POWER QUALITY ANALYZERS, METERS & LOGGERS
GROUND RESISTANCE TESTER
Simple Logger® II TRMS Current
Three-Phase Power Quality Analyzer
Simple Logger® II 4-Channel Bluetooth Edition
DATA LOGGERS
DATA LOGGERS
Multi-Function
Four channel logger with two
AC voltage and two AC current
inputs that directly measure and
record up to 600V
SPECIFICATIONS
MODEL L564
ELECTRICAL
IP
50
Rated
cover closed
FEATURES
• Four input channels (2 voltage & 2 current)
• User programmable recording
modes: Start/Stop, FIFO, Extended
Recording Mode (XRMTM) and
Alarm Recording
• Powered by standard Alkaline batteries
for a period of up to 180 days
• Stores 1,000,000 measurements
• Includes FREE DataView® software
for data storage, real-time display,
analysis and report generation
• Includes set of 3 color-coded
(1 red/1 black/1 white) 5 ft leads with
color-coded alligator clips
Wireless Bluetooth data communication
•
(Class 2 Bluetooth module included)
• Safety Ratings 600V CAT IV; 1000V CAT III
Channels
Connection Current Channel Voltage Channel
Input Connection
Input Range
Accuracy
(50/60Hz)
Input Impedance
Sample Rate
Storage Rate
Storage Modes
Recording Length
Memory
Communication
Power Source
Battery Life
MECHANICAL
Dimensions
Weight (with battery)
Case
Vibration
Shock
Drop
Two 3 pin connector Three recessed 4mm banana jacks
(for use with iron core current probes
with a voltage output)
0 to 10mV unspecified
±(0.5% of Reading + 1mV)
50 to 1000mV:
±(0.5% of Reading + 0.5mV)
15 minutes to 8 weeks, programmable using DataView
The recorded data is stored in non-volatile memory and
will be retained even if the battery is low or removed.
Up to 180 days (dependent on storage rate/recording length)
Four (two voltage & two current)
ac
0 to 1V
10 to 50mV:
100kΩ 16MΩ
64 samples/cycle
Programmable from 125ms to 1 per day
Start/Stop, FIFO, Extended Recording Mode (XRM
Bluetooth connection (communicates up to 30 ft)
4 x 1.5V C-cell Alkaline batteries (included)
5.904 x 5.904 x 3.568" (150 x 150 x 91mm)
and Store on Alarm
1,000,000 measurements (2MB).
2.1 lbs (0.95kg)
UL94-V0
IEC 68-2-6 (1.5mm, 10 to 55Hz)
IEC 68-2-27 (30G)
IEC 68-2-32 (1m)
±(0.5% of Reading + 1V)
±(0.5% of Reading + 0.5V)
PRODUCT INCLUDES
Model L564
ac
0 to 600V
0 to 5V unspecified
5 to 50V:
50 to 600V:
™
)
®
Special
product
features
▼
APPLICATIONS
• Single/split phase and 2 phase load monitoring
• Neutral and ground voltage/current,
current monitoring
• Intermittent problem detection
• Harmonic voltage and current monitoring using
DataView
®
software
Alkaline batteries, USB cable for firmware
Bluetooth USB adapter, set of 3
color-coded (1 red/1 black/1 white) 5 ft
leads with color-coded alligator clips,
twelve color-coded input ID markers,
mounting hardware, 4 x 1.5V C-Cell
updates, and USB stick supplied with
®
DataView
software and user manual.
• Residential power monitoring
• Fault voltage detection
• Load profiling
CATALOG NO. DESCRIPTION
2126.36 Simple Logger® II Model L564 (4-Channel, TRMS, Bluetooth, Voltage & Current, DataView® software)
Technical Assistance (800) 343-1391
www.aemc.com
![](/html/5b/5ba8/5ba8fa183e529ad53cbecb937d8f9d7f19aa82045f3ae87ddf19d776b96e395e/bg2.png)
DATAVIEW®
Software for Data Loggers
Data Analysis and Reporting Software for Data Loggers
Typical DataView® Functional Displays
Quick and simple configuration of all functions and
settings from one dialog box.
Configure all data logger functions
of the Simple Logger
• Display and analyze real-time data on your PC
• Configure all data logger functions and
parameters from your PC including sample rate, recording
length, channel configuration and more
• Create and store a complete library of configurations that can
be uploaded to the logger as needed
• Zoom in and out and pan through sections of the graph to
analyze the data
• Download, display and analyze recorded data
• Display waveforms, trend graphs, harmonics (AC models)
and text summaries
• Create custom views and reports
• Print reports using standard or custom templates you design
• Free software upgrades are available on
our website www.aemc.com
®
II Models
Configure all alarm functions with straightforward selections.
Real-time view of trend, waveform and status screens.
www.aemc.com
Real-time display of all active inputs on computer through
®
DataView
software.
Technical Assistance (800) 343-1391