AEMC Instruments MF 300-6-2-10, MN03, MF 3000-10-2-1, MF 300-6-2-10 HF, MF 300-10-2-10 HF User manual

...
AC Current Probe Model MN251T
User Manual

DESCRIPTION

The MN251T is the latest in compact AC Current probes. Designed to meet the most stringent demands in industry and electrical contracting, it also meets the latest safety and performance standards. The probe has a measurement range up to 240 Arms which makes it the perfect tool for measurement with DMMs, recorders, power and harmonic meters. The Model MN251T is compatible with any AC voltmeter, multimeter, or other voltage measurement instrument that is capable of displaying 1mV of output per amp of measured current, voltmeter accuracy of 0.75% or better and an input impedance of ≥ 1 MΩ.

WARNING The safety warnings are provided to ensure the safety of personnel and proper operation of the instrument. Read the instruction completely.

• Use caution on any circuit: potentially high voltages and currents may be present and m ay pose a shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device before it is connected around the conductor.
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.

INTERNATIONAL ELECTRICAL SYMBOLS

This symbol signifies that the current probe is protected by double or reinforced insulation. Use only factory specified re pl ac em ent parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.

RECEIVING YOUR SHIPMENT Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify

your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
ELECTRICAL SPECIFICATIONS
Nominal Range: 200A Measurement Range: 0.1 to 240A Transformation Ratio: Voltage out put Output Signal: 1mV/A Accuracy and Phase Shift*:
Accuracy: 0.5 to 10A: 3.0% Reading ± 0.5mV
10 to 40A: 2.5% Reading ± 0.5mV 40 to 100A: 2.0% Reading ± 0.5mV 100 to 240A: 1.0% Reading ± 0.5mV
Phase Shift: 0.5 to 10A: Not Specified
(*Reference conditions: 64 to 82°F (18 to 28°C), 20 to 75% RH, external magnetic field < 40 A/m, 48 to 65Hz sine wave, distortion factor less than 1%, no DC component, no external current carrying conductor, test sampl e centered.) Load impedance > 1MΩ.

Frequency Range: 40 to 10kHz Limit Operating Conditions:

200A permanently to 1k H z Derating above 3kHz: 200 A x (1/0.333 F), F in kHz
10 to 40A: ≤ 5° 40 to 100A: ≤ 3° 100 to 240A: ≤ 2.5°
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com

Crest Factor: 3 @ 200Arms with an error (due to CF) of 3%

Working Voltage: 600Vrms Common Mode Voltage: 600Vrms Influence of Adjacent Conductor:

< 15mA/A at 50Hz Influence of DC on AC signal:

DC Current < 20A, < 5% Influence of Conductor Position in Jaw:

0.5% of mV output @ 50/60Hz Influence of Frequency:

40Hz to 1kHz: 3% of mV output 1kHz to 10kHz: 12% of mV output

Influence of Load: < 3% of mA output from 40Hz to 1kHz

< 12% of mA output from 1kHz to 10kHz Influence of Temperature:

150 ppm/°K, or 0.15% of mV output per 10°K Influence of Humidity (10 - 90% RH):

0.2% of mV output per 10°K @ 18°C to 28°C

MECHANICAL SPECIFICATIONS

Operating Temperature:

14° to 131°F (-10° to +55°C) Storage Temperature:

-40° to 158°F (-40° to +70°C) Operating Relative Humidity:

50° to 95°F (10° to 35°C) 85% RH (without roll-off above 95°F [35°C])

Maximum Cable Diameter: One Ø 0.78" (20mm), bus bar 0.78 x 0.2” (20 x

5mm) Case Protection:

IP 40 (IEC 529) Drop Test:

Test per IEC 68-2-32: 1.0m drop on 38mm of oak on concrete.

Mechanical Shock: Test per IEC 68-2-27

Vibration: Test per IEC 68-2-6

Dimensions:
5.47 x 2.00 x 1.18" (139 x 51 x 30 mm)
Weight: 180 g (6.5 oz) Polycarbonate Material:
Jaws: Polycarbonate with 10% fiberglass charge,
Red UL 94 V0
Case: Polycarbonate 920A Gray
Opening Operations - Life: > 50,000 Output:
10 ft (3m) insulated lead with BNC connector

SAFETY SPECIFICATIONS

Electrical:
Double insulation or reinforced insulation between the primary or secondary and the outer cas e of the handle conforms to IEC 1010-2-32.

Common Mode Voltage: 600V CAT III, Pollution Degree 2

Dielectric Strength: 5550V, 50/60 Hz between primary, secondary

and the outer case of the handle Electromagnetic Compatibility:

EN 50081-1 Class B EN 50082-2 Electrost atic discharge
IEC 1000-4-2 Radiated field IEC 1000-4-3 Fast transients IEC 1000-4-4 Magnetic field at 50/60 Hz IEC 1000-4-8

ORDERING INFORMATION

AC Current Probe MN251T................ Cat #2132.59

Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com

OPERATION Please make sure that you have already read and fully understand the WARNING section on page 1.

Making Measurements with the AC Current Probe Model MN251T:

• Connect the BNC connector to your voltage-measuring instrument. The AC current probe has an output of 1mV/A. This means that for 200A AC in a conductor around which the probe is clamped, 200 mV AC will come out of the probe leads to your DMM or instrument. Select the range which corresponds to the measured current. If the current magnitude is unknown, start with the highest range and work down until the appropriate range and resolution are reached. Clamp the probe around the conductor. Take the reading on the meter and multiply it by 1000 to obtain the measured current (e.g, 150mV reading = 150 x 1000 = 150,000mA or 150A).
• For best accuracy, avoid if possible, the proximity of other conductors which may create noise.

Tips for Making Precise Measurements:

• When using a current probe with a meter, it is important to select the range that provides the best resolution. Failure to do this may result in measurement errors.
• Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for power measurement.
MAINTENANCE Warning:
• For maintenance use only original factory replaceme nt pa rts.
• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so.
• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into the probe.

Cleaning: To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times.

Failure to do so may result in error in readings. To clean the probe jaws, use very fine sand paper (fine 600) to avoid scratching the jaw, then gently clean with a soft oiled cloth.

REPAIR AND CALIBRATION You must contact our Service Center for a Customer Service Authorization number (CSA#). This will ensure

that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# on the outside of the shipping container.
Chauvin Arnoux
®
, Inc. d.b.a. AEMC® Instruments
(Or contact your authorized dist ribu to r)
NOTE: All customers must obtain a CSA# before returning any instrument. TECHNICAL AND SALES ASSISTANCE
If you are experiencing any technical problem s, or require any assistance with the pr op er use or ap pli ca ti on of this instrument, please contact our technical hotline:
ITED WARRANTY
LIM
The current probe is warranted to the owner for a period of two years from the date of original purchase against defects in manufacture. This limited warranty is given by AEMC from whom it was purchased. This warranty is void if the unit has been tampered with, abused or if the defect is related to service not performed by AEMC
lease print the online Warranty Coverage Inform ation for your records.
P
®
Instruments.
®
Instruments, not by the distributor
99-MAN 100455.v1 09/17