AEMC MD300 Data sheet

AC Current Probe Model MD301
The Model MD301 is built for ruggedness, versatility and ease of use. It is designed with a unique hook-shaped jaw that enables the user to “pry” into or “hook” onto cables (will accept 2 x 500kcmil) or even smaller bus bars.
The Model MD301 measures up to 500A. It provides a voltage output proportional to the measured current.
Technical Assistance (800) 343-1391 www.aemc.com 1 of 4
This voltage output enables instruments without current ranges to measure, display or log currents on an AC voltage range.
The electronics and batteries are self-contained in the handles. The output of AC probes is
d c /Aa c .
1mV

Features

Unique hook-shaped jaws that enable the user to “pry” into or “hook” onto cables
Maximum conductor size is 2 x 500kcmil
Works as a traditional current transformer with ratio of 1000:1

Applications

Electric utility
Field testing
HVAC
Industrial maintenance
Laboratory
Plant maintenance
MD301_120107 (pdf) 0410 Rev. 02

Specifications

MODEL MD301
ELECTRICAL
Nominal Range 500A Measurement Range 2 to 500Aa c Transformation Ratio Voltage output Output Signal 1mVd c /Aa c Accuracy (500A Range)
25A 5% of Reading 100A 2% of Reading 250A 1% of Reading 500A 1% of Reading Phase Shift 25A 100A 250A 500A
Overload 700A for 10 min Frequency Range 48 to 1000Hz
(error: add 2% to the ref.)
Load Impedance 100kΩ Working Voltage 600Vrms Common Voltage 600Vrms Output Termination 5 ft Lead
MECHANICAL
Operating Temperature -5° to 122°F (-15° to 50°C) Storage Temperature -40° to 185°F (-40° to 85°C) Jaw Opening 1.3” (33mm) Maximum Conductor Size 1.18” (30mm), Max Bus Bar size: 2.48 x 0.20” (63 x 5mm) Dimensions 2.6 x 7.68 x 1.34” (66 x 195 x 34mm) Weight 14.82 oz (420g)
Polycarbonate Material Handles: 10% fiberglass charged polycarbonate UL94 VO
SAFETY
Electrical EN 61010-2-032 600V CAT III, Pollution: 2; 300V CAT IV, Pollution: 2
Electromagnetic EN 50081-1 Class B; EN 50082-2 Electrostatic discharge IEC 1000-4-2;
Compatibility Radiated field IEC 1000-4-3; Fast transients IEC 1000-4-4; Magnetic field at 50/60Hz IEC 1000-4-8
Double Insulation Yes
CE Mark Yes
Note: Reference conditions:
23°C ± 5°K, 20 to 75% RH, external magnetic field < 40A/m, no DC component, no external current carrying conductor, test sample centered, 10Ω load.
MD301_120107 (pdf) 0410 Rev. 02