Aemc instruments JM5A, JM1000, JM1500, JM500 User Manual

AC Current Probe Model JM500/1000/1500/5A
User Manual

DESCRIPTION

The Current Probe (Catalog # 2117.15) is designed for use in industrial environments. The “squared” jaws permit multiple conductor or bus bar positioning. The current output makes it the perfect tool for measurement with DMMs, recorders, power and harmonic meters. This AC Current Probe offers a 10 ft. lead with safety 4mm banana plug.

WARNING

These safety warnings are provided to ensure the safety of personnel and proper operation of the instrument.
• Read the instruction manual completely and follow all the safety information before attempting to use or service this instrument.
• Use caution on any circuit: Potentially high voltages and currents may be present and may pose a shock hazard.
• Read the Safety Specifications section prior to using the current probe. Never exceed the maximum voltage ratings given.
• Safety is the responsibility of the operator.
• ALWAYS connect the current probe to the display device before clamping the probe onto the sample being tested.
• ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use. Replace any defective parts immediately.
• NEVER use the current probe on electrical conductors rated above 600 V in overvoltage category III (CAT III). Use extreme caution when clamping around bare conductors or bus bars.

INTERNATIONAL ELECTRICAL SYMBOLS

This symbol signifies that the current probe is protected by double or reinforced insulation. Use only specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using the instrument.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the carrier and notify your distributor at once, giving a detailed description of any damage.

PACKAGING

The AC Current Probe is shipped with this instruction manual and a product warranty and registration card. You can now regi ster on line at www.aemc.com

INSTRUMENT COMPATIBILITY

This AC Current Probe is compatible with any AC Ammeter, multimeter, or other current measuring instrument with an input impedance lower than .2. To achieve the stated accuracy, use it with an Ammeter having an accuracy of 0.75%.
INSTRUMENTS
4.72"
(120 mm)
Ø =2.52" (64 mm)
Cable max.
1.97 x 5.31" (50 x 135 mm) or
2.52 x 3.94" (64 x 100 mm) Bus Bar max.
1.89"
(48 mm)
P1 P2
12.40"
(315 mm)
S2
S1
Black
Red

ELECTRICAL SPECIFICATIONS

Current Range:
1 to 500A AC continuous cycle 1 to 1000A AC continuous cycle 1 to 1500A AC continuous cycle
Transformation Ratio:
500:5, 1000:5, 1500:5
Output Signal:
10 mA AC/A AC (5A at 500A) 5 mA AC/A AC (5A at 1000A)
3.33 mA AC/A AC (5A at 1500A)
Accuracy and Phase Shift*: 500A RANGE
Primary current 25A 100A 500A Accuracy % 5% 3% 3% Phase shift
Load Impedance: 0.2 Overload: 700A for 10 mn Ampere Second Product: 3.5 A.s Accuracy: Per IEC 185-26-27
Class 0.5 (5 VA) from 48 to 1000 Hz