AERCO Steam Generator User Manual

Page 1
Instruction No.
AERCO INTERNATIONAL, Inc., Northvale, New Jersey, 07647 USA
SG-101
Installation, Operation
& Maintenance Instructions
PACKAGED STEAM GENERATOR
MODEL SS1B PLUS
Printed in U.S.A. MAY, 2003
Page 2
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
Telephone Support
Direct to AERCO Technical Support (8 to 5 pm EST, Monday through Friday) (800) 526-0288
Printing May, 2003
The information contained in this operation and maintenance manual is subject to change without notice from AERCO International, Inc.
AERCO International, Inc. 159 Paris Avenue Northvale, NJ 07647-0128
AERCO makes no warranty of any kind with respect to this material, including but not limited to implied warranties of merchantability and fitness for a particular application. AERCO International is not liable for errors appearing in this manual. Nor for incidental or consequential damages occurring in connection with the furnishing, performance, or use of this material.
© Aerco International, Inc., 2003
Page 3
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

TABLE OF CONTENTS

Section Page
SAFETY PRECAUTIONS SG-101-1 GENERAL INFORMATION SG-101-3 INSTALLATION SG-101-5 PRINCIPLES OF OPERATION SG-101-7 OPERATING PROCEDURES SG-101-8 ROUTINE MAINTENANCE SG-101-10 TROUBLESHOOTING SG-101-11 CORRECTIVE MAINTENANCE SG-101-12 DESCALING BY THERMAL SHOCK SG-101-13 DISASSEMBLY SG-101-14 REASSEMBLY SG-101-16 RECOMMENDED SPARE PARTS SG-101-19
SAFETY PRECAUTIONS
Installing or operating personnel must, at all times, observe all safety regulations. The following warnings are general and must be given the same attention as specific precautions included in the instructions
FLUIDS UNDER PRESSURE MAY CAUSE INJURY TO PERSONNEL OR
SHUT OFF ALL INCOMING AND OUTGOING STEAM AND WATER STOP VALVES AND CAREFULLY (see Step OP8, Shutdown, in OPERATING PROCEDURES Section) BEFORE PERFORMING ANY MAINTENANCE.
DAMAGE TO EQUIPMENT WHEN RELEASED
WARNING!
LIVE STEAM CAN CAUSE SEVERE BURNS
NEVER ATTEMPT TO SEARCH FOR LEAKAGE IN A LIVE STEAM SYSTEM BY “FEEL”. USE A MIRROR OR OTHER SUITABLE POLISHED OBJECT.
WARNING!
DECREASE ALL TRAPPED PRESSURES TO ZERO
SG-101-1
Page 4
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
THIS PAGE INTENTIONALLY BLANK
SG-101-2
Page 5
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
GENERAL INFORMATION

INTRODUCTION

This instruction covers a HELITHERM Series A or Series B Steam to Water Heat Exchanger. Steam is the primary Converted to steam is the secondary side fluid.
The number of coils included in a particular Heater is denoted by the last two digits in the Heat Exchanger Model No. That is: 01 = 1 coi1, 03 = 3 coils, 10 = 10 coils, 15 = 15 coils, etc.
The Style designation for a Heat Exchanger denotes materials of construction for the various components. If this information is required for a specific heat exchanger, or contact the nearest AERCO Sales Representative.
or tube side fluid. Water
or shell

ACCESSORIES

Accessories included in the AERCO B-Plus Steam Generator Package Assembly are (see Figures SG-101-1, SG-101-8, and SG-101-10):
Over-Pressure Limit System, including the fo1lowing:
Steam Pressure Controller - Installed in the Control Box
Liquid Level Controller - mounted on the side of the Generator
Water Solenoid Valve -- installed at the cold water inlet
Inlet and Outlet Steam Pressure Gages -- -­mounted" below the Control Box
Over-Pressure Limit System, including the following:
Pressure Switch - installed in the Control
Box
Air Solenoid Valve -- installed in the
Control Box
Indicator Lights -- "Power On" and "Over
Pressure" -- installed in the Control Box
Pressure & Temperature Relief Valve – size furnished as required in accordance with the design Btu output of the Generator -- located in the Generator top head
Inverted Bucket Steam Trap -- located in the Condensate Outlet (see Figure SG-101-1)
All other items, such as: stop valves, check valves, strainers, unions or flanges and other piping and fittings as shown in Figure SG-101-2 are to be furnished by the installer or user.
NOTE
The AERCO Steam Generator carries the standard AERCO warranty against defective material and workmanship. HOWEVER, AERCO cannot honor its warranty if the installer or user deviates in any way from the instructions and precautions included herein or makes any alteration of the equipment from that as originally furnished without the written approval of AERCO.
NOTE
THIS INSTRUCTION COVERS ONLY THE STEAM GENERATOR PORTION OF THE MODEL B-PLUS PACKAGED ASSEMBLY. SEPARATE INSTRUCTIONS ARE INCLUDED IN THIS PACKAGE COVERING THE PRIMARY STEAM CONTROL VALVE
STEAM PRESSURE CONTROLLER LIQUID LEVEL CONTROLLER OVER-PRESSURE LIMIT SYSTEM AND ITS COMPONENTS AND OTHER ACCESSORIES INCLUDED IN THE GENERATOR PACKAGE.
SG-101-3
,
Page 6
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
TABLE 1
GENERATOR
MODEL
SS1B+02 2
SS1B+03 3
SS1B+04 4
SS1B+05 5
SS1B+06 6
SS1B+07 7
SS1B+08 8
SS1B+09 9
SS1B+10 10
SS1B+11 11
SS1B+12 12
SS1B+13 13
SS1B+14 14
NOTE: 120V/60 Hz ELECTRICAL POWER SUPPLY AND 25 PSIG AIR SUPPLY REQUIRED
STEAM FLOW CONTROL VALVE WITH PNEUMATIC OPERATOR - SEE TABLE 2
SS1B+15 15
NO. OF
COILS
HEATING
SURFACE
2
FT
(M2) A
15
(1.39)
20
(1.86)
25
(2.32)
30
(2.79)
35
(3.25)
40
(3.72)
45
(4.18)
50
(4.65)
55
(5.11)
60
(5.57)
65
(6.04)
70
(6.50)
75
(6.97)
INCHES
DIMENSIONS
INCHES (CM)
B
40.75
55.00
(103.5)
(139.70)
45.75
60.00
(116.20)
(152.40)
49.75
64.00
(126.37)
(162.56)
54.75
69.00
(139.07)
(175.26)
58.75
73.00
(149.23)
(185.42)
63.75
78.00
(161.93)
(198.12)
67.75
82.00
(172.09)
(208.28)
72.75
87.00
(184.79)
(220.98)
76.75
91.00
(194.95)
(281.14)
81.75
96.00
(207.65)
(243.84)
85.75
100.00
(217.81)
(254.00)
90.75
105.00
(230.51)
(266.70)
94.75
109.00
(240.67)
(276.86)
TABLE 2
VALVE
PRIMARY ST EAM
SIZE
INLET SIZE, NPT
INCHES
1.00 1.00
1.25 1.25
1.50 1.50
2.00 2.00 5.08
C
21.00
(53.34)
26.00
(66.04)
30.00
(76.20)
35.00
(88.90)
40.00
(101.60)
45.00
(114.30)
50.00
(127.00)
55.00
(139.70)
60.00
(152.40)
65.00
(165.10)
70.00
(177.80)
75.00
(190.50)
80.00
(203.20)
CM
2.54
3.18
3.81
APPROX. WT.
LBS. (KG)
DRY
WET
520
660
(237)
(300)
570
720
(259)
(327)
610
770
(277)
(350)
640
830
(291)
(377)
670
880
(304)
(400)
710
930
(322)
(422)
740
980
(336)
(445)
770
1030
(350)
(468)
800
1080
(363)
(490)
840
1130
(381)
(513)
870
1180
(395)
(536)
900
1230
(409)
(558)
930
1280
(422)
(581)
DIMENSIONS ARE SHOWN IN INCHES (CENTIMETERS)
ASME CODE CERTIFICATION STAMP
TABLE 3
HEAT EXCHANGER DESIGN PARAMETERS
SHELL
SIDE
TUBE
SIDE
MAX. WORKING
PRESSURE PSIG (kPa)
50
(345)
250
(1723)
MAX.
TEMP.
DEG. F (DEG. C)
(204)
(204)
400
400
TEST
PRESSURE
PSIG (kPa)
75
(517)
375
(2584)
U-7
Figure SG-101-1. Dimensions for AERCO Packaged Steam Generator, Model SS1B-PLUS
SG-101-4
Page 7
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

INSTALLATION

1. Dimensions for an AERCO Steam Generator Model SS1B-PLUS are shown in Figure SG-101-1.
2. Uncrate the Generator carefully. Set it upright by using a block and tackle or hoist attached to the lifting lugs on the top head of the Generator (the eye bolts shown in Figure SG-101-9). Always use the lifting lugs and/or move the Generator.
3. If possible, for easy in-place maintenance, locate the Generator where there is at least 2 feet clearance all around the unit and where the head room clearance is equal to or more than dimension C in Figure SG-101­1 for the size Generator furnished.
4. It is suggested that the Generator be secured to the floor. However, any other means for securing the Generator may be used. If piping is used to secure the Generator, the piping must provision for expansion.
5. Make all piping connections as instructed in Step 6 below and in accordance with Figure SG-101-2 or with any specific piping diagram which may have been furnished by AERCO for this installation.
6. For best Generator performance, observe the following very carefully in making the piping installation:
include ample
to lift
d. Include all of the stop valves, check
valves, steam traps and other elements in the piping as shown in Figure SG­101-2 or as separately specified by AERCO. Note that the steam trap and Generator drain valve are included in the Generator assembly.
e. Be sure to include a vacuum breaker in
the steam outlet line ahead of the stop valve. This assures no vacuum buildup during operation.
f. The condensate return piping should be
arranged to permit condensate to drain freely by gravity from the Generator bottom head. Failure to do so may result in Generator improper operation and/or in damage to the primary steam/condensate system.
g. All drain discharges -- relief valve in the
top head of the Generator and drain valve in the bottom head -- should be piped directly to a convenient floor drain.
7. Before making final piping connections to and from the Generator, blow out all piping thoroughly.
8. Make the necessary air-operated Control Valve supply air connection to the connector through the side of the control box. THE SUPPLY AIR PRESSURE MUST BE MAINTAINED AT 25 PSIG.
a. Do not use cement or red lead in
making up pipe joints.
b. For Generator connection types, sizes,
and locations, see Figure SG-101-1.
c. All piping to the Generator top head
should be provided with unions or flanges which are located beyond the outside diameter of the Generator head to permit removal of the head and she!1for in-place maintenance.
SG-101-5
9. Connect 110V 60 Hz power supply wiring through the side of the control box to the electrical junction box.
Page 8
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
SECONDARY STEAM OUT
STEAM HEADER
CONTROL BOX
LEVEL CONTROLLER
P
PRIMARY STEAM IN
CONDENSATE OUT
COLD WATER SUPPLY IN
DRAIN
LEGEND
PRESSURE
STOP VALVE
RELIEF VALVE
CONTROL VALVE
STRAINER
RELIEF VALVE
STEAM TRAP
Figure SG-101-2. Piping Connections for AERCO Steam Generator
P
GAGE
PIPE UNION OR FLANGES
VACUUM BREAKER
SG-101-6
Page 9
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

PRINCIPLE OF OPERATION

The AERCO Helitherm Heat Exchanger (Generator) SS1B-P1us consists of four principal parts (see Figure SG-101-3):
1. Shell with Top and Bottom Heads
2. Coils assembled to Primary Steam Riser and Condensate Return
3. Pressure Control Unit
4. Water Level Control Unit
Cold Water enters the Generator through the inlet connection and dispenser (dispersion tube) in the bottom head. The Cold Water in the shell, then, flows upward among the coils (heating surfaces) and, heated, is converted to Secondary Steam which is discharged through the Secondary Steam outlet connection in the top head.
Primary Steam enters through the Primary Steam Control Valve and its inlet connection in the bottom head and is fed through the Primary Steam riser to the inlet of each coil unit. The Primary Steam then flows through each coil unit simultaneously in parallel, leaves through each coil outlet as Condensate, enters the condensate return, and leaves the Generator through the condensate outlet connection in the bottom head of the Generator.
The Pressure Controller senses the pressure of the Secondary Steam at any given moment and signals the Primary Steam Control Valve to modulate between full open or closed as necessary to maintain the required Secondary Steam outlet pressure.
The Water Level Controller senses the level of water in the Generator at any given moment and signals the Water Solenoid Valve to open or dose as necessary to maintain the desired water level in the Generator.
Figure SG-101-3. AERCO Steam Generator
Schematic
SG-101-7
Page 10
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

OPERATING PROCEDURES

OP1. With the installation entirely completed,
including:
All piping connections have been made,
All connecting piping has been cleaned and blown out,
All connections per steps 8 and 9 under INSTALLATION have been made,
turn ON the electrical power supply and open any stop valve(s) in the Cold Water inlet line Hold the relief valve in the Generator top head open to allow air to escape (otherwise an air pocket will be built up and the Generator will not fill properly). The Level Controller will hold the Water Solenoid Valve open to allow water to flow into the Generator shell until the desired water level is reached, at which time the Level Controller will close the Water Solenoid Valve. Then close the relief valve.
OP6. Follow the instructions furnished with
the air-operated Pressure Controller and Control Valve and:
a. Introduce Primary Steam to the
Generator.
b. Adjust the Pressure Controller until
the Secondary Steam outlet pressure is being held steady at the desired pressure. If the Secondary Steam outlet pressure is erratic, see step OP7 below.
c. Close the process steam outlet
valve which was opened in step OP4}.
OP7. If the Secondary Steam outlet pressure
is erratic, especially during load changes:
a. Put a load on the Generator by
opening a steam outlet or outlets in the process as quickly as possible.
OP2. Temporarily set the Pressure Switch
(58) in the Control Box to its high pressure limit. See Figure SG-101-8, (Item 58) and the wiring diagram in Figure SG-101-4.
OP3. Set the Pressure Controller (53) in the
Control Box at the pressure desired to be held at the Secondary Steam outlet.
OP4. Open any stop valve(s) in the
Secondary Steam outlet line. Open a steam outlet valve in the process to insure a flow of steam from the Generator. For best results in adjusting the pressure control, a steam flow of 10% to 23% of Generator rating is desirable.
OP5. Slowly open all stop valves in the
Primary Steam inlet and Condensate outlet lines.
b. Adjust the Pressure Controller to
provide best response on load changes. See the instruction furnished with the Controller.
OP8. Adjust the Over-Pressure Limit System
Pressure Switch (58) in the Control Box to its desired setting -- usually 5 to 7 psig higher than the desired Secondary Steam pressure.
OP9. The Generator is now set for operation.
No further operation procedure is necessary unless, or until, further pressure control adjustments may be required. If so, repeat steps OP4, OP5, OP6, OP8, and, if necessary, step OP7.
SG-101-8
Page 11
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
OP10. To SHUT DOWN the system:
a. Close all stop valves in the Primary
Steam inlet and Condensate outlet lines.
b. In this order,
close any stop valves
in:
(1) the Secondary Steam outlet line,
(2) the Cold Water inlet line.
OP11. For DRAINING THE GENERATOR, see
the instructions included under ROUTINE MAINTENANCE.
OP12. To START UP again, with the shell filled
per step OP1 above, open the stop valves in the following order:
a. stop valve in the Cold Water inlet
line,
b. stop valve in the Secondary Steam
outlet 1ine, and
c. stop valves in the Primary Steam
inlet and Condensate outlet lines.
OP13. After each startup, check the pressure
control, If necessary, make adjustments per steps OP4 through OP8 above.
Figure SG-101-4. Over-Pressure Limit System Wiring Diagram
SG-101-9
Page 12
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

ROUTINE MAINTENANCE

The constant flexure of the coils under varying load conditions automatically provides a descaling action and prevents a buildup of brittle scale. A periodic blow-down (draining) is required lo remove accumulated solids.
After the first 3 months of initial operation, drain the Generator as outlined below. Examine the water being drained:
Check the pressure control at least once every 3 months. Make any necessary adjustments per steps OP4 through OP8 of the OPERATING PROCEDURES Section.
DRAIN THE HEATER as follows:
RM1. Close all stop valves in the Primary
Steam inlet and Condensate outlet lines.
a. If the amount of solids appears to be
heavy, set a schedule to drain the Generator every 3 months.
b. If the amount of solids appears to be
light, set a schedule to drain the Generator every 6 months.
c. Even if the amount of solids appears
to be very light, drain the Generator at least once each year.
d. Also, see the TROUBLESHOOTING
and CORRECTIVE MAINTENANCE which follow. If descaling by thermal shock is required, schedule that procedure in ROUTINE MAINTENANCE
RM2. RM2. In this order, close the stop valves
in:
a. the Cold Water inlet line
b. the Secondary Steam outlet line,
RM3. Carefully open the relief valve in the
Generator top head to relieve pressure in the Generator shell.
RM4. With the relief valve being held open (to
prevent creating a vacuum), open the drain valve and drain the Generator completely.
RM5. To refill the Generator and place it back
into service, close the drain valve and follow steps OP1, OP12 and OP13 in the OPERATING PROCEDURES Section.
SG-101-10
Page 13
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
p

TROUBLESHOOTING

SYMPTOM
PROBABLE CAUSE & REMEDY
“CORRECTIVE MAINTENANCE” ITEM NO.
A. Generator does not maintain required pressure at
rated capacity.
B. Secondary Steam pressure is too high.
C. Secondary Steam outlet pressure fluctuates
widely.
D. Insufficient Water to the Generator.
E. Excess or insufficient Condensate being returned
from the Generator.
F. Steam being discharged into Condensate drain,
G. Relief Valve pops.
H. Generator shuts down below, at, or too near
above required Secondary Steam outlet
ressure.
I. Loud banging in Generator or in Primary Steam or
Condensate piping (not to be confused with a normal clicking noise).
CM1, CM2, CM5, CM8, CM9, CM11, CM12, CM13
CM1, CM5, CM7, CM9
CM2, CM5, CM7, CM8, CM9, CM11, CM13
CM3, CM4
CM5, CM11
CM12, CM13
CM7, CM9, CM10
CM10
CM5, CM6
SG-101-11
Page 14
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

CORRECTIVE MAINTENANCE

Refer to the previous TROUBLESHOOTING Table. The following are probable causes and remedies for improper action of the Generator.
CM1. The Primary or Secondary Pressure
Gage may read wrong. Check each with a gage that is known to be correct.
CM2. Primary Steam pressure is too low.
Check the Primary Steam pressure gage below the Control Box. If the reading is low, adjust the steam pressure to that which is required. If there is a restriction in the Primary Steam supply line, the gage reading will drop excessively when the Generator calls for full steam even though the pressure appears to be normal when the load is light. If the Primary Steam supply pressure is correct, its pressure gage reading should reach design pressure for steam in the coils as the Generator Secondary Steam outlet pressure drops. If it does not, check the operation of the Primary Steam Control Valve.
CM3. Water level is low or water supply fails.
Check the operation of the Level Controller and Water Solenoid at the Cold Water inlet.
CM4. Cold Water pressure is low. Check and
correct, if necessary, the Water pressure to the Generator.
CM5. Condensate return piping has not been
installed so that the Condensate drains freely by gravity and/or the Condensate check valve leaks or has failed. If necessary, rearrange the Condensate return piping per step 6f in the INSTALLATION Section. Inspect the check valve and replace it if it is leaking or has failed. Also, check to make sure that there is no restriction in the Condensate drain line.
CM6. Primary Steam supply line is not
properly trapped. Install a trap as indicated in Figure SG-101-2.
CM7. The Primary Steam Control Valve does
not close. Check the instructions covering the Valve.
CM8. The Primary Steam Control Valve does
not open. Check the instructions covering the Valve.
CM9. The Secondary Steam pressure control
system is not operating properly. Check the instructions covering the Pressure Controller in the Control Box.
CM10. The Over-Pressure Limit System is out
of adjustment or some component of the system has failed. Check out the system setting per step OP8 under OPERATING PROCEDURES above. Inspect and repair or replace the pressure switch and solenoid valve.
CM11. There is a leak in the Generator coil(s),
steam riser, or Condensate return, causing water from the shell to leak into the heating coil system, or steam or condensate from the coil system into the shell. To verify such a leak, shut off the Primary Steam supply and break a connection in the Condensate line – BE CAREFULL TO AVOID SEVERE BURNS --.Condensate will drain from the coil system initially, but the flow should stop after a minute or two. If the flow continues, water is leaking from the pressurized shell side to the tube side of the Generator. Disassemble, inspect, repair (if possible), replace, and reassemble the Generator as outlined in the DISASSEMBLY and REASSEMBLY Sections.
CM12. The Generator coils are scaled up.
Descale the Generator by thermal shock in the manner outlined under DESCALING BY THERMAL SHOCK.
CM13. The Generator is being utilized at a rate
higher than its design capacity. Contact the nearest AERCO Representative for advice in remedying this problem.
SG-101-12
Page 15
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

DESCALING BY THERMAL SHOCK METHOD

Where, under certain conditions of continuous steady usage, the cold water is so hard or alkaline that normal flexure of the coils (see ROUTINE MAINTENANCE) and routine blow­down (draining the Generator shell) will not remove scale build-up on the coils, the heating surfaces (coils) may be thermally shocked, without damage to any part of the Generator, to dislodge scale solids.
Proceed as follows:
TS5. Inject a flow of cold water through the
relief valve connection for about 2 minutes. Then shut off the water flow and open the Condensate drain line stop vaIve to drain off all Condensate.
TS6. Repeat steps TS4 and TS5 several
times until the water coming from the Generator drain appears to be relatively free of solids.
TS1. Drain the Heater per steps RM1 through
RM4 in the ROUTINE MAINTENANCE Section. However, instead of holding the relief valve open in step RM4, remove the relief valve from the Generator top head.
TS2. Open the Generator drain valve. Leave
the drain valve open until step TS8 in the following procedure.
TS3. Connect a source of cold water (for
example, a hose) to the open relief valve connection.
TS4. Open all stop valve(s) in the Primary
Steam inlet line and the Condensate outlet line to allow steam to the Generator. After about 30 seconds, or until steam is blowing out of the condensate drain line, close the stop valve in the Condensate outlet line. Leave the Primary Steam inlet line open for about 2 minutes longer, then close all Primary Steam inlet stop valves.
TS7. Remove the cold water source from the
relief valve connection. Open the stop valve in the main Cold Water inlet line and allow a complete flushing of the Generator shell.
TS8. After
TS9. If Cold Water conditions are so severe
the Generator shell has been
completely drained, close the Generator drain valve, replace the relief valve, and place the Generator back into operation per steps OP1, OP12, and OP 13 in the OPERATING PROCEDURES section.
that thermal shocking does not remove scale deposits, contact the nearest AERCO Representative for advice.
SG-101-13
Page 16
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

DISASSEMBLY

Reference illustrations:
SG-101-4 Over-Pressure Limit System Wiring Diagram SG-101-8 Generator Control Box
Assembly
SG-101-9 Generator Assembly SG-101-10 Generator Package Assembly
Special Tools Required;
(1) Torque wrench for 5/8" nuts.
(2) A block and tackle or ratchet or winch hoist is recommended for lifting off the Generator top head and shell, or for lifting and moving the Generator.
NOTE that all part item numbers given in parentheses ( ) in the instructions below refer to those shown in Figure SG-101-8, SG-101-9, or SG-101-10.
D1. Shut down and drain the Generator in
accordance with steps RM1 through RM4 under ROUTINE MAINTENANCE above.
D2. Disconnect ALL external piping from the
Generator top head, including that to the Relief Valve (24). Disconnect the Secondary Steam outlet piping at the union or flanges located beyond the outside diameter of the Generator top head.
D3. Disconnect Union (29) located above
the Level Controller (34).
D4. Disconnect the power supply wiring to
the Control Box and the wiring between the Control Box and the Level Controller,
D5. Disconnect the air supply and control air
piping from the Control Box.
D6. Close the Shutoff Cock (38) in the
Primary Steam Pressure Gage line and disconnect the Compression Fitting (25).
D7. Mark the edge of the Generator bottom
head flanges in order to indicate their correct relative positions upon reassembly.
D8. Remove Nuts (l4) and Studs (12) from
the Generator bottom head flanges.
D9. Using a hoist or block and tackle
attached to the Lifting Lugs (2) on the Generator top head, CAREFULLY lift the top head and shell STRAIGHT off the Generator riser and coil, assembly., DO NOT SCRAPE lining against the coil tubing.
D10. Clean and inspect the inside of the shell
and the Steam Riser/Condensate Return/Coils assembly for obvious damage.
D11. With the Condensate Return stop valves
closed, open the stop valve(s) in the Primary Steam inlet line to allow Primary Steam to the Generator coils. Any leak in the coils. Steam riser, or Condensate return will become visible quickly. Note where the leaks are and shut off the Primary Steam.
D12. If a coil must be replaced,
open end wrench to disconnect the unions holding the coils to the Steam riser and Condensate return. Be careful not to damage the spud threads (see Figure SG-101-6).
D13. If either the Steam riser or Condensate
return must be replaced, it is recommended that the Generator be reassembled and returned to the AERCO factory for replacement. (AERCO has the proper factory setup, pressure testing equipment, ready access to any needed additional parts, and the expertise necessary to provide a guaranteed replacement.) Contact the nearest AERCO Representative for instruction for making the return.
use a 1-5/16"
UP
the shell
SG-101-14
Page 17
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
If, however, returning the Generator to the AERCO factory is impractical, field replacement may be made but cannot be guaranteed by AERCO. If this decision is made, proceed as follows:
a. Remove all coils per step D12
above. Examine each coil carefully to make sure that replacement at this time is not an advisable action.
b. Remove the damaged Steam riser
or Condensate return.
D14. If the shell copper liner has been
damaged, reassemble the Generator and return it to the AERCO factory for replacement of the 1iner. Contact the nearest AERCO Representative for instruction for making the return.
D15. If it is necessary for any reason to
remove the Generator top Head (1) from the Shell (11):
a. Disconnect the Compression
Fittings (25) from their connections at the top Head and pull the Tubing (23) aside.
b. Remove the Nuts (14), Studs (3)
and (12), and Lifting Lugs (Eye Bolts) (2), and lift the Head off the Shell.
SG-101-15
Page 18
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

REASSEMBLY

Reference illustrations:
Same as DISASSEMBLY, plus:
SG-101-5 Alignment of Steam Riser and Condensate Return
SG-101-6 Assembly of Coil to Steam Riser or Condensate Return
SG-101-7 Coil Spacing Tool
Special Tools Required; DISASSEMBLY, plus a coil spacing tool as shown in Figure SG-101-7.
Same as for
Figure SG-101-5. Alignment of Steam Riser
and Condensate Return
NOTE
All part item numbers shown in parentheses ( ) in the following instructions refer to those shown in Figures SG-101-8, SG-101-9, or SG-101-10.
R1. If either the steam riser (7) or
Condensate Return (8) must be replaced:
a. Use pipe joint compound or Teflon
tape on the threads and screw the replacement Steam Riser and/or Condensate Return into the Generator lower head.
b. Tighten the Riser or Return taking
care to line up the spud centers with the raised indicators on the bosses in the head casting as shown in Figure SG-101-5.
R2. If a coil must be replaced:
a. See Figure SG-101-6. A conical Coil
Gasket (10) is required for each Coil union in the Generator. It is recom­mended that Coil Gaskets (10) be replaced whenever a coil is reassembled to a Riser or Return, even though the Coil itself is not being replaced. Snap the gasket into the Riser or Return spud.
Figure SG-101-6. Assembly of Coil to Steam
Riser or Condensate Return
b. Before
c. Assemble the Coil union to the
attempting to assemble the Coils to the Riser or Return spuds, wrap each spud with Teflon tape and apply a lubricant (grease) to the back of the union nuts and shoulders on the Coil tail pieces (see Figure SG-101-6). Rotate the nuts to spread the lubricant.
Condensate Return (8) first. Do not tighten. Assemble the other Coil union to the Steam Riser (7).
SG-101-16
Page 19
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
d. Using a torque wrench, tighten both
unions to approximately 75 ft-lb while holding the coil so that the turns of the coil remain perfectly horizontal, where they are brazed to the tail pieces, after tightening. NOTE: Never wrench to tighten a union nut. Deformation and subsequent leaking may result.
e. Space the Coil tubes evenly
throughout the Generator, with each tube space at least 1/2" wide. It is especially important that no tubes rest on any Coil unions. A spacing tool may be made up similar to that shown in Figure SG-101-7 (avail­able from AERCO, Part No. 12523). Insert the tool flat between the Coil tubes and twist the tool until the desired spacing is obtained.
f. Test for leaks per step D11 of the
DISASSEMBLY Section. Make any corrections necessary.
use a hammer on a
d. Realign the Tubing (23) and
reconnect the Compression Fittings (25) to their connections at the top Head.
R5. Place the Gasket (13) on the Generator
bottom Head flange.
R6. Using a hoist or block and tackle
attached to the Lifting Lugs (2) on the Generator top Head (1), CAREFULLY lower the top Head and Shell STRAIGHT DOWN over the Coil and Riser assembly. DO NOT SCRAPE the Shell lining against the Coil tubing.
R7. Before resting the Shell flange onto the
bottom Head flange, make sure that the Shell is positioned properly by lining up the marking put on the edges of the flanges in step D7 of the DISASSEM­BLY Section. For further assurance, check to see that the raised indicators on the outside diameters of each of the top and bottom Head flanges line up with each other. This is very important.
R3. Clean all gaskets and gasket surfaces
thoroughly. AERCO recommends that new
gaskets (13) be used whenever reassembling either the top or bottom head to the shell.
R4. If the Generator Top Head (1) has been
removed from the Shell (11):
a. Clean the Gasket surfaces
thoroughly and place a Gasket (13)
Gasket is recommended) on
(a new
the Shell top flange.
b. Replace the Generator top Head
onto the top of the Shell, lining up
the stud holes.
c. Reassemble the Studs (3) and (12),
the Lifting Lugs (Eye Bolts) (2), and
Nuts (14) into the Head and Shell
flanges. Cross-tighten the Nuts to
approximately 75 ft-lb torque to
obtain uniform seating. Then,
progressively tighten the Nuts to
approximately 150 ft-lb torque for a
tight seal.
R8. Assemble the Studs (12) and Nuts (l4)
into the bottom Head and Shell flanges. Tighten the Nuts in the same manner as in step R4c above.
R9. Reconnect the Compression Fitting (25)
in the Primary Steam Pressure Gage line and open the Shutoff Cock (38).
R10. Reconnect Union (29) located above the
Level Controller (34).
R11. Reconnect the air supply and control air
piping to the Control Box.
R12. Reconnect the power supply wiring to
the Control Box and all wiring between the Control Box and the Level Controller (34).
R13. Reconnect all external piping to the
Generator Top Head, including that to the Relief Valve (24).
R14. Refill and place the Generator back into
operation in accordance with steps OP1, OP12 and OP13 in the OPERATING PROCEDURES Section.
SG-101-17
Page 20
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
Figure SG-101-7. Coil Spacing Tool
SG-101-18
Page 21
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS

RECOMMENDED SPARE PARTS

Quantity
Per Generator
* 9 Coil Assembly SG-101-9
** 10 Conical Coil Gasket SG-101-9
4 13 Head Gasket SG-101-9 1 24 Relief Valve SG-101-10 1 42 Water Solenoid Valve SG-101-10 1 53 Pressure Controller SG-101-8 1 58 Pressure Switch SG-101-8 1 62 Air Solenoid Valve SG-101-8 1 65 Compound Pressure Gage SG-101-8 1 75 Green Indicator Light SG-101-8 1 78 Red Indicator Light SG-101-8
* Minimum of 2 to a maximum of the number in your largest Generator
Item No.
** 2 per Spare Coil Assembly, Item 9 plus 2
Part Name
Shown in Figure No.
SG-101-19
Page 22
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
TABLE 1
GENERATOR
MODEL
SS1B+02 2
SS1B+03 3
SS1B+04 4
SS1B+05 5
SS1B+06 6
SS1B+07 7
SS1B+08 8
SS1B+09 9
SS1B+10 10
SS1B+11 11
SS1B+12 12
SS1B+13 13
SS1B+14 14
NOTE: 120V/60 Hz ELECTRICAL POWER SUPPLY AND 25 PSIG AIR SUPPLY REQUIRED
STEAM FLOW CONTROL VALVE WITH PNEUMATIC OPERATOR - SEE TABLE 2
SS1B+15 15
NO. OF
COILS
HEATING
SURFACE
2
FT
(M2) A
15
(1.39)
20
(1.86)
25
(2.32)
30
(2.79)
35
(3.25)
40
(3.72)
45
(4.18)
50
(4.65)
55
(5.11)
60
(5.57)
65
(6.04)
70
(6.50)
75
(6.97)
DIMENSIONS INCHES (CM)
B
40.75
55.00
(103.5)
(139.70)
45.75
60.00
(116.20)
(152.40)
49.75
64.00
(126.37)
(162.56)
54.75
69.00
(139.07)
(175.26)
58.75
73.00
(149.23)
(185.42)
63.75
78.00
(161.93)
(198.12)
67.75
82.00
(172.09)
(208.28)
72.75
87.00
(184.79)
(220.98)
76.75
91.00
(194.95)
(281.14)
81.75
96.00
(207.65)
(243.84)
85.75
100.00
(217.81)
(254.00)
90.75
105.00
(230.51)
(266.70)
94.75
109.00
(240.67)
(276.86)
TABLE 2
VALVE
INCHES
PRIMARY ST EAM
SIZE
INLET SIZE, NPT
INCHES
1.00 1.00
1.25 1.25
1.50 1.50
2.00 2.00 5.08
C
21.00
(53.34)
26.00
(66.04)
30.00
(76.20)
35.00
(88.90)
40.00
(101.60)
45.00
(114.30)
50.00
(127.00)
55.00
(139.70)
60.00
(152.40)
65.00
(165.10)
70.00
(177.80)
75.00
(190.50)
80.00
(203.20)
CM
2.54
3.18
3.81
APPROX. WT.
LBS. (KG)
DRY
WET
520
660
(237)
(300)
570
720
(259)
(327)
610
770
(277)
(350)
640
830
(291)
(377)
670
880
(304)
(400)
710
930
(322)
(422)
740
980
(336)
(445)
770
1030
(350)
(468)
800
1080
(363)
(490)
840
1130
(381)
(513)
870
1180
(395)
(536)
900
1230
(409)
(558)
930
1280
(422)
(581)
DIMENSIONS ARE SHOWN IN INCHES (CENTIMETERS)
ASME CODE CERTIFICATION STAMP
TABLE 3
HEAT EXCHANGER DESIGN PARAMETERS
SHELL
SIDE
TUBE
SIDE
MAX. WORKING
PRESSURE
PSIG (kPa)
50
(345)
250
(1723)
MAX.
TEMP.
DEG. F (DEG. C)
400
(204)
400
(204)
TEST
PRESSURE
PSIG (kPa)
75
(517)
375
(2584)
U-7
Figure 1. Dimensions for SS1B-PLUS
SG-101-20
Page 23
INSTRUCTIONS – AERCO HELITHERM STEAM GENERATOR MODEL SS1B-PLUS
ITEM
QTY
NO.
REQ. DESCRIPTION
1 1 TOP HEAD 20886 2 2 5/8" EYE BOLT 12865 3 2 5/8"-llx4"L6STUD 6-248 4 2 1/4"-20 SOC. HEAD CAP SCREW 6816 5 1 RISER SUPPORT P IN 6690 6 | RISER SUPPORT BRACKET 6641 7 1 STEAM INLET RISER ASSY 18888 8 1 CONDENSATE RETURN ASSY 8676
9 TABLE
COIL ASSEMBLY 844-A
PART NO
10 TABLE
11 1 SHELL ASSEMBLY TABLE A 12 28 5/8"-11x3-l/2" LG STUD 6-173 13 2 HEAD GASKET BG 14 62 5/8"-11 NUTS 6-178
15 1 16 1 BOTTOM HEAD & SKID ASSY 18890
USED ONLY WITH MODELS SS1B+07 THRU SS1B+15
CONICAL GASKET 8079
WATER INLET DISPERSION TUBE
122480
TABLE A
MODEL SS1B+02 2 4 B20 SS1B+03 3 6 B24 SS1B+04 4 8 B29 SS1B+05 5 10 B33 SS1B+06 6 12 B38 SS1B+07 7 14 B42 SS1B+08 8 16 B47 SS1B+09 9 18 B51 SS1B+10 10 20 B56 SS1B+11 11 22 B60 SS1B+12 12 24 B65 SS1B+13 13 26 B69 SS1B+14 14 28 B74 SS1B+15 15 30 B78
QUANTITY REQ. ITEM 9 ITEM 10
ITEM 11 PART NO
Figure SG-101-9. AERCO Steam Generator Model SS1B-PLUS Assembly and Parts List
SG-101-21
Page 24
INSTRUCTIONS - AERCO HELITHERM STEAM GENERATOR - MODEL SS1B-PLUS
)
)
ITEM
QTY
NO.
REQ 21 1 1"xl/4"NPT REDUCING BUSHING 9-493 22 4 3/8"x1/2"HUB 90° CONDUIT 122104 23 A/R 3/8"OD TYPE L COPPER TUBING RM6041 24 1 PRESS. RELIEF VALVE (NOTE A)122500 25 3 3/8"OD TUBE x 1/4" NPT COMR 8-6 26 3 1" NPT STREET ELL 9-328 27 1 1" NPT 90° ELL 9-222 28 1 2''x1” REDUCING BUSHING 9-365 29 3 1"NPT UNION 9-291 30 1 CONTROL BOX ASSEMBLY (SEE ASSY
31 A/R 3/8" TYPE LT CONDUIT RM2000 32 A/R 14 GA. BLACK STRANDED WIRE RM4524 33 A/R 14 GA. WHITE STRANDED WIRE RM4525 34 1 LIQUID LEVEL CONTROLLER 122501 35 A/R 1/4"IMPOLENE TUBING RM3041 36 1 1/4"xl/8" NPT 90° IMPOLENE COMP. 8-4 37 1 AIR OP CONTROL VALVE (NOTE C)20774 38 1 1/4" FEMALE/MALE SHUTOFF COCK 121975 39 1 INSULATION (NOTE B) 18777 40 A/R 1" BLACK IRON PIPE RM358 41 1 HEATER ASSEMBLY (NOTE B 42 1 1/2" WATER SOLENOID 5134 43 1 1" NPT BALL VALVE 12820-7 44 1 2" NPT BALL VALVE 12820­45 1 STEAM INLET ASSEMBLY 18762 46 1 VALVE SPOOL PIECE (NOTE C 47 1 INVERTED BUCKET STEAM TRAP 122502
DESCRIPTION
PART
NO.
20887
A/R - LENGTH OR QUANTITY AS REQUIRED NOTE A - WHEN ORDERING STATE SIZE NOTE B - WHEN ORDERING STATE NUMBER OF COILS IN HEATER NOTE C - WHEN ORDERING STATE CONTROL VALVE SIZE
Figure SG-101-10. AERCO Packaged Steam Generator Model SS1B-PLUS Assembly and Parts List
SG-101-22
Page 25
Loading...