AC Current Probe Model SR604

The Model SR604 is designed for use in industrial and utility environments. The unique ergonomic design allows it to easily clamp onto cables or small bus bars. It is built to the highest safety and performance standards including the CE Mark and is UL approved for Canada and United States.
Excellent transformation and low phase shift, plus a broad frequency response, permit accurate measure­ments of current for power and power quality measurements. The high quality magnetic cores and uniform windings provide sensitivity for very low level current measurements, as well as measurements up to 1200A The Model SR604 works as a traditional current transformer (with a ratio of 1000:1) and provides current outputs in mA/A for use on DMMs, power and harmonic meters, data loggers, recorders or instruments with current ranges.
Technical Assistance (800) 343-1391 www.aemc.com 1 of 4
a c .

Features

Measurement range of
100mA to 1200A
Large jaw opening accommodates
conductors up to two 500MCM conductors
Ergonomic design and easy
operation
Conforms to EN 61010, 600V Cat. III
safety standard
Low phase shift for power
measurements
Available with mA output signals
Designed for DMMs, recorders,
loggers, oscilloscopes, power and harmonic meters
• ULapprovedforCanadaand United States
• DoubleInsulation
CE Mark
a c

Applications

Power quality measuring
Low industrial loads
Measuring around cable bundles
Power load monitoring
Waveform analysis
SR604_211344 (pdf) 0308 Rev. 05

Specifications

MODEL SR604*
ELECTRICAL
Nominal Range 1000A Measurement Range 0.1 to 1200A Transformation Ratio 1000: 1 Output Signal 1mA Accuracy (1000A Range)
0.1 to 10A 3% + 0.1A 50A 1.5% of Reading 200A 0.75% of Reading 1000A 0.5% of Reading 1200A 0.5% of Reading Phase Shift (1000A Range)
50A 1.5° 200A 0.75° 1000A 0.5° 1200A 0.5°
Overload 1200A for 40 min ON, 20 min OFF Frequency Range 30Hz to 5kHz; current derating
above 1kHz using the formula: 1000A x 1/F (in kHz)
Load Impedance 5 max Working/Common
Mode Voltage Output Termination Lead
MECHANICAL
Operating Temperature -14° to 122°F (-10° to 50°C) Storage Temperature -4° to 158°F (-20° to 70°C) Operating Relative
Humidity Jaw Opening 2.25" (57mm) max
Maximum Conductor Size 2.05" (52mm) Maximum Bus Bar Size One 1.95 x 0.19" (50 x 5mm)
Dimensions 4.37 x 8.50 x 1.77" (111 x 216 x 45mm) Weight 1.21 lbs (550g)
Polycarbonate Material Handles: Polycarbonate + ABS, Gray, UL94 V0. Jaws: Polycarbonate, Red, UL94 V0
SAFETY
Electrical EN 61010-2-032
UL Approval Yes – Canada and United States Double Insulation
Yes
CE Mark Yes
Note: Reference conditions: 23 ± 3°K, 20 to 75% RH, 48 to 65Hz, external magnetic field < 40A/m, no DC component, no external current
carrying conductor, test sample centered. Load impedance 0.2 @ lead < 40m for 250A range.
*Diode Protection for open secondary (Output)
a c /Aa c : (1Aa c @ 1000A)
600V Cat. III
0 to 85% @ 35°C