change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this
material, including but not limited to implied warranties of
merchantability and fitness for a particular application.
AERCO is not liable for errors appearing in this manual,
nor for incidental or consequential damages occurring in
connection with the furnishing, performance, or use of this
material.
2
GF-122 AERCO XPC GATEWAY
Foreword
The AERCO XPC (Extended Protocol Converter) allows a Building Automation Systems (BAS) or
Energy Management System (EMS) utilizing BACnet, Johnson N2 or LonWorks protocol to
communicate with AERCO boilers and water heaters which utilize Modbus.
The AERCO XPC Gateway can monitor and control up to 300 points. Each XPC is individually
programmed to your specific needs.
The information provided in this document is divided into an Introduction followed by three (3) parts:
• Introduction – An introduction to and general description of the AERCO XPC Gateway.
• Part
• Part
• Part
I - Provides a top-level description of the AERCO XPC Gateway features and capabilities.
It also includes detailed set-up and programming instructions to interface the XPC
Gateway to the AERCO equipment to be monitored or controlled on the network.
II - Provides the set-up and programming instructions to interface the AERCO XPC
Gateway to a Building Automation System (BAS) or Energy Management System (EMS)
which utilizes BACnet, Johnson N2 or LonWorks protocol.
III – Provides the protocol mapping points for the standard configurations which can be
monitored or controlled.
PHRASES, ABBREVIATIONS & ACRONYMS
The phrases, abbreviations and acronyms used in this document are listed in the following table.
Phrases, Abbreviations and Acronyms
Phrase, Abbreviation
or Acronym
ARCnet Attached Resource Computer network. This is a Local Area Network (LAN)
similar to Ethernet.
ASCII American Standard Code for Information Interchange
ASHRAE American Society of Heating, Refrigerati ng and Air Conditioning Engineers
BACnet Building Automation and Control network. Protocol developed by ASHRAE.
BAS Building Automation System, often used interchangeably with EMS (see
below)
Baud Rate Symbol rate, or simply the number of distinct symbol changes (signaling
events) transmitted per second. It is not equal to bits per second, unless
each symbol is 1 bit long.
BCM Boiler Control Module used in a Modulex (MLX) Boil er
Meaning
BMS (BMS II) Boiler Management System (Boiler Management System II)
Bias Resistors A pair of resistors used to force the communi cation line to a definite logic
state so that noise is not picked up as invalid dat a during communication.
C-More Controller
(or Control Box)
DIP Dual In-Line Package
A control system developed by AERCO and currently used in all Benchmark
and KC Series product lines.
3
GATEWAY COMMUNICATIONS MANUAL
EIA Electronic Industries Alliance
EIA-232
(or RS232)
EIA-485
(or RS485)
EMS Energy Management System
Ethernet A computer networking technology for Local Area Networks (LANs)
FDX Full-Duplex
HDX Half-Duplex
Hex Hexadecimal Number (0 - 9, A - F)
I/O Box Input/Output (I/O) Box currently used on al l B enchmark and KC Series
IP Internet Protocol
LonWorks A communication protocol developed by t he Echelon Corporation for control
LSB Least Significant Byte
MLX Modulex Boiler
Modbus® A serial, half-duplex data transmission protocol developed by AEG Modicon
MSB Most Significant Byte
A standard for serial, full-duplex (FDX) transmission of data based on the
EIA-232 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the
EIA-485 Standard
products
applications
MS/TP Master-Slave/Token-Passing (usually over RS485 networks)
N2 A communications protocol developed by Johnson Controls
PTP Point-to-Point (usually over RS232 networks)
Response Time The maximum amount of time allowed to receive a response to a request
RS232
(or EIA-232)
RS422
(or EIA-422)
RS485
(or EIA-485)
RTU Remote Terminal Unit
SLTA Serial LonTalk Adapter
Terminating Resistor A resistor placed at each end of a daisy-chain or multi-dr op network in order
XPC Extended P rotocol Converter (manufactured by OEM Ctrl)
A standard for serial, full-duplex (FDX) transmission of data based on the
RS232 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the
RS422 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the
RS485 Standard
to prevent reflections that may cause invalid data in the communication
4
GF-122 AERCO XPC GATEWAY
TABLE OF CONTENTS
SECTION 1 INTRODUCTION AND GENERAL DESCRIPTION ................................................ 10
1.5.1 Port 1a ........................................................................................................................................................ 13
1.5.2 Port 2 .......................................................................................................................................................... 13
1.5.3 Local Access Port ...................................................................................................................................... 13
3.2 INTERFACING THE XPC GATEWAY TO BMS, MODEL 158 .................................................. 47
3.2.1 BMS Set-Up For Monitoring ..................................................................................................................... 48
3.2.2 C-More Boilers Being Network-Controlled by a BMS ............................................................................. 51
3.2.3 BMS Setup For Remote Setpoint Control From the XPC Gateway .......................................................... 53
3.3 INTERFACING THE XPC GATEWAY TO BMS II, MODEL 5R5-384 ....................................... 55
3.3.1 BMS II Set-Up For Monitoring ................................................................................................................. 56
5
GATEWAY COMMUNICATIONS MANUAL
3.3.2 C-More Boilers Being Network-Controlled by a BMS II .......................................................................... 59
3.3.3 Modulex Boile rs Being Network-Controlled by a BMS II ........................................................................ 60
3.3.4 BMS II Setup For Remote Setpoint Control From The XPC Gateway ..................................................... 61
SECTION 4 AERCO XPC GATEWAY TO BCM CONTROLLED MODUL E X BOILERS .. 64
4.1 CONNECTION AND SET-UP OF BOILER COMMUNI CATIONS MODULES (BCMS) .......... 64
4.2 BCM WIRING CONNECTIONS TO AERCO XPC GATEWAY .................................................. 65
4.2.1 BCM Wiring Connections to XPC Port 2 .................................................................................................. 65
4.2.2 BCM Wiring Connections to XPC Port 1a ................................................................................................ 66
4.3 CONFIGURING THE BCM CONTROLLER ................................................................................. 67
SECTION 5 XPC GATEWAY TO ECS CONTROLLED HOT WATER HEATERS .................. 68
5.1 CONNECTION AND SET-UP OF ELECTRONIC CONTROL SYSTEM (ECS) ......................... 68
5.2 ECS WIRING CONNECTIONS TO AERCO XPC GATEWAY ................................................... 70
5.2.1 ECS Wiring Connec t ions to XPC Port 2 .................................................................................................... 70
5.2.2 ECS Wiring Connec t ions to XPC Port 1a .................................................................................................. 71
5.3 CONFIGURING THE ECS CONTROLLER .................................................................................. 72
5.4 CONFIGURING THE ECS CONTROLLER FOR REMOTE SETPOINT OPERATION ............. 72
SECTION 6 WHAT IS PART II OF THIS DOCUMENT ABOUT? .............................................. 74
14.1 MOST COMMON COMMUNICATION PROBLEMS ................................................................ 88
14.1.1 No Receive LED Indication ..................................................................................................................... 88
AERCO Boilers and Water Heaters equipped with any of the AERCO Control Systems listed below
can communicate directly with a Building Automation System (BAS) or Energy Management System
(EMS) utilizing Modbus RTU protocol. The AERCO Control Systems include:
• C-More Control System
• Boiler Management System (BMS or BMS II)
• Boiler Communications Module (BCM)
• Electronic Control System (ECS)
Although most BAS and EMS Systems support Modbus communication, many installations may
already be utilizing different types of communication protocol. In addition to Modbus, the most
commonly used protocols are BACnet, LonWorks and N2. In order to bridge the gap between
Modbus and other popular protocols, AERCO has developed the AERCO XPC Communications
Gateway. This Gateway makes connectivity to AERCO equipment as simple as “plug-and-play”.
The remaining sections in Part I provide top level descriptions of the AERCO Gateway and how it can
be implemented to provide connectivity between AERCO equipment and a BAS or EMS system
utilizing Modbus or other popular communication protocols.
Sections 2 through 5 provide detailed information and procedures for implementing network set-ups
to interface the XPC Gateway to AERCO boilers and water heaters.
1.2 REFERENCE DOCUMENTS
References to the following documents are included in the appropriate sections and subsections of
this manual:
AC-105 Electronic Control System
Installation, Operation & Maintenance Manual
GF-124
HA025132 2404/2408 Control Setpoint Programmer Installation
Installation, Operation & Maintenance Manual
Controller & Boiler Communications Module (BCM)
and Operation Handbook
1.3 AERCO XPC GATEWAY PURPOSE AND USE
The primary purpos e of the AERCO XPC Gateway is to allow monitoring or control of AERCO units.
Due to the operational nature of the Gateway, it should not be used to configure the system.
Configuration (or setup information) should not be constantly changed since this information is
generally stored in EEPROM non-volatile memory in the AERCO Controllers (C-More, BMS, and
10
GF-122 AERCO XPC GATEWAY
ECS). This type of memory can be read as often as needed, however, it has a limited number of
write cycles.
The Gateway is preprogrammed with standard monitor and control points. These standard points are
those most often requested by AERCO customers (see Part III). If different or additional points are
required for a particular system, custom factory programming is available. There are five (5) standard
pre-programmed configurations to choose from:
• Programmed for 4 C-More controlled boilers and 1 Boiler Management System (BMS/BMS II)
• Programmed for 1 BMS/BMS II and 8 C-More controlled boilers
• Programmed for 1 BMS/BMS II and 12 C-More controlled boilers
• Programming for 1 BMS II and 4 BCM controlled Modulex boilers
• Programmed for 4 ECS controlled water heaters
Multiple XPC Gateways can be used in certain situations.
If necessary, the XPC Gateway can accept up to 300 monitor and control points. Network points and
unit addresses are pre-programmed in the Gateway. In addition, all of the supported protocols –
BACNET, LonWorks, and N2 are preprogrammed for all points. They can be easily selected using
the DIP switches provided on the Gateway.
1.4 AERCO XPC GATEWAY DESCRIPTION
The XPC Gateway Controller is shown in Figure 1-1. The Gateway is housed i n a compact enclosure
measuring approximately 6” H x 8” W x 3” D as shown in Figure 1-2. The installed location of the
Gateway will depend on the types of AERCO equipment being used with the Gateway.
Figure 1-1. AERCO XPC Gateway
11
GATEWAY COMMUNICATIONS MANUAL
Figure 1-2. AERCO XPC Gateway Installed in Enclosure
NOTE
If desired, the Gateway can always be wall-mounted, regardless of the
types of AERCO equipment being used. However, signaling wire
lengths must not exceed 50 feet for RS232 and 3000 feet for RS485
networks.
• Benchmark Series Boilers: XPC Gateway can be installed behind the front panel door of the
Benchmark below the Input/Output (I/O) Box.
• KC1000 Series Boilers or Heaters: XPC Gateway can be installed on the left side of the unit
above the Input/Output (I/O) Box.
• Boiler Management System (BMS/BMS II): XPC Gateway is normally mounted on a wall in
close proximity to the BMS.
• Indirect-Fired Heaters with ECS Control System: Gateway is normally wall-mounted.
• Modulex Boilers equipped with Boiler Control Modules (BCMs).
The Gateway is powered by 24 VAC, 50/60 Hz, single-phase, 20 VAC. Power and Input/Output
(I/O) signal connections are made via four grommetted cutouts (one on each side and two on
the bottom surface of the Gateway enclosure. I/O signal wiring is routed through the left-side and
bottom-left cutouts of the Gateway enclosure. Connection to the Lon module is accomplished via
the bottom-right cutout. Input power wiring (24 VAC, 50/60 Hz) and earth ground wire is routed
through the right-side cutout of the enclosure to minimize noise on the signal wiring.
12
GF-122 AERCO XPC GATEWAY
1.5 GATEWAY PORTS & JUMPERS
The Gateway Input/Output (I/O) signal ports are located on the left side of the XPC Gateway, behind
the enclosure cover as illustrated in Figure 1-3. In addition, jumpers are also provided on the left side
of the Gateway to select the physical type of network being utilized on port 2. The following
subsections provide brief descriptions of the ports and jumpers provided.
1.5.1 Port 1a
Port 1a (Figure 1-3, Detail “A”) can only be configured for RS485 communication or special ARC156.
This port is normally used for BAS connections. However, if the BAS is communicating via BACnet
PTP or is connected to a LonWorks SLTA module, Port 1a cannot be used. Refer to the AERCO XPC
Gateway Integration Guide included as Part II of this manual.
1.5.2 Port 2
Port 2 (Figure 1-3, Detail “B”) can be configured for RS485 or RS232 communication. This port
normally connects to AERCO equipment except when the BAS is utilizing BACnet PTP or a
LonWorks SLTA. In this case, Port 1a must be used for the AERCO equipment. The jumpers located
below Port 2 are used to select RS485 or RS232 (EIA-485 or EIA-232) communication and either a 2wire or 4-wire communication interface (see para. 1.5.5).
1.5.3 Local Access Port
The Local Access Port (Figure 1-3, Detail “C2”) is used to program or read Gateway setup
information or to monitor network traffic from the Gateway with a PC using a special interface module.
Special network display monitors can also be connected to this port to display network information.
1.5.4 Optional Plug-In Module (Port 1b)
A 14-pin connector labeled Port 1b is for an optional plug-in module. Currently, there is a LonWorks
transceiver module that allows LonWorks FTT10A communication without the use of a Serial Lon
Talk Adapter (SLTA).
1.5.5 Jumper Settings
Two jumpers are located side-by-side below PORT 2 on the Gateway (Figure 1-3, Detail “D”). These
jumpers provide the following functions:
• EIA-232/EIA-485 Jumper
connector to select either an EIA-485 (RS485) or EIA-232 (RS232) connection to the
BAS. Setting the jumper to the lower position selects EIA-485 (RS485) which is the
default position. Setting the jumper to the upper position selects EIA-232 (RS232).
• 2-Wire/4-Wire Jumper
connector. Setting the jumper to the upper position selects 2-wire communication. Setting
the jumper to the lower position selects 4-wire communication.
- This jumper is connected across 8 of the 12 pins of the header
– This jumper is connected across 2 of the 3 pins of the header
13
GATEWAY COMMUNICATIONS MANUAL
+12V
RNET-
RNET+
GND
COM
NET-
RX
TX
FORMAT
POWER
NET+
CMNET
ONE's
ERR
RUN
OPTIONS
TEN's
BATT
24VAC
GND
POWER
485
232
LN-
/S
+12
GND
LN+
2W
RX
TX
4W
BT485
Net +
Net -
Shield
Port 1a
Tx1
Rx1
Port 1b
Port 2
4w
2w
Gnd
+12V
Gnd
Rnet+
Sense
Rnet +
Rnet -
R n e t
Rnet+12V
Local
Access
10's
1's
0
134
5
2
78
9 6
0
134
5
2
78
9 6
4
3
2
1
On
5
6
7
8
Run
Error
Power
Format
Gnd
Hot
EIA-232
EIA-485
Baud
EIA485
19.2k
38.4k 76.8k
BMS
Port 2
ARC156
Port 1
9600
BMS
Switches
(0 = off, 1 = on)
MSTP (m)
MSTP (s)
PTP
8 7 6 5
Protocol
0 0 0 0
0 0 0 1
0 0 1 0
BACnet
BMS
Port 1
TYPE: 002106
Enclosed Energy Management Equipment
Made in USA
®
24V ac
2w 4w
Tx+
n/c
n/c
Net+
Rx+
Rx-
Tx-Net-
232
Tx
DTR
DCD
Rx
Signal Ground
+
-
Batt
CR
2032
BT485
Lon SLTA
1 1 0 1
Lon PlugIn
Ethernet
1 1 1 1
1 1 1 0
N2
Modbus
®
®
0 1 1
0 1 0 0
0
Tx2
Rx2
E143900
88FO
R
Class 2, 24Vac
Conductors Only
Use Copper
50-60Hz, 10VA, 0.42A
®
XPC
PORT 1a
( DETAIL “A”)
PORT 2
( DETAIL “B”)
RNET
(
DETAIL “C1”)
PORT 1b
JUMPERS
( DETAIL “D”)
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
8
7
6
5
4
32
1
ON
INPUT
POWER
( 24 VAC)
DIP
SWITCHES
( DETAIL “E”)
ADDRESS
SELECT
SWITCHES
( DETAIL “F”)
BATTERY
(3V)
LOCAL
ACCESS
PORT
(DETAIL “C2”)
NOTE: Ground
(see Sht 2 of 3).
RNET
(DETAIL “C1”)
Ground connection lug for
Earth ground connection lug. Connect
is attached to
Mounting Panel
Figure 1-3. XPC Gateway Ports, Jumpers and Switches (Sheet 1 of 3)
attached to Mounting Panel
(see Figure 1-3, Sht 2 of 3).
Images:
All connectors on
this page are
shown in the same
orientation as
shown on the
referenced PCB
illustration in
Figure1-3, Sheet 1
of 3.
GF-122 AERCO XPC GATEWAY
Net+ Tx+ Tx
Net- Tx- Rx
N/C Rx+ DTR
N/C Rx- DCD
Signal Ground
Gnd
Rnet +
Rnet -
+12V
Rnet +
Sense
Gnd
Rnet -
+12V
determines the
determines the
10 decimal
10 decimal
position (10, 20,
position (10, 20,
30, 40, etc.) of
30, 40, etc.) of
determines the 1
decimal position
(1, 2, 3, 4, etc.)
10’s
1’s
Figure 1-3. XPC Gateway Ports, Jumpers and Switches (Sheet 3 of 3)
15
GATEWAY COMMUNICATIONS MANUAL
BAUD Rate
DIP Switch 1
DIP Switch 2
9600
OFF
OFF
19.2 K
OFF
ON
38.4 K
ON
OFF
76.8 K
ON
ON
1.6 POWER INPUT, PROTOCOL SELECTION & GATEWAY ADDRESSING
The Gateway input power connections, protocol selection, and Gateway addressing are
accomplished utilizing the connector and switches on the right side of the XPC Gateway as shown in
Figure 1-3. The following subsections provide brief descriptions of the ports and jumpers provided.
IMPORTANT
It is imperative that the XPC Gateway be powered by an isolated 24
VAC power supply which is dedicated only for use by the XPC
Gateway. Failure to observe this precaution will result in improper
Gateway operation.
1.6.1 Input Power Connection
The Gateway is powered by 24 VAC (Class 2), 50/60 Hz, 20 VA. The input power connector is
located on the upper right side of the Gateway (Figure 1-3, Sheet 1 of 3).
When connecting the power source, an earth ground MUST be connected to the ground screw on the
mounting panel. See Figure 1-3, Sheet 2 of 3.
In addition, a 3 volt lithium battery (CR2032) is installed below the AC power connector. This battery
is used to retain the current monitoring/control data stored in volatile memory.
WARNING
Do not remove the battery when the power is off. Doing so may erase
some recorded data as well as programming, especially on older
models not utilizing non-volatile memory. The battery maintains the
integrity of the data and coding contained in memory whenever the
supply voltage is not present.
1.6.2 Protocol and Baud Rate Select
Protocol and baud rate selection are accomplished using the 8 DIP switches shown in Figure 1-3,
Detail “E”. The DIP switches can be set to the ON (left) or OFF (right) position. The functions and
settings for each of these switches are listed in the Tables 1 and 2 which follow.
Table 1 Baud Rate Select Switches
• DIP Switch 3 selects whether XPC Port 1 or Port 2 will be connected to the BAS used with the
• DIP Switch 4 will normally be set to ON for RS485 communication. It should only be set to OFF if
Gateway. When DIP Switch 3 is OFF, Port 1 is connected to the BAS. When set to ON, Port 2 is
connected to the BAS. The other port will be used for connection of AERCO equipment.
the BAS Port is 1 and the BAS is communicating BACnet using the ARC156 method.
16
GF-122 AERCO XPC GATEWAY
DIP Switch Settings
Protocol
8 7 6
5
Comments
BACnet
RS485 communication to BACnet
BACnet
BACnet
RS232 communication to BACnet
Johnson
RS485 communication to Johnson N2
Modbus
DO NOT USE FOR THIS
LonWorks
Serial LonTalk Adapter required.
LonWorks
Lon Option Card required
Table 2 Building Automation System (BAS) Protocol
MS/TP
Master
MS/TP
Slave
PTP
N2
SLTA
FTT10a
OFF OFF OFF OFF
OFF OFF OFF ON
OFF OFF ON OFF
OFF OFF ON ON
OFF ON OFF OFF
ON ON OFF ON
ON ON ON OFF
1.6.3 Gateway Address Switches
Master
DO NOT USE FOR THIS
APPLICATION
Master
Master
APPLICATION
(currently available from Echelon)
The Gateway contains two rotary address switches labeled 0 - 9 as shown in Figure 1-3, Detail “F”.
The upper switch is labeled “10’s” and the lower switch is labeled “1’s”. When multiple Gateways are
used and controlled by a single BAS/EMS, each Gateway must have its own unique address. Do not
set both the “10’s” and the “1’s” address switches to “0”. Doing so will disable the Gateway on the
network.
1.7 GATEWAY STATUS INDICATORS
In addition to the ports and switches described in the previous subsections, the XPC Gateway
contains seven (7) LED Status Indicators which can be monitored during Gateway operation. These
LED Status Indicators are illustrated and described in Figure 1-4 and Table 3.
17
GATEWAY COMMUNICATIONS MANUAL
+12V
RNET-
RNET+
GND
COM
NET-
RX
TX
FORMAT
POWER
NET+
CMNET
ONE's
ERR
RUN
OPTIONS
TEN's
BATT
24VAC
AGND
POWER
RNET
485
232
LOCAL ACCESS
LN-
/S
+12
GND
LN+
2W
RX
TX
4W
BT485
Net +
Net -
Shield
Port 1a
Tx1
Rx1
Port 1b
Port 2
4w
2w
Gnd
+12V
Gnd
Rnet+
Sense
Rnet +
Rnet -
R n e t
Rnet+12V
Local
Access
10's
1's
0
134
5
2
78
9 6
0
134
5
2
78
9 6
4
3
2
1
On
5
6
7
8
Run
Error
Power
Format
Gnd
Hot
EIA-232
EIA-485
Baud
EIA485
19.2k 38.4k 76.8k
BMS
Port 2
ARC156
Port 1
9600
BMS
Switches
(0 = off, 1 = on)
MSTP (m)
MSTP (s)
PTP
8 7 6 5
Protocol
0 0 0 0
0 0 0 1
0 0 1 0
BACnet
BMS
Port 1
TYPE: 002106
Enclosed Energy Management Equipment
Made in USA
®
24V ac
2w
4w
Tx+
n/c
n/c
Net+
Rx+
Rx-
Tx-Net-
232
Tx
DTR
DCD
Rx
Signal Ground
+
-
Batt
CR
2032
BT485
Lon SLTA
1 1 0 1
Lon PlugIn
Ethernet
1 1 1 1
1 1 1 0
N2
Modbus
®
®
0
1 1
0 1 0 0
0
Tx2
Rx2
E143900
88FO
R
Class 2, 24Vac
Conductors Only
Use Copper
50-60Hz, 10VA, 0.42A
®
XPC
POWER
LED
RUN
LED
ERROR
LED
TX1
LED
RX1
LED
TX2
LED
RX2
LED
RNET
LOCAL
ACCESS
PORT
LED STATUS
TX1
Green LED flashes when data is being transmitted from
RX1
Green LED flashes when data is being received by the
Green LED lights when 24 VAC power is being supplied
RUN
Green LED lights to show Gateway status as described
TX2
Green LED flashes when data is being transmitted to
RX2
Green LED flashes when data is being received from
Figure 1-4. XPC Gateway Status LED Locations
INDICATOR
(LED1)
(LED2)`
POWER
(LED3)
(LED4)
ERROR
(LED5)
(LED6)
(LED7)
Table 3 Gateway LED Status Indicators
the BAS connected to Port 1.
BAS connected to Port 1.
to the Gateway.
in Table 4.
Red LED lights to show Gateway status as described in
Table 4.
the AERCO equipment connected to Port 2.
the AERCO equipment connected to Port 2.
FUNCTION
18
If RUN LED Shows:
And ERROR LED Shows:
Status is:
2 flashes per second
Off
Normal
2 flashes per second
2 flashes,
Five minute auto-restart delay
2 flashes per second
3 flashes,
Gateway has just been
2 flashes per second
4 flashes,
Two or more devices on the
2 flashes per second
On
Exec halted after frequent
See also Part II “Communication LED’s”.
Table 4 RUN & ERROR LED Status
GF-122 AERCO XPC GATEWAY
alternating with RUN LED
then Off
then pause
after system error
formatted
network have the same
ARC156 network address
system errors or control
program halted
1.8 BASIC GATEWAY OPERATION
The Gateway scans the points list from top to bottom in a round-robin fashion. It will continually
retrieve the information from the programmed Modbus address and hold it for the BAS to read. The
information is therefore not real-ti me. How current the information is will depend on how quickly the
Gateway can scan all of the required pre-programmed points.
Information is updated based on the update time and priority of the information. If a point is not
updated within the allotted update time because the Gateway was not able to read it in time, the value
of that point will default to its programmed default value (usually zero).
To speed up the update rate of points and prevent dropouts (going to default value), communication
to any unused points can be disabled. This prevents the Gateway from waiting the full Response
Time programmed before moving to the next point, thereby reducing the scan cycle time interval.
19
GATEWAY COMMUNICATIONS MANUAL
5-pin port supports EIA-232, EIA-485 2-wire or 4-wire
1.9 XPC GATEWAY REFERENCE DATA
The functional, physical and environmental specifications for the Gateway are listed in Table 5.
Table 5 AERCO XPC Gateway Specifications
Specification Description
Maximum number of points 300
Power 24 VAC ±10%, 50-60 Hz, 20 VA power consumption, Class 2
source only, 100 VA or less
Port 1a 3-pin port supports EIA-485 (RS485) 2-wire communication.
Protocols supported:
• BACnet over ARC156
• BACnet MS/TP
• Modbus (RTU/ASCII)
• Johnson N2
This port can be configured as a device port or a BAS port
NOTE: Port 1a or Port 1b can be used, but not both.
Port 1b 14-pin communication port supports plug-in cards such as
LonWorks or future Ethernet.
Port 2
Rnet Port
Local Access Port For local communication with a laptop computer running
• EIA-485 2-wire BACnet MS/TP, Modbus (RTU/ASCII),
Johnson N2
• EIA-485 4-wire BACnet MS/TP, Modbus (RTU/ASCII)
This port can be configured as a device port or BAS port.
4-pin port supports up to four RS Standard sensors and one
RS Plus, RS Pro, or RS Pro-F sensor for averaging or
high/low select control.
WebCTRL or AppLoader.
16-bit memory bus
20
GF-122 AERCO XPC GATEWAY
Width
4 in. (102mm)
Height
5 in. (127mm)
Depth
1.75 in. (51mm)
Add for the LonWorks Card:
Width
1.8 in. (45.72mm)
Height
3.25 in. (82.55mm)
Depth
1.5 in. (38.1mm)
Distance apart cannot exceed ribbon cable:
9.75 in. (247.65 mm)
Width
2 in. (51 mm)
Height
4.8 in. (122mm)
LonWorks Option Card
1.325 in. (33.66 mm) apart – top 2 holes
.475 in. (12.07 mm) from edge
.890 in. (22.61 mm) bottom hole – from edge
Width
8.94 in. (227 mm) apart – top 2 & bottom 2 holes
Height
5.00 in. (127 mm) between top 2 & bottom 2 holes
Table 6 XPC Gateway Specifications - Continued
Specification Description
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000
hours of data retention during power outages
Protection Built-in surge and transient protection circuitry - internal solid
state Polyswitches on the incoming power and network
connections.
Status Indicators LED's indicate status of communications, running, errors, and
power.
Environmental operating
range
-40° to 150°F (-40° to 65.6°C), 10–95% relative humidity, noncondensing
Overall dimensions
(without enclosure)
Mounting hole dimensions
(without enclosure)
Mounting hole dimensions
in enclosure
Rommended panel depth 1.75 in. (51mm)
Weight 9 oz.
BACnet support Conforms to the Advanced Application Controller (B-AAC)
Standard Device Profile as defined in ANSI/ASHRAE Standard
135-2004 (BACnet) Annex L
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-
Class A, CE EN50082-1997
1.10 QUICK SETUP GUIDE
A Quick Setup Guide is provided as additional guidance to configuring and integrating the AERCO
XPC Communications Gateway. The guide now follows.
21
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC QUICK SETUP GUIDE
Follow the instructions below to quickly wire and set up the AERCO XPC between your
Building Automation System (BAS) and AERCO equipment - Boiler Management System
(BMS/BMSII), Boiler Controls (C-MORE on Benchmark or KC1000 boilers or Boiler Control
Module (BCM) on Modulex (MLX) boilers), or Electronic Control System (ECS).
Select the 2 pages that apply to your configuration – one from pages 2 to 5 which outlines the
wiring and set up between your BAS and the AERCO XPC, and the other from pages 6 to
10 which outlines the wiring and set up between the AER CO X PC and AERCO equipment.
Note: The AERCO XPC cannot share power with other equipment. It must have its own
dedicated 24VAC supply else communication dropouts could result.
AERCO XPC
AERCO
EQUIPMENT
BUILDING
AUTOMATION
SYSTEM
An extra ground wire must be connected to the earth ground screw in the XPC metal plate.
1.10.1 Quick Setup Guide
22
1.10.2 BACNET MS/TP to AERCO XPC
BACNET M S/TP TO AERCO XPC
XPC Port 1a:
•Wir e to Port 1a + to “Net+”, - to “Net-”, and Shi eld connecte d at one end only. If to XPC then to
“Shi eld” connec tor.
8-Position Dipswitch:
•Dipswi tch 1,2 set to BACNET MS/ TP communi cati on baud rate;
•Dipswi tch 3 = Off (B.A. S. on port 1);
•Dipswi tch 4 = O n (EI A485 on port 1) ;
•Dipswitch 5-8 = Off, O ff, Off, Off (for bacnetms/tp(m));
Rotary Address Switches:
•2 Rotar y Address Swit ches set to BacnetID address for t he XPC)
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES .
AERCO XPC
BACNET
MS/TP
Port 1a Port 2
RS485
RS485
BAS
bacnet
GF-122 AERCO XPC GATEWAY
23
GATEWAY COMMUNICATIONS MANUAL
LON TO AERCO XPC (wit h LON-OC)
XPC “Net” Port on LON-OC:
•Wir e to “Net ” Port on LON-OC Polari ty does not matt er in this case. Connect shield at one end onl y.
8-Position Dipswitch:
•Dipswi tch 1, 2 = On, Off ( 38.4 K baud);
•Dipswi tch 3 = Off (B.A. S. on port 1);
•Dipswi tch 4 = On (por t 1b) ;
•Dipswitch 5-8 = Off, On, On, On (for Lon plug-in).
Rotary Address Switches:
•Not appl icable in thi s case.
Note: Lon XIF fil es are downloada ble from “ www.aerco. com ”.
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES .
AERCO XPC
LON
Port 1b Port 2
Ftt -10a
BAS
Lon
LON-OC
Net
Ribbon
cable
Ftt-10a
1.10.3 LON to AERCO XPC (with LON-OC)
24
1.10.4 LON to AERCO XPC (with SLTA)
LON TO AERCO XPC (with SLTA)
XPC Port 2:
•Wire SLTA to XPC P ort 2 “TX” to “RX”, “RX” to “TX”, “G nd” to “Signal Ground”, and Shield connected at one end only.
•Place 4-position jumper on EIA-232 (t wo top rows);
•Place 2-position jumper on 2W;
•Jumper “DTR” and “DCD” on SLTA port (port 2).
8-Position Dipswitch:
•Dipswitch 1, 2 = On, Off (38.4 K baud);
•Dipswitch 3 = On (B.A.S. on port 2);
•Dips witc h 4 = Off;
•Dips witc h 5-8 = On, Off, On, On (for Lon SLTA).
Rotary Address Switches:
•Not applicable in this case.
Note: Lon XIF files are on enclosed CD or downloadable from “www.aerco. com”.
BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES.
AERCO XPC
LON
Port 2 Port 1a
Ftt -10a
BAS
Lon
SLTA
Net
Ftt-10a
RS232
RS232
RS232
GF-122 AERCO XPC GATEWAY
25
GATEWAY COMMUNICATIONS MANUAL
JOHNSON N2 TO AERCO XPC
XPC Port 1a:
•Wir e to Port 1a + to “Net+”, - to “Net-”, and Shi eld connecte d at one end only. If to XPC then to
“Shi eld” connec tor.
8-Position Dipswitch:
•Dipswi tch 1,2 = Off, Off (9600 baud r ate);
•Dipswi tch 3 = Off (B.A. S. on port 1);
•Dipswi tch 4 = O n (EI A485 on port 1) ;
•Dipswitch 5-8 = On, On, Off, Off ( for N2) ;
Rotary Address Switches:
•2 Rotar y Address Swit ches set to N2 unit address for the XPC)
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
JOHNSON
N2
RS485
BAS
N2
Port 1a Port 2
RS485
1.10.5 LON to XPC (with LON-OC)
26
GF-122 AERCO XPC GATEWAY
AERCO XPC TO BO ILER MANAGEMENT SYSTEM
(BMS)
XPC Part Number:
•“25024-1” for 1 BMS and up t o 4 C-MOREs, or “25024-2” for 1 BM S and up to 12 C-MOREs , or
“25024-4” for 1 BMS and up to 4 MLX Boil ers (wi th BCMs), or 25024-5 for 1 BMS and up to 8 C-MOREs
XPC Port 2 to BMS Port JP12:
•Wir e to XPC Por t 2 “TX ” t o “RXD”, “ RX” to “ TXD” , “ Signal Gr ound” t o “G ND”, and Shiel d connecte d at
one end only t o the BMS at the “SHIELD” i nput. Jumper “ DTR” and “DCD” on port 2.
•Place 4-posi tion j umpe r on EIA-232 ( two top rows) ;
•Place 2-posi tion j umpe r on 2W;
XPC Software Setup:
•Modbus Respons e Ti me = 20(x100 msec) (default);
BMSII RS232 Software Setup:
•RS232 Mode = M odbus Slave; RS232 Baudrate= 9600; Modbus Addr ess = 128; Modbus Pass Thru =
Enabled (if r eading informati on from boi lers, else leave Disabled );
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
BMS
Port 1a Po rt 2
RS232 RS485
RS232
modbus
JP 12 JP 11
1.10.6 AERCO XPC to Boiler Management System (BMS)
27
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC TO BO ILER MANAGEMENT SYSTEM II
(BMSII)
XPC Part Number:
•“25024-1” for 1 BMSII and up to 4 C-MORE, or “25024-2” for 1 BMSII and up to 12 C-MOREs , or
“25024-4” for 1 BMSI I and up t o 4 MLX Boil ers ( wit h BCMs) , or 25024-5 for 1 BMSII and up to 8 CMOREs
XPC Port 2 to BMSII Port JP5:
•Wi re to XPC Por t 2 “T X” t o “RXD” , “ RX” to “ TXD” , “ Si gnal Gr ound” t o “G ND”, and Shiel d connecte d at
one end only. If to the BMSII at t he “SHI ELD” input . Jumper “ DTR” and “ DCD” on port 2.
•Place 4-posi tion j umpe r on EIA-232 ( two top rows);
•Place 2-posi tion j umpe r on 2W;
XPC Software Setup:
•Modbus Response Time = 20(x100 msec) (default);
BMSII RS232 Menu Setup:
•RS232 Mode = Modbus Slave; RS232 Baudrate= 9600; Modbus Addr ess = 128; Modbus Pass Thru =
Enabled (if r eading informati on from boi lers, else leave Disabled );
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
BMSII
Port 1a Po rt 2
RS232 RS485RS232
modbus
JP5 JP6
1.10.7 AERCO XPC to Boiler Management System II (BMS II)
28
1.10.8 AERCO XPC to C-More
AERCO XPC TO C -MORE
XPC Part Number:
•25024-1 or 63046-1 for 1 BMS and up to 4 C-MOREs; 25024-2 for 1 BMS and up to 12 C-MOREs; 25024-5 for 1
BMS and up to 8 C-MOREs
XPC Port 2 to C-MORE (I/O Box) RS485:
•Wire to XPC Port 2 “Net+” to “RS485+” , “Net-” to “RS485-”, and Shield connected at one end only - to the C-
MORE (I/O Box) at the “SHLD” input.. Daisy chain to the other units..
•Place 4-position jumper on EIA-485 ( t wo bot t om rows);
•Place 2-position jumper on 2W;
XPC Software Setup:
•Modbus Response Time = 2 (x100 msec); (Must be changed using AppLoader Software and Programmer Cable.)
C-MORE Setup:
•For Monitor Only “Comm Address” = (boiler addr ess s t ar t ing with “1” ) ;
•For M onitor and Remote Setpt Control via Modbus Se t “Comm Address ” as above; Set “Boiler Mode” to
“Remote Setpt” ; Set “Remote Signal” to “Network”.
BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES
AERCO XPC
C-MORE
Port 1a Po rt 2
RS485 RS485
modbus
GF-122 AERCO XPC GATEWAY
29
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC TO BCM (on MLX Boiler )
XPC Part Number:
•25024-4 or 63046-4 for 1 BMS and up to 4 MLX (with BCM Controls)
XPC Port 2 to BCM Port Y2:
•Wire to XPC Port 2 “Net+” to Y2 pin 1; “Net-” to Y2 pin 2; and Shield connected at one end only - to the XPC at
the “SHIELD” input.. Daisy chain to the other units..
•Place 4-position jumper on EIA-485 ( two bottom rows);
•Place 2-position jumper on 2W;
XPC Software Setup (Must be changed using AppLoader Software and Programmer Cable.):
•Modbus Response Time = 2 (x100 msec); Only if Remote Setpoint control is to be done, set these points from
“False” to “T rue” – “Req Outlet T emp” and “ Net Direct Drive” – for all your boiler addres ses.
BCM Setup:
•Set Addres s Dipswitch on each BCM start ing from 1; Keep termination jumper off on all BCMs;
BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES
AERCO XPC
BCM
Port 1a Po rt 2
RS485 RS485
modbus
1.10.9 AERCO XPC to BCM (on MLX Boiler)
30
Loading...
+ 163 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.