AC Current Probes Model JM813 (pdf) 10/05 Rev. 03
Technical Assistance (800) 343-1391 www.aemc.com1of 4
AC Current Probe
Model JM813
The Model JM813 is a high
performance AC current probe for
higher currents. Excellent transformation
and low phase shift, plus a broad
frequency response, permit accurate
measurements of current and power.
The high quality magnetic cores and
uniform windings provide for accurate
measurements up to 3600A
AC.
The “squared” jaw permits multiple
conductor or bus bar positioning.
The Model JM813 provides excellent
True RMS capabilities and reliable
signal reproduction.
The Model JM813 works as a traditional current transformer providing
current outputs (mA) over a broad
range of transformation ratios. The
Model JM813 is designed for use on
DMMs, power and harmonic meters,
recorders or instruments with AC
current ranges.
Features
• Nominal range: up to 3000AAC
(continuous cycle for the full
temperature range)
• Transformation ratio: 3000:3
• Output: 1mA/A
• Designed for use on DMMs, power
and harmonic meters, recorders or
instruments with AC current ranges
Applications
• Field testing
• Electrical utility
• HVAC
• Industrial maintenance
• Laboratory
• Plant maintenance

AC Current Probes Model JM813 (pdf) 10/05 Rev. 03
Technical Assistance (800) 343-1391 www.aemc.com2of 4
Specifications
MODEL JM813
ELECTRICAL
Nominal Range 3000A
Measurement Range 1 to 3600A
Transformation Ratio 3000:3
Output Signal 1mAAC/AAC (3A @ 3000A)
Accuracy (1000A Range)
150A 1.5% of Reading
600A 0.75% of Reading
3000A 0.5% of Reading
Phase Shift (1000A Range)
150A 1.5°
600A 0.75°
3000A 0.5°
Overload 3600A for 5 min
Frequency Range 30Hz to 5kHz; current
derating above 1kHz
for continuous use
Load Impedance ≤0.6Ω
Working/Common
Mode Voltage
600V
AC
Output Termination 5 ft Lead
MECHANICAL
Operating Temperature 14° to 122°F (-10° to 50°C)
Storage Temperature -13° to 176°F (-25° to 80°C)
Jaw Opening 3.54" (90mm)
Maximum Conductor Size Cable: 2.52" Ø max (64mm); Bus bar: 1.97 x 5.31" (50 x 135mm); 2.52 x 3.94" (64 x 100mm)
Dimensions 4.72 x 12.40 x 1.89" (120 x 315 x 48mm)
Weight 2.65 lbs (1200g)
Polycarbonate Material Handles: 10% fiberglass charged polycarbonate UL94 VO; Jaws: ABS UL V2
SAFETY
Electrical EN 61010-2-32
Double Insulation Yes
CE Mark Yes
Note: Reference conditions:
23°C ± 3°K, 20 to 85% RH, 48 to 65Hz, external magnetic field <40A/m, no DC component, no external current carrying conductor,
test sample centered. Load impedance 0.55Ω.

AC Current Probes Model JM813 (pdf) 10/05 Rev. 03
Technical Assistance (800) 343-1391 www.aemc.com3of 4
Ø=2.52" (64mm)
ORDERING INFORMATION CATALOG NO.
AC Current Probe Model JM813 (Jack – 1mA/A – 3000A max) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #2110.93
Includes a user manual
Accessories (Optional)
Banana plug adaptor (to nonrecessed plug) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #1017.45
Leads, set of 2, 5 ft safety (1000V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #2111.29
Banana/BNC Connector XF-SS (4mm banana plug) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cat. #2111.32
Jacks:
Two standard
safety banana
jacks (4mm)
Cable max.
1.97 x 5.31" (50 x 135mm) or
2.52 x 3.94" (64 x 100mm)
Bus Bar max.
P1 P2
12.01"
(305mm)
4.72"
(120mm)
1.89"
(48mm)

AC Current Probes Model JM813 (pdf) 10/05 Rev. 03
Technical Assistance (800) 343-1391 www.aemc.com4of 4
Contact Us
United States and Canada:
Chauvin Arnoux
®
, Inc.
d.b.a. AEMC
®
Instruments
200 Foxborough Blvd.
Foxborough, MA 02035 USA
(508) 698-2115 • Fax (508) 698-2118
www.aemc.com
Customer Support – for placing an order, obtaining price and delivery:
customerservice@aemc.com
Sales Department – for general sales information:
sales@aemc.com
Repair and Calibration Service – for information on repair and calibration, obtaining a user manual:
repair@aemc.com
Technical and Product Application Support – for technical and application support:
techinfo@aemc.com
Webmaster – for information regarding www.aemc.com:
webmaster@aemc.com
South America, Central America, Mexico, Caribbean, Australia and New Zealand:
Chauvin Arnoux
®
, Inc.
d.b.a. AEMC
®
Instruments
15 Faraday Drive
Dover, NH 03820 USA
(978) 526-7667 • Fax (978) 526-7605
export@aemc.com
www.aemc.com
All other countries:
Chauvin Arnoux SCA
190, rue Championnet
75876 Paris Cedex 18, France
33 1 44 85 45 28 • Fax 33 1 46 27 73 89
info@chauvin-arnoux.com
www.chauvin-arnoux.com