATOR (TUBE CORE)
Water contents
°/L
dm
3
74+74 74+106 74+165 106+165 165+165 165+200 200+200 200+200 200+200
A/E 113 +113 113+165 113+165 165+165 165+165 165+188 188+188 188+188 188+188
Water connections (VICTAULIC)
°/L
ø
4"+4" 4"+4" 4"+5" 4"+5" 5"+5" 5"/6" 6"/6" 6"/6" 6"/6"
A/E 4"+4" 4"+5" 4"+5" 5"+5" 5"+5" 5"/6" 6"/6" 6"/6" 6"/6"
Electric resistor (Effi ciency/std/opt.)
NO Water fi lter (dim/std/opt.) NO Quantity 2
DESUPERHEATERS (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
192 207 219 234 246 264 276 288 303
L 180 193 203.5 216.5 227 244 257 270 283
A 223.2 221.2 238.2 249.8 266.5 281.2 298 314.7 326.2
E 195.5 205.5 222 232 248.5 263 278 293 303
Quantity all 222222222
Water fl ow rate
°
l/h
33024 35604 37668 40248 42312 45408 47472 49536 52116
L 30960 33196 35002 37238 39044 41968 44204 46440 48676
A 38390 38046 40970 42966 45838 48366 51256 54128 56106
E 33626 35346 38184 39904 42742 45236 47816 50396 52116
Pressure drop of the exchanger
°
kPa
444445667
L 444445566
A 444445788
E 444445677
Water connections (VICTAULIC) Ø
2"
Desuperheater weight All kg 80 100 90 110 120 120 120 120 120
HEAT RECOVERY (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
1084 1144 1226 1285 1367 1428 1527 1626 1686
L 1084 1144 1226 1285 1367 1428 1527 1626 1686
A 1084 1144 1226 1285 1367 1428 1527 1626 1686
E 1084 1144 1226 1285 1367 1428 1527 1626 1686 Quantity All 222222222 Water fl ow rate All l/h 186448 196768 210872 221020 235124 245616 262644 279672 289992 Pressure drop of the exchanger All kPa 51 56 58 63 65 65 62 70 76 Water connections (VICTAULIC) Ø
4"
Weight All kg
528 550 583 605 638 669 680 680 680
PUMP/S No. 1 - 2 x circuit OPTIONAL
PUMPS
PA PC PE PG PJ
Input power kW 4 5,5 7,5 9,2 11 Input current A
5,5 7,5 10 12,5 15 Weight kg 109 117 121 140 148 Water connections (VICTAULIC) diam
According to the fitted evaporator
NOMINAL REFERENCE CONDITIONS DESUPERHEATER
Outlet water temperature 45°C Δt 5°C
TO THE TOTAL RECOVERY
Outlet water temperature 45°C Δt 5°C
INSPY. 1003. 4138305_03
23
NS Vers. U.M.
3602 3902 4202 4502 4802 5002 5202 5402 5702
EXPANSION TANK
Capacity
-
dm
3
25 Calibration pressure Bar 1.5 Quantity 4
SAFETY VALVE
Calibration bar 6 6 6666666 Quantity no.
2 + 2 2 + 2 2 + 2 2 + 2 2 + 2 2 + 3 3 + 3 3 + 3 3 + 3
SOUND DATA
Sound power
°
dB(A)
99 100 100 100 100 101 101 101 101
L 929292929293939393
Sound pressure
°
dB(A)
66,4 67,3 67,3 67,2 67,2 68,1 68,0 68,0 68,0
L 59,4 59,3 59,3 59,2 59,2 60,1 60,0 60,0 60,0
Sound power
A
dB(A)
99 100 100 100 100 101 101 101 101
E 929292929293939393
Sound pressure
A
dB(A)
66,2 67,1 67,1 67,0 67,0 68,0 68,0 68,0 68,0
E
59,2 59,1 59,1 59,0 59,0 60,0 60,0 60,0 60,0
DIMENSIONS°/L
Height ALL
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450 Width 2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 7160 8150 8150 9140 9140 10120 11100 11100 11100 Weight when empty
Kg
7280 7830 8180 8750 9090 9360 10100 10200 10350 Weight when empty with desuper­heater
7360 7930 8270 8860 9210 Weight when empty with total heat
recovery
7808 8380 8763 9355 9728 10029 10780 10880 11030 Weight during operation
7428 8010 8419 9021 9420 9725 10500 10600 10750
DIMENSIONS A/E
Height
mm
2450 2450 2450 2450 2450 2450 2450 2450 2450 Width 2200 2200 2200 2200 2200 2200 2200 2200 2200 Depth 9140 10120 10120 11100 11100 11100 11100 11100 11100 Weight when empty
Kg
8610 9180 9410 9820 10200 10450 10750 10800 10850 Weight when empty with desuper­heater
8690 9280 9500 9930 10320 10570 10870 10920 10970 Weight when empty with total heat
recovery
9138 9730 9993 10425 10838 11119 11430 11480 11530 Weight during operation 8836 9458 9688 10150 10530 10803 11126 11176 11226
Sound power
Aermec determines the sound power value on the basis of measurements taken in accordance with standard 9614-2, in compliance with the Eurovent certification.
Sound pressure
Sound pressure in an unrestricted range on a reflec­tive plane (directional fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
INSPY. 1003. 4138305_03
24
6.4. TECHNICAL DATA NS 6003 … 7203
NS Vers. U.M. 6003 6303 6603 6903 7203
Cooling capacity:
°
kW
1264 1321 1372 1430 1480
L 1176 1227 1268 1319 1361
A 1372 1419 1486 1532 1600
E 1278 1319 1384 1425 1490
Total input power
°
kW
469 490 504 525 539
L 485 505 520 540 555
A 432 448 463 479 494
E 452 467 484 499 516
Evaporator water flow rate
°
l/h
217410 227210 235980 245960 254560
L 202270 211040 218100 226870 234090
A 235980 244070 255589 263500 275200
E 219820 226870 238050 245100 256280
Evaporator pressure drops
°
kPa
53 46 48 41 43
L 4640413536
A 4543464447
E
39 37 40 38 41
ENERGY INDICES
EER
°
W/W
2,69 2,69 2,72 2,72 2,75
L 2,43 2,43 2,44 2,44 2,45
A 3,18 3,17 3,21 3,20 3,24
E 2,83 2,82 2,86 2,86 2,89
ESEER
°
W/W
3,76 3,78 3,76 3,81 3,76
L 3,65 3,67 3,65 3,70 3,65
A 4,28 4,25 4,28 4,29 4,28
E
4,15 4,12 4,15 4,16 4,15
ELECTRICAL DATA
Total input current
°
A
778 820 841 883 904
L 795 834 858 898 921
A 723 757 780 814 837
E 733 763 791 821 849
Maximum current
°/L
A
1050 1067 1107 1124 1164
A/E 1071 1088 1128 1145 1185
Peak current
°/L
A
1013 1072 1064 1122 1122
A/E
1034 1093 1085 1143 1143
Charge
Oil Kg 35 + 35 + 35 35 + 35 + 35 35 + 35 + 35 35 + 35 + 35 35 + 35 + 35
COMPRESSOR (TWIN-SCREW)
No. of compressors/circuits ALL no./no. 3/3 3/3 3/3 3/3 3/3 Capacity control
Standard thermostatic valve
% 40-100
Capacity control
Electronic thermostatic valve
%
25-100
FANS (AXIAL)
Quantity
°/L
20 22 22 24 24
A/E 26 28 28 30 30
Input power
°/L
kW
28 30,8 30,8 33,6 33,6
A/E 36,4 39,2 39,2 42 42
Input current
°/L
A
60 66 66 72 72
A/E 78 78 78 90 90
Air fl ow rate
°
m³/h
365000 405000 400000 440000 435000
L 268000 296000 290000 318000 312000
A 446000 490000 484000 528000 522000
E
306000 325000 330000 349000 354000
NOMINAL REFERENCE CONDITIONS
Inlet water temperature 12°C Outlet water temperature 7°C Outside air temperature d.b. 35°C Δt 5°C
INSPY. 1003. 4138305_03
25
NS Vers. U.M. 6003 6303 6603 6903 7203 ENLARGED FANS (AXIAL)
Quantity
°/L
20 22 22 24 24
A/E 26 28 28 30 30
Input power
°
kW
40 44 44 48 48
L 26 28,6 28,6 31,2 31,2
A 5256566060
E 33,8 36,4 36,4 39 39
Input current
°
A
80 88 88 96 96
L 52 57,2 57,2 62,4 62,4
A 104 112 112 120 120
E 67,6 72,8 72,8 78 78
Air fl ow rate
°
m³/h
365000 405000 400000 440000 435000
L 268000 296000 290000 318000 312000
A 446000 490000 484000 528000 522000
E
306000 325000 330000 349000 354000
FANS INVERTER (AXIAL)
Quantity
°/L
20 22 22 24 24
A/E 26 28 28 30 30
Input power
°
kW
40 44 44 48 48
L 26 28,6 28,6 31,2 31,2
A 5256566060
E 33,8 36,4 36,4 39 39
Input current
°
A
80 88 88 96 96
L 52 57,2 57,2 62,4 62,4
A 104 112 112 120 120
E 67,6 72,8 72,8 78 78
Air fl ow rate
°
m³/h
365000 405000 400000 440000 435000
L 268000 296000 290000 318000 312000
A 446000 490000 484000 528000 522000
E
306000 325000 330000 349000 354000
EVAPORATOR (TUBE CORE)
Water contents
°/L
dm
3
74+74 +165 74+106+ 165 74+165+165 106+165 +165 165+165 +165
A/E
113+113+ 165 113+165+165 113+165+165 165+165+165 165+165+165
Water connections (VICTAULIC)
°/L
ø
4"+4"+5" 4"+4"+5" 4"+5"+5" 4"+5"+5" 5"+5"+5"
A/E 4"+4"+5" 4"+5"+5" 4"+5"+5" 5"+5"+5" 5"+5"+5"
Electric resistor (Effi ciency/std/opt.)
øNO
Water fi lter (dim/std/opt.) Quantity 3 3 3 3 3
DESUPERHEATERS (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
315 330 342 357 369
L 294 307 317 330 340.5
A 343 354.7 371.5 383 400
E 319.5 330 346 356 372.5
Quantity all 3 3 3 3 3
Water fl ow rate
°
l/h
54180 56760 58824 61404 63468
L 50568 52804 54524 56760 58566
A 58996 61008 63898 65876 68800
E 54954 56760 59512 61232 64070 Pressure drop of the exchanger all kPa 4 4 4 4 4 Water connections (VICTAULIC) Ø
2"
Desuperheater weight All kg 80 + 60 90+60 90+60 110+60 120+60
HEAT RECOVERY (PLATE HEAT) OPTIONAL
Recovered effi ciency
°
kW
1768 1827 1910 1969 2051
L 1768 1827 1910 1969 2051
A 1768 1827 1910 1969 2051
E 1768 1827 1910 1969 2051 Quantity All 3 3 3 3 3 Water fl ow rate All l/h 304096 314244 328520 338668 352772 Pressure drop of the exchanger All kPa 55 59 60 63 65 Water connections (VICTAULIC) Ø
4"
Weight All kg 847 869 902 924 957
PUMP/S No. 1 - 2 x circuit OPTIONAL
PUMPS
PA PC PE PG PJ
Input power kW 4 5,5 7,5 9,2 11 Input current A 5,5 7,5 10 12,5 15 Weight kg 109 117 121 140 148 Water connections (VICTAULIC)
According to the fitted evaporator
NOMINAL REFERENCE CONDITIONS DESUPERHEATER
Outlet water temperature 45°C Δt 5°C
TO THE TOTAL RECOVERY
Outlet water temperature 45°C Δt 5°C
INSPY. 1003. 4138305_03
26
NS Vers. U.M. 6003 6303 6603 6903 7203 EXPANSION TANK
Capacity
-
dm
3
25 Calibration pressure Bar 1.5 Quantity 6
SOUND DATA
Sound power
°
dB(A)
101 101 101 102 102
L 9393939394
Sound pressure
° 67,9 67,8 67,8 68,7 68,7 L 59,9 59,8 59,8 59,7 60,7
Sound power
A 101 101 101 102 102
E 9393939394
Sound pressure
A 67,6 67,5 67,5 68,4 68,4
E
59,6 59,5 59,5 59,4 60,4
DIMENSIONS°/L
Height All
mm
2450 2450 2450 2450 2450
Width
°/L
2200 2200 2200 2200 2200 Depth 11530 12520 12520 13510 13510 Weight when empty
Kg
11390 12210 12250 13230 13570 Weight when empty with desuper­heater
11520 12360 12410 13400 13750 Weight when empty with total heat
recovery
12237 13079 13152 14154 14527 Weight during operation 11703 12555 12654 13666 14065
DIMENSIONS A/E
Height All
mm
2450 2450 2450 2450 2450
Width
A-E
2200 2200 2200 2200 2200 Depth 14490 15470 15470 16450 16450 Weight when empty
Kg
13760 14330 14560 14970 15350 Weight when empty with desuper­heater
13900 14480 14710 15140 15530 Weight when empty with total heat
recovery
14607 15199 15462 15894 16307 Weight during operation 14151 14773 15003 15465 15845
Sound power
Aermec determines the sound power value on the basis of measurements taken in accordance with standard 9614-2, in compliance with the Eurov­ent certification.
Sound pressure
Sound pressure in an unrestricted range on a reflec­tive plane (directional fact. Q=2), 10m away from the unit external surface, complying with ISO 3744.
INSPY. 1003. 4138305_03
27
-6
-10
-5
0
5
10
15
20
25
30
35
40
46
5
0
-4 1514131211109876543210-2
46
46
42
7. OPERATING LIMITS
The devices in their standard configura­tions are not suitable for installation in salty environments. For the operating limits, refer to dia­gram, valid for t = 5°C.
NOTE
Contact our technical sales depart­ment if the unit needs to operated outside the operating limits
Wind breaks should be implemented if the unit is installed in particularly windy areas, to prevent a malfunction of the DCPX
-6
-10
-5
0
5
10
15
20
25
30
35
40
42
50
-4 1514131211109876543210-2
42
42
38
-6
-10
-5
0
5
10
15
20
25
30
35
40
48
50
-4 1514131211109876543210-2
48
48
44
Standard operation
Standard operation
Standard operation
Operation with
glycol and with
DCPX accessory
Operation with
glycol and with
DCPX accessory
Operation with
glycol and with
DCPX accessory
Operation with DCPX
accessory
Operation with DCPX
accessory
Operation with DCPX
accessory
Operation with
glycol
Operation with
glycol
Operation with
glycol
Processed water temperature °C
Processed water temperature °C
Processed water temperature °C
Outside air temp. bs °C Outside air temp. bs °C Outside air temp. bs °C
COOLING
Side High
pressure
Side Low
pressure
Maximum pressure allowable
bar
22 16,5
Maximum temperature allowable
°C 120 55
Minimum temperature allowable
°C -10 -10
7.1. OPERATING LIMITS GRAPH VERSIONS «° and L»
7.2. OPERATING LIMITS GRAPH VERSIONS «A and E» for 5402-5702
7.3. DESIGN DATA
7.4. OPERATING LIMITS GRAPH VERSIONS «A and E»
INSPY. 1003. 4138305_03
28
8. CORRECTION FACTORS
8.1. STANDARD VERSION
8.2. STANDARD VERSION IN SILENCED FORM
The cooling capacity yielded and the input electrical capacity in conditions other than rated conditions are ob­tained by multiplying the rated values (Pc, Pa) by the respective correction coefficients (Cf, Ca). The following diagrams allow you to obtain the correction coefficients to be used for the various versions of the de­vices, in cold mode; next each curve the external air temperature to which it refers is shown.
KEY Cf: correction coefficient of the
cooling capacity.
Ca: correction coefficient of the input power.
FOR t DIFFERENT FROM 5°C Tab. 8.1.1. is used for the correction fac­tors of the cooling capacity and input power of the water consumption. To take into account the exchanger soiling, apply the relative fouling fac­tors, Tab. 8.2.1.
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
-5-6 -4 -3 -2 -1 0 1 2 3 4 5 6 7
8 9 10 11121314 15 16
-5-6 -4 -3 -2 -1 0 1 2 3 4 5 6 7
8 9 10 11121314 15 16
Cf
Ca
42°C
42°C
40°C
40°C
35°C
35°C
30°C
30°C
25°C
25°C
20°C
20°C
VERSION Y
VERSION Y
Outside air temperature
Outside air temperature
Evaporator water temperature (Δt=5°C)
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
1.30
1.40
1.50
-5-6 -4 -3 -2 -1 0 1 2 3 4 5 6 7
8 9 10 11121314 15 16
-5-6 -4 -3 -2 -1 0 1 2 3 4 5 6 7
8 9 10 11121314 15 16
Cf
Ca
42°C
42°C
40°C
40°C
35°C
35°C
30°C
30°C
25°C
25°C
20°C
20°C
VERSION Y
VERSION Y
Outside air temperature
Outside air temperature
Evaporator water temperature (Δt=5°C)