AERCO XPC GATEWAY User Manual

AERCO XPC Gateway Communications
USER MANUAL
GF-122
OMM-0044_0C
AERCO XPC GATEWAY
Communications Manual
For Interfacing
AERCO Equipment
To
Building Automation Systems
Utilizing:
BACnet, N2, or LonWorks Protocol
Printed in U.S.A REVISED 11/10/2011
GATEWAY COMMUNICATIONS MANUAL
The information contained in this manual is subject to
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday):
1-800-526-0288
AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913
www.AERCO,com
© AERCO International, Inc., 2009
change without notice from AERCO International, Inc.
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application.
AERCO is not liable for errors appearing in this manual, nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
2
GF-122 AERCO XPC GATEWAY
Foreword
The AERCO XPC (Extended Protocol Converter) allows a Building Automation Systems (BAS) or Energy Management System (EMS) utilizing BACnet, Johnson N2 or LonWorks protocol to communicate with AERCO boilers and water heaters which utilize Modbus.
The AERCO XPC Gateway can monitor and control up to 300 points. Each XPC is individually programmed to your specific needs.
The information provided in this document is divided into an Introduction followed by three (3) parts:
Introduction – An introduction to and general description of the AERCO XPC Gateway.
Part
Part
Part
I - Provides a top-level description of the AERCO XPC Gateway features and capabilities.
It also includes detailed set-up and programming instructions to interface the XPC Gateway to the AERCO equipment to be monitored or controlled on the network.
II - Provides the set-up and programming instructions to interface the AERCO XPC
Gateway to a Building Automation System (BAS) or Energy Management System (EMS) which utilizes BACnet, Johnson N2 or LonWorks protocol.
III – Provides the protocol mapping points for the standard configurations which can be
monitored or controlled.
PHRASES, ABBREVIATIONS & ACRONYMS
The phrases, abbreviations and acronyms used in this document are listed in the following table.
Phrases, Abbreviations and Acronyms
Phrase, Abbreviation
or Acronym
ARCnet Attached Resource Computer network. This is a Local Area Network (LAN)
similar to Ethernet. ASCII American Standard Code for Information Interchange ASHRAE American Society of Heating, Refrigerati ng and Air Conditioning Engineers BACnet Building Automation and Control network. Protocol developed by ASHRAE. BAS Building Automation System, often used interchangeably with EMS (see
below) Baud Rate Symbol rate, or simply the number of distinct symbol changes (signaling
events) transmitted per second. It is not equal to bits per second, unless
each symbol is 1 bit long. BCM Boiler Control Module used in a Modulex (MLX) Boil er
Meaning
BMS (BMS II) Boiler Management System (Boiler Management System II) Bias Resistors A pair of resistors used to force the communi cation line to a definite logic
state so that noise is not picked up as invalid dat a during communication. C-More Controller
(or Control Box) DIP Dual In-Line Package
A control system developed by AERCO and currently used in all Benchmark
and KC Series product lines.
3
GATEWAY COMMUNICATIONS MANUAL
EIA Electronic Industries Alliance EIA-232
(or RS232) EIA-485
(or RS485) EMS Energy Management System Ethernet A computer networking technology for Local Area Networks (LANs) FDX Full-Duplex HDX Half-Duplex Hex Hexadecimal Number (0 - 9, A - F) I/O Box Input/Output (I/O) Box currently used on al l B enchmark and KC Series
IP Internet Protocol LonWorks A communication protocol developed by t he Echelon Corporation for control
LSB Least Significant Byte MLX Modulex Boiler Modbus® A serial, half-duplex data transmission protocol developed by AEG Modicon MSB Most Significant Byte
A standard for serial, full-duplex (FDX) transmission of data based on the
EIA-232 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the
EIA-485 Standard
products
applications
MS/TP Master-Slave/Token-Passing (usually over RS485 networks) N2 A communications protocol developed by Johnson Controls PTP Point-to-Point (usually over RS232 networks) Response Time The maximum amount of time allowed to receive a response to a request RS232
(or EIA-232) RS422
(or EIA-422) RS485
(or EIA-485) RTU Remote Terminal Unit SLTA Serial LonTalk Adapter Terminating Resistor A resistor placed at each end of a daisy-chain or multi-dr op network in order
XPC Extended P rotocol Converter (manufactured by OEM Ctrl)
A standard for serial, full-duplex (FDX) transmission of data based on the
RS232 Standard
A standard for serial, full-duplex (FDX) transmission of data based on the
RS422 Standard
A standard for serial, half-duplex (HDX) transmission of data based on the
RS485 Standard
to prevent reflections that may cause invalid data in the communication
4
GF-122 AERCO XPC GATEWAY
TABLE OF CONTENTS
SECTION 1 INTRODUCTION AND GENERAL DESCRIPTION ................................................ 10
1.1 INTRODUCTION ............................................................................................................................ 10
1.2 REFERENCE DOCUMENTS .......................................................................................................... 10
1.3 AERCO XPC GATEWAY PURPOSE AND USE .......................................................................... 10
1.4 AERCO XPC GATEWAY DESCRIPTION .................................................................................... 11
1.5 GATEWAY PORTS & JUMPERS .................................................................................................. 13
1.5.1 Port 1a ........................................................................................................................................................ 13
1.5.2 Port 2 .......................................................................................................................................................... 13
1.5.3 Local Access Port ...................................................................................................................................... 13
1.5.4 Optional Plug-In Module (Port 1b) ............................................................................................................ 13
1.5.5 Jumper Settings .......................................................................................................................................... 13
1.6 POWER INPUT, PROTOCOL SELECTION & GATEWAY ADDRESSING .............................. 16
1.6.1 Input Power Connection ............................................................................................................................ 16
1.6.2 Protocol and Baud Rate Select ................................................................................................................... 16
1.6.3 Gateway Address Switches ........................................................................................................................ 17
1.7 GATEWAY STATUS INDICATORS ............................................................................................. 17
1.8 BASIC GATEWAY OPERATION .................................................................................................. 19
1.9 XPC GATEWAY REFERENCE DATA .......................................................................................... 20
1.10 QUICK SETUP GUIDE ................................................................................................................. 21
1.10.1 Quick Setup Guide ................................................................................................................................... 22
1.10.2 BACNET MS/TP to AERCO XPC .......................................................................................................... 23
1.10.3 LON to AERCO XPC (with LON-OC) ................................................................................................... 24
1.10.4 LON to AERCO XPC (with SLTA) ........................................................................................................ 25
1.10.5 LON to XPC (with LON-OC) .................................................................................................................. 26
1.10.6 AERCO XPC to Boiler Management System (BMS) .............................................................................. 27
1.10.7 AERCO XPC to Boiler Management System II (BMS II) ...................................................................... 28
1.10.8 AERCO XPC to C-More ......................................................................................................................... 29
1.10.9 AERCO XPC to BCM (on MLX Boiler) ................................................................................................. 30
1.10.10 AERCO XPC to ECS (with Eurotherm Control) ................................................................................... 31
SECTION 2 INTERFACING THE XPC WITH C-MORE CONTROLLED UNITS ................... 34
2.1 INTRODUCTION ............................................................................................................................ 34
2.2 PHYSICAL NETWORK WIRING .................................................................................................. 34
2.3 C-MORE BOILERS OR HEATERS CONTROLLED BY BAS VIA THE GATEWAY ............... 34
2.4 C-MORE CONTROLLER MODBUS COMMUNICATION INTERFACE ................................... 35
2.5 RS485 LOOP TERMINATING RESISTORS AND BIAS .............................................................. 37
2.5.1 C-More Boiler Controller Terminating Resistor and Bias ......................................................................... 37
2.5.2 BAS Terminating Resistor and Bias .......................................................................................................... 41
2.6 C-MORE CONTROLLER WIRING CONNECTIONS TO AERCO XPC GATEWAY ................ 41
2.6.1 C-More Wiring C onnections to XPC Port 2 .............................................................................................. 41
2.6.2 C-More Wiring C onnections to XPC Port 1a ............................................................................................ 42
2.7 CONFIGURING THE C-MORE CONTROLLERS ........................................................................ 43
2.7.1 C-More Controller Monitoring and Configuration Control ....................................................................... 43
2.7.2 Direct Drive Control and Monitoring ........................................................................................................ 44
2.7.3 Remote Setpoint Control ............................................................................................................................ 44
SECTION 3 INTERFACING THE XPC TO BOILER MANAGEM ENT SYSTEMS .................. 47
3.1 INTRODUCTION ............................................................................................................................ 47
3.2 INTERFACING THE XPC GATEWAY TO BMS, MODEL 158 .................................................. 47
3.2.1 BMS Set-Up For Monitoring ..................................................................................................................... 48
3.2.2 C-More Boilers Being Network-Controlled by a BMS ............................................................................. 51
3.2.3 BMS Setup For Remote Setpoint Control From the XPC Gateway .......................................................... 53
3.3 INTERFACING THE XPC GATEWAY TO BMS II, MODEL 5R5-384 ....................................... 55
3.3.1 BMS II Set-Up For Monitoring ................................................................................................................. 56
5
GATEWAY COMMUNICATIONS MANUAL
3.3.2 C-More Boilers Being Network-Controlled by a BMS II .......................................................................... 59
3.3.3 Modulex Boile rs Being Network-Controlled by a BMS II ........................................................................ 60
3.3.4 BMS II Setup For Remote Setpoint Control From The XPC Gateway ..................................................... 61
SECTION 4 AERCO XPC GATEWAY TO BCM CONTROLLED MODUL E X BOILERS .. 64
4.1 CONNECTION AND SET-UP OF BOILER COMMUNI CATIONS MODULES (BCMS) .......... 64
4.2 BCM WIRING CONNECTIONS TO AERCO XPC GATEWAY .................................................. 65
4.2.1 BCM Wiring Connections to XPC Port 2 .................................................................................................. 65
4.2.2 BCM Wiring Connections to XPC Port 1a ................................................................................................ 66
4.3 CONFIGURING THE BCM CONTROLLER ................................................................................. 67
SECTION 5 XPC GATEWAY TO ECS CONTROLLED HOT WATER HEATERS .................. 68
5.1 CONNECTION AND SET-UP OF ELECTRONIC CONTROL SYSTEM (ECS) ......................... 68
5.2 ECS WIRING CONNECTIONS TO AERCO XPC GATEWAY ................................................... 70
5.2.1 ECS Wiring Connec t ions to XPC Port 2 .................................................................................................... 70
5.2.2 ECS Wiring Connec t ions to XPC Port 1a .................................................................................................. 71
5.3 CONFIGURING THE ECS CONTROLLER .................................................................................. 72
5.4 CONFIGURING THE ECS CONTROLLER FOR REMOTE SETPOINT OPERATION ............. 72
SECTION 6 WHAT IS PART II OF THIS DOCUMENT ABOUT? .............................................. 74
SECTION 7 PROTOCOL OVERVIEW ............................................................................................ 74
7.1 WHAT IS A PROTOCOL? .............................................................................................................. 74
7.2 WHY ARE THERE SO MANY PROTOCOLS? ............................................................................. 74
7.3 WHY BUILD INTHE MOST WIDELY USED PROTOCOLS? .................................................... 75
7.4 WHAT DOES THE SITE INTEGRATOR NEED? ......................................................................... 75
SECTION 8 BACNET .......................................................................................................................... 76
SECTION 9 BACNET OVER ARC156 .............................................................................................. 76
9.1 CONFIGURING THE AERCO XPC FOR ARC156 ....................................................................... 76
SECTION 10 BACNET MS/TP ............................................................................................................. 78
10.1 CONFIGURING THE AERCO XPC FOR BACNET MS/TP ....................................................... 78
SECTION 11 BACNET PTP ................................................................................................................. 80
11.1 CONFIGURING THE AERCO XPC FOR BACNET PTP ........................................................... 80
SECTION 12 JOHNSON CONTROLS (N2) ....................................................................................... 82
12.1 CONFIGURING THE AERCO XPC FOR N2 F OR PORT 1A .................................................... 82
SECTION 13 LONWORKS ................................................................................................................... 84
13.1 CONFIGURING THE AERCO XPC FOR LONTALK VIA SLTA-10 ........................................ 84
13.2 CONFIGURING THE AERCO XPC FOR LONWORKS OPTION CARD ................................. 86
SECTION 14 TROUBLESHOOTING ................................................................................................. 88
14.1 MOST COMMON COMMUNICATION PROBLEMS ................................................................ 88
14.1.1 No Receive LED Indication ..................................................................................................................... 88
14.1.2 Wiring termination ................................................................................................................................... 88
14.1.3 Jumper selection ...................................................................................................................................... 88
14.1.4 Dipswitch selection .................................................................................................................................. 88
14.1.5 Addressing ............................................................................................................................................... 88
14.2 BACNET OVER ARC156 ............................................................................................................. 88
14.3 BACNET MS/TP ............................................................................................................................ 89
14.4 BACNET PTP ................................................................................................................................. 90
14.5 N2 ................................................................................................................................................... 90
14.6 LONWORKS .................................................................................................................................. 91
14.7 COMMISSIONING THE XPC FOR LONWORKS ...................................................................... 91
14.8 COMMUNICATION LED'S .......................................................................................................... 92
SECTION 15 COMPLIANCE ............................................................................................................... 94
15.1 FCC COMPLIANCE ...................................................................................................................... 94
15.2 BACNET COMPLIANCE ............................................................................................................. 94
SECTION 16 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT 94
16.1 ANALOG VALUE (PAR) .............................................................................................................. 96
16.2 BINARY VALUE (PAR), (CLOCK), AND (STAT) ..................................................................... 97
16.2.1 notification_class .................................................................................................................................. 98
6
GF-122 AERCO XPC GATEWAY
16.2.2 notify_type ............................................................................................................................................. 98
16.2.3 out_of_service ...................................................................................................................................... 98
16.2.4 present_value ....................................................................................................................................... 98
16.2.5 relinquish_default ................................................................................................................................. 98
16.2.6 time_delay ............................................................................................................................................. 98
16.3 ANALOG VALUE (STAT) ........................................................................................................... 99
16.4 BINARY VALUE (PAR), (CLOCK), AND (STAT) ................................................................... 101
16.5 BINARY VALUE (MODULE ALARM) .................................................................................... 102
16.6 CALENDAR ................................................................................................................................. 103
16.7 DEVICE ........................................................................................................................................ 103
16.8 FILE .............................................................................................................................................. 105
16.9 MULTI_STATE VALUE ............................................................................................................. 105
16.10 MULTI_STATE VALUE (STAT) ............................................................................................. 106
16.11 NOTIFICATION CLASS ........................................................................................................... 107
16.12 PROGRAM ................................................................................................................................. 107
16.13 SCHEDULE ................................................................................................................................ 108
16.14 TREND_LOG (NON-BACNET PROPERTY) .......................................................................... 109
SECTION 17 BACNET DATA LINK LAYER OPTIONS ............................................................... 110
SECTION 18 CONFORMANCE STATEMENT FOR MODBUS IMPL EMENTATION ........... 111
SECTION 19 CONFORMANCE STATEMENT FOR JOHNSON N2 IMPLEMENTATION .... 113
SECTION 20 CONFORMANCE STATEMENT FOR LONWORKS IMPLEMENTATION ..... 116
SECTION 21 INTRODUCTION to Part III ...................................................................................... 120
SECTION 22 APPLOADER SOFTWARE UTILITY ...................................................................... 120
SECTION 23 PROGRAM FILES AND FILENAMES ..................................................................... 120
SECTION 24 CONTROL POINTS AND SPEED OF OPERATION ............................................. 121
SECTION 25 MODBUS TIMERS ...................................................................................................... 121
SECTION 26 MODBUS RESPONSE TIME ..................................................................................... 122
SECTION 27 MODBUS INTERPACKET Delay .............................................................................. 122
SECTION 28 AERCO EQUIPMENT MONITOR & CONTROL POINT DEFINITIONS ......... 123
SECTION 29 PROTOCOL MAPPING TABLES ............................................................................. 129
SECTION 30 C-MORE BOILER CONTROLLER STATUS & FAULT MESSAGES ................ 185
SECTION 31 ERROR CODES ........................................................................................................... 188
7
GATEWAY COMMUNICATIONS MANUAL
THIS PAGE INTENTIONALLY BLANK
8
GF-122 AERCO XPC GATEWAY
INTRODUCTION
AERCO XPC DESCRIPTION
QUICK SETUP GUIDE
And
9
GATEWAY COMMUNICATIONS MANUAL
DOCUMENT
TITLE
AERCO
(www.aerco.com)
GF-108M,
Boiler Management System (BMS or BMS II) GF-112
C-More Control Panel Operation Manual
GF-114
Modbus Communication Manual
GF-115-C
Operation & Wiring Guides for Modulex E8
Eurotherm
(www.eurotherm.com/controllers/2400_doc.htm)
HA026230
2000 Series Communication Handbook

SECTION 1 INTRODUCTION AND GENERAL DESCRIPTION

1.1 INTRODUCTION

AERCO Boilers and Water Heaters equipped with any of the AERCO Control Systems listed below can communicate directly with a Building Automation System (BAS) or Energy Management System (EMS) utilizing Modbus RTU protocol. The AERCO Control Systems include:
C-More Control System
Boiler Management System (BMS or BMS II)
Boiler Communications Module (BCM)
Electronic Control System (ECS)
Although most BAS and EMS Systems support Modbus communication, many installations may already be utilizing different types of communication protocol. In addition to Modbus, the most commonly used protocols are BACnet, LonWorks and N2. In order to bridge the gap between Modbus and other popular protocols, AERCO has developed the AERCO XPC Communications Gateway. This Gateway makes connectivity to AERCO equipment as simple as “plug-and-play”.
The remaining sections in Part I provide top level descriptions of the AERCO Gateway and how it can be implemented to provide connectivity between AERCO equipment and a BAS or EMS system utilizing Modbus or other popular communication protocols.
Sections 2 through 5 provide detailed information and procedures for implementing network set-ups to interface the XPC Gateway to AERCO boilers and water heaters.

1.2 REFERENCE DOCUMENTS

References to the following documents are included in the appropriate sections and subsections of this manual:
AC-105 Electronic Control System
Installation, Operation & Maintenance Manual
GF-124
HA025132 2404/2408 Control Setpoint Programmer Installation
Installation, Operation & Maintenance Manual
Controller & Boiler Communications Module (BCM)
and Operation Handbook

1.3 AERCO XPC GATEWAY PURPOSE AND USE

The primary purpos e of the AERCO XPC Gateway is to allow monitoring or control of AERCO units. Due to the operational nature of the Gateway, it should not be used to configure the system. Configuration (or setup information) should not be constantly changed since this information is generally stored in EEPROM non-volatile memory in the AERCO Controllers (C-More, BMS, and
10
GF-122 AERCO XPC GATEWAY
ECS). This type of memory can be read as often as needed, however, it has a limited number of write cycles.
The Gateway is preprogrammed with standard monitor and control points. These standard points are those most often requested by AERCO customers (see Part III). If different or additional points are required for a particular system, custom factory programming is available. There are five (5) standard pre-programmed configurations to choose from:
Programmed for 4 C-More controlled boilers and 1 Boiler Management System (BMS/BMS II)
Programmed for 1 BMS/BMS II and 8 C-More controlled boilers
Programmed for 1 BMS/BMS II and 12 C-More controlled boilers
Programming for 1 BMS II and 4 BCM controlled Modulex boilers
Programmed for 4 ECS controlled water heaters
Multiple XPC Gateways can be used in certain situations. If necessary, the XPC Gateway can accept up to 300 monitor and control points. Network points and
unit addresses are pre-programmed in the Gateway. In addition, all of the supported protocols – BACNET, LonWorks, and N2 are preprogrammed for all points. They can be easily selected using the DIP switches provided on the Gateway.

1.4 AERCO XPC GATEWAY DESCRIPTION

The XPC Gateway Controller is shown in Figure 1-1. The Gateway is housed i n a compact enclosure measuring approximately 6” H x 8” W x 3” D as shown in Figure 1-2. The installed location of the Gateway will depend on the types of AERCO equipment being used with the Gateway.
Figure 1-1. AERCO XPC Gateway
11
GATEWAY COMMUNICATIONS MANUAL
Figure 1-2. AERCO XPC Gateway Installed in Enclosure
NOTE
If desired, the Gateway can always be wall-mounted, regardless of the types of AERCO equipment being used. However, signaling wire lengths must not exceed 50 feet for RS232 and 3000 feet for RS485 networks.
Benchmark Series Boilers: XPC Gateway can be installed behind the front panel door of the Benchmark below the Input/Output (I/O) Box.
KC1000 Series Boilers or Heaters: XPC Gateway can be installed on the left side of the unit above the Input/Output (I/O) Box.
Boiler Management System (BMS/BMS II): XPC Gateway is normally mounted on a wall in close proximity to the BMS.
Indirect-Fired Heaters with ECS Control System: Gateway is normally wall-mounted.
Modulex Boilers equipped with Boiler Control Modules (BCMs).
The Gateway is powered by 24 VAC, 50/60 Hz, single-phase, 20 VAC. Power and Input/Output (I/O) signal connections are made via four grommetted cutouts (one on each side and two on the bottom surface of the Gateway enclosure. I/O signal wiring is routed through the left-side and bottom-left cutouts of the Gateway enclosure. Connection to the Lon module is accomplished via the bottom-right cutout. Input power wiring (24 VAC, 50/60 Hz) and earth ground wire is routed through the right-side cutout of the enclosure to minimize noise on the signal wiring.
12
GF-122 AERCO XPC GATEWAY

1.5 GATEWAY PORTS & JUMPERS

The Gateway Input/Output (I/O) signal ports are located on the left side of the XPC Gateway, behind the enclosure cover as illustrated in Figure 1-3. In addition, jumpers are also provided on the left side of the Gateway to select the physical type of network being utilized on port 2. The following subsections provide brief descriptions of the ports and jumpers provided.

1.5.1 Port 1a

Port 1a (Figure 1-3, Detail “A”) can only be configured for RS485 communication or special ARC156. This port is normally used for BAS connections. However, if the BAS is communicating via BACnet PTP or is connected to a LonWorks SLTA module, Port 1a cannot be used. Refer to the AERCO XPC Gateway Integration Guide included as Part II of this manual.

1.5.2 Port 2

Port 2 (Figure 1-3, Detail “B”) can be configured for RS485 or RS232 communication. This port normally connects to AERCO equipment except when the BAS is utilizing BACnet PTP or a LonWorks SLTA. In this case, Port 1a must be used for the AERCO equipment. The jumpers located below Port 2 are used to select RS485 or RS232 (EIA-485 or EIA-232) communication and either a 2­wire or 4-wire communication interface (see para. 1.5.5).

1.5.3 Local Access Port

The Local Access Port (Figure 1-3, Detail “C2”) is used to program or read Gateway setup information or to monitor network traffic from the Gateway with a PC using a special interface module. Special network display monitors can also be connected to this port to display network information.

1.5.4 Optional Plug-In Module (Port 1b)

A 14-pin connector labeled Port 1b is for an optional plug-in module. Currently, there is a LonWorks transceiver module that allows LonWorks FTT10A communication without the use of a Serial Lon Talk Adapter (SLTA).

1.5.5 Jumper Settings

Two jumpers are located side-by-side below PORT 2 on the Gateway (Figure 1-3, Detail “D”). These jumpers provide the following functions:
EIA-232/EIA-485 Jumper connector to select either an EIA-485 (RS485) or EIA-232 (RS232) connection to the BAS. Setting the jumper to the lower position selects EIA-485 (RS485) which is the default position. Setting the jumper to the upper position selects EIA-232 (RS232).
2-Wire/4-Wire Jumper connector. Setting the jumper to the upper position selects 2-wire communication. Setting the jumper to the lower position selects 4-wire communication.
- This jumper is connected across 8 of the 12 pins of the header
– This jumper is connected across 2 of the 3 pins of the header
13
GATEWAY COMMUNICATIONS MANUAL
+12V
RNET-
RNET+
GND
COM
NET-
RX
TX
FORMAT
POWER
NET+
CMNET
ONE's
ERR
RUN
OPTIONS
TEN's
BATT
24VAC
GND
POWER
485
232
LN-
/S
+12
GND LN+
2W
RX
TX
4W
BT485
Net +
Net -
Shield
Port 1a
Tx1
Rx1
Port 1b
Port 2
4w
2w
Gnd
+12V
Gnd
Rnet+
Sense
Rnet + Rnet -
R n e t
Rnet­+12V
Local
Access
10's
1's
0
134
5
2
78
9 6
0
134
5
2
78
9 6
4 3 2 1
On
5
6
7
8
Run
Error
Power
Format
Gnd
Hot
EIA-232
EIA-485
Baud
EIA485
19.2k
38.4k 76.8k
BMS
Port 2
ARC156
Port 1
9600
BMS
Switches
(0 = off, 1 = on)
MSTP (m) MSTP (s)
PTP
8 7 6 5
Protocol
0 0 0 0 0 0 0 1 0 0 1 0
BACnet
BMS
Port 1
TYPE: 002106
Enclosed Energy Management Equipment
Made in USA
®
24V ac
2w 4w
Tx+
n/c
n/c
Net+
Rx+
Rx-
Tx-Net-
232 Tx
DTR
DCD
Rx
Signal Ground
+
-
Batt
CR
2032
BT485
Lon SLTA
1 1 0 1
Lon PlugIn
Ethernet
1 1 1 1
1 1 1 0
N2
Modbus
®
®
0 1 1
0 1 0 0
0
Tx2
Rx2
E143900
88FO
R
Class 2, 24Vac
Conductors Only
Use Copper
50-60Hz, 10VA, 0.42A
®
XPC
PORT 1a
( DETAIL “A”)
PORT 2
( DETAIL “B”)
RNET
(
DETAIL “C1”)
PORT 1b
JUMPERS
( DETAIL “D”)
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
8 7 6 5 4 32
1
ON
INPUT POWER
( 24 VAC)
DIP
SWITCHES
( DETAIL “E”)
ADDRESS
SELECT
SWITCHES
( DETAIL “F”)
BATTERY
(3V)
LOCAL
ACCESS
PORT
(DETAIL “C2”)
NOTE: Ground
(see Sht 2 of 3).
RNET
(DETAIL “C1”)
Ground connection lug for
Earth ground connection lug. Connect
is attached to Mounting Panel
Figure 1-3. XPC Gateway Ports, Jumpers and Switches (Sheet 1 of 3)
RNET connector. DO NOT
REMOVE. This ground
MUST be connected when
power is applied to the
Gateway Controller.
Figure 1-3. XPC Gateway Chassis Ground Locations (Sheet 2 of 3)
earth ground here.
14
8
7 6 5 4
32
1
ON
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
10's
1's
DETAIL F
DETAIL E
EIA-485
EIA-232
2W
4W
DETAIL D
Tx +
Port 2
DETAIL B
2W
4W
232
Net+
Tx
Net -
Tx -
Rx
N/C
Rx +
DTR
N/C
Rx -
DCD
SIGNAL
GROUND
Net + Net -
Shield
PORT 1a
DETAIL A
RNET
Gnd
Rnet +
Rnet -
+12V
DETAIL C1
Local
Access
Gnd
Rnet +
Rnet -
+12V
Sense
DETAIL C2
Port 2
2W
4W
232
Local Access
RNET
Port 1a
Net +
DETAIL B
This BCD switch
of the address.
This BCD switch
the address.
This BCD switch
the address.
Note for all Pinout
NOTE: This ground must be
Net -
Shield
attached to Mounting Panel (see Figure 1-3, Sht 2 of 3).
Images:
All connectors on
this page are
shown in the same
orientation as shown on the
referenced PCB
illustration in
Figure1-3, Sheet 1
of 3.
GF-122 AERCO XPC GATEWAY
Net+ Tx+ Tx
Net- Tx- Rx
N/C Rx+ DTR N/C Rx- DCD
Signal Ground
Gnd
Rnet +
Rnet -
+12V
Rnet +
Sense
Gnd
Rnet -
+12V
determines the
determines the 10 decimal
10 decimal position (10, 20,
position (10, 20, 30, 40, etc.) of
30, 40, etc.) of
determines the 1 decimal position (1, 2, 3, 4, etc.)
10’s
1’s
Figure 1-3. XPC Gateway Ports, Jumpers and Switches (Sheet 3 of 3)
15
GATEWAY COMMUNICATIONS MANUAL
BAUD Rate
DIP Switch 1
DIP Switch 2
9600
OFF
OFF
19.2 K
OFF
ON
38.4 K
ON
OFF
76.8 K
ON
ON

1.6 POWER INPUT, PROTOCOL SELECTION & GATEWAY ADDRESSING

The Gateway input power connections, protocol selection, and Gateway addressing are accomplished utilizing the connector and switches on the right side of the XPC Gateway as shown in Figure 1-3. The following subsections provide brief descriptions of the ports and jumpers provided.
IMPORTANT
It is imperative that the XPC Gateway be powered by an isolated 24 VAC power supply which is dedicated only for use by the XPC Gateway. Failure to observe this precaution will result in improper Gateway operation.

1.6.1 Input Power Connection

The Gateway is powered by 24 VAC (Class 2), 50/60 Hz, 20 VA. The input power connector is located on the upper right side of the Gateway (Figure 1-3, Sheet 1 of 3).
When connecting the power source, an earth ground MUST be connected to the ground screw on the mounting panel. See Figure 1-3, Sheet 2 of 3.
In addition, a 3 volt lithium battery (CR2032) is installed below the AC power connector. This battery is used to retain the current monitoring/control data stored in volatile memory.
WARNING
Do not remove the battery when the power is off. Doing so may erase some recorded data as well as programming, especially on older models not utilizing non-volatile memory. The battery maintains the integrity of the data and coding contained in memory whenever the supply voltage is not present.

1.6.2 Protocol and Baud Rate Select

Protocol and baud rate selection are accomplished using the 8 DIP switches shown in Figure 1-3, Detail “E”. The DIP switches can be set to the ON (left) or OFF (right) position. The functions and settings for each of these switches are listed in the Tables 1 and 2 which follow.
Table 1 Baud Rate Select Switches
DIP Switch 3 selects whether XPC Port 1 or Port 2 will be connected to the BAS used with the
DIP Switch 4 will normally be set to ON for RS485 communication. It should only be set to OFF if
Gateway. When DIP Switch 3 is OFF, Port 1 is connected to the BAS. When set to ON, Port 2 is connected to the BAS. The other port will be used for connection of AERCO equipment.
the BAS Port is 1 and the BAS is communicating BACnet using the ARC156 method.
16
GF-122 AERCO XPC GATEWAY
DIP Switch Settings
Protocol
8 7 6
5
Comments
BACnet
RS485 communication to BACnet
BACnet BACnet
RS232 communication to BACnet
Johnson
RS485 communication to Johnson N2
Modbus
DO NOT USE FOR THIS
LonWorks
Serial LonTalk Adapter required.
LonWorks
Lon Option Card required
Table 2 Building Automation System (BAS) Protocol
MS/TP Master
MS/TP Slave
PTP
N2
SLTA
FTT10a
OFF OFF OFF OFF
OFF OFF OFF ON
OFF OFF ON OFF
OFF OFF ON ON
OFF ON OFF OFF
ON ON OFF ON
ON ON ON OFF

1.6.3 Gateway Address Switches

Master
DO NOT USE FOR THIS APPLICATION
Master
Master
APPLICATION
(currently available from Echelon)
The Gateway contains two rotary address switches labeled 0 - 9 as shown in Figure 1-3, Detail “F”. The upper switch is labeled “10’s” and the lower switch is labeled “1’s”. When multiple Gateways are used and controlled by a single BAS/EMS, each Gateway must have its own unique address. Do not set both the “10’s” and the “1’s” address switches to “0”. Doing so will disable the Gateway on the network.

1.7 GATEWAY STATUS INDICATORS

In addition to the ports and switches described in the previous subsections, the XPC Gateway contains seven (7) LED Status Indicators which can be monitored during Gateway operation. These LED Status Indicators are illustrated and described in Figure 1-4 and Table 3.
17
GATEWAY COMMUNICATIONS MANUAL
+12V
RNET-
RNET+
GND
COM
NET-
RX
TX
FORMAT
POWER
NET+
CMNET
ONE's
ERR
RUN
OPTIONS
TEN's
BATT
24VAC
AGND
POWER
RNET
485
232
LOCAL ACCESS
LN-
/S
+12
GND LN+
2W
RX
TX
4W
BT485
Net + Net -
Shield
Port 1a
Tx1 Rx1
Port 1b
Port 2
4w
2w
Gnd
+12V
Gnd
Rnet+
Sense
Rnet + Rnet -
R n e t
Rnet­+12V
Local
Access
10's
1's
0
134
5
2
78
9 6
0
134
5
2
78
9 6
4 3 2 1
On
5
6
7
8
Run
Error
Power
Format
Gnd
Hot
EIA-232
EIA-485
Baud
EIA485
19.2k 38.4k 76.8k
BMS
Port 2
ARC156
Port 1
9600
BMS
Switches
(0 = off, 1 = on)
MSTP (m) MSTP (s) PTP
8 7 6 5
Protocol
0 0 0 0 0 0 0 1 0 0 1 0
BACnet
BMS
Port 1
TYPE: 002106
Enclosed Energy Management Equipment
Made in USA
®
24V ac
2w
4w
Tx+
n/c n/c
Net+
Rx+ Rx-
Tx-Net-
232
Tx
DTR DCD
Rx
Signal Ground
+
-
Batt
CR
2032
BT485
Lon SLTA
1 1 0 1
Lon PlugIn Ethernet
1 1 1 1
1 1 1 0
N2 Modbus
®
®
0
1 1
0 1 0 0
0
Tx2
Rx2
E143900
88FO
R
Class 2, 24Vac
Conductors Only
Use Copper
50-60Hz, 10VA, 0.42A
®
XPC
POWER
LED
RUN
LED
ERROR
LED
TX1
LED
RX1 LED
TX2
LED
RX2 LED
RNET
LOCAL
ACCESS
PORT
LED STATUS
TX1
Green LED flashes when data is being transmitted from
RX1
Green LED flashes when data is being received by the
Green LED lights when 24 VAC power is being supplied
RUN
Green LED lights to show Gateway status as described
TX2
Green LED flashes when data is being transmitted to
RX2
Green LED flashes when data is being received from
Figure 1-4. XPC Gateway Status LED Locations
INDICATOR
(LED1)
(LED2)`
POWER
(LED3)
(LED4)
ERROR
(LED5)
(LED6)
(LED7)
Table 3 Gateway LED Status Indicators
the BAS connected to Port 1.
BAS connected to Port 1.
to the Gateway.
in Table 4. Red LED lights to show Gateway status as described in
Table 4.
the AERCO equipment connected to Port 2.
the AERCO equipment connected to Port 2.
FUNCTION
18
If RUN LED Shows:
And ERROR LED Shows:
Status is:
2 flashes per second
Off
Normal
2 flashes per second
2 flashes,
Five minute auto-restart delay
2 flashes per second
3 flashes,
Gateway has just been
2 flashes per second
4 flashes,
Two or more devices on the
2 flashes per second
On
Exec halted after frequent
See also Part II “Communication LED’s”.
Table 4 RUN & ERROR LED Status
GF-122 AERCO XPC GATEWAY
alternating with RUN LED
then Off
then pause
after system error
formatted
network have the same ARC156 network address
system errors or control program halted

1.8 BASIC GATEWAY OPERATION

The Gateway scans the points list from top to bottom in a round-robin fashion. It will continually retrieve the information from the programmed Modbus address and hold it for the BAS to read. The information is therefore not real-ti me. How current the information is will depend on how quickly the Gateway can scan all of the required pre-programmed points.
Information is updated based on the update time and priority of the information. If a point is not updated within the allotted update time because the Gateway was not able to read it in time, the value of that point will default to its programmed default value (usually zero).
To speed up the update rate of points and prevent dropouts (going to default value), communication to any unused points can be disabled. This prevents the Gateway from waiting the full Response Time programmed before moving to the next point, thereby reducing the scan cycle time interval.
19
GATEWAY COMMUNICATIONS MANUAL
5-pin port supports EIA-232, EIA-485 2-wire or 4-wire

1.9 XPC GATEWAY REFERENCE DATA

The functional, physical and environmental specifications for the Gateway are listed in Table 5.
Table 5 AERCO XPC Gateway Specifications
Specification Description
Maximum number of points 300 Power 24 VAC ±10%, 50-60 Hz, 20 VA power consumption, Class 2
source only, 100 VA or less
Port 1a 3-pin port supports EIA-485 (RS485) 2-wire communication.
Protocols supported:
BACnet over ARC156
BACnet MS/TP
Modbus (RTU/ASCII)
Johnson N2
This port can be configured as a device port or a BAS port NOTE: Port 1a or Port 1b can be used, but not both.
Port 1b 14-pin communication port supports plug-in cards such as
LonWorks or future Ethernet.
Port 2
Rnet Port
Local Access Port For local communication with a laptop computer running
Memory 1 MB non-volatile battery-backed RAM, 1 MB Flash memory,
communications. Protocols supported:
EIA-232 BACnet PTP, Modbus (RTU/ASCII), LonWorks SLTA
EIA-485 2-wire BACnet MS/TP, Modbus (RTU/ASCII), Johnson N2
EIA-485 4-wire BACnet MS/TP, Modbus (RTU/ASCII)
This port can be configured as a device port or BAS port. 4-pin port supports up to four RS Standard sensors and one
RS Plus, RS Pro, or RS Pro-F sensor for averaging or high/low select control.
WebCTRL or AppLoader.
16-bit memory bus
20
GF-122 AERCO XPC GATEWAY
Width
4 in. (102mm)
Height
5 in. (127mm)
Depth
1.75 in. (51mm)
Add for the LonWorks Card:
Width
1.8 in. (45.72mm)
Height
3.25 in. (82.55mm)
Depth
1.5 in. (38.1mm)
Distance apart cannot exceed ribbon cable:
9.75 in. (247.65 mm)
Width
2 in. (51 mm)
Height
4.8 in. (122mm)
LonWorks Option Card
1.325 in. (33.66 mm) apart – top 2 holes
.475 in. (12.07 mm) from edge
.890 in. (22.61 mm) bottom hole – from edge
Width
8.94 in. (227 mm) apart – top 2 & bottom 2 holes
Height
5.00 in. (127 mm) between top 2 & bottom 2 holes
Table 6 XPC Gateway Specifications - Continued
Specification Description
Battery 10-year Lithium CR2032 battery provides a minimum of 10,000
hours of data retention during power outages
Protection Built-in surge and transient protection circuitry - internal solid
state Polyswitches on the incoming power and network connections.
Status Indicators LED's indicate status of communications, running, errors, and
power.
Environmental operating range
-40° to 150°F (-40° to 65.6°C), 10–95% relative humidity, non­condensing
Overall dimensions (without enclosure)
Mounting hole dimensions (without enclosure)
Mounting hole dimensions in enclosure
Rommended panel depth 1.75 in. (51mm) Weight 9 oz. BACnet support Conforms to the Advanced Application Controller (B-AAC)
Standard Device Profile as defined in ANSI/ASHRAE Standard 135-2004 (BACnet) Annex L
Listed by UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B-
Class A, CE EN50082-1997

1.10 QUICK SETUP GUIDE

A Quick Setup Guide is provided as additional guidance to configuring and integrating the AERCO XPC Communications Gateway. The guide now follows.
21
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC QUICK SETUP GUIDE
Follow the instructions below to quickly wire and set up the AERCO XPC between your
Building Automation System (BAS) and AERCO equipment - Boiler Management System (BMS/BMSII), Boiler Controls (C-MORE on Benchmark or KC1000 boilers or Boiler Control Module (BCM) on Modulex (MLX) boilers), or Electronic Control System (ECS).
Select the 2 pages that apply to your configuration – one from pages 2 to 5 which outlines the
wiring and set up between your BAS and the AERCO XPC, and the other from pages 6 to 10 which outlines the wiring and set up between the AER CO X PC and AERCO equipment.
Note: The AERCO XPC cannot share power with other equipment. It must have its own
dedicated 24VAC supply else communication dropouts could result.
AERCO XPC
AERCO
EQUIPMENT
BUILDING
AUTOMATION
SYSTEM
An extra ground wire must be connected to the earth ground screw in the XPC metal plate.

1.10.1 Quick Setup Guide

22

1.10.2 BACNET MS/TP to AERCO XPC

BACNET M S/TP TO AERCO XPC
XPC Port 1a:
Wir e to Port 1a  + to “Net+”, - to “Net-”, and Shi eld connecte d at one end only. If to XPC then to “Shi eld” connec tor.
8-Position Dipswitch:
Dipswi tch 1,2 set to BACNET MS/ TP communi cati on baud rate;
Dipswi tch 3 = Off (B.A. S. on port 1);
Dipswi tch 4 = O n (EI A485 on port 1) ;
Dipswitch 5-8 = Off, O ff, Off, Off (for bacnetms/tp(m));
Rotary Address Switches:
2 Rotar y Address Swit ches set to BacnetID address for t he XPC)
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES .
AERCO XPC
BACNET
MS/TP
Port 1a Port 2 RS485
RS485
BAS
bacnet
GF-122 AERCO XPC GATEWAY
23
GATEWAY COMMUNICATIONS MANUAL
LON TO AERCO XPC (wit h LON-OC)
XPC “Net” Port on LON-OC:
Wir e to “Net ” Port on LON-OC Polari ty does not matt er in this case. Connect shield at one end onl y.
8-Position Dipswitch:
Dipswi tch 1, 2 = On, Off ( 38.4 K baud);
Dipswi tch 3 = Off (B.A. S. on port 1);
Dipswi tch 4 = On (por t 1b) ;
Dipswitch 5-8 = Off, On, On, On (for Lon plug-in).
Rotary Address Switches:
Not appl icable in thi s case.
Note: Lon XIF fil es are downloada ble from “ www.aerco. com ”. BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES .
AERCO XPC
LON
Port 1b Port 2
Ftt -10a
BAS
Lon
LON-OC
Net
Ribbon cable
Ftt-10a

1.10.3 LON to AERCO XPC (with LON-OC)

24

1.10.4 LON to AERCO XPC (with SLTA)

LON TO AERCO XPC (with SLTA)
XPC Port 2:
Wire SLTA to XPC P ort 2 “TX” to “RX”, “RX” to “TX”, “G nd” to “Signal Ground”, and Shield connected at one end only.
Place 4-position jumper on EIA-232 (t wo top rows);
Place 2-position jumper on 2W;
Jumper “DTR” and “DCD” on SLTA port (port 2).
8-Position Dipswitch:
Dipswitch 1, 2 = On, Off (38.4 K baud);
Dipswitch 3 = On (B.A.S. on port 2);
Dips witc h 4 = Off;
Dips witc h 5-8 = On, Off, On, On (for Lon SLTA).
Rotary Address Switches:
Not applicable in this case. Note: Lon XIF files are on enclosed CD or downloadable from “www.aerco. com”. BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES.
AERCO XPC
LON
Port 2 Port 1a
Ftt -10a
BAS
Lon
SLTA
Net Ftt-10a
RS232
RS232
RS232
GF-122 AERCO XPC GATEWAY
25
GATEWAY COMMUNICATIONS MANUAL
JOHNSON N2 TO AERCO XPC
XPC Port 1a:
Wir e to Port 1a  + to “Net+”, - to “Net-”, and Shi eld connecte d at one end only. If to XPC then to “Shi eld” connec tor.
8-Position Dipswitch:
Dipswi tch 1,2 = Off, Off (9600 baud r ate);
Dipswi tch 3 = Off (B.A. S. on port 1);
Dipswi tch 4 = O n (EI A485 on port 1) ;
Dipswitch 5-8 = On, On, Off, Off ( for N2) ;
Rotary Address Switches:
2 Rotar y Address Swit ches set to N2 unit address for the XPC)
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
JOHNSON
N2
RS485
BAS
N2
Port 1a Port 2 RS485

1.10.5 LON to XPC (with LON-OC)

26
GF-122 AERCO XPC GATEWAY
AERCO XPC TO BO ILER MANAGEMENT SYSTEM
(BMS)
XPC Part Number:
“25024-1” for 1 BMS and up t o 4 C-MOREs, or “25024-2” for 1 BM S and up to 12 C-MOREs , or “25024-4” for 1 BMS and up to 4 MLX Boil ers (wi th BCMs), or 25024-5 for 1 BMS and up to 8 C-MOREs
XPC Port 2 to BMS Port JP12:
Wir e to XPC Por t 2  “TX ” t o “RXD”, “ RX” to “ TXD” , “ Signal Gr ound” t o “G ND”, and Shiel d connecte d at one end only t o the BMS at the “SHIELD” i nput. Jumper “ DTR” and “DCD” on port 2.
Place 4-posi tion j umpe r on EIA-232 ( two top rows) ;
Place 2-posi tion j umpe r on 2W;
XPC Software Setup:
Modbus Respons e Ti me = 20(x100 msec) (default);
BMSII RS232 Software Setup:
RS232 Mode = M odbus Slave; RS232 Baudrate= 9600; Modbus Addr ess = 128; Modbus Pass Thru = Enabled (if r eading informati on from boi lers, else leave Disabled );
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
BMS
Port 1a Po rt 2
RS232 RS485
RS232
modbus
JP 12 JP 11

1.10.6 AERCO XPC to Boiler Management System (BMS)

27
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC TO BO ILER MANAGEMENT SYSTEM II
(BMSII)
XPC Part Number:
“25024-1” for 1 BMSII and up to 4 C-MORE, or “25024-2” for 1 BMSII and up to 12 C-MOREs , or “25024-4” for 1 BMSI I and up t o 4 MLX Boil ers ( wit h BCMs) , or 25024-5 for 1 BMSII and up to 8 C­MOREs
XPC Port 2 to BMSII Port JP5:
Wi re to XPC Por t 2  “T X” t o “RXD” , “ RX” to “ TXD” , “ Si gnal Gr ound” t o “G ND”, and Shiel d connecte d at one end only. If to the BMSII at t he “SHI ELD” input . Jumper “ DTR” and “ DCD” on port 2.
Place 4-posi tion j umpe r on EIA-232 ( two top rows);
Place 2-posi tion j umpe r on 2W;
XPC Software Setup:
Modbus Response Time = 20(x100 msec) (default);
BMSII RS232 Menu Setup:
RS232 Mode = Modbus Slave; RS232 Baudrate= 9600; Modbus Addr ess = 128; Modbus Pass Thru = Enabled (if r eading informati on from boi lers, else leave Disabled );
BE SURE TO CYCLE AERCO XPC POWER AFTER MAKING ANY DIPSWITCH OR JUMPER CHANGES
AERCO XPC
BMSII
Port 1a Po rt 2
RS232 RS485RS232
modbus
JP5 JP6

1.10.7 AERCO XPC to Boiler Management System II (BMS II)

28

1.10.8 AERCO XPC to C-More

AERCO XPC TO C -MORE
XPC Part Number:
25024-1 or 63046-1 for 1 BMS and up to 4 C-MOREs; 25024-2 for 1 BMS and up to 12 C-MOREs; 25024-5 for 1 BMS and up to 8 C-MOREs
XPC Port 2 to C-MORE (I/O Box) RS485:
Wire to XPC Port 2 “Net+” to “RS485+” , “Net-” to “RS485-”, and Shield connected at one end only - to the C- MORE (I/O Box) at the “SHLD” input.. Daisy chain to the other units..
Place 4-position jumper on EIA-485 ( t wo bot t om rows);
Place 2-position jumper on 2W;
XPC Software Setup:
Modbus Response Time = 2 (x100 msec); (Must be changed using AppLoader Software and Programmer Cable.)
C-MORE Setup:
For Monitor Only “Comm Address” = (boiler addr ess s t ar t ing with “1” ) ;
For M onitor and Remote Setpt Control via Modbus Se t “Comm Address ” as above; Set “Boiler Mode” to
“Remote Setpt” ; Set “Remote Signal” to “Network”.
BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES
AERCO XPC
C-MORE
Port 1a Po rt 2
RS485 RS485
modbus
GF-122 AERCO XPC GATEWAY
29
GATEWAY COMMUNICATIONS MANUAL
AERCO XPC TO BCM (on MLX Boiler )
XPC Part Number:
25024-4 or 63046-4 for 1 BMS and up to 4 MLX (with BCM Controls)
XPC Port 2 to BCM Port Y2:
Wire to XPC Port 2 “Net+” to Y2 pin 1; “Net-” to Y2 pin 2; and Shield connected at one end only - to the XPC at the “SHIELD” input.. Daisy chain to the other units..
Place 4-position jumper on EIA-485 ( two bottom rows);
Place 2-position jumper on 2W;
XPC Software Setup (Must be changed using AppLoader Software and Programmer Cable.):
Modbus Response Time = 2 (x100 msec); Only if Remote Setpoint control is to be done, set these points from “False” to “T rue” – “Req Outlet T emp” and “ Net Direct Drive” – for all your boiler addres ses.
BCM Setup:
Set Addres s Dipswitch on each BCM start ing from 1; Keep termination jumper off on all BCMs;
BE SURE TO CYCLE AERCO XPC POW ER AFTER MAKI NG ANY DI PSW ITCH O R JUMPER CHANG ES
AERCO XPC
BCM
Port 1a Po rt 2
RS485 RS485
modbus

1.10.9 AERCO XPC to BCM (on MLX Boiler)

30

1.10.10 AERCO XPC to ECS (with Eurotherm Control)

GF-122 AERCO XPC GATEWAY
31
GATEWAY COMMUNICATIONS MANUAL
THIS PAGE INTENTIONALLY LEFT BLANK
32
GF-122 AERCO XPC GATEWAY
PART I
AERCO XPC DESCRIPTION
&
SET-UP INSTRUCTIONS FOR INTERFACING
WITH AERCO EQUIPMENT
33
GATEWAY COMMUNICATIONS MANUAL

SECTION 2 INTERFACING THE XPC WITH C-MORE CONTROLLED UNITS

2.1 INTRODUCTION

The AERCO XPC Gateway can be connected to any C-More-controlled gas-fired boiler or water heater. The XPC is configured to work in a “plug-and-play” fashion with AERCO equipment utilizing Modbus (RS485) communication. The default Modbus communication configuration for all AERCO equipment is Modbus RTU, 9600 baud, 8 data bits, 1 stop bit, and no parity.
The information in this Section provides basic planning set-up and programming details for implementing a communication network utilizing the AERCO XPC Gateway with up to 12 C-More controlled boilers or water heaters. Network control and monitoring is provided by a Master third-party BAS or EMS. Set-up information for the Master BAS/EMS is provided in the AERCO XPC Gateway Integration Guide, included as Part II of this manual.

2.2 PHYSICAL NETWORK WIRING

All signal wiring connections between the AERCO XPC Gateway and other AERCO equipment should be implemented using shielded, twisted-pair wiring from 18 to 24 AWG. Examples of suitable wire types are: Belden #9841, #8761, #3105A, or equivalent.
The physical locations of the wiring connections necessary to implement a communications network comprised of the XPC Gateway and AERCO boilers and/or water heaters and a third party BAS or EMS are provided in the following subsections. Where applicable, connector pinout information is provided for all AERCO equipment. Refer to the AERCO XPC Gateway Integration Guide (Part II of this manual) for connection of BAS/EMS equipment used with the XPC Gateway. Also, refer to the BAS/EMS manufacturer’s equipment manual.

2.3 C-MORE BOILERS OR HEATERS CONTROLLED BY BAS VIA THE GATEWAY

As mentioned in Section 1, C-More Controllers can communicate directly with a BAS utilizing Modbus RTU protocol via a RS485 network. However, if the BAS does not support Modbus, the XPC Gateway is required to provide the necessary protocol translation.
All Modbus networks are implemented utilizing a Master-Slave technique where only one device, the Master, can initiate a communication sequence. AERCO C-More Controllers can only function as Slave devices on a Modbus network
34
GF-122 AERCO XPC GATEWAY
BAS
MASTER
SLAVE
#1
SLAVE
#2
SLAVE#3SLAVE#4SLAVE
#5
XPC
GATEWAY
Modbus RS485 devices should be wired in a “Daisy-Chain” configuration similar to the example shown Figure 2-1. DO NOT wire the units in a “Star” configuration where all devices are connected to a central point (node).
Figure 2-1. Typical Daisy-Chain Modbus/RS485 Network
Subsections 2.4 through 2.7 provide the set-up and programming instructions necessary to implement a communications network utilizing the AERCO XPC and C-More Controller Slaves controlled by a Master BAS.

2.4 C-MORE CONTROLLER MODBUS COMMUNICATION INTERFACE

The RS485 Modbus communication (COMM) connections for C-More Controller slaves are made in the Input/Output (I/O) Box shown in Figure 2-2. Identical I/O Boxes are used for Benchmark Boilers and KC1000 Boilers or Water Heaters. The connections are made at the RS485 COMM terminals labeled + (plus), and – (minus). Observe the NOTE in Figure 2-2 and never terminate wire shields to the G (Ground) terminal.
35
GATEWAY COMMUNICATIONS MANUAL
Figure 2-2. I/O Box RS485 COMM Terminal Connections
36
GF-122 AERCO XPC GATEWAY

2.5 RS485 LOOP TERMINATING RESISTORS AND BIAS

A terminating resistor (120 ohms) on each end of the RS485 loop is designed to match the electrical impedance characteristic of the twisted-pair loop and prevent echoes or cross-talk from corrupting data on the line.
Bias may be necessary on the RS485 loop to minimize noise on the circuit. Loop bias is accomplished by activating pull-up/pull-down resistors on the last C-More Controller in the chain.
When connected directly to the XPC, a terminating resistor should not be needed unless the circuit is very long (> 2000 feet) or the number of nodes is high (> 20). If termination is activated in the C-More, a 120 Ohm resistor must be placed across the XPC RS-485 connections. Bias is generally not needed unless excess noise on the bus seems to warrant it. Activating bias, even when not needed, will not harm the communications.

2.5.1 C-More Boiler Controller Terminating Resistor and Bias

C-More Boiler Controllers can function only as Slave devices on a Modbus Network. Since the Slaves are connected in a “Daisy-Chain” configuration, the terminating resistor must be enabled only in the last More Boiler Controller in the chain. In addition, bias must also be implemented only in the last C-More Boiler Controller. This is accomplished by setting a DIP switches on the Primary Micro-Controller (PMC) Board contained in the applicable C-More Boiler Controller. The last unit in the chain must be energized (even if disabled) to enable bias.
C-
To activate the DIP switches, proceed as follows: Remove power from the last C-More Boiler Controller in the RS485 loop. Loosen and remove the four (4) screws securing the front panel assembly to the chassis as shown in
Figure 2-3. Carefully separate the panel from the chassis. Use care to avoid applying undue stress to the ribbon
cable connected between the back of the panel and the chassis-mounted printed circuit boards.
CAUTION
The C-More Boiler Controller Printed Circuit Boards contain electronic components that are sensitive to electrostatic discharge (ESD). Prior to performing the following steps, put on an anti-static wrist strap and connect the clip lead to earth ground. Failure to observe this precaution may result in permanent damage to on-board ESD-sensitive components.
1. Attach an anti-static wrist strap to your wrist and connect the clip lead to earth ground.
2. From the back of the Panel Assembly (Figure 2-4), locate the RS485 DIP switches on the PMC
Board.
3. Refer to Figure 2-5 and set the “TERM” switch to the ON (Up) position.
4. Set the BIAS2 and BIAS1 switches to the ON (Up) position.
5. After the DIP switches have been set, reposition the Front Panel Assembly on the chassis and secure
it in place with the four screws.
37
GATEWAY COMMUNICATIONS MANUAL
FRONT PANEL SCREWS (4 PL)
THE C-MORE CONTROLLER MODEL SHOWN WITH A HORIZONTAL PANEL CONTROL LAYOUT IS USED ON KC1000 BOILERS. BENCHMARK BOILERS UTILIZE C-MORE CONTROLLERS WITH A VERTICAL PANEL CONTROL LAYOUT.
NOTE:
Figure 2-3. C-More Control Panel - Front View
38
GF-122 AERCO XPC GATEWAY
RIBBON
CABLE
RS485
DIP SW.
CONTROL PANEL REAR VIEW – KC1000
C32
Q1
C41
C29
C20
C31
C35
C47
C44
R29
R30
HB
C53
R74
C4
C3
U1
CBS3
R69
C50
R67
R68
Y1
C52
C57
J2
CR1
C1
C5
U17
R76
C51
R71 R73 R72
C2
JP2
R70
U21
C56
C6
C64
R75
J4
U13
U20
C59
C49
C48
C61
CBS4
U14
R78
R79
DS5DS4
RS232
TX
RX
C60
C62
C46
U19
U15
U18
C58
C55
C54
DS3
R77
Y2
U16
C63
B1
R16
U11
R66
U10
R15
C45
R14
C19
C16
R32 R17
C18
R18
C34
U4
R33 C27
R31
C26
U6
R47
C39
R55
U2
R1
C7
U8
R53
C36
R81
R45
R44
C37
R48
S2
R46
C38
R49
J1
BIAS1
TERM
BIAS2
R50
C40
CBS1
RS485
C11
J3
R51
R9
BH1
U3
R10 C12
C13
DS1
RS485
TX
RX
R52
U7
DS2
R54
R5
C10
R7
R8
R6
S1
R11
R65
C9
R34
R12
R13 C14
C15
R36
C28
C25
R35
C23
R37
R38
C30
U5
C43
C65
R2
R3
R58
C8
R62
R4
R80
OFF = VOLT
CURR/VOLT ON = CURR
Q2
R57
C66
R64
R56
CBS2
R25
U12
R20
U9
R19
C17
R27
R23
R21
R22 C21
R28
R26
C24
R60
R41 R40
R24
R39
C22
R42 R43
C33
R61
R63
C42
R59
CR2
CONTROL PANEL REAR VIEW – BENCHMARK
C32
Q1
C41
C29
C20
C31
C35
C47
C44
R29
R30
HB
C53
R74
C4
C3
U1
CBS3
R69
C50
R67
R68
Y1
C52
C57
J2
CR1
C1
C5
U17
R76
C51
R71 R73 R72
C2
JP2
R70
U21
C56
C6
C64
R75
J4
U13
U20
C59
C49
C48
C61
CBS4
U14
R78 R79
DS5DS4
RS232
TX
RX
C60
C62
C46
U19
U15
U18
C58
C55
C54
DS3
R77
Y2
U16
C63
B1
R16
U11
R66
U10
R15
C45
R14
C19
C16
R32 R17
C18
R18
C34
U4
R33 C27
R31
C26
U6
R47
C39
R55
U2
R1
C7
U8
R53
C36
R81
R45
R44
C37
R48
S2
R46
C38
R49
J1
BIAS1
TERM
BIAS2
R50
C40
CBS1
RS485
C11
J3
R51
R9
BH1
U3
R10 C12
C13
DS1
RS485
TX
RX
R52
U7
DS2
R54
R5
C10
R7
R8
R6
S1
R11
R65
C9
R34
R12
R13 C14
C15
R36
C28
C25
R35
C23
R37
R38
C30
U5
C43
C65
R2
R3
R58
C8
R62
R4
R80
OFF = VOLT
CURR/VOLT ON = CURR
Q2
R57
C66
R64
R56
CBS2
R25
U12
R20
U9
R19
C17
R27
R23 R21
R22 C21
R28
R26
C24
R60
R41 R40
R24
R39
C22
R42 R43
C33
R61
R63
C42
R59
CR2
RIBBON
CABLE
RS485
DIP SW.
PMC
BOARD
PMC
BOARD
Figure 2-4. C-More Control Panel - Rear Views
39
GATEWAY COMMUNICATIONS MANUAL
C32
Q1
C41
C29
C20
C31
C35
C47
C44
R29
R30
HB
C53
R74
C4
C3
U1
CBS3
R69
C50
R67
R68
Y1
C52
C57
J2
CR1
C1
C5
U17
R76
C51
R71 R73 R72
C2
JP2
R70
U21
C56
C6
C64
R75
J4
U13
U20
C59
C49
C48
C61
CBS4
U14
R78
R79
DS5DS4
RS232
TX
RX
C60
C62
C46
U19
U15
U18
C58
C55
C54
DS3
R77
Y2
U16
C63
B1
R16
U11
R66
U10
R15
C45
R14
C19
C16
R32
R17
C18
R18
C34
U4
R33
C27
R31
C26
U6
R47
C39
R55
U2
R1
C7
U8
R53
C36
R81
R45
R44
C37
R48
S2
R46
C38
R49
J1
BIAS1
TERM
BIAS2
R50
C40
CBS1
RS485
C11
J3
R51
R9
BH1
U3
R10 C12
C13
DS1
RS485
TX
RX
R52
U7
DS2
R54
R5
C10
R7
R8
R6
S1
R11
R65
C9
R34
R12
R13
C14
C15
R36
C28
C25
R35
C23
R37
R38
C30
U5
C43
C65
R2
R3
R58
C8
R62
R4
R80
OFF = VOLT
CURR/VOLT ON = CURR
Q2
R57
C66
R64
R56
CBS2
R25
U12
R20
U9
R19
C17
R27
R23 R21
R22 C21
R28
R26
C24
R60
R41 R40
R24
R39
C22
R42 R43
C33
R61
R63
C42
R59
CR2
SEE DETAIL “A”
S2
BIAS1
TERM
BIAS2
RS485
DETAIL “A”
SET THE BIAS2, TERM & BIAS1 DIP SWITCHES TO THE ON (UP) POSITION TO ACTIVATE EACH FUNCTION IF NECESSARY.
PMC BOARD
RIBBON CABLE CONNECTOR (J1)
Figure 2-5. C-More Control Panel PMC Board
40
GF-122 AERCO XPC GATEWAY
EIA-485
EIA-232
2W
4W

2.5.2 BAS Terminating Resistor and Bias

Refer to the BAS manufacturer’s Technical Manual and follow their recommended guidelines for termination resistors and bias.
NOTE
DO NOT connect C-More boilers to the XPC Gateway as described in subsection 2.6 if the boilers are being controlled by a BMS Master on the Modbus network. Refer to Section 3, subsection 3.3 for wiring and set-up instructions when controlled by the BMS.

2.6 C-MORE CONTROLLER WIRING CONNECTIONS TO AERCO XPC GATEWAY

XPC Port 2 is normally used to connect to AERCO equipment, except when the controlling BAS is utilizing a LonWorks SLTA module, or communicating via BACnet PTP. In this case, Port 1a of the XPC must be used to connect AERCO equipment. Therefore, follow the appropriate wiring instructions in subsection 2.6.1 (Port 2) or 2.6.2 (Port 1a) as applicable.

2.6.1 C-More Wiring Connections to XPC Port 2

When the controlling BAS is utilizing BACnet MS/TP, Johnson N2 or LonWorks protocol without an SLTA, use XPC Port 2 as follows:
1. Position the EIA-232/EIA-485 and 2W/4W jumpers to EIA-485 and 2W respectively as shown in Figure 2-6.
Figure 2-6. Port 2 Jumper Settings
2. At the I/O Box for the first C-More Controller, connect the RS-485 COMM terminals as follows: (a) Connect the RS485 COMM + (plus) terminal to the Net + (plus) terminal on XPC Port 2. (b) Connect the RS485 COMM – (minus) terminal to the Net – (minus) terminal on XPC Port 2. (c) DO NOT connect the wire shield to the Ground (G) terminal at the I/O Box. Connect the wire
shield only to the SIGNAL GROUND terminal at XPC Port 2. Refer to Figure 2-7.
41
GATEWAY COMMUNICATIONS MANUAL
+
G
-
2W
4W
232 Net + Net -
N/C N/C
Tx +
Tx
Tx -
Rx
DTR
Rx -
DCD
SIGNAL
GROUND
Rx +
Port 2
R
E
D
(
+
)
B
L
U
E
(
-
)
S
H
I
E
L
D
RE
D (
+
)
B
L
U
E
(
-)
S
H
I
E
L
D
RED (+)
BLUE (-)
DAISY-CHAIN
TO OTHER UNITS
(
+
TO +, - TO
-)
TIE TOGETHER WITH
SHIELDS OF OTHER
UNITS
C-MORE I/O BOX
RS485 COMM
XPC GATEWAY
+
G
-
R
E
D
(
+
)
B
L
U
E
(
-
)
S
H
I
E
L
D
RE
D
(
+
)
B
L
U
E
(-
)
S
H
I
E
L
D
DAISY-CHAIN
TO OTHER UNITS
(
+
TO
+, -
TO
-)
TIE TOGETHER WITH
SHIELDS OF OTHER
C-MORE UNITS
Net +
Net -
Shield
PORT 1a
C-MORE I/O BOX
RS485 COMM
XPC GATEWAY
RED (+)
BLUE (-)
Figure 2-7. Port 2 Wiring Connections
3. At the XPC Gateway, ensure that DIP switch 3 is set to the OFF (right) position.

2.6.2 C-More Wiring Connections to XPC Port 1a

Connect to XPC Port 1a as follows:
1. At the I/O Box for the first
2. At the XPC Gateway, ensure that DIP switch 3 is set to ON (left) and 4 is set to OFF (right) position.
C-More Controller, connect the RS-485 COMM terminals as follows: (a) Connect the RS485 + (plus) terminal to the Net + (plus) terminal on XPC Port 1a. (b) Connect the RS485 – (minus) terminal to the Net – (minus) terminal on XPC Port 1a. (c) DO NOT connect the wire shield to the Ground (G) terminal at the I/O Box. Connect the wire
shield only to the SIGNAL GROUND terminal at XPC Port 1a. Refer to Figure 2-8.
Figure 2-8. Port 1a Wiring Connections
42
GF-122 AERCO XPC GATEWAY

2.7 CONFIGURING THE C-MORE CONTROLLERS

The C-More Boiler Controller can be set up for three types of Modbus (RS485) operating modes. These modes are as follows:
Monitoring and Configuration Only
Modbus Direct Drive Control and Monitoring
Modbus Remote Setpoint Control and Monitoring
The following subsections provide the procedures necessary to set up the C-More Boiler Controllers for each of the above modes of operation. These procedures assume that the required wiring connections for Modbus (RS485) operation have already been accomplished as described in subsection 2.6.
NOTE
The appropriate password must be entered in the Setup Menu of the C­More Controller, prior to changing any of the current settings. Refer to Section 2 of C-More Controller Operation Manual GF-112 for detailed information on menu processing procedures.

2.7.1 C-More Controller Monitoring and Configuration Control

Each C-More Controller must be programmed with a distinct network address. The standard XPC Gateway supports addresses 1 through 12 for C-More controlled boilers or water heaters. Contact AERCO if additional addresses are required. Proceed as follows to program a valid address at each More Controller:
1. Scroll through the Setup menu until Comm Address is displayed.
2. With Comm Address displayed, press the CHANGE key.
3. Using the ▲ or ▼ arrow key, enter a valid address between 1 and 12.
4. Press the ENTER key to store the Comm Address in memory.
5. Repeat steps 1 through 4 for each C-More Controller on the Modbus network.
6. Upon power-up, the Gateway will begin to read C-More Controller information after its preliminary checks.
C-
43
GATEWAY COMMUNICATIONS MANUAL

2.7.2 Direct Drive Control and Monitoring

Direct Drive Control of the C-More Boiler Controller is no longer allowed via the AERCO XPC Gateway.

2.7.3 Remote Setpoint Control

Remote Setpoint Control of the C-More Boiler Controller is set up as follows:
1. Enter and store a valid Comm Address using the procedures in subsection 2.7.1.
2. Scroll through the Configuration Menu and change the following menu items to the settings shown: MENU OPTION
Boiler Mode Remote Setpoint Remote Signal Network
3. The C-More Controller is now set for Remote Setpoint operation via the RS485 (Modbus) Network.
AERCO recommends that the Setpoint Limiting feature in the Configuration Menu be enabled. Also, ensure that the Failsafe Mode setting is set to the desired setting (Shutdown or Constant Setpoint) in the event that the Network signal is lost.
SETTING
44
GF-122 AERCO XPC GATEWAY
NOTES:
1. IF BAS CONTAINS A 4-WIRE RS485 PORT, TIE THE TWO POSITIVE (+) AND NEGATIVE (-) LEADS TOGETHER AS SHOWN IN DETAIL “A”
2. IF BAS CONTAINS ONLY A RS232 PORT, A RS232-TO-RS485 CONVERTER WILL BE REQUIRED.
3. THE LAST C-MORE BOILER ON THE RS485 LOOP MUST HAVE ITS TERMINATION RESISTOR (TERM) TURNED ON. ALSO, BIAS (BIAS1, BIAS2) MAY BE REQUIRED. CHECK WITH THE BAS MANUFACTURER.
+
-
RS485 COMM
(P/O I/O BOX)
C-MORE
NETWORK BOILER 1
-
+
RS485 COMM
P/O I/O BOX
C-MORE
NETWORK BOILER 2
TO OTHER NETWORK
BOILERS
(SEE NOTE 3)
XPC GATEWAY
PORT
1a
NET +
NET -
SHLD
NET +
N/C
N/C
GND
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTES)
PORT
2
NET -
RS485
T+
R-
R+
T-
SHIELD
4-WIRE RS485 PORT
DETAIL “A”
C-MOREs CONNECTED TO XPC PORT 2
45
Figure 2-9. C-More Controller Sample Network Diagrams (Sheet 1 of 2)
GATEWAY COMMUNICATIONS MANUAL
NOTES:
1. PORT 2 CONNECTIONS AND JUMPER POSITIONS WILL DEPEND ON THE AVAILABLE PORTS ON THE BAS BEING USED. SEE DETAIL “A”.
2. THE LAST C-MORE BOILER ON THE RS485 LOOP MUST HAVE ITS TERMINATION RESISTOR (TERM) TURNED ON. ALSO, BIAS (BIAS1, BIAS2) MAY BE REQUIRED. CHECK WITH THE BAS MANUFACTURER.
+
-
RS485 COMM
(P/O I/O BOX)
C-MORE
NETWORK BOILER 1
-
+
RS485 COMM
P/O I/O BOX
C-MORE
NETWORK BOILER 2
TO OTHER NETWORK
BOILERS
(SEE NOTE 2)
XPC GATEWAY
PORT
1a
NET +
NET -
SHLD
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTES)
PORT
2
SEE NOTE 1
JUMPERS
2W
4W
232
Net +
Net -
N/C
N/C
Tx +
Tx
Tx -
Rx
DTR
Rx -
DCD
SIGNAL GROUND
Rx +
Port 2
DETAIL “A”
C-MOREs CONNECTED TO XPC PORT 1a
46
Figure 2-9. C-More Controller Sample Network Diagrams (Sheet 2 of 2)
GF-122 AERCO XPC GATEWAY
1
9
RS232 PORT (DB9 - FEMALE)
INTERNAL RS485 & RS232 CONNECTORS LOCATED BEHIND COVER (SEE FIGURE 3-2, VIEW A – A)
PANEL COVER
A
A

SECTION 3 INTERFACING THE XPC TO BOILER MANAGEMENT SYSTEMS

3.1 INTRODUCTION

The XPC Gateway can be connected to either an AERCO BMS, Model 168 or BMS II , Model 5R5-384 to provide monitoring or control by a third party BAS. The Modbus connection to monitor or control either a BMS or BMS II is via the unit’s RS232 port.
Although the BMS and BMS II are extremely similar in many respects, separate procedures are provided in subsections 3.2 (BMS) and 3.3 (BMS II) for the two models to avoid any possible confusion. Refer to the appropriate procedures related to your installation.

3.2 INTERFACING THE XPC GATEWAY TO BMS, MODEL 158

The BMS (Model 158) contains both an external RS232 port (DB9) and an internal RS232 port. The external RS232 port is located on the left side of the BMS and the internal RS232 port is located on the terminal board behind the connection cover of the BMS. These connections are shown in Figures 3-1 and 3-2. The BMS external RS232 and internal RS232/RS485 connector pinouts are shown in Figure 3-3. Although either RS232 port can be used, AERCO recommends using the internal RS232 port.
Figure 3-1. BMS Left Side View
47
GATEWAY COMMUNICATIONS MANUAL
L
N
AUX
FLT
ALARM
SYS
START
SET
BACK
INT2
INT1
4-20
MA
161514
13
12
11
-10
+9
SHIELD 8
REF
TEMP
HDR
TEMP
SEN
SHIELD 3
4
5
6
7
OUT
AIR
SEN
1
2
BLR
1
+1
-2
+3
-4+5-6
+7-8+9
-10
+11
-12
+13
-14
+15
-16
BLR2BLR3BLR4BLR5BLR6BLR7BLR
8
85-265 VAC
JP4
JP3
JP2
+(B)
-(A)
SHLD RXD
TXD
GND
RS485 TO BLRS
RS232
JP11
JP12
VIEW A – A
RS485
CONNECTOR
RS232
CONNECTOR
DB9 (FEMALE)
PIN 5
GND
PIN 3
TxD
PIN 2
RxD
5 1
9
6
RXD
TXD
GND
RS232
JP12
+(B) -(A)
SHLD
RS485 TO BLRS
JP11
NOT
USED
EXTERNAL RS232 PORT
INTERNAL RS485 & RS232 PORTS
RS485 PORT RS232 PORT
Figure 3-2. Partial Front View With Cover Removed
Figure 3-3. BMS RS232 & RS485 Connectors
The following subsections provide the procedures necessary connect the BMS to the XPC Gateway and configure it for monitoring or remote setpoint control by a BAS.

3.2.1 BMS Set-Up For Monitoring

XPC Gateway Port 2 is normally used to connect to the AERCO BMS, except when the monitoring BAS is utilizing a LonWorks SLTA, or is communicating via BACnet PTP. In this case, XPC Port 1a must be used to connect the BMS. Therefore, follow the appropriate wiring instructions in subsection 3.2.1.1 (Port
2) or 3.2.1.2 (Port 1a) as applicable.
48
GF-122 AERCO XPC GATEWAY
EIA-485
EIA-232
2W
4W
2W
4W
232 Net + Net -
N/C N/C
Tx +
Tx
Tx -
Rx
DTR
Rx -
DCD
SIGNAL
GROUND
Rx +
Port 2
R
E
D
BL
U
E
G
R
E
E
N
(
G
N
D
)
RE
D
B
L
U
E
G
R
E
E
N
(G
N
D
)
RXD
TXD
GND
RS232
JP12
XPC GATEWAY
BMS
JUMPER
3.2.1.1 BMS Wiring Connections to XPC Port 2
When the BAS being used is communicating via BACnet MS/TP, Johnson N2 or LonWorks without an SLTA, connect to XPC Port 2 as follows:
1. Position the XPC EIA-232/EIA-234 and 2W/4W jumpers to EIA-232 and 2W respectively as shown in Figure 3-4.
Figure 3-4. Port 2 Jumper Settings
2. Refer to Figures 3-2 and 3-3 to locate the internal RS232 connector inside the wiring area of the BMS.
3. At the BMS internal RS232 connector (JP12), refer to Figure 3-5 and connect the wire leads as follows:
(a) Connect the TXD terminal of the BMS RS232 connector to Rx terminal on XPC Port 2. (b) Connect the RXD terminal of the BMS RS232 connector to Tx terminal on XPC Port 2. (c) Connect the GND terminal of the BMS RS232 connector to SIGNAL GROUND terminal on XPC
Port 2.
(d) Add a jumper between the DTR and DCD terminals on XPC Port 2. See Figure 1-3 (Detail B).
Figure 3-5. Port 2 Wiring Connections for BMS
4. At the XPC Gateway, ensure that DIP switch 3 is set to the OFF (right) position.
49
GATEWAY COMMUNICATIONS MANUAL
RXD
TXD
GND
RS232
JP12
Net + Net ­Shield
PORT 1a
XPC GATEWAY
RS232-TO-RS485
CONVERTER
TXD
RXD
GND
GND
B (+)
A
(-)
RED (+)
BLUE (-)
GREEN (GND)
RED
ORANGE
IMPORTANT
CHECK INPUT & OUTPUT
POLARITY ON CONVERTER
BEING USED
BMS
RS232
RS485
+12V
SEE CONVERTER
INSTRUCTIONS
(124958)
3.2.1.2 BMS Wiring Connections to XPC Port 1a
When the BAS being used is communicating via LonWorks with an SLTA, or BACnet PTP, an RS485-to­RS232 converter will be required to connect the BMS to Port 1a of the XPC.
1. Refer to Figures 3-2 and 3-3 to locate the internal RS232 connector JP12 inside the wiring area of the BMS.
2. If the AERCO RS232-to-RS485 Converter (part no. 124942) is used, the RS232 side of the converter contains a connector that plugs directly into header connector JP12 in the BMS. However, If a third party converter is used, connect the RS232 receive (RxD) and transmit (TxD) wire leads to the internal RS232 connector (JP12) as shown in Figure 3-6. DO NOT connect the wire shield on this side of the converter.
NOTE
If a third-party RS232-to-RS485 Converter is used, consult the manufacturer’s instruction manual for signal polarity.
3. At the RS485 side of the converter (Figure 3-6), connect the wire leads as follows: (a) Connect the T D B (+) terminal to the Net + terminal on XPC Port 1a. (b) Connect the T D A (-) terminal to the Net - terminal on XPC Port 1a. (c) Connect the GND terminal to the Shield terminal on XPC Port 1a.
Figure 3-6. Port 1a Wiring Connections for BMS
NOTE
A BMS option is available with a built-in RS485-to-232 Converter (part no,
124943). Therefore, AERCO recommends that the internal RS232 be used. However, the external RS232 port (DB9) can be used if necessary.
4. On the right side of the XPC Gateway Module, check to ensure that DIP switches 3 and 4 are set to the ON (left) position.
50
GF-122 AERCO XPC GATEWAY
3.2.1.3 Configuring the BMS
Once the BMS has been wired to the Gateway as described in subsection 3.2.1.1 or 3.2.1.2, turn on power to the BMS and perform the following configuration settings:
NOTE
Refer to AERCO Instruction Manual GF-108M for additional information on BMS keypad functions and displays.
1. Press the FIELD ADJ key on the BMS front panel to enter the Field Adjust mode.
2. Press the AIR TEMP key once. RS2 32 MODE will appear in the top line of the display. If necessary, press the ▲ or ▼ arrow key until MODBUS SLAVE appears in the second line of the display.
3. Press the AIR TEMP key again. RS232 BAUDRATE will appear in the top line of the display. Press the ▲ or ▼ arrow key until 9600 appears in second line of the display..
4. Press the AIR TEMP key again. MODBUS ADDRESS will appear in the top line of the display. Press the ▲ or ▼ arrow key until an address of 128 appears in the second line of the display. Contact AERCO if another BMS address is required.
5. This completes setup of the BMS.
Refer to subsection 2.3 to connect the required C-More Controllers in a “daisy chain” configuration. Also, refer to the sample network wiring diagram in Figure 2-9.
NOTE
When the C-More is connected to the AERCO BMS/BMS II, bias and termination switches must be activated.
Do not proceed to the next step until all required AERCO equipment is connected.
Turn On the BMS and all of the C-More Controllers.
Apply 24 VAC power to the XPC Gateway.
Following preliminary power-up checks, the XPC Gateway will begin to read BMS data and allow it to be controlled by the BAS Master.

3.2.2 C-More Boilers Being Network-Controlled by a BMS

When the BMS is controlling C-More Boilers on the RS485 Modbus network it is the single “Master” device. No other device, such as the Gateway or a BAS can assume control of the network. However, the BMS also functions as a communications Gateway which permits a BAS to monitor the BMS as well as the boilers on the Modbus network. This is accomplished utilizing the RS232 port of the BMS.
The Modbus Pass Thru feature allows AERCO boiler system owners to link their Energy Management Systems (EMS) and/or Building Automation Systems (BAS) to communicate directly with AERCO C-More boiler control units as far as reading operational parameters are concerned. In this case, the Boiler Management System (BMS) simply “passes through” operating parameter information directly from the C-More boiler control unit to the customer’s EMS/BAS. This is accomplished by enabling the Modbus Pass Thru feature on the BMS/BMS II units.
51
GATEWAY COMMUNICATIONS MANUAL
+
G
-
TERMINATE SHIELD
AT BMS ONLY
+ (B)
- (A) SHLD
C-MORE I/O BOX
RS485 COMM
BMS RS485
JP11
FIRST UNIT
S
H
I
E
L
D
TIE TOGETHER WITH
SHIELDS OF OTHER
C-MORE UNITS
R
E
D
(
+
)
B
L
U
E
(
-
)
R
E
D
(
+
)
BLUE (-)
Although it is recommended to utilize the AERCO BMS for boiler system control, a customer may opt to utilize their own boiler system control system. If such is the case, the BMS/BMS II may be removed entirely allowing the customer’s BAS/EMS system to interact directly (possibly using a protocol translating XPC Communications Gateway device, if needed) with the C-More boiler controller. If the BMS/BMS II is kept in the loop and Modbus Pass Thru is enabled, those control functions normally set by the BMS/BMS II will continue to do so. All other control functions will now be facilitated by BAS/EMS commands passed thru the BMS/BMS II directly to the C-More boiler controller.
If the BAS being utilized supports Modbus RTU protocol, it can be connected to the BMS either directly or via a RS485-to-RS232 converter. However, if the BAS does not support Modbus protocol and utilizes BACnet, N2 or LonWorks, the AERCO XPC Gateway must be used as described below.
1. Make the connections between the BMS and XPC Gateway as instructed in subsections 3.2.1.1 or
3.2.1.2.
2. Set up the C-More Boiler Controllers as described in Section 2, subsections 2.3 through 2.5.1.
3. Connect the C-More Boiler Controllers in a “Daisy-Chain” configuration.
4. Refer to Figure 3-7 and connect the RS485 COMM terminals of the first internal RS485 connector JP11 as follows:
(a) (a) Connect the RS485 COMM + terminal to the +(B) terminal of JP11 in BMS. (b) Connect the RS485 COMM - terminal to the -(A) terminal of JP11 in BMS. (c) Terminate the shield at the BMS end only.
Figure 3-7. BMS Connections to C-More Controller
C-More Boiler to the BMS
5. With the BMS in the Field Adjust Mode, continue pressing the AIR TEMP key until MODBUS PASS
6. With PASS THRU set to ENABLED, both the BMS and the boilers can now be monitored.
NOTE
Refer to AERCO Instruction Manual GF-108M for additional information on BMS keypad functions and displays.
THRU is displayed. Press the ▲ or ▼ arrow key until the second line of the display shows ENABLED.
52
GF-122 AERCO XPC GATEWAY
NOTE
The Gateway Response Time for Modbus must be adjusted to 2 seconds in order for the communication to work efficiently. This is due to the extra lag in communications to the boiler when going through the BMS. Since the BMS control operations take priority, it may delay the processing of a Gateway command by a second or two depending on what it is doing at the moment.

3.2.3 BMS Setup For Remote Setpoint Control From the XPC Gateway

For remote setpoint control of a BMS, set up the wiring connections as described in subsection 3.2. Upon completion of all wiring connections, configure the BMS as follows:
1. Press the FIELD ADJ key on the BMS front panel to enter the Field Adjust Mode. The yellow LED on the key should be lit.
2. Press the AIR TEMP key until RS2 32 MODE is shown on the top line of the display. If necessary, press the ▲ or ▼ arrow key until MODBUS SLAVE appears in the second line of the display.
3. Press the AIR TEMP key again until RS232 BAUDRATE is shown on the top line of the display. Press the ▲ or ▼ arrow key to select a baud rate of 9600.
4. Press the AIR TEMP key again until MODBUS ADDRESS is shown on the top line of the display. Press the ▲ or ▼ arrow key to set the BMS address to 128.
5. Press the FIELD ADJ key to exit the Field Adjust Mode. The yellow LED on the key should go off.
6. To set the BMS for Remote Operation, press the CONFIG SYS key to enter the System Configuration mode. The red LED on the key will light.
7. Press the FIELD ADJ key until HDR SET MODE is shown in the top line of the display. Press the ▲
or ▼ arrow key to select REMOTE SET TEMP.
8. Press the CONFIG SYS key to exit the System Configuration Mode. The red LED on the key will go off.
The BMS is now set up for Remote Setpoint control by a BAS. In the event of control signal interruption, AERCO recommends that the TEMP FAIL MODE setting be set to SWITCH INPUTS if you want the BMS to continue running the boilers in the CONSTANT SET TEMP mode. In this case, ensure that the
REF TEMP is set to the desired setpoint temperature.
NOTE
Sample network diagrams showing the BMS connected to Port 2 and Port 1a of the AERCO XPC Gateway are provided in Figure 3-8. These samples are intended for reference purposes only and do not depict all possible network scenarios.
53
GATEWAY COMMUNICATIONS MANUAL
NOTE: PORT 1a CONNECTIONS WILL DEPEND ON THE
AVAILABLE PORTS ON THE BAS BEING USED. IF THE BAS CONTAINS A 4-WIRE RS485 PORT, SEE
DETAIL “A”. IF THE BAS CONTAINS ONLY A RS232 PORT, A
RS485-TO-RS232 CONVERTER WILL BE REQUIRED.
RXD TXD
GND
+(B)
-(A)
SHLD
TO C-MORE BOILERS CONTROLLED VIA RS485 NETWORK
BMS
JP11
JP12
RS232
XPC GATEWAY
PORT
1a
NET +
NET -
SHLD
TX
DTR
DCD
GND
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTE)
PORT
2
RX
RS485
T+
R-
R+
T-
SHIELD
4-WIRE RS485 PORT
DETAIL “A”
NOTE: PORT 2 CONNECTIONS AND JUMPER POSITIONS
WILL DEPEND ON THE AVAILABLE PORTS ON THE BAS BEING USED. SEE DETAIL “A”.
XPC GATEWAY
PORT
1a
NET +
NET -
SHLD
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTE)
PORT
2
SEE NOTE
JUMPERS
RS485-TO- RS232
CONVERTER
RXD TXD
GND
+(B)
-(A)
SHLD
TO C-MORE BOILERS CONTROLLED VIA RS485 NETWORK
BMS
JP11
JP12
RS232
RS485
2W
4W 232 Net + Net -
N/C N/C
Tx + Tx Tx - Rx
DTR
Rx - DCD
SIGNAL GROUND
Rx +
Port 2
DETAIL “A”
B+ A-
GND
RXD
TXD
GND
+12V
SEE CONVERTER
INSTRUCTIONS
(124958)
BMS CONNECTED TO XPC PORT 2
Figure 3-8. BMS Sample Network Diagrams (Sheet 1 of 2)
BMS CONNECTED TO XPC PORT 1a
Figure 3-8. BMS Sample Network Diagrams (Sheet 2 of 2)
54
GF-122 AERCO XPC GATEWAY
SENSORS & 4-20 mA
INTERLOCKS
& SETBACK
RS485
& RS232
AC POWER
RELAYS

3.3 INTERFACING THE XPC GATEWAY TO BMS II, MODEL 5R5-384

The BMS II (Model 5R5-384) contains an internal RS232 port which provides Modbus connections to the XPC Gateway. In addition, the BMS II contains an internal RS485 port which provides monitoring and control of the Boilers connected to the BMS II. These internal RS232 and RS485 ports are located on the terminal board behind the wiring compartment cover of the BMS II. These locations and connector pinouts for these ports are shown in Figures 3-9 and 3-10.
Figure 3-9. BMS II With Wiring Compartment Cover Removed
55
GATEWAY COMMUNICATIONS MANUAL
ISO
12V
RXD
TXD
232
ISOGND
485
ISOGND
485 A
485 B
RS232
RS485
JP5
JP6
EIA-485
EIA-232
2W
4W
Figure 3-10. BMS II RS232 & RS485 Pinout Assignments

3.3.1 BMS II Set-Up For Monitoring

XPC Gateway Port 2 is normally used to connect to the AERCO BMS, except when the monitoring BAS is utilizing a LonWorks SLTA, or is communicating via BACnet PTP. In this case, XPC Port 1a must be used to connect the BMS. Therefore, follow the appropriate wiring instructions in subsection 3.3.1.1 (Port
2) or 3.3.1.2 (Port 1a) as applicable.
3.3.1.1 BMS Wiring Connections to XPC Port 2
When the BAS being used is communicating via BACnet MS/TP, Johnson N2 or LonWorks without an SLTA, connect to XPC Port 2 as follows:
1. Position the XPC EIA-232/EIA-485 and 2W/4W jumpers to EIA-232 and 2W respectively as shown in Figure 3-11.
Figure 3-11. Port 2 Jumper Settings
2. Refer to Figures 3-9 and 3-10 to locate the internal RS232 connector inside the wiring area of the BMS II.
3. At the BMS II internal RS232 connector (JP5), refer to Figure 3-12 and connect the wire leads as follows:
(a) Connect the TXD terminal of the BMS RS232 connector to Rx terminal on XPC Port 2. (b) Connect the RXD terminal of the BMS RS232 connector to Tx terminal on XPC Port 2. (c) Connect the GND terminal of the BMS RS232 connector to SIGNAL GROUND terminal on XPC
Port 2.
(d) Add a jumper between the DTR and DCD terminals on the XPC Port 2. See Figure 1-3 (Detail B).
56
GF-122 AERCO XPC GATEWAY
2W 4W 232 Net + Net -
N/C
N/C
Tx +
Tx
Tx - Rx
DTR
Rx -
DCD
SIGNAL
GROUND
Rx +
Port 2
R
E
D
BL
UE
G
R
E
E
N
(
G
N
D
)
RE
D
B
L
U
E
G
R
EE
N
(
G
N
D
)
XPC GATEWAY
BMS II
JUMPER
232
ISO GND
TXD RXD
ISO 12V
JP5
Figure 3-12. Port 2 Wiring Connections for BMS
4. At the XPC Gateway, ensure that DIP switch 3 is set to the OFF (right) position.
3.3.1.2 BMS II Wiring Connections to XPC Port 1a
When the BAS being used is communicating via LonWorks with an SLTA, or BACnet PTP, an RS485-to­RS232 converter will be required to connect the BMS to Port 1a of the XPC.
1. Refer to Figures 3-9 and 3-10 to locate the internal RS232 connector JP5 inside the wiring area of the BMS.
2. If the AERCO RS232-to-RS485 Converter (part no. 124942) is used, the RS232 side of the converter contains a connector that plugs directly into header connector JP5 in the BMS II. However, If a third party converter is used, connect the RS232 receive (RxD) and transmit (TxD) wire leads to the internal RS232 connector (JP5) as shown in Figure 3-13. DO NOT connect the wire shield on this side of the converter.
NOTE
If a third-party RS232-to-RS485 Converter is used, consult the manufacturer’s instruction manual for signal polarity.
3. At the RS485 side of the converter (Figure 3-13), connect the wire leads as follows: (a) Connect the TD B (+) terminal to the Net + terminal on XPC Port 1a. (b) Connect the TD A (-) terminal to the Net - terminal on XPC Port 1a. (c) Connect the GND terminal to the Shield terminal on XPC Port 1a.
57
GATEWAY COMMUNICATIONS MANUAL
Net + Net -
Shield
PORT 1a
XPC GATEWAY
RS232-TO-RS485
CONVERTER
TXD
RXD
GND
GND
B (+)
A
(-)
RED (+)
BLUE (-)
GREEN (GND)
RED
ORANGE
IMPORTANT
CHECK INPUT & OUTPUT
POLARITY ON CONVERTER
BEING USED
BMS
RS232 RS485
232
ISO GND
TXD
RXD
ISO 12V
JP5
+12V
GND
Figure 3-13. Port 1a Wiring Connections for BMS
NOTE
A BMS II option is available with a built-in RS485-to-232 Converter (part no,
124943).
4. On the right side of the XPC Gateway Module, check to ensure that DIP switches 3 and 4 are set to the ON (left) position.
3.3.1.3 Configuring the BMS II
Once the BMS II has been wired to the Gateway as described in subsection 3.3.1.1 or 3.3.1.2, turn on power to the BMS II and perform the following configuration settings:
NOTE
Refer to AERCO Instruction Manual GF-124 for additional information on BMS II keypad functions and displays.
1. Press the MENU key and go to the SETUP MENU.
2. Press the ▲ arrow key. ENT ER PASSWORD will be displayed requesting the valid password to be entered.
3. Using the ▲ and ▼ arrow keys, enter the valid level 1 password (159) and then press the ENTER key. LEVEL 1 PASSWORD will be displayed.
4. Press the MENU key again. RS232 MENU is displayed.
5. Press the ▲ arrow key. RS232 MODE appears in the first line of the display.
6. If MODBU S SLAVE is not toggle the display to MODBUS SLAVE. Press the ENTER key to store the setting.
displayed in the second line of the display, press the CHANGE key and
7. While still in the RS232 MENU, press the ▲ arrow key. RS232 BAUDRATE is displayed in the first line of the display.
8. If 9600 i s not using the ▲ or ▼ arrow key. Press the ENTER key to store the 9600 Baud Rate.
displayed in the second line of the display, press the CHANGE key and select 9600
58
GF-122 AERCO XPC GATEWAY
9. Press the ▲ arrow key again. MODBUS ADDRESS appears in the first line of the display.
10. Press the CHANGE key and select the desired Modbus address for the BMS II using the ▲ and arrow keys. Press the ENTER key to store the selected address.
11. This completes the required configuration setup for the BMS II.
Refer to subsection 2.3 to connect the required C-More Controllers in a “daisy chain” configuration. Also, refer to the sample network wiring diagram in Figure 2-9. Do not proceed to the next step until all required AERCO equipment is connected.
Turn On the BMS II and all of the C-More Controllers.
Apply 24 VAC power to the XPC Gateway.
Following preliminary power-up checks, the XPC Gateway will begin to read BMS II data and allow it to be controlled by the BAS Master.

3.3.2 C-More Boilers Being Network-Controlled by a BMS II

When the BMS II is controlling C-More Boilers on the RS485 Modbus network it is the single “Master” device. No other device, such as the XPC Gateway or a BAS can assume control of the network. However, the BMS II also functions as a communications Gateway which permits a BAS to monitor the BMS II as well as the boilers on the Modbus network. This is accomplished utilizing the RS232 port of the BMS II.
If the BAS being utilized supports Modbus RTU protocol, it can be connected to the BMS II either directly or via a RS485-to-RS232 converter. However, if the BAS does not support Modbus protocol and utilizes BACnet, N2 or LonWorks, the AERCO XPC Gateway must be used as described below.
1. Make the connections between the BMS II and XPC Gateway as instructed in subsections 3.3.1.1 or
3.3.1.2.
2. Set up the C-More Boiler Controllers as described in Section 2, subsections 2.3 through 2.5.1.
3. Connect the C-More Boiler Controllers in a “Daisy-Chain” configuration.
4. Refer to Figure 3-14 and connect the RS485 COMM terminals of the first RS485 connector JP6 as follows:
(a) Connect the RS485 COMM + terminal to the 485 B terminal of JP6 in the BMS II. (b) Connect the RS485 COMM - termin al to the 485 A terminal of JP6 in the BMS II. (c) On the BMS II, connect the shield to SHLD terminal no. 3 NOT
the BMS II RS485 connector (JP6).
NOTE
Be sure to activate the termination and bias resistors by setting the DIP switches on the last C-More when connected to the BMS II.
C-More Boiler to the BMS II
to the 485 ISOGND terminal of
59
GATEWAY COMMUNICATIONS MANUAL
+
G
-
TERMINATE SHIELD
AT BMS II ONLY
C-MORE I/O BOX
RS485 COMM
FIRST UNIT
S
H
I
E
L
D
TIE TOGETHER WITH
SHIELDS OF OTHER
C-MORE UNITS
R
E
D
(
+
)
B
L
U
E
(
-
)
R
E
D
(
+
)
B
L
U
E
(
-
)
SHLD
(JP7, TERM. #3)
485 A
485 B
ISO GND
BMS II RS485 (JP6)
Figure 3-14. BMS II Connecti ons to C-More Controller
NOTE
Refer to AERCO Instruction Manual GF-124 for additional information on BMS II keypad functions, displays and password entries.
5. With the BMS II in the RS232 MENU, scroll to the MODBUS PASS THRU menu option.
6. If ENABLED is not
displayed in the second line of the display, press the CHANGE key and toggl e the
display to ENABLED using the ▲ or ▼ arrow key. Press the ENTER key to store the setting.
7. With MODBUS PASS THRU set to ENABLED, both the BMS II and the boilers can now be monitored.
NOTE
The Gateway Response Time for Modbus must be adjusted to 2 seconds in order for the communication to work efficiently. This is due to the extra lag in communications to the boiler when going through the BMS II. Since the BMS II control operations take priority, it may delay the processing of a Gateway command by a second or two depending on what it is doing at the moment.

3.3.3 Modulex Boilers Being Network-Controlled by a BMS II

When the BMS II is controlling C-More Boilers on the RS485 Modbus network it is the single “Master” device. No other device, such as the XPC Gateway or a BAS can assume control of the network. However, the BMS II also functions as a communications Gateway which permits a BAS to monitor the BMS II as well as the boilers on the Modbus network. This is accomplished utilizing the RS232 port of the BMS II.
If the BAS being utilized supports Modbus RTU protocol, it can be connected to the BMS II either directly or via a RS485-to-RS232 converter. However, if the BAS does not support Modbus protocol and utilizes BACnet, N2 or LonWorks, the AERCO XPC Gateway must be used as described below.
60
GF-122 AERCO XPC GATEWAY
1. Make the connections between the BMS II and XPC Gateway as instructed in subsections 3.3.1.1 or
3.3.1.2.
2. Refer to Figure 3-15 and make connections between Boiler Control Module (BCM) of the Modulex Boiler as follows:
(a) Connect terminal 1 of BCM connector Y2 to the 485 B terminal on the BMS II RS485 connector
JP6.
(b) Connect terminal 2 of BCM connector Y2 to the 485 A terminal on the BMS II RS485 connector
JP6.
(c) Terminate the shield at the BMS SHLD terminal no. 3 (JP7).
3. Connect the BCM Controllers in a “Daisy-Chain” configuration. Tie all shields together between the BCMs on the network.
4. On the last BCM module in the daisy chain connect the termination jumper.
5. On the BMS II, activate the 2 bias DIP switches by pushing them both down (towards the PCB).

3.3.4 BMS II Setup For Remote Setpoint Control From The XPC Gateway

For remote setpoint control of a BMS II, set up the wiring connections as described in subsection 3.3.1. Upon completion of all wiring connections, configure the BMS II as follows:
NOTE
Refer to AERCO Instruction Manual GF-124 for additional information on BMS II keypad functions and displays.
1. Press the MENU key and go to the SETUP MENU.
2. Press the ▲ arrow key. ENTER PASSWORD will be displayed requesting the valid password to be entered.
3. Using the ▲ and ▼ arrow keys, enter the valid level 1 password (159) and then press the ENTER key. LEVEL 1 PASSWORD will be displayed.
4. Press the MENU key and go to the FIELD ADJUST MENU.
5. Using the ▲ or ▼ arrow key, go to the HEADER SET MODE option.
6. If REMOTE SETPOINT is not select REMOTE SETPOINT using the ▲ or ▼ arrow key. Press the ENTER key to store the selection.
7. Next, press the ▲ arrow key and go to the REMOTE SIGNAL option.
8. If MODBUS is not display to MODBUS. Press the ENTER key to store the selection.
The BMS II is now set up for Remote Setpoint control from a XPC Gateway. In the event of control signal interruption from the XPX, AERCO recommends that the FAIL SAFE MODE option in the
CONFIGURATION MENU be set to CONSTANT SETPOINT with the INTERNAL SETPT (FIELD ADJUST MENU) set to the desired temperature.
displayed in the second line of the display, press the CHANGE key and toggle the
displayed in the second line of the display, press the CHANGE key and
61
GATEWAY COMMUNICATIONS MANUAL
NOTE
Sample network diagrams showing the BMS II connected to Port 2 and Port 1a of the AERCO XPC Gateway are provided in Figure 3-15. These samples are intended for reference purposes only and do not depict all possible network scenarios.
62
GF-122 AERCO XPC GATEWAY
NOTE: PORT 1a CONNECTIONS WILL DEPEND ON THE
AVAILABLE PORTS ON THE BAS BEING USED. IF THE BAS CONTAINS A 4-WIRE RS485 PORT, SEE
DETAIL “A”. IF THE BAS CONTAINS ONLY A RS232 PORT, A
RS485-TO-RS232 CONVERTER WILL BE REQUIRED.
RXD TXD
GND
+(B)
-(A)
SHLD
TO C-MORE OR MODULEX BOILERS CONTROLLED VIA RS485 NETWORK
BMS II
JP6
JP5
RS232
XPC GATEWAY
PORT
1a
NET +
NET -
SHLD
TX
DTR DCD GND
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTE)
PORT
2
RX
RS485
T+
R-
R+
T-
SHIELD
4-WIRE RS485 PORT
DETAIL “A”
NOTE: PORT 2 CONNECTIONS AND JUMPER POSITIONS
WILL DEPEND ON THE AVAILABLE PORTS ON THE BAS BEING USED. SEE DETAIL “A”.
XPC GATEWAY
PORT
1a
NET +
NET ­SHLD
EIA-232
EIA-485
2W
4W
TO BAS
(SEE NOTE)
PORT
2
SEE NOTE
JUMPERS
RS485-TO- RS232
CONVERTER
RS232
RS485
2W
4W 232
Net +
Net -
N/C N/C
Tx +
Tx
Tx -
Rx
DTR
Rx - DCD
SIGNAL GROUND
Rx +
Port 2
DETAIL “A”
B+ A-
GND
RXD
TXD
GND
RXD TXD
GND
+(B)
-(A)
SHLD
TO C-MORE OR MODULEX BOILERS CONTROLLED VIA RS485 NETWORK
BMS II
JP6
JP5
JP7
+12V
ISO 12V
ISO GND
BMS II CONNECTED TO XPC PORT 2
BMS II CONNECTED TO XPC PORT 1a
63
Figure 3-15. BMS II Sample Network Diagrams
GATEWAY COMMUNICATIONS MANUAL
SECTION 4 AERCO XPC GATEWAY TO BCM
CONTROLLED MODULEX BOILERS

4.1 CONNECTION AND SET-UP OF BOILER COMMUNICATIONS MODULES (BCMS)

The BCM is used to provide Modbus (RS485) connectivity for AERCO Modulex Series Boilers. When equipped with BCMs, the Modulex Boilers can be monitored and/or controlled by a BAS via the AERCO XPC Gateway. Modbus (RS485) connections are made at BCM connector Y2. Proceed as follows to access the BCM wiring connections:
1. Disconnect all power from the Modulex Boiler.
2. Remove the top and front covers from the Modulex Boiler to provide access to the BCM.
3. Refer to Figure 4-1 and locate the BCM switches on the front of the unit.
4. Remove the four screws securing the BCM mounting bracket and separate the bracket from the back of the panel to provide access to the BCM connectors.
5. Locate the Modbus wiring connections on BCM connector Y2 (Figure 4-2).
6. Proceed to subsection 4.2 and wire the BCM to the appropriate XPC port connector for the application being used.
Figure 4-1. Modulex Boiler With BCM
64
GF-122 AERCO XPC GATEWAY
7 6 5 4 3 2 1
Y2
Y2
Y3
Y4
Y1
SW1
A1
I 0
MODBUS A (-)
MODBUS B (+)
BCM FRONT VIEW
EIA-485
EIA-232
2W
4W

4.2 BCM WIRING CONNECTIONS TO AERCO XPC GATEWAY

XPC Port 2 is normally used to connect to AERCO equipment, except when the controlling BAS is utilizing a LonWorks SLTA module, or communicating via BACnet PTP. In this case, Port 1a of the XPC must be used to connect AERCO equipment. Therefore, follow the appropriate wiring instructions in subsection 4.2.1 (Port 2) or 4.2.2 (Port 1a) as applicable.

4.2.1 BCM Wiring Connections to XPC Port 2

When the controlling BAS is utilizing BACnet MS/TP, Johnson N2 or LonWorks protocol without an SLTA, use XPC Port 2 as follows:
1. On the XPC Gateway, position the EIA-232/EIA-485 and 2W/4W jumpers to EIA-485 and 2W respectively as shown in Figure 4-3.
Figure 4-2. BCM Modbus (RS485) Connections
65
GATEWAY COMMUNICATIONS MANUAL
2 1
TERMINATE SHIELD
AT XPC ONLY
BCM
CONNECTOR Y2
FIRST UNIT
SH
I
E
L
D
TIE TOGETHER WITH
SHIELDS OF OTHER
C-MORE UNITS
R
E
D
(
+)
B
L
U
E
(
-
)
R
E
D
(
+)
B
L
UE
(
-
)
5
4
6
3
7
2W
4W 232 Net + Net ­N/C N/C
Tx +
Tx
Tx -
Rx
DTR
Rx - DCD
SIGNAL
GROUND
Rx +
Port 2
XPC GATEWAY
DAISY-CHAIN
TO OTHER UNITS
(+ TO +, - TO -)
RED (+)
BLUE (-)
Figure 4-3. Port 2 Jumper Settings
2. Connect BCM terminals Y2-1 and Y2-2 to XPC Port 2 (Figure 4-4) as follows: (a) Connect the Y2-1 (Modbus B +) terminal to the “NET +” terminal of Port 2 on the XPC (b) Connect the Y2-2 (Modbus A -) terminal to the “NET -” terminal of Port 2 on the XPC.
3. On the XPC Gateway, check to ensure that DIP switch 3 is set to the OFF position.

4.2.2 BCM Wiring Connections to XPC Port 1a

When the controlling BAS is connected to Port 2 and is using a LonWorks SLTA or communicating via BACnet PTP, connect the BCM to XPC Port 1a as follows:
1. Connect BCM terminals Y2-1 and Y2-2 to XPC Port 1a (Figure 4-5) as follows:
Figure 4-4. XPC Port 2 Connections to BCM
NOTE
The positions of the EIA-232/EIA-485 and 2W/4W jumpers will depend on the available ports on the controlling BAS being used.
(a) Connect the Y2-1 (Modbus B +) terminal to the “NET +” terminal of Port 1a on the XPC (b) Connect the Y2-2 (Modbus A -) terminal to the “NET -” terminal of Port 1a on the XPC.
66
GF-122 AERCO XPC GATEWAY
2 1
TERMINATE SHIELD
AT XPC ONLY
BCM
CONNECTOR Y2
FIRST UNIT
S
H
I
EL
D
TIE TOGETHER WITH
SHIELDS OF OTHER
BCM UNITS
R
E
D
(
+)
B
L
U
E
(
-
)
R
E
D
(
+
)
B
L
U
E
(
-
)
5
4
6
3
7
Net +
Net -
Shield
PORT 1a
XPC GATEWAY
DAISY-CHAIN
TO OTHER UNITS
(+ TO +, - TO -)
RED (+)
BLUE (-)
Figure 4-5. XPC Port 1a Connections to BCM
2. On the XPC Gateway, check to ensure that DIP switches 3 and 4 are set to ON.

4.3 CONFIGURING THE BCM CONTROLLER

Refer to AERCO manual GF-115-C, Section 7 and program a communication address between 1 and 4 for the standard XPC Gateway. Ensure that each BCM Controller on the network has its own distinct address. Contact AERCO if more than 4 BCM uni ts will be placed on the network or a different address range is required.
1. Set the communications baud rate to 9600.
2. This completes the required connections and settings and for the BCM.
3. Reattach the BCM mounting bracket to the front of the Modulex Boiler and replace all removed
Upon power-up, the Gateway should begin to read the BCM information after its preliminary checks.
panels.
67
GATEWAY COMMUNICATIONS MANUAL
SECTION 5 XPC GATEWAY TO
ECS CONTROLLED HOT WATER HEATERS

5.1 CONNECTION AND SET-UP OF ELECTRONIC CONTROL SYSTEM (ECS)

The AERCO Electronic Control System (ECS) used to control indirect fired water heaters can be connected to an RS485 Modbus network, when equipped with an optional Communications Board (AERCO part no. 64009). RS485 Modbus connections to the ECS are made on the rear of the Temperature Controller (Eurotherm 2408) contained in the Control Box. Proceed as follows to access the Temperature Controller wiring connections:
1. Disconnect power from the ECS Control Box.
2. Loosen the captive screw on the right-front portion of the Control Box (Figure 5-1) to open the hinged panel door.
PANEL DOOR
CAPTIVE SCREW
2408
RUNAUTO HOLD
MAN
TEMP CONTROLLER
B-PLUS
OVER TEMP SWITCH
TM
WATER HEATER
PT.NO.
PT.NO.
Figure 5-1. ECS Control Panel Front View
3. Next, open the door and loosen the captive screw at the top of the recessed panel (Figure 5-2). Swing down the recessed panel to access the rear wiring connections on the Temperature Controller (Figure 5-3).
68
GF-122 AERCO XPC GATEWAY
PANEL CAPTIVE
SCREW
B-PLUS
TM
PT.NO.
SET
F
AUTO
RUN
MAN HOLD
OP 1
OP 2
SP2
REM
2408
OVER TEMP SWITCH
TEMP CONTROLLER
PT.NO.
WATER HEATER
OVERTEMP SWITCH
2408 TEMPERATURE
CONTROLLER
PANEL REAR
Figure 5-2. Recessed Panel Behind Control Box Door
Figure 5-3. Control Box Swing-Down Panel Rear View (Steam-to-Water Unit)
69
GATEWAY COMMUNICATIONS MANUAL
1A
HA
1B
HB
1C
HC
2A 2B
1D
HE HF
HD
3B
3D
3C
2D 3A
2C
JD
JF
JE
JB JC
JA
LA LB LC AA AB AC
VI V+ V-
In1 In2
C
2408 CONTROLLER
L N
RS485 MODBUS CONNECTIONS
EIA-485
EIA-232
2W
4W
4. Refer to the Temperature Controller RS485 terminal connections shown in Figure 5-4.
Figure 5-4. Temperature Controller (Eurotherm 2408) Terminal Connections
5. Proceed to subsection 5.2 and wire the ECS to the appropriate XPC port connector for the application being used.

5.2 ECS WIRING CONNECTIONS TO AERCO XPC GATEWAY

XPC Port 2 is normally used to connect to AERCO equipment, except when the controlling BAS is utilizing a LonWorks SLTA module, or communicating via BACnet PTP. In this case, Port 1a of the XPC must be used to connect AERCO equipment. Therefore, follow the appropriate wiring instructions in subsection 5.2.1 (Port 2) or 5.2.2 (Port 1a) as applicable.
NOTE
Do not connect the termination resistors sent with the ECS. This will impede communication.

5.2.1 ECS Wiring Connections to XPC Port 2

When the controlling BAS is utilizing BACnet MS/TP, Johnson N2 or LonWorks protocol without an SLTA, use XPC Port 2 as follows:
1. Position the EIA-232/EIA-485 and 2W/4W jumpers to EIA-485 and 2W respectively as shown in Figure 5-5.
2. Connect ECS terminals HE and HF to XPC Port 2 (Figure 5-6) as follows:
Figure 5-5. Port 2 Jumper Settings
70
GF-122 AERCO XPC GATEWAY
2W 4W 232 Net + Net -
N/C N/C
Tx + Tx
Tx - Rx
DTR
Rx - DCD
SIGNAL
GROUND
Rx +
Port 2
PART OF
EUROTHERM 2408
REAR CONNECTOR
XPC GATEWAY
HD HE
HF
S
H
I
E
L
D
B
L
U
E
(
-
)
R
E
D (
+
)
S
H
I
E
LD
TIE TOGETHER WITH
SHIELDS OF OTHER
UNITS
DAISY-CHAIN
TO OTHER UNITS
(
+
TO
+, -
TO
-)
B
L
UE
(
-
)
R
E
D
(
+
)
RED (+)
BLUE (-)
PART OF
(a) Connect the “HF” termin al to the “NET +” terminal of Port 2 on the XPC (b) Connect the “HE” terminal to the “NET -” terminal of Port 2 on the XPC.
Figure 5-6. XPC Port 2 Connections to ECS Temperature Controller
3. On the XPC Gateway, check to ensure that DIP switch 3 is set to the OFF position.

5.2.2 ECS Wiring Connections to XPC Port 1a

When the controlling BAS is connected to Port 2 and is using a LonWorks SLTA or communicating via BACnet PTP, connect the ECS to XPC Port 1a as follows:
1. Connect ECS terminals HE and HF to XPC Port 1a (Figure 5-7) as follows: (a) Connect the “HF” termin al to the “NET +” terminal of Port 1a on the XPC (b) Connect the “HE” terminal to the “NET -” terminal of Port 1a on the XPC.
NOTE
The positions of the EIA-232/EIA-485 and 2W/4W jumpers will depend on the available ports on the controlling BAS being used.
EUROTHERM 2408
REAR CONNECTOR
HD
HE HF
DAISY-CHAIN
TO OTHER UNITS
+
TO +, - TO
(
BLUE (-)
)
+
(
D
E
R
RED (+)
BLUE (-)
D
L
E
I
SH
TIE TOGETHER WITH
SHIELDS OF OTHER
-)
UNITS
71
E
R
S
H
D
BLUE (-)
I
E
XPC GATEWAY
)
+
(
L
D
Net +
Net -
Shield
PORT 1a
GATEWAY COMMUNICATIONS MANUAL
Figure 5-7. XPC Port 1a Connections to ECS Temperature Controller
2. On the XPC Gateway, check to ensure that DIP switches 3 and 4 are set to ON.

5.3 CONFIGURING THE ECS CONTROLLER

Refer to Eurotherm Communications Handbook HA026230, Chapter 5 and program a communication address between 29 and 32 for the standard XPC Gateway. Ensure that each ECS Controller on the network has its own distinct address. Contact AERCO if more than 4 ECS units will be placed on the network or a different address range is required.
1. Set the communications baud rate to 9600.
2. This completes the required connections, settings and programming for the ECS.
3. Close the swing-down hinged panel of the Control Box and close the door.
4. Upon power-up, the Gateway should begin to read the ECS information after its preliminary checks.

5.4 CONFIGURING THE ECS CONTROLLER FOR REMOTE SETPOINT OPERATION

In addition to the instructions as indicated above in section 5.3 follow the steps below to configure the ECS Controller for remote setpoint operation via the XPC Gateway.
1. Page to “ACCS”.
2. Scroll and enter the code as 24.
3. Scroll and at the “GOTO” menu choose “Conf”.
4. At the “Conf” screen enter the code as 8.
5. Press the scroll button once and then the page button until you find “SP”
6. Scroll until you find “rmt” and set the parameter value to “SP”.
7. Press the page and scroll buttons at the same time to go to “exit”.
8. Press the up arrow to select “yes” and then the instrument will reboot.
9. Once the instrument has returned to its normal state, press the page button until you see “SP”.
10. Scroll until you see ”L-R” and using the up arrow select “rmt”.
11. Once you have selected “rmt” press the page and scroll buttons at the same time to return to the normal temp display.
12. You should now be able to control the setpoint remotely.
72
The AERCO XPC Gateway is manufactured by OE MCtrl. This
GF-122 AERCO XPC GATEWAY
AERCO XPC GATEWAY
INTEGRATION GUIDE
PART
II
Integration Guide contains information ext ract ed from
documentation developed by OEMCtrl.
73
GATEWAY COMMUNICATIONS MANUAL

SECTION 6 WHAT IS PA RT II OF THIS DOCUMENT ABOUT?

This document will enable you to integrate the XPC Gateway into a Building Automation System (BAS), which is communicating using one of the three standard protocols described below.
NOTE
It is assumed that the XPC translator has been configured by the factory and is functioning correctly. The factory should supply the site integrator with an object listing, which enables the integrator to gather information from the translator.

SECTION 7 PROTOCOL OVERVIEW

Protocols are the communication languages spoken by control devices. The main purpose of a protocol is to communicate information in the most efficient method possible. Different protocols exist to provide different kinds of information for different applications.
In the BAS application, many different protocols are used, depending on the manufacturer. More and more owners are demanding that their entire facilities be seamlessly linked together and presented to their support staff in one easy-to-use front end terminal display.
AERCO’s XPC translator has the ability to understand multiple protocols. So, no matter what company your customer chooses for the controls throughout their building, AERCO’s XPC translator will communicate with them without the added cost of programming a customized communications Gateway.

7.1 WHAT IS A PROTOCOL?

A set of formal rules describing how to transmit data, especially across a network
Low level protocols define
the electrical and physical standards to be observed bit-and-byte-ordering the transmission, error detection, and correction of the bit stream
High level protocols deal with data formatting, including
syntax of messages terminal-to-computer dialogue character sets the sequencing of messages, etc.
It is a language spoken between electronic devices For example: the protocol IP, which stands for Internet Protocol for two devices to communicate with each other, they must speak the same protocol or have a protocol translator.

7.2 WHY ARE THERE SO MANY PROTOCOLS?

74
GF-122 AERCO XPC GATEWAY
Because any two pieces of building automation equipment can vary with application, so can their communications protocol
To facilitate the communications between the various applications in a robust and efficient manner, protocols are designed with those specific applications in mind

7.3 WHY BUILD INTHE MOST WIDELY USED PROTOCOLS?

Manufacturers can now provide a translator with their units that can be seamlessly integrated into a BAS
For the building owner, it means upgrade and expansion costs will be competitive
Expensive Gateways are eliminated
Field selection of the protocol requires less up-front coordination, thus reducing manufacturing costs
Flexibility and simple configuration allows the customer to make future additions and changes
without additional costs
More opportunities for sales

7.4 WHAT DOES THE SITE INTEGRATOR NEED?

The building owner must supply the following information to the site integrator:
Protocol Conformance Statement (Refer to SECTION 16)
Unit-specific object listing (for LonWorks, an XIF file may be required.) See Application Note for file
generation
The site integrator then supplies the building owner with the:
Device address
Network baud rate
Network numbers (BACnet only)
The specific site settings are then applied to the translator using this information. Each protocol setting has a unique configuration. Refer to the section on Configuring Protocols.
75
GATEWAY COMMUNICATIONS MANUAL

SECTION 8 BACNET

BACnet, which stands for Building Automation and Controls network, is a protocol developed by ASHRAE. BACnet was developed as a response to industry concerns about increased networking of BAS components using proprietary communications methods. In the past, these proprietary communications severely limited the building owners' choices for system expansion, upgrade, and replacement. Every major controls vendor in North America, as well as academics, end users, consulting engineers, and government groups participated in its development.
BACnet has been accepted as an open standard by the American National Standards Institute (ANSI) and the European CEN standards. It is also being adopted as an international ISO standard.
BACnet is designed to include all building systems, lighting, security, fire, heating, ventilation, and air conditioning. Its purpose is to promote interoperability - sharing data between systems made by different vendors. It provides the necessary tools to develop a specification for systems that are to be interoperable. BACnet provides methods and standards for representing information, for requesting and interpreting information, as well as for transporting information.

SECTION 9 BACNET OVER ARC156

ARCnet is an embedded networking technology well suited for real-time control applications in both the industrial and commercial marketplaces. Its robust performance and the availability of low-cost silicon make it the network of choice in BASs.
ARC156 is a unique implementation of ARCnet. ARC156 is similar to master-slave / token passing (MS/TP). The main difference between the two is speed. ARC156 baud rate is 156K baud whereas MS/TP tops out at 76.8K baud.
Also, ARC156 uses a separate communications co-processor to handle the network traffic and a separate processor to handle the program execution. This provides faster processing of applications and handling of communications on the network. ARC156 is the standard communications method used by our translators.

9.1 CONFIGURING THE AERCO XPC FOR ARC156

1. Turn off the XPC's power.
2. Using the rotary switches, set the translator's address. Set the Tens (10's) switch to the tens digit of the address, and set the Ones (1's) switch to the ones digit.
EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the arrow
on the Ones (1's) switch to 1. See illustration below.
76
GF-122 AERCO XPC GATEWAY
3. Comm selector DIP Switches 1 - 8 are all OFF.
4. Port 1a is the only port that speaks BACnet over ARC156. Connect the communications wiring to Port
1a in the screw terminals labeled Net +, Net -, and Gnd. See the illustration below.
NOTE
USE THE SAME POLARITY THROUGHOUT THE NETWORK SEGMENT.
Wire specifications:
22 AWG, low-capacitance, twisted, stranded, shielded copper wire
2000 feet (609.60 meters) before needing a Repeater.
If the XPC is at either end of a network segment, connect a BT485 to the XPC.
5. Turn on the XPC's power.
6. Set the correct network number to the unique BACnet ARC156 network at the site.
77
GATEWAY COMMUNICATIONS MANUAL
Baud Rate
DIP Switch 1
DIP Switch 2
9600
Off
Off
38.4
On
Off
76.8
On
On

SECTION 10 BACNET MS/TP

BACnet Master Slave/Token Passing or MS/TP is used for communicating BACnet over a sub-network of BACnet-only translators. Each translator on the network has the ability to hear the broadcast of any other device on the network. The speed of an MS/TP network ranges from 9600 baud to 76.8K baud.

10.1 CONFIGURING THE AERCO XPC FOR BACNET MS/TP

1. Turn off the XPC's power.
2. Using the rotary switches, set the translator's address. Set the Tens (10's) switch to the tens digit of
the address, and set the Ones (1's) switch to the ones digit.
EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the arrow on the Ones (1's) switch to 1.
3. Set the Comm Selector DIP Switches 1 - 8 for baud rate, port number, wiring, and protocol.
Set the Comm Selector DIP Switches 1 and 2 for the appropriate communications speed (9600,
19.2k, 38.4k, or 76.8k bps).
NOTE
USE THE SAME BAUD RATE FOR ALL DEVICES ON THE NETWORK SEGMENT.
19.2 Off On
Set Comm Selector DIP Switch 3 to OFF for BAS Port 1.
Set Comm Selector DIP Switch 4 to ON for EIA-485 2-wire.
Set Comm Selector DIP Switches 5 - 8 OFF for MS/TP (m).
78
GF-122 AERCO XPC GATEWAY
The following example shows the DIP Switches set for 38.4k, Port 1, and MS/TP (m).
NOTE
MS/TP (M) IS RECOMMENDED.
4. Connect the communications wiring to Port 1a. Connect to Net+, Net-, and Gnd.
Wire specifications
A dedicated 22 AWG to 18 AWG twisted pair wire (EIA 485)
2000 feet (610 meters) for 76.8 kbps
Devices should be daisy chained and not star wired.
If the XPC is at either end of a network segment, connect a BT485 to the XPC.
NOTE
USE THE SAME POLARITY THROUGHOUT THE NETWORK SEGMENT.
5. Turn on the power for the XPC by connecting power terminals .
6. Set the correct network number to the unique BACnet MS/TP network at the site.
79
GATEWAY COMMUNICATIONS MANUAL
Baud Rate
DIP Switch 1
DIP Switch 2
9600
Off
Off
38.4
On
Off
76.8
On
On

SECTION 11 BACNET PTP

PTP is used to connect two distinct BACnet networks so that information can be shared between the networks. PTP uses an EIA-232 connection between two BACnet half-routers. This connection allows for two different BACnet networks to speak to each other, even at different baud rates.

11.1 CONFIGURING THE AERCO XPC FOR BACNET PTP

1. Turn off the XPC's power.
2. Using the rotary switches, set the translator's address. Set the Tens (10's) switch to the tens digit of
the address, and set the Ones (1's) switch to the ones digit.
EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the arrow on the Ones (1's) switch to 1.
3. Set the Comm Selector DIP Switches 1 - 8 for baud rate, port number, wiring, and protocol:
Set the Comm Selector DIP Switches 1 and 2 for the appropriate communications speed (9600,
19.2k, 38.4k, or 76.8k bps).
NOTE
USE THE SAME BAUD RATE FOR ALL DEVICES ON THE NETWORK SEGMENT.
19.2 Off On
Set Comm Selector DIP Switch 3 to ON for Port 2.
Set Comm Selector DIP Switch 4 (Port 1) will be set by the manufacturer.
Set Comm Selector DIP Switch 5 - 8 for BACnet PTP.
The following example shows the DIP Switches set for 38.4k, Port 2, and BACnet PTP.
80
4. Connect the communications wiring to Port 2.
EIA-232, 2-wire
Connect to Tx, Rx, DTR, DCD, and Gnd using three wire termination with pins 3 and 4 jumpered. Wiring must go plus-to-minus and minus-to-plus, Gnd-to-Gnd.
GF-122 AERCO XPC GATEWAY
Wire Specifications:
18–28 AWG; twisted pair preferable
50 feet (15.24 meters) maximum length
DO NOT POWER THE DEVICE FROM THE SAME TRANSFORMER THAT POWERS THE XPC.
NOTE
81
GATEWAY COMMUNICATIONS MANUAL
Modem (25-pin)
Null Modem
S2-DB9
Device
5. See table below to wire the XPC to a modem.
Null Modem Cable
Cable (9-pin)
(9-pin)
TX - pin 2 TX - pin 3 TX - pin 3 TX - pin 1 RX - pin 3 RX - pin 2 RX - pin 2 RX - pin 2 DTR - pin 20 DTR - pin 4 DTR - pin 4 DTR - pin 3 DCD - pin 8 DCD - pin 1 DCD – pin 1 DCD - pin 4 GND - pin 7 GND - pin 5 GND - pin 5 GND - pin 5
Set the following DIP switch settings on the modem:
NOTE
A US ROBOTICS EXTERNAL MODEM IS HIGHLY RECOMMENDED.
(5 pin)
6. Turn on the XPC's power.

SECTION 12 JOHNSON CONTROLS (N2)

N2 is not a standard protocol, but one that was created by Johnson Controls, Inc. that has been made open and available to the public. Johnson Controls is the only company to use the N2 Bus protocol as their standard network protocol. Because it is open and still prevalent within the industry, N2 is a standard offering for our XPC translators.

12.1 CONFIGURING THE AERCO XPC FOR N2 FOR PORT 1A

1. Turn off the XPC's power.
2. Using the rotary switches, set the translator's address. Set the Tens (10's) switch to the tens digit of
the address, and set the Ones (1's) switch to the ones digit. EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the
arrow on the Ones (1's) switch to 1. See illustration below.
82
GF-122 AERCO XPC GATEWAY
.
3. Set the Comm Selector DIP Switches 1 - 8 for baud rate, port number, wiring, and protocol:
Set the Comm Selector DIP Switches 1 and 2 for 9600 bps.
NOTE
USE THE SAME BAUD RATE FOR ALL DEVICES ON THE NETWORK SEGMENT.
Set Comm Selector DIP Switch 3 to OFF for BAS Port 1.
Set Comm Selector DIP Switch 4 to ON for EIA-485 2-wire.
Set the Comm Selector DIP Switches 5 through 8 for N2.
The following example shows the DIP Switches set for 9600 baud, Port 1a, and N2.
4. Connect the communications wiring to Port 1a. Connect to Net+, Net-, and Gnd.
83
GATEWAY COMMUNICATIONS MANUAL
Wire specifications:
A dedicated 22 AWG to 18 AWG twisted pair wire (EIA 485)
2000 feet (610 meters) for 76.8 kbps, or
3000 feet (914.4 meters) for 9600 bps, 19.2 kbps, or 38.4 kbps, before needing a Repeater.
Devices should be daisy chained and not star wired.
If the XPC is at either end of a network segment, connect a BT485 to the XPC
NOTE
USE THE SAME POLARITY THROUGHOUT THE NETWORK SEGMENT.
5. Turn on the XPC's power.

SECTION 13 LONWORKS

LonWorks is an open protocol that was originally developed by Echelon Corporation. It is now maintained by Echelon in collaboration with members of the LonMark Interoperability Association. It requires the use of Echelon’s Neuron microprocessor to encode and decode the LonWorks packets.
The LonWorks protocol is based on the concept of using standardized functional profiles to control similar pieces of equipment. The AERCO XPC is a LonWorks compatible device, but is not a LonMark device. A LonMark device has been thoroughly tested by Echelon (LonMark.org) and has been given the LonMark logo indicating compliance with the LonWorks profile specification. All LonMark devices require the use of proprietary hardware manufactured by Echelon Corp. In order to reduce the cost of adding that hardware on every module, the data packets are formatted in the manner specified by the LonWorks documentation and subsequently handed off to the LonWorks Option Card.

13.1 CONFIGURING THE AERCO XPC FOR LONTALK VIA SLTA-10

1. Turn off the XPC's power.
2. Using the rotary switches, set the translator's address. Set the Tens (10's) switch to the tens digit of
the address, and set the Ones (1's) switch to the ones digit.
EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the arrow on the Ones (1's) switch to 1.
84
GF-122 AERCO XPC GATEWAY
Baud Rate
DIP Switch 1
DIP Switch 2
9600
Off
Off
19.2
Off
On
38.4
On
Off
3. Set the Comm Selector DIP Switches 1 - 8 for baud rate, port number, wiring, and protocol:
Set the Comm Selector DIP Switches 1 and 2 for the appropriate communications speed (9600,
19.2k, 38.4k, or 76.8k bps).
USE THE SAME BAUD RATE FOR ALL DEVICES ON THE NETWORK SEGMENT.
NOTE
76.8 On On
Set Comm Selector DIP Switch 3 to ON for Port 2.
Set Comm Selector DIP Switch 4 (Port 1) will be set by the manufacturer.
Set Comm Selector DIP Switch 5 - 8 for LonWorks SLTA. The following example shows the DIP
Switches set for 38.4k, Port 2, and LonWorks SLTA.
85
GATEWAY COMMUNICATIONS MANUAL
4. Connect the communications wiring to Port 2.
Wire Specifications:
18–28 AWG; twisted pair preferable
50 feet (15.24 meters) maximum length
NOTE
Do not power the device from the same transformer that powers the XPC.
5. Set the following SLTA-10 DIP Switch settings.
6. Turn on the XPC's power.

13.2 CONFIGURING THE AERCO XPC FOR LONWORKS OPTION CARD

1. Turn off the XPC's power.
2. Using the rotary switches, set a unique address. Set the Tens (10's) switch to the tens digit of the
address, and set the Ones (1's) switch to the ones digit. EXAMPLE: If the translator’s address is 01, point the arrow on the Tens (10's) switch to 0 and the
arrow on the Ones (1's) switch to 1.
3. Set the Comm Selector DIP Switches 1 - 8 to ON, OFF, OFF, ON, OFF, ON, ON, ON exactly as shown in step 4 below. The baud rate must be 38.4 K for the LonWorks Option card to work.
86
GF-122 AERCO XPC GATEWAY
Set the Communication mode for Port 1 using DIP Switch 4.
NOTE
When using Port 1b with the LonWorks Option Card, Port 1a cannot be used.
4. Set the Comm Selector DIP Switches 5 through 8 for LonWorks Option Card. The following example
shows the DIP Switches set for 38.4k baud, Port 1b, and LonWorks Option Card.
5. Connect LON Port to the LonWorks Option Card with the supplied ribbon cable.
NOTE
LonWorks Option Card must be OFF before being connected.
6. Set the Communications Selection jumpers to EIA-485 2-wire.
7. Turn on the XPC's power.
87
GATEWAY COMMUNICATIONS MANUAL

SECTION 14 TROUBLESHOOTING

14.1 MOST COMMON COMMUNICATION PROBLEMS

The following are some communication problems that are common to all protocols.

14.1.1 No Receive LED Indication

This means that no AERCO equipment is seen by the XPC. Check the configuration and wiring.

14.1.2 Wiring termination

If wiring an EIA-485 connection, the wire is terminated plus (+) to plus (+) and minus (-) to minus (-). If the receive LED is solid, this means you have the connection incorrectly terminated.
If the wiring is an EIA-232 connection, the wire must connect TX to RX. The GND must be connected to GND. The termination resistor may be wrong. Remove it temporarily.

14.1.3 Jumper selection

Make sure the jumper for the communication port is set to the communication networks wiring type EIA-485 or EIA-232.

14.1.4 Dipswitch selection

Make sure the correct protocol is chosen. Switches 5, 6, 7, & 8. Make sure the correct baud rate is chosen. Switches 1 & 2.
NOTE
These settings are defined at translator start-up. Power must be cycled to make a settings change.

14.1.5 Addressing

The rotary address switches define the translator’s individuality on the network. Each device must have a unique address.

14.2 BACNET OVER ARC156

Verify BAS and controller settings:
1. Communication Selection jumper is set to BACnet over ARC156
2. BAS configured to speak 2—wire EIA--485 to the translator.
3. Rotary address switches set for the controller’s unique slave address.
4. Proper connection wiring.
5. BAS reading or writing to the proper BACnet objects in the translator - download the latest points list
for the translator to verify.
6. BAS is sending requests to the proper ARC156 MAC address of the controller.
7. Confirm the correct BACnet network number.
8. Present the BAS company with a copy of your translator’s BACnet PICS so that they know which
BACnet commands are supported.
88
GF-122 AERCO XPC GATEWAY
NOTE

14.3 BACNET MS/TP

1. Both set to speak BACnet MS/TP.
Comm Selector DIP switches 5, 6, 7, and 8
Both set to speak BACnet MS/TP.
2. Both set for the same baud rate.
Comm Selector DIP Switches 1 and 2
Verify by obtaining a Modstat
3. BAS configured to speak 2—wire EIA--485 to the translator.
4. Both set to 8 data bits, No Parity, and 1 stop bit.
5. Rotary address switches set for the translator’s unique slave address.
6. Proper connection wiring.
7. BAS reading or writing to the proper BACnet objects in the translator - download the latest points list for the translator to verify.
8. BAS is sending requests to the proper MS/TP MAC address of the translator.
9. Present the BAS company with a copy of your translator's BACnet PICS so that they know which BACnet commands are supported.
It may be necessary to adjust the following two MS/TP Protocol timing settings.
1. Max Masters - defines the highest MS/TP Master MAC address on the MS/TP network.
For example, if there are 3 master nodes on an MS/TP network, and their MAC addresses are 1, 8, and 16, then Max Masters would be set to 16 (since this is the highest MS/TP MAC address on the network).
This property optimizes MS/TP network communications by preventing token passes and “poll for master” requests to non—existent Master nodes
In the above example, MAC address 16 would know to pass the token back to MAC address 1 instead of counting up to MAC address 127). Each MS/TP master node on the network must have their Max Masters set to this same value. The default is 127.
2. MaxInfo Frames
receives the token. Any positive integer is a valid number. The default is 10 and should be ideal for the majority of applications. In cases where the translator is the target of many requests, this number could be increased as high as 100 or 200.
It should be noted that:
See SECTION 16 for the BACnet Protocol Conformance Statement.
- defines the maximum number of responses that will be sent when the translator
MS/TP networks can be comprised of both Master and Slave nodes. Valid MAC addresses for Master nodes are 0 – 127 and valid addresses for Slave nodes are 0 -- 254.
See Protocol Maps in SECTION 29.
89
GATEWAY COMMUNICATIONS MANUAL
If the integrator attempts to communicate to the translator but does not get a response, make sure
the translator is set as a BACnet MS/TP (m) master. The BACnet software asks the translators, “Who Is?” This is to auto-locate devices on the network. Only translators set as masters will answer this request.
See SECTION 16 for the BACnet Protocol Conformance Statement.

14.4 BACNET PTP

Verify BAS and translator settings:
1. Both set to speak BACnet PTP.
Comm Selector DIP switches 5, 6, 7, and 8
By getting a Modstat of the translator through the BACview. Hit the “FN” key and the ’.’ key at the
same time. Scroll to the bottom of the page to the section entitled “Network Communications” to view the active protocol and baud rate.
2. Both set for the same baud rate.
Comm Selector DIP Switches 1 and 2
Verify via the BACview by obtaining a Modstat
3. BAS configured to speak 2—wire EIA--485 to the translator.
4. Both set to 8 data bits, No Parity, and 1 stop bit.
5. Rotary address switches set for the translator’s unique slave address.
6. Proper connection wiring.
7. BAS reading or writing to the proper BACnet objects in the translator - download the latest points list for the translator to verify.
8. BAS is sending requests to the proper BACnet device instance of the translator.
9. Present the BAS company with a copy of your translator's BACnet PICS so that they know which BACnet commands are supported.
See SECTION 16 for the BACnet Protocol Conformance Statement

14.5 N2

Verify BAS and translator settings:
1. Both set to speak N2.
Comm Selector DIP Switches 3, 4, 5, and 6
By getting a Modstat of the translator through the BACview. Hit the “FN” key and the ’.’ key at the
same time. Scroll to the bottom of the page to the section entitled “Network Communications” to view the active protocol and baud rate.
2. Both set for 9600 baud rate.
Comm Selector DIP Switches 1 and 2
Verify via the BACview by obtaining a Modstat
3. BAS configured to speak 2—wire EIA--485 to the translator.
4. Both set to 8 data bits, No Parity, and 1 stop bit.
90
GF-122 AERCO XPC GATEWAY
5. Rotary address switches set for the translator’s unique slave address.
6. Proper connection wiring.
7. BAS reading or writing to the proper network point addresses in the translator - download the latest points list for the translator to verify.
8. BAS is sending requests to the proper slave address of the translator.
See SECTION 19 for the N2 Protocol Conformance Statement

14.6 LONWORKS

Verify BAS and translator settings:
1. Both set to speak LonWorks protocol.
Comm Selector DIP Switches 3, 4, 5, and 6
By getting a Modstat of the translator through the BACview. Hit the “FN” key and the ’.’ key at the
same time. Scroll to the bottom of the page to the section entitled “Network Communications” to view the active protocol and baud rate.
2. Both set for 9600 baud rate.
Comm Selector DIP Switches 1 and 2
Verify via the BACview by obtaining a Modstat
3. Configure BAS to speak 2—wire EIA--485 to the SLTA or LonWorks Plug-in.
4. Proper connection wiring.
5. BAS reading or writing to the proper network point addresses in the translator - download the latest points list for the translator to verify.
6. BAS is sending requests to the proper slave address of the translator from the SLTA-10 or LonWorks Plug-in card.
See SECTION 20 for the LonWorks Protocol Conformance Statement

14.7 COMMISSIONING THE XPC FOR LONWORKS

Before a device can participate on a LonWorks network, it must be commissioned. Commissioning allows the system integrator to associate the device hardware with the LonWorks system’s network layout diagram. This is done using the device’s unique Neuron ID. Together, the XPC and its LonWorks Option Card serve as a single LonWorks device or node. The LonWorks Option Card’s internal Neuron chip provides a unique Neuron ID.
A network management tool such as Echelon’s LonMaker is used to commission each device, as well as, to assign addressing. Specific instructions regarding the commissioning of LonWorks devices should be obtained from documentation supplied with the LonWorks network management tool.
91
GATEWAY COMMUNICATIONS MANUAL
When a new device is first commissioned onto the LonWorks network, the system integrator must upload the device’s External Interface File (XIF) information. LonWorks uses the XIF to determine the points (network variables) that are available from a device. A typical LonWorks device has a set of predefined network variables. These are the variables bound or accessed by the network management tool.
NOTE
The network variables defined on the XPC Network Variables Property pages determine its XIF information. If any information is changed, added, or deleted on the Network Variable Property pages, the XPC must be removed from the network management tool’s database and recommissioned, including uploading the XIF information again.
There are some issues with LonWorks that should be considered when using the XPC: Device Configuration Information (XIF)
When members of the object cache are modified, you must modify the device configuration
information (XIF) from that originally imported into the LonWorks network management tool. The new information will not be recognized by the network management tool until it is imported again from the XPC.
The user must first undefine all of the network variable bindings and the device,
recommission the device, and establish the network variable bindings again.
Modifications to the object cache should be avoided once the device is fully commissioned
and operational. Any modifications to the addressing schemes should also be avoided once the XPC is commissioned.
Address parameters
If the address parameters are modified, the LonWorks Option Card will be set to Node Offline,
and Unconfigured, which means it no longer communicates with the LonWorks network.
This does not require deletion or importing the device configuration information again but
does require the device to be recommissioned by the network management tool.
Point configuration
When the XPC is first commissioned onto the LonWorks network, the system integrator
should use the Browse features of the network management tool to check the data that is available from the module.
Any changes in point count and point configuration should be made prior to performing any
further system integration.
XPC may be deleted and re-imported as many times as necessary to ensure that the points
are correct.
NOTE
For these reasons, all parameters on the module driver parameter page should be configured prior to connecting this device to a LonWorks network.
The Browse feature
The Browse features of the network management tool allow you to read real-time values from the
XPC. This provides all of the tools necessary to test an integration prior to binding network variables to other LonWorks nodes.

14.8 COMMUNICATION LED'S

92
GF-122 AERCO XPC GATEWAY
The LED’s indicate if the translator is speaking to the devices on the network. The LED’s should reflect communication traffic based on the baud rate set. The higher the baud rate the LED’s would become more solid.
LEDs
Power Lights when power is being supplied to the translator.
The XPC is protected by internal solid state Polyswitches on the incoming power and network connections. These Polyswitches are not replaceable and will reset themselves if the condition that caused the fault returns to normal.
Rx Lights when the translator receives data from the network
segment; there is an Rx LED for Ports 1 and 2.
Tx Lights when the translator transits data from the network
segment; there is an Rx LED for Ports 1 and 2.
Run Lights based on translator health. See table below. Error Lights based on translator health. See table below.
The Run and Error LED's indicate translator and network status.
Status
93
GATEWAY COMMUNICATIONS MANUAL

SECTION 15 COMPLIANCE

15.1 FCC COMPLIANCE

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with the instruction manual, harmful interference to radio communications may result. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at the user’s own expense.
CAUTION
Changes or modifications not expressly approved by the responsible party for compliance could void the user’s authority to operate the equipment.

15.2 BACNET COMPLIANCE

BACnet® is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of the BACnet manufacturers Association (BMA). BTL
®
is a registered
trademark of the BMA.
• Rev. 10/17/2007
SECTION 16 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE
STATEMENT
Date: 7/15/05 Vendor Name: OEM
Product Names: Extended Protocol Converter Product Model Number: XPC Applications Software Version: HW_Exec_B Firmware Revision: 2.0 BACnet Protocol Revision: 3
Product Description:
The Unitary Protocol Converter is a Gateway designed to allow a single piece of equipment (e.g. chiller, variable speed drive, etc.) to be integrated into an existing Building Automation System. The XPC communicates to the equipment through its designated Device Port and exposes data to the BAS through its Network Port. The communications protocol used by the Network Port is DIP switch­selectable. BACnet options include BACnet over ARC156, BACnet MS/TP, and BACnet PTP with dial up modem support. Other non-BACnet protocols are also available, depending on the specific firmware
94
GF-122 AERCO XPC GATEWAY
DS-RP-B
AE-ACK-B
SCHED-E-B
T-ATR-B
DM-DDB-B
DS-RPM-A*
AE-ASUM-B
DM-DOB-A*
DS-RPM-B
AE-INFO-B
DM-DOB-B
DS-WP-A*
AE-ESUM-B
DM-DCC-B
DS-WP-B
DM-PT-A*
DS-WPM-A*
DM-PT-B
DS–COV-A*
DM-UTC-B
DS–COV-B
DM-RD-B
DS–COVU-
DM-LM-B
DS–COVU-
DM-BR-B NM-CE-A*
downloaded to the XPC module. The communications protocol used by the Device Port is configured at the factory through software and is dictated by the specified equipment. BACnet objects are spawned within the device as a result of downloading graphical control programs.
BACnet Standardize Device Profile (Annex L): B-AAC
List of all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-A* AE-N-I-B SCHED-I-B T-VMT-I-B DM-DDB-A*
DS-WPM-B DM-TS-B
A*
B
* Dynamic Binding is not supported when MS/TP is configured in slave mode.
Segmentation Capability:
Able to transmit segmented messages: (NO) Window Size: Able to receive segmented messages: (NO) Window Size: Standard Object Types Supported: On a separate page, please list each standard Object Type supported (i.e., an object of this type may be
present in the product). For each standard Object Type supported provide the following data:
Whether objects of this type are dynamically creatable using BACnet’s CreateObject service
Whether objects of this type are dynamically deletable using BACnet’s CreateObject service
List of all optional properties supported
List of all properties that are writable where not otherwise required by this standard
List of proprietary properties and for each its property identifier, datatype, and meaning
List of any property range restrictions
95
GATEWAY COMMUNICATIONS MANUAL

16.1 ANALOG VALUE (PAR)

Analog Value
(PAR):
1. Creatable? NO
2. Deletable? NO
3. Optional Properties Supported:
4. Writeable Properties:
5. Proprietary properties:
6. Range Restrictions:
acked_transitions cov_increment deadband description event_enable event_time_stam ps high_limit limit_enable low_limit notification_class notify_type priority_array reliability relinquish_default time_delay
cov_increment deadband description event_enable high_limit limit_enable low_limit notification_class notify_type out_of_service present_value relinquish_default time_delay units
None
description present_value
relinquish_default
notification_class time_delay
limited to 50 octets in length limited by min_pres_value and
max_pres_value properties limited by min_pres_value and
max_pres_value properties must be valid notification_class 0 to 4294967295
96
Binary Value (PAR) and Binary Value (CLOCK) and Binary Value (STAT):

16.2 BINARY VALUE (PAR), (CLOCK), AND (STAT)

1. Creatable? NO
2. Deletable? NO
GF-122 AERCO XPC GATEWAY
3. Optional Properties Supported:
acked_transitions active_text alarm_value change_of_state_count change_of_state_time description elapsed_active_time event_enable event_time_stamps inactive_text minimum_off_time minimum_on_time notification_class notify_type priority_array reliability relinquish_default time_delay time_of_active_time_re set time_of_state_count_re set
97
GATEWAY COMMUNICATIONS MANUAL
Binary Value (PAR) and Binary Value (CLOCK) and Binary Value (STAT):
4. Writeable Properties:
5. Proprietary Properties:
6. Range Restrictions:
active_text alarm_value change_of_state_count description elapsed_active_time event_enable inactive_text minimum_off_time minimum_on_time
16.2.1 notification_cla
ss
16.2.2 notify_type
16.2.3 out_of_service
16.2.4 present_value
16.2.5 relinquish_defa
ult
16.2.6 time_delay
None
active_text change_of_state_count description elapsed_active_time inactive_text minimum_off_time minimum_on_time notification_class time_delay
limited to 50 octets in length 0 to 4294967295 limited to 50 octets in length 0 to 4294967295 limited to 50 octets in length 0 to 4294967295 0 to 4294967295 must be valid notification_class 0 to 4294967295
98

16.3 ANALOG VALUE (STAT)

time_delay
GF-122 AERCO XPC GATEWAY
Analog Value (STAT):
1. Creatable? NO
2. Deletable? NO
3. Optional Properties Supported:
acked_transitions cov_increment deadband description event_enable event_time_stamp
s high_limit limit_enable low_limit notification_class notify_type reliability
99
GATEWAY COMMUNICATIONS MANUAL
units
time_delay
0 to 4294967295
Analog Value (STAT):
4. Writeable Properties:
cov_increment deadband description event_enable high_limit limit_enable low_limit notification_class notify_type out_of_service
5. Proprietary Properties:
6. Range Restrictions:
time_delay
None
description notification_class
limited to 50 octets in length must be valid notification_class
100
Loading...