Aemc instruments MN213 User Manual

AC Current Probe Model MN213
User Manual
DESCRIPTION
The MN213 (Cat. #2115.75) is the latest in compact AC current probes. Designed to meet the most stringent demands in industry and electrical contracting, it also meets the latest safety and performance standards. The probe has a measurement range up to 240Arms which makes it a perfect tool for measurement with DMMs, recorders, power and harmonic meters. The Model MN213 is compatible with any AC ammeter, multimeter, or other current measurement instrument with an input impedance lower than 1. To achieve the stated accuracy, use the MN213 with an ammeter having an accuracy of
0.75% or better.
WARNING
The safety warnings are provided to ensure the safety of personnel and proper operation of the instrument. Read the instruction completely.
• Use caution on any circuit: potentially high voltages and currents may be present and may pose a shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device before it is connected around the conductor
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the current probe is protected by double or reinforced insulation. Use only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES
CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage.
1.36" (35mm)
0.87" (22mm)
Ø =0.43" max
(11mm)
4.53" (115mm)
Black
Red
1.4" (36mm)