AC Current Probes Model JM850A (pdf) Rev. 03 10/05
Technical Assistance (800) 343-1391 www.aemc.com2of 4
MODELS JM850A
ELECTRICAL
Nominal Range 1000A, 2000A, 3000A
Measurement Range 1 to 3400A
Transformation Ratio 1000:1, 2000:1, 3000:1
Output Signal 1mA
AC/AAC (1A @ 1000A)
0.5mA
AC
/AAC (1A @ 2000A)
0.333mAAC/AAC (1A @ 3000A)
Accuracy (1000A Range)
50A 3% of Reading
200A 1.5% of Reading
1000A 1% of Reading
Phase Shift (1000A Range)
50A 3°
200A 1.5°
1000A 1°
Accuracy (2000A Range)
100A 1.5% of Reading
400A 0.75% of Reading
2000A 0.5% of Reading
Phase Shift (2000A Range)
100A 1.5°
400A 0.75°
2000A 0.5°
Accuracy (3000A Range)
150A 1.5% of Reading
600A 0.75% of Reading
3000A 0.5% of Reading
Phase Shift (2000A Range)
150A 1.5°
600A 0.75°
3000A 0.5°
Overload 1400A for 10 min (1000A)
2400A for 10 min (2000A)
3400A for 10 min (3000A)
Frequency Range 30 to 1000Hz, current derating above 1000Hz for continuous use
Load Impedance 2.5Ω (1000A);
5Ω (2000A;
10Ω (3000A)
Working/Common
Mode Voltage
600V
AC
Output Termination Jack
MECHANICAL
Operating Temperature 14° to 122°F (-10° to 50°C)
Storage Temperature -13° to 176°F (-25° to 80°C)
Jaw Opening 3.54" (90mm)
Maximum Conductor Size Cable: 2.52" Ø max (64mm); Bus bar: 1.97 x 5.31" (50 x 135mm); 2.52 x 3.94" (64 x 100mm)
Dimensions 4.72 x 12.40 x 1.89" (120 x 315 x 48mm)
Weight 2.65 lbs (1200g)
Polycarbonate Material Handles: 10% fiberglass charged polycarbonate UL94 VO; Jaws: ABS UL V2
SAFETY
Electrical EN61010-2-32
Electromagnetic EN 50081-1 Class B; EN 50082-2 Electrostatic discharge IEC 1000-4-2;
Compatibility Radiated field IEC 1000-4-3; Fast transients IEC 1000-4-4; Magnetic field at 50/60Hz IEC 1000-4-4
Double Insulation Yes
CE Mark Yes
Note: Reference conditions:
23°C ± 3°K, 20 to 85% RH, 45 to 65Hz, external magnetic field <40A/m, no DC component, no external current carrying conductor,
test sample centered.
Specifications