Aemc instruments MN115 User Manual

AC Current Probe Models MN115
User Manual

DESCRIPTION

The MN115 (Catalog #2110.72) is a high accuracy voltage output current probe for tight areas such as crowded wiring. Extends DMM AC measurements to 100 A AC. The Model MN115 offers a 5 ft. lead with safety 4mm banana plug.

WARNING

These safety warnings are provided to ensure the safety of personnel and proper operation of the instrument.
• Read the instruction manual completely and follow all the safety information before attempting to use or service this instrument.
• Use caution on any circuit: Potentially high voltages and currents may be present and may pose a shock hazard.
• Read the Safety Specifications section prior to using the current probe. Never exceed the maximum voltage ratings given.
• Safety is the responsibility of the operator.
• ALWAYS connect the current probe to the display device before clamping the probe onto the sample being tested.
• ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use. Replace any defective parts immediately.
• NEVER use the current probe on electrical conductors rated above 600 V in overvoltage category III (CAT III). Use extreme caution when clamping around bare conductors or bus bars.

INTERNATIONAL ELECTRICAL SYMBOLS

This symbol signifies that the current probe is protected by double or reinforced insulation. Use only specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.

RECEIVING YOUR SHIPMENT

Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage.

PACKAGING

The AC Current Probe MN115 is shipped with this instruction manual and a product warranty and registration card.

INSTRUMENT COMPATIBILITY

The Model MN115 is compatible with any voltmeter, multimeter, or other voltage measuring instruments with an input impedance greater than 100 K. To achieve the stated accuracy, use the MN115 with an ammeter having an accuracy of 0.75% or better.
Ø =0.47" max.
(12 mm)
Black
1.26"
(32 mm)

ELECTRICAL SPECIFICATIONS

Current Range: 1 A to 100 A AC, continuous
Output Signal: 10 mV AC/A AC
(1 V @ 100 A)
4.53" (115 mm)
0.87"
(22 mm)
Accuracy and Phase Shift*:
Accuracy: 1 to 100 A: 2% ± 50 mA 40 Hz to 3 kHz: 3.5% ± 50 mA
Phase Shift:
1 to 100 A: 6° 50 to 60 Hz
Red
(*Reference conditions: 23°C ± 3°K, 20 to 85% RH, 48 to 65 Hz, external magnetic field < 40 A/m, no DC component, no external current carrying conductor, test sample centered.) Load impedance 1 MΩ.
Overload:
120 A continuous
Frequency Range:
30 Hz to 5 kHz
Load Impedance:
100 KΩ min.
Working Voltage:
600 V AC
Common Mode Voltage:
600 V AC

MECHANICAL SPECIFICATIONS

Operating Temperature:
14° to 122°F (-10° to 50°C)
Storage Temperature:
-40° to 176°F (-40° to 80°C)
Output:
Insulated 5 ft. (1.5 m) lead with safety 4mm banana plug

SAFETY SPECIFICATIONS

Electrical:
- 600 V max common mode between output and ground
- 3 kV 50/60 Hz dielectric f or 1 mn between core and output cable

ORDERING INFORMATION

AC Current Probe MN115 ....... Cat #2110.72

Accessories:

Banana plug adapter
(to nonrecessed plug) ............ Cat #1017. 45
Temperature Influence:
< 0.2% per 10°K
Maximum Cable Diam eter :
0.47” Ø max. (12 mm)
Dimensions:
1.26 x 4.53 x 0.87" (32 x 115 x 22 mm)
Weight:
160 g (6 oz)
Colors:
Dark gray handles with red cover
Polycarbonate Material:
Handle: 10% Fiberglass charged polycarbonate UL 94 V0

OPERATION

Making Measurements with the AC Current Probe Model MN115
Connect the black (S2) and red (S1) terminals to the 2 V range of your DMM or instrument. The MN115 has a ratio of 100:1. This means that for 100 A AC in the conductor around which the probe is clamped, 1 V AC will come out of the probe leads to your DMM or instrument. The output is 10 mV AC per Amp. Select the range on your DMM or instrument which best corresponds to the measured current. If the magnitude is unknown, start with the highest range (2 V AC) then work down until the appropriate range and resolution is reached. Clamp the probe around the conductor. Take the reading on the meter and multiply it by 100 to obtain the measured current (e.g., 59 mV reading: 59 x 100 = 5900 mA or 5.9 A).
For best accuracy, avoid if possible, the proximity of other conductors which may create noise.
Tips for Making Precise Measurements
When using a current probe with a meter, it is important to select the range that prov
ides the best
resolution. Failure to do this may result in measurement errors.
Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for power measurement.

MAINTENANCE:

Warning

For maintenance use only original factory replacement parts.
To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
To avoid electrical shock and/or damage to the instrument, do not get wa
ter or other foreign agents into
the probe.

Cleaning

To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times. Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine
600) to avoid scratching the jaw, then gently clean with a soft oiled cloth.

REPAIR AND CALIBRATION

You must contact our Service Center for a Customer Service Authorization number (CSA#). This will ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# on the outside of the shipping container. If the instrument is returned for calibration, we need to know if you want a standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus recorded calibration data).
Chauvin Arnoux
®
, Inc. d.b.a. AEMC® Instruments
15 Faraday Drive Dover, NH 03820 USA Tel: (800) 945-2362 (Ext. 360)
(603) 749-6434 (Ext. 360)
Fax: (603) 742-2346 or (603) 749-6309 repair@aemc.com
(Or contact y
our authorized distributor)
Costs for repair, standard calibration, and calibration traceable to N.I.S.T. are available.
NOTE: All customers must obtain a CSA# before returning any instrument.