AEMC ML914 Data sheet

Page 1
POWER QUALITY ANALYZERS, METERS & LOGGERS
R
A
T
I
N
G
S
A
F
E
T
Y
GROUND RESISTANCE TESTER
Simple Logger® II TRMS Current
Three-Phase Power Quality Analyzer
Simple Logger® II 4-Channel Bluetooth Edition
DATA LOGGERS
DATA LOGGERS
Multi-Function
4-Channel MiniFlex® Model ML914
Four channel logger includes four
integral 6" flexible current probes
SPECIFICATIONS
MODEL ML914
ELECTRICAL
IP 50
Rated
cover closed
FEATURES
• Includes four integral MiniFlex® flexible
current probes that will measure up to 1000A TRMS with 0.1A resolution
• Dual range 100/1000A user selectable per channel
• 64 samples per cycle
• Programmable storage rates from 125ms
to 1 per day
• 4 user selectable storage modes
• Stores up to 1,000,000 measurements in
non-volatile memory
• Powered by standard Alkaline batteries
for a period of up to 180 days
• Lightweight and compact
• 6 LED indicators quickly and clearly display
logger status
• Wireless Bluetooth data communication
(Class 2 Bluetooth module included)
• Includes FREE DataView
data storage, real-time display, analysis and report generation
• EN 61010-1; 600V CAT IV, 1000V CAT III
®
software for
Channels Input
Range Accuracy
(50/60Hz)
Resolution Sample Rate Storage Rate Storage Modes Recording Length Memory
Communication Power Source Battery Life
MECHANICAL
Dimensions Max Conductor
Size Weight
(with battery) Case Vibration Shock
6" Captive AC MiniFlex
ac 5 to 1000Aac
1 to 100A
0 to 1A unspecified
1 to 100A:
±(1% of Reading + 0.5A)
Programmable from 125ms to 1 per day
Start/Stop, FIFO, Extended Recording Mode (XRM
15 minutes to 8 weeks, programmable using DataView
The recorded data is stored in non-volatile memory and
will be retained even if the battery is low or removed.
5.904 x 5.904 x 3.568" (150 x 150 x 91mm) w/o Sensor
1,000,000 measurements (2MB)
Bluetooth connection (communicates up to 30 ft)
4 x 1.5V C-cell Alkaline batteries (included)
(dependent on storage rate/recording length)
IEC 68-2-6 (1.5mm, 10 to 55Hz)
Four
®
Flexible Sensors
0.1A
64 samples/cycle
Up to 180 days
1.77" (45mm) diameter
2.4 lbs (1.1kg)
UL94-V0
IEC 68-2-27 (30G)
0 to 5A unspecified
5 to 1000A:
±(1% of Reading + 1A)
™
)
®
Special product
▼
APPLICATIONS
• Single/Split phase and 3 phase
load monitoring
•
Neutral and ground current monitoring
•
Intermittent problem detection
•
Harmonic current monitoring using
DataView
•
Machine load monitoring
•
Fault current detection
•
Load profiling
®
software
Bluetooth USB adapter, twelve color-coded
PRODUCT INCLUDES
input ID markers, mounting hardware, 4 x
1.5V C-Cell Alkaline batteries, USB cable for firmware updates, and
USB stick supplied with DataView
software and user manual.
®
CATALOG NO. DESCRIPTION
2126.40 Simple Logger® II Model ML914 (4-Channel, TRMS, Bluetooth, MiniFlex
Technical Assistance (800) 343-1391
®
100/1000Aac, DataView® software)
www.aemc.com
Page 2
Data Analysis and Reporting Software
Typical DataView® Functional Displays
Configure all data logger functions
Quick and simple configuration of all functions and settings from one dialog box.
DATAVIEW®
DATAVIEW®
Software for Data Loggers
Software for Data Loggers
• Display and analyze real-time data on your PC
• Configure all data logger functions and
parameters from your PC including sample rate, recording length, channel configuration and more
• Create and store a complete library of configurations that can
be uploaded to the logger as needed
• Zoom in and out and pan through sections of the graph to
analyze the data
• Download, display and analyze recorded data
• Display waveforms, trend graphs, harmonics (AC models)
and text summaries
• Create custom views and reports
• Print reports using standard or custom templates you design
• Free software upgrades are available on
our website www.aemc.com
Configure scale functions.
Configure all alarm functions with straightforward selections.
Technical Assistance (800) 343-1391
Real-time display of all active inputs on computer through
®
DataView
software.
www.aemc.com