Aemc instruments MN251T User Manual

AC Current Probe Model MN251T
User Manual

DESCRIPTION

The MN251T is the latest in compact AC Current probes. Designed to meet the most stringent demands in industry and electrical contracting, it also meets the latest safety and performance standards. The probe has a measurement range up to 240 Arms which makes it the perfect tool for measurement with DMMs, recorders, power and harmonic meters. The Model MN251T is compatible with any AC voltmeter, multimeter, or other voltage measurement instrument that is capable of displaying 1mV of output per amp of measured current, voltmeter accuracy of 0.75% or better and an input impedance of ≥ 1 MΩ.

WARNING The safety warnings are provided to ensure the safety of personnel and proper operation of the instrument. Read the instruction completely.

• Use caution on any circuit: potentially high voltages and currents may be present and may pose a shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device before it is connected around the conductor.
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.

INTERNATIONAL ELECTRICAL SYMBOLS

This symbol signifies that the current probe is protected by double or reinforced insulation. Use only factory specified re pl ac em ent parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.

RECEIVING YOUR SHIPMENT Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify

your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage.
ELECTRICAL SPECIFICATIONS
Nominal Range: 200A Measurement Range: 0.1 to 240A Transformation Ratio: Voltage out put Output Signal: 1mV/A Accuracy and Phase Shift*:
Accuracy: 0.5 to 10A: 3.0% Reading ± 0.5mV
10 to 40A: 2.5% Reading ± 0.5mV 40 to 100A: 2.0% Reading ± 0.5mV 100 to 240A: 1.0% Reading ± 0.5mV
Phase Shift: 0.5 to 10A: Not Specified
(*Reference conditions: 64 to 82°F (18 to 28°C), 20 to 75% RH, external magnetic field < 40 A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sample centered.) Load impedance > 1MΩ.

Frequency Range: 40 to 10kHz Limit Operating Conditions:

200A permanently to 1k H z Derating above 3kHz: 200 A x (1/0.333 F), F in kHz
10 to 40A: ≤ 5° 40 to 100A: ≤ 3° 100 to 240A: ≤ 2.5°