AC Current Probe
Model MN213
User Manual
DESCRIPTION
The MN213 (Cat. #2115.75) is the latest in compact AC current probes. Designed to meet the most
stringent demands in industry and electrical contracting, it also meets the latest safety and performance
standards. The probe has a measurement range up to 240Arms which makes it a perfect tool for
measurement with DMMs, recorders, power and harmonic meters. The Model MN213 is compatible with
any AC ammeter, multimeter, or other current measurement instrument with an input impedance lower
than 1. To achieve the stated accuracy, use the MN213 with an ammeter having an accuracy of
0.75% or better.
WARNING
The safety warnings are provided to ensure the safety of personnel and proper operation of the
instrument. Read the instruction completely.
• Use caution on any circuit: potentially high voltages and currents may be present and may pose
a shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device
before it is connected around the conductor
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III
pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the current probe is protected by double or reinforced insulation. Use
only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before
using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from
HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES
CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately
with the carrier and notify your distributor at once, giving a detailed description of any damage.

ELECTRICAL SPECIFICATIONS
Current Range: 50mA to 100AAC, continuous
Output Signal: 1mA
Accuracy*:
50mA to 100A: 1% ± 0.05A
(with non inductive load)
Phase Shift: N/A
(*Reference conditions: 23°C ± 3°K, 20 to
70% RH, external magnetic field < 40 A/m,
48 to 65Hz sine wave, no DC component, no
external current carrying conductor, test
sample centered.) Load impedance 1Ω.
Overload:
150A continuously
Frequency Range:
48 to 65Hz
Load Impedance:
5Ω max
Working Voltage:
300V on insulated conductor
Common Mode Voltage:
AC Cat. III
100V
AC/AAC (150mA @ 150A)
Polycarbonate Material:
Handle: 10% Fiberglass charged polycarbonate
UL 94 V0
Output:
Insulated 5 ft (1.5 m) lead with safety 4mm
banana plug
SAFETY SPECIFICATIONS
Electrical:
300V working voltage on insulated conductor
100V max common mode between output and
ground, Cat. III
3kV 50/60Hz dielectric for 1mn
ORDERING INFORMATION
AC Current Probe MN123...............Cat #2129.12
Accessories:
Banana plug adapter
(to non-recessed plug) .....................Cat #1017.45
MECHANICAL SPECIFICATIONS
Operating Temperature:
-13° to 122°F (-25° to 50°C)
Storage Temperature:
-40° to 176°F (-40° to 80°C)
Maximum Cable Diameter:
0.43” Ø max. (11mm)
Dimensions:
1.4 x 4.53 x 0.87"
(36 x 115 x 22mm)
Weight:
160 g (6 oz)
Colors:
Dark gray handles with red cover

OPERATION
Making Measurements with the AC Current Probe Model MN123
• Connect the black (S2) and red (S1) terminals to the 200mA range of your DMM or instrument. The
MN123 has a ratio of 1000:1. This means that for 100A
clamped, 100mA
AC will come out of the probe leads to your DMM or instrument. The output is 1mAAC
AC in the conductor around which the probe is
per Amp. Select the range on your DMM or instrument which best corresponds to the measured
current. If the magnitude is unknown, start with the highest range (200mA
AC) then work down until the
appropriate range and resolution is reached. Clamp the probe around the conductor. Take the reading
on the meter and multiply it by 1000 to obtain the measured current (e.g., 59mA reading: 59 x 1000 =
59,000mA or 59A).
• For best accuracy, avoid if possible, the proximity of other conductors which may create noise.
Tips for Making Precise Measurements
• When using a current probe with a meter, it is important to select the range that provides the best
resolution. Failure to do this may result in measurement errors.
• Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air
gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for
power measurement.
MAINTENANCE:
Warning
• For maintenance use only original factory replacement parts.
• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into
the probe.
Cleaning
To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times.
Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth.
REPAIR AND CALIBRATION
You must contact our Service Center for a Customer Service Authorization number (CSA#). This will
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA#
on the outside of the shipping container. If the instrument is returned for calibration, we need to know if you
want a standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus
recorded calibration data).
Chauvin Arnoux
®
, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive • Dover, NH 03820 USA
Tel: (800) 945-2362 (Ext. 360)
(603) 749-6434 (Ext. 360)
Fax: (603) 742-2346 or (603) 749-6309
repair@aemc.com
(Or contact your authorized distributor)
Costs for repair, standard calibration, and calibration traceable to N.I.S.T. are available.
NOTE: All customers must obtain a CSA# before returning any instrument.
TECHNICAL AND SALES ASSISTANCE