AEMC MR411 Data sheet

CURRENT MEASUREMENT PROBES
AC/DC Current Probes & DC/AC MicroProbes
MR400 & MR500 Series
AC/DC current probes designed to extend current measuring capabilities of DMMs, oscilloscopes and other instruments
SpecificationS
MODELS MR411 MR521
Measurement Range AC
Measurement Range DC
Output Signal Voltage (mV)
(AC in AC, DC in DC)
Maximum Conductor Size Ø Cable
Bus Bar
Output Connection
Power Source
0.5 to 40A
0.5 to 400A
0.5 to 60A
0.5 to 600A
10mV/A
1mV/A
One 1.18" (30mm) Two 0.95" (24mm)
Two x 500kcmil
Two 1.2 x 0.4" (31.5 x 10mm)
Lead with
safety banana plug
One 9V Alkaline battery (included)
0.5 to 100A
0.5 to 1000A
0.5 to 150A
0.5 to 1500A
10mV/A
1mV/A
One 1.5" (39mm)
Two 0.98" (25mm)
Two 1.96 x 0.19"
(50 x 5mm)
Lead with
safety banana plug
featureS
MR400 Series has a
measurement range of 400AAC/600ADC
MR500 Series has a measurement range of
1000AAC/1500ADC
Two distinct jaw shapes to be used for hooking
or prying around the conductor
Low phase shift for power measurements
Designed for DMMs, recorders, oscilloscopes,
power and harmonic meters
EN 61010, 600V CAT III, 300V CAT IV,
Pollution Degree 2
Models K100 & K110
Very small and compact, our microprobes are designed for accurate measurements of very low currents with 50µA
SpecificationS
MODELS K100 K110
Current Range
Output (Vout)
Resolution
Accuracy
Output Noise
Frequency Response
Power Source
Battery Life
0 to ± 4.5A
DC: 50μA typical, AC: 100μA typical
DC: ±1% of Reading
AC: ±2% of Reading,
<100μV, DC to 3kHz <100μV, DC to 3kHz
(@ -3dB sine)
DC
0 to 3Arms
1mV/mA 10mV/mA
DC: ±0.5% of Reading
± 200μA,
AC: ±0.8% of Reading,
± 200μA
DC to 2kHz
One 9V Alkaline battery (included)
20 hours
dc sensitivity
0 to ± 450mADC
0 to 300mArms
DC: 50μA typical,
AC: 100μA typical
± 150μA,
± 200μA
DC to 1.5kHz
(@ -3dB sine)
featureS
Measures extremely
Outputs signal proportional to total current
Low noise
Ultra-compact size and non-contact clamp-on
Simple plug-in operation
Designed for use with digital multimeters and
Accurate display of waveforms
No range or mode (AC/DC) switching required
Red LED indicates momentary or continuous
Green LED indicates power and battery condition
Model K100
low level DC from 100μA
(DC + AC)
convenience
oscilloscopes
overload
CATALOG NO. DESCRIPTION
1200.68 AC/DC Current Probe Model MR411 (Lead – 10mV/A – 60A max & 1mV/A – 600A max)
1200.69 AC/DC Current Probe Model MR521 (Lead – 10mV/A – 150A max & 1mV/A 1500A – max)
2111.73 DC/AC MicroProbe Model K110 (10mV/mA – 450mA max)
86
www.aemc.com
Technical Assistance (800) 343-1391
PRICE NIST CALIBRATION
$ 364.00 $ 65.00 $ 389.00 $ 65.00 $ 635.00 $ 65.00 $ 675.00 $ 65.00
Loading...