AEG IH24E, IH21E, IH18E User Manual

Instantaneous
IH 18 electronic LCD
Water Heater
IH 21 electronic LCD IH 24 electronic LCD
Instructions for installation and use
Contents Page
Important instructions for the user 3
General 3 Operating the appliance 3 Temperature preselection 3 Hot water flowrate 4 Care and maintenance of the appliance 4
Important instructions for the installer 5 General 5 Appliance constitution 5 Technical data 6 Appliance function 7 Safety temperature and pressure limiter 7 Installing the appliance 8 Dimensioned diagram 8 Appliance installation 9 Hood dismounting 9 Wall mounting 9
Water connection 10 Concealed installation 10 Installation versions 11 Cleaning the strainer insert 12 Flowrate limiter 12
Electrical connection 13 Mains connection 13/14 Circuit diagram 14 Temperature selector range limitation 15 Hood assembly 15
Using the appliance for the first time and checking 16 Fault-finding 17 Fault indications 18 Important for the expert 19 Customer service 20
2
Important instructions for the user
IH electronic LCD
General
- Installation and startup should only ever be performed by an approved installer or authorised installation firm.
- Before using the appliance, please read through these instructions carefully. The manufacturer cannot accept any liability for damage
resulting from failure to follow these instructions.
- Fittings and connecting pipes may get hot. Therefore keep children well
away.
Operating the appliance
The ELECTROLUX IH electronic instantaneous water heater heats the water as the latter continuously flows through it. When the hot water tap is opened, the appliance switches on at a flowrate of around 3 l/min. When the hot water valve is closed or if the flowrate is reduced below 2.5 l/min, the appliance switches itself off again. The appliance is suitable for household use and should only ever be used for heating of drinking water. One or more tapping points can be supplied with hot water.
Temperature preselection
The electronic system allows continuous temperature selection in the range from 30°C to 60°C.
Recommendation for energy-saving operation: 40°C for washbasin, shower, and bath (knob tangibly engages).
55°C for kitchen sink. If this temperature is no longer needed, the appliance should be reset to the 40°C energy-saving level.
CAUTION! When operating with prewarmed water (for example solar-energy plant) the outlet - temperature could be higher than prefixed in the LCD­display.
When the appliance is operated with a thermostatic mixer tap, the temperature setting on the instantaneous water heater must be around 8°C higher than on the thermostatic mixer tap.
3
Hot water flowrate
Cold
water
tempe
rature
°C
Outlet temperature
40°C
Outlet temperature
55°C
6
10
14
18 kW
l/min
7,6
8,6
(*8)
9,9
(*8)
21 kW
l/min
8,8
10
(*9)
11,6
(*9)
24 kW
l/min
10,1
11,5
(*10)
13,2
(*10)
18 kW
l/min
5,3
5,7
6,3
21 kW
l/min
6,1
6,7
7,3
24 kW
l/min
7
7,6
8,4
(*) limited to this figure by the built-in flowlimiter
Up to the appliance’s max. power limit, the instantaneous water heater supplies the set hot water temperature regardless of the water flowrate selected.
If the hot water temperature is not attained when the hot water valve is fully opened, more water flows than can be heated by the appliance power. In this case, the hot water tap must be slightly closed.
The built-in automatic flowlimiter limits the flow in such a way that also with fully opened warm water outlet valve and low cold water inlet temperatures a shower-fair outlet temperature (approx. 40°C) remains.
Because of the different inlet temperatures, the hot water output varies depending on the season. The following outlet flowrates for bath or shower water (40°C) or washbasin/ sink water (55°C) are attained at the inlet temperatures of 6°C, 10°C, and 14°C.
Care and maintenance of the appliance
Clean the plastic housing as necessary with a damp cloth and dilute soap solution. Never use any abrasive, scouring, and solvent-containing detergents. The instantaneous water heater generally needs no maintenance. Regular inspection of the appliance by a trained engineer will ensure its operational reliability and prolong its service life.
bubblers of the fittings or hand shower head must therefore be cleaned from time to time.
Scale deposits in the outlet of fittings reduce the water flowrate. The air
4
123
4
5
12
13
4a
5a
14
6
7
8
9
10
11
15
16
Important instructions for the installer General
The instantaneous water heater is manufactured and tested in conformity with the valid IEC specifications and DIN standards. The appliance complies with the Appliance Safety Act. The indications given on the rating plate, the technical connection specifications of the electricity and water companies in the geographical area concerned, and VDE 0100 and DIN 1988 must be observed when the appliance is being installed. Before all work on the equipment the mains voltage supply must be interrupted.
The specific resistance of the water at the installation site should not be less than 1100
ΩΩ
cm.
ΩΩ
This appliance complies with the following EC Directives:
- the ”Low-Voltage Directive” 72/23/EEC of 19.02.1973, including Amendment Directive 93/68/EEC
- the”Electromagnetic Compatibility” Directive 89/336/EEC of
03.05.1989 including Amendment Directive 92/31/EEC
Appliance constitution
1 = Back wall 2 = Thermal sensor 3 = Quick fastener for appliance
mounting 4 = Upper cable bushing 4a =Lower cable bushing 5 = Upper mains connection
terminal (factory-prefitted) 5a = Lower mains connection
terminal (transpose mains
connection terminal) 6 = Flowrate sensor 7 = Safety temperature and
pressure limiter 8 = Electronic module 9 = Temperature Display 10 =Temperature selector knob 11 =Flowrate limiter 12 = Strainer insert, connection
for direct tapping fitting 13 =Cold water connection 14 = Hot water connection 15 = Thermostat 16 = Heating block
5
Technical data
Model
Type
unvented
Nominal capacity
Liters
0,4
Dimensions Width Height Depth
mm
226
469
95
Weight
kg
3,9
Nominal overpressure
Mpa (bar)
1 (10)
Protection class to VDE
I
Protection type to VDE
IP 25 (splash-water protected)
Test mark
See rating plate
Water connection
G 1/2 A
Electrical connection
3 / PE ~ 380 V
Nominal output
kW1821
24
Spec. water resistance at 15 °C
Ohm cm
> 1100
Switch-on flow pressure*)
0.035 (0,35)
Switch-on flowrate
l/min
3
Mains retroactive effect
Free from any mains retroactive effect
to DIN EN 60555/VDE 0838
VDEW Approval
Maximum inlet temperature
°C
< 70 (power engagement up to 45 °C)
IH E
24 LCD
IH E
21 LCD
IH E
18 LCD
Flowrate limitation l/min 8 9 10
0.03 (0,3)
0.04 (0,4)
*) In addition to the flow pressures of the instantaneous water heater itself, consideration must be given to the pressure losses in the household pipework.
6
Appliance function
The fully electronically controlled ELECTROLUX IH instant water heater is a pressurised appliance for the supply of one or more tapping points and heats the water as the latter continuously flows through it. A flowrate sensor switches on the heating at a flowrate of around 3 l/min and off again at around 2,5 l/min. The microprocessor controlled electronic system automatically adapts the heating power with regard for the inlet temperature, the temperature set on the temperature selector knob, and the water flowrate. The user thus has hot water available in an energy-saving system giving the exact temperature required without any time limitation whatever.
The nominal operating pressure is 1MPa. If this value is exceeded, a pressure reducing valve should be provided in the household pipework. A safety valve is not necessary. The bare wire resistance heating system has a high efficiency. Its low weight and extremely low water content also make it suitable for hard, lime-containing water qualities.
Safety temperature and pressure limiter
In the event of a fault, the inbuilt safety temperature and pressure limiter isolates the appliance from the mains supply on all contacts. Before the appliance is switched back on, a trained engineer must ascertain and eliminate the cause of the fault (see page 17). Then carefully press in the contact rocker with a screwdriver until it audibly engages.
Important: Don't block up the contact rocker!
Pressurepoint for screwdriver
Important! The safety temperature and pressure limiter should never be adapted or modified in any way!
7
Installing the appliance
1
2
3
4
4a
3a
5
6
226
190
100
95
37,5
5
4
6
9
2
9
3
395
21
30
The appliance should only ever be installed or stored in frost-free premises.
Dimensioned diagram
1 = Quick fastener for appliance mounting 2 = Wall mounting 3 = Upper connection terminal (factory-set) 3a = Lower connection terminal for electrical connection 4 = Upper cable bushing 4a = Lower cable bushing for electrical connection 5 = Cold water connection with strainer insert 6 = Hot water outlet
8
Appliance installation
1
2
3
Carefully unpack and take out the enclosed pack. Prepare the appliance for assembly.
Hood dismounting
Press in the engagement lug on the underside of the appliance from above or from the front with a screwdriver and take off the hood. Pull out the connection lead of the temperature set-point pickup on the electronic system.
The rotational range of the temperature selector knob can be limited (see page 15).
Wall mounting
Mark out wall-plug holes with the mounting template supplied, insert wall-plugs, and screw on fixing rail (1). Take out threaded pin (2) from the enclosed pack and screw in. Then prepare water connections, mount appliance on threaded pin and retaining rail, and fix by turning the quick fastener (3) one quarter revolution.
9
Water connection
The water inlet temperature on the cold water connection should be max. 70°C. Upwards of 45°C, the appliance system is arranged not to apply any more heating power. If plastic pipe systems are used as installation material, the pipe manufacturer must expressly and unreservedly confirm the applicability and quality of his pipes for this application.
Concealed installation
Insert connector with shutoff spindle (1) in cold water connection and double- nipple (2) in hot water outlet using hemp packing. The shutoff spindle must point downwards and the screw slot aligned in the flow direction of the water. The shutoff unit
must not be used for throttling.
The ELECTROLUX IH electronic can be operated with all pressure fittings suitable for instantaneous water heater.
10
Installation versions
1
2
3
4
For fittings directly on the appliance, the bushing openings pre-embossed in the appliance hood must be cut out for the extension pipes of the fitting. The supporting sheet (1) enclosed with the fitting fixes the extension pipes in position and seals the housing openings. To ensure moisture protection, the supporting sheet must be fitted.
Fitting must be vertically seated and centrally under the appliance. Seal appliance connection to the wall, where necessary, with G 1/2 A blind plugs (2) (fitting accessory).
If a cold water supply is made to the appliance, the shutoff adapter (3) should be replaced by an adapter with a wood screw (4) for fixing the fitting in place.
The following tapping fittings are suitable:
D 169 - Special mixer tap with swivelling outlet D 159 - Special shower mixer tap D 149 - Special bath mixer tap with change-over tub/shower
Important! After completion of the water installation, the appliance should be thoroughly flushed with cold water (open the hot water valve). The strainer insert may possibly need cleaning afterwards.
11
Cleaning the strainer insert
2
1
3
1
2
If the water flowrate is reduced by dirt from the cold water line, the strainer­insert should be cleaned as follows:
Shut off cold water on shutoff unit (1)
Loosen cap nut (2 ) using a spanner
Take out and clean strainer (3)
Re-assemble in reverse sequence
Open cold water on shutoff unit (1); check
tightness
Flow rate limiter
The flow rate limiter (2) is installed in the cold water connector (1) to allow a constant outlet temperature at high flow pressures of approx. 40° C, suitable for showering. (See table page 4 and 6)
12
Electrical connection
1
2
3
max.10
4
20
150
The electrical connection should only ever be made after the water is connected! The appliance is only suitable for a fixed connection of 380 V 3 ~ (three-phase current) .
The appliance must be connected to the protective conductor.
Important note: The wiring must be arranged so that the appliance can be
de-energised (disconnected from the electricity supply) before any intervention involving the fuses being unscrewed, the automatic safety devices being switched off, or similar measures being taken (isolating gap width of at least 3 mm).
Mains connection lead
The connection cable must project from the wall over an insulated length of at least 20 mm.
Mains connection on top
Electrical connection terminal (3) factory-prefitted. Cut out cable inlet opening (1). Slide flexible inlet bush (2) over connection cable, insert it through the back wall opening, and screw fixing strap under connection terminal (4).
13
Mains connection underneath (alternative)
3
2
1
L1(R)
L2(S)
L3(T)
PE
Heizblock
3
4 2
5
1
W4 W3 W2 W1
3
4
2
5
1
Elektronik
LED
1 2
IN
S2
L1
L2
L3
K
S
D
LCD
For this connection version, transpose the mains connection terminal (1) from top to bottom.
Note the terminal designation on the back wall, and do not cross the connection leads to the safety temperature limiter.
Carry out cable inlet opening (2), inlet bush (3), and bush fixing under the mains connection terminal as described above for mains connection.
Important! Moisture protection is only guaranteed with the inlet bush fitted in position.
Circuit diagram
Heating block
Main connec­tion terminal
Safety­temperature and pressure
limiter
Electronic system
14
Temperature selector range limitation
IN
The maximum temperature able to be set can be limited to 40°C or 45°C.
Important! Before dismantling, set the knob to the minimum temperature of 30°C.
Detach the temperatur set-point pickup (2) in the appliance hood. Turn the setting dial (3) so that the printed set-point coincides with the hood mark (1).
Do not twist the selector axis and plate of the temperature set-point pickup when reassembling!
Hood dismounting
Plug the connection lead of the temperature set-point pickup into the electronic system, suspend the appliance hood in the upper edge of the back wall, and swivel it downwards until it audibly engages. If necessary, the hood can be suppli­mentarily fixed with a screw next to the engagement lug.
15
Using the appliance for the first time and checking
The unit must be installed and started up by an approved firm of installers which accepts liability for safety and proper function.
Before the appliance is energised (connected to the electricity supply),
it should be thoroughly flushed with cold water and the tightness of the screwed joints checked.
After the instantaneous water heater is energised (connected to the electricity supply), it should be inspected by a trained engineer to ensure that it is in proper working order. For protection of the heating systems, the system is arranged for a switch-on delay of 5 - 25 s at initial startup and after the appliance has not been live for any length of time. Important: After any work carried out on the water supply unit, the appliance should also be thoroughly flushed with cold water (vented) before being switched on again. Only then should the appliance be reconnected to the electricity supply.
After initial startup, the user should be familiarised with operation of the appliance and the instructions for installation and use handed over for safekeeping.
16
Fault-finding (important instructions for the trained engineer)
In the event of any fault, a check should first be made to ascertain whether the fuse and line protection switch have tripped.
CauseFault Remedy
- Heating system does not switch on
- Hot water flowrate too low
- Safety temperature and pressure limiter has tripped
- Active fault indicator (LED)
- Appliance is not live
- Strainer insert is clogged
- Soiling or scaling of bubblers and shower heads
- Defective heating system
- Inadmissibly high cold water inlet tempera­ ture (over 70 °C)
- Inadmissibly high outlet temperature (over 70 °C)
- System fault (see table on page 18)
Check the voltage
Clean strainer insert (see page 12)
Dismantle and clean the bubblers and showers heads
Inspection and repair only by the trained engineer
Appliance should not be operated with preheated water over 70 °C
Inspection and repair only by the trained engineer
Inspection and repair only by the trained engineer
17
Fault indications
- L1 or L3 phase missing
- L2 phase missing
Fault
pattern
Idicator Possible faults
LED 1 LED 2
1 No display
Appliance does
not work
- Flowrate sensor not plugged Defective
Hot water temperature
too low
2
FLASHES
short
FLASHES
long
- Setpoint generator not fitted
3
4
5
6
ON
- Water flow > 20 l/min
No display
warm water temp.37°C
Constant
FLASHES
short
FLASHES
long
degree rgulation
No correct
- Temperature sensor not plugged / Defective
- Electronic defective
FLASHES
long
FLASHES
short
No heat output
FLASHES
long
OFF
No heat output
- Outlet temperature 70°C>
FLASHES
long
ON
- Inlet temperature > 45°C
No heat output
OFF
18
Important for the expert
V
1
2
1 2
Fehleranzeige
The electronic controls the safety-function of the appliance. When a fault is noticed, the fault indicator (LED) blinks and the heating element is switched off. After the fault has been recitified, fault memory will be automatically cancelled. Instructions for the fault finding see in "Instructions for installation and use" page 17and 18.
Fault indicator
19
Customer service
Serial No..
If your appliance has a fault, please contact your customer service centre for advice.
Electric appliances should only ever be repaired by a trained electrician, since the user may be seriously endangered by improper repairs.
A list of the addresses of customer service centres is attached. If your appliance requires service, you will need to quote these numbers indicated on the rating plate.
To save enquiries, copy the data from the rating plate and keep them handy.
Subject to change 267791-K33895-8040
EHT Haustechnik GmbH
Gutenstetter Straße 10
D-90449 Nürnberg GERMANY
Loading...